RFI_DOCUMENT.pdf
PDF 189 KB Posted
- Attached to
- VGLZ162028 - Renovate Bldg. 168; Wellness Center
- Solicitation number
- W912JB-18-B-5004
About this file
RFI's
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SELFRIDGE BLDG. 168 RENOVATION
W912JB-18-B-5004
RFI’S
1. Will the building be occupied during construction? ANSWER: The building will be partially occupied during construction, but not enough to hinder construction activities. Refer to Statement of Work (SOW) for coordination instructions.
2. Will temp walls be required for this project? If so, can you provide a plan where you want the temp walls built and what requirements for it? ANSWER: The SOW does not mention temporary walls. The SOW does mention to provide barricades. Please adhere to the SOW’s Life Safety instructions.
3. Drawing AD01 call for the complete wall demo at the lecture hall, rm #130 (option 1). There is railing that sits above this new walls. Can you provide a wall detail on what’s the extent of that wall demo? ANSWER: See detail #1 on sheet A103.
4. On drawings A101, there’s a reference to note #9 in the restroom but there’s no #9 in the floor plan key notes. Please advise. ANSWER: See addendum #1 AD1-2 Architectural Drawing Revisions Paragraph *B.” Item 1.
5. What is the deck height? ANSWER: Cannot answer this question as not enough information was given to identify which deck it is? Please resubmit this question with more detail.
6. Is there a spec on the signage? ANSWER: See signage details and notes on sheet a 301. Delete signage note 1.1 (does not apply to this project). See sheet a101 for T1 and T2 sign locations (outside of toilet rooms in corridor 118).
File details come from the government source that posted it.