AECOM

27777 Franklin Road, Ste. 2000

Southfield, MI 48034 T: 248.204.5900

F: 248.204.5901 www.aecom.com

Addendum No. 1

Client: Selfridge Air National Guard Base Project Name: Renovate Bldg. 168 – Wellness Center

Location: Selfridge ANG Base, Michigan

Project No.: 60554155

Issue Date: February 21, 2018

This addendum refers to: drawings AD01, A101, A103 and A200 revised and not reissued. And includes drawings revised and reissued herein numbered E101, E201 and E300.

AD1-1 NOTICE

A. This Addendum No. 1 to the contract documents for the above captioned project supersedes all contrary and/or conflicting information on said contract documents, where are hereby amended in certain particulars, as follows:

AD1-2 ARCHITECTURAL DRAWING REVISIONS

A. Refer to drawing AD01 “First Floor Demolition Plan” (not issued)

1. All existing ceiling fans shall remain in place located in Lecture Hall

130.

B. Refer to drawing A101 “First Floor Plan” (not issued).

1. Add Floor Plan Keynote No. 9 that shall read: “Provide: 12" x 12" wall access panel 'Nystrom' model no. ET-C-12X12-B (or equal).”

2. Revised Floor Plan Keynote No. 8 to read: “Provide: 30" x 30" ceiling access panel ‘Nystrom’ model no. ET-C-30X30-B (or equal).”

C. Refer to drawing A103 “First Floor Reflected Ceiling Plan” (not issued).

1. Revised note pointing to access panel in room # A114 Kitchenette to read: Provide new 30"x30" ceiling access panel 'Nystrom' model number ET-C-30X30-B (or equal).”

2. Changed incorrect room name “Student Flight Lounge” to the correct name: “Airmen’s Lounge.”

Addendum No. 1 AECOM

Renovate Bldg. 168 – Wellness Center

60554155

February 21, 2018

D. Refer to drawing A200 “Door and Room Finish Schedule” (not issued).

1. Revised Door Schedule. At door numbers 102 & 104 add the following item to the “Notes” column: “Provide “CECO” Brand

‘Sound-Tech Xpress Door System’ – STC-45 or equal.”

2. Revised Door Schedule. At door number 112, in the “Notes “column:

remove note: “Provide door seals – ‘Reese’ DS78A & 370A” and add note “Provide “CECO” Brand ‘Sound-Tech Xpress Door System’ –

STC-45 or equal.”

AD1-3 ELECTRICAL DRAWING REVISIONS

A. Refer Drawing 101 “First Floor Lighting Plan” (drawing re-issued).

1. Refer to general note 3, panel ID changed to LP-B1 including all new branch circuit numbers.

2. Panel LP-B was relocated to room 114.

3. Added panel LP-B1 in room 114.

B. Refer Drawing E201 “First Floor Electrical Power and Special Systems

Plan” (drawing re-issued).

1. Refer to general note 3, panel ID changed to LP-B1 including all new branch circuit numbers.

2. Panel LP-B was relocated to room 114.

3. Added panel LP-B1 in room 114.

C. Refer Drawing E300 “Partial One-Line Diagram” (drawing re-issued).

1. Revised one-line diagram.

2. Modified panel schedule LP-B.

3. Added panel schedule LP-B1.

EX.RTU-1

EX.RTU-2

110111112113

116117

EX. LP-KITCHEN

TO REMAIN

EX. LP-C

TO REMAIN

FA

CP

EX. BOILER PANEL

EX. MDP

EX. MAIN SERVICE DISCONNECT

EX.

MAIN FIRE

ALARM

PANEL

ETR

ETR

ETR

ETR

ETR

ETR, WAITING

ETR, COUNSELING

NEW

LP-B

a b a a a a b b b b

2 4

FAMILY READINESS

OFFICE

AREA DEFENSE

COUNSEL

FAMILY READINESS

YELLOW RIBBON

FAMILY READINESS

ASSISTANT

MEN'S

TOILET

STUDENT FLIGHT

CLASSROOM

WOMEN'S

TOILET

KITCHENETTE

J.C.

I.T. CLOSET

TOUCHDOWN

OFFICE

VOLUNTEER

STORAGE

111CONFERENCE RM/

COMPUTER LAB

FAMILY READINESS

MULTI-PURPOSE ROOM

LECTURE HALL

MEN'S

TOILET

WOMEN'S

TOILET

AIRMEN'S

LOUNGE

DIRECTOR OF

PYSCH. HEALTH

VESTIBULE

VESTIBULE

STAIRS

SARC

OFFICE

SARC

WAITING

SARC

COUNSELING

VOLUNTEER

STORAGE

CORRIDOR

CORRIDOR

CHAPLAIN 1

CHAPLAIN 2

CHAPLAIN 3

CHAPLAIN

ASSASTANTS (3)

STAGE

BOILER RM

TOILET

OS OSOS

OS

OS

OS

OS

OS OS

2 2

NEW

LP-B1

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

LIGHTING PLAN

E101

NORTH

FIRST FLOOR LIGHTING PLAN

ALL 2X4 LIGHT FIXTURES ARE TYPE LT1 UNLESS NOTED OTHERWISE.

REUSE EXISTING LIGHTING CIRCUIT, EXTEND AS REQUIRED.

RELOCATED LIGHT FIXTURE.

WIRE FIXTURES TO CIRCUIT FEEDING ROOM / AREA, "AHEAD OF LOCAL SWITCH CONTROL". UPON

LOSS OF UTILITY POWER EBU FIXTURES SHALL PROVIDE 90 MINUTES OF EMERGENCY EGRESS

ILLUMINATION.

EXISTING LIGHTING FIXTURES AND CONTROLS TO REMAIN OPERATIONAL IN THIS ROOM.

L1

L2

L3

L4

L5

LIGHTING KEY NOTES

1. REFER TO DRAWING E000 FOR SYMBOL LIST AND E400 FOR PARTIAL ONE-LINE DIAGRAM AND PANEL

SCHEDULES.

2. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL. COORDINATE ALL FIRE ALARM

SYSTEM OUTAGES WITH THE OWNER.

3. ALL CIRCUITS ARE FED FROM PANEL LP-B1, CIRCUIT NUMBER INDICATED UNLESS NOTED OTHERWISE.

4. NOT USED

5. FOR ALL 20A, 120V/1PH CIRCUITS OF LENGTH 75FT. OR GREATER, PROVIDE 2#10, 1#10G, 3 4" C UNLESS

NOTED OTHERWISE.

6. COORDINATE ALL OUTLET LOCATIONS WITH ARCHITECTURAL INTERIOR ELEVATIONS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE EXISTING ELECTRICAL WORK FOR POSSIBLE

INTERFERENCE WITH NEW WORK. EXISTING ELECTRICAL WORK INTERFERING WITH OR REQUIRING

MODIFICATION FOR NEW REQUIREMENTS SHALL BE DISCONNECTED, REMOVED OR REROUTED TO

SUIT FINAL INSTALLATION.

8. ADJACENT AREAS OF THE BUILDING ARE TO REMAIN FULLY OPERATIONAL. COORDINATE ALL

REQUIRED POWER AND/OR SYSTEMS SHUTDOWNS WITH THE OWNER.

9. WORK MAY BE REQUIRED TO BE PERFORMED ON "OFF" HOURS TO AVOID INTERFERING WITH THE

BUILDINGS OPERATION. COORDINATE WITH THE OWNER AND CONSTRUCTION MANAGER.

10. UNLESS NOTED OTHERWISE, ALL SINGLE PHASE BRANCH CIRCUITS FOR LIGHTING AND POWER RECEPTACLES SHALL BE (2) #12 AND (1) #12 GROUND IN 3/4" CONDUIT. CONDUCTORS SHALL BE 600

VOLT 90°C RATING AND TYPE THWN OR XHHW INSULATION.

11. CONDUIT IN FINISHED AREAS SHALL BE CONCEALED IN CEILING SPACES OR IN WALLS UNLESS NOTED

OTHERWISE.

12. PROVIDE UPDATED TYPEWRITTEN PANEL DIRECTORIES FOR EXISTING PANEL BOARDS WHERE LOADS

HAVE BEEN REMOVED OR ADDED.

13. LABEL ALL RECEPTACLES AND LIGHT SWITCHES WITH THE PANEL ID AND CIRCUIT NUMBER FROM WHICH THEY ARE FED. RECEPTACLES AND LIGHT SWITCH LABELS SHALL BE MADE USING A BRADY HANDHELD LABELING SYSTEM IDENTIFYING THE PANEL AND CIRCUIT NUMBER. NORMAL POWER BLACK WITH WHITE LETTER #TL52200 WITH LABEL PART # PTL-45-430, FONT SIZE 7 AND BRADY #LAM-3-103

CLEAR POLYESTER APPLIED OVER THE TOP OF THE LABEL.

14. WHEN RELOCATING OR REMOVING A LIGHTING FIXTURE, RECEPTACLE, OR OTHER ELECTRICAL DEVICE, BUT NOT OTHERS ON THE SAME CIRCUIT, THE CIRCUIT SHALL BE EXTENDED FOR CONTINUED

SERVICE TO REMAINING ITEMS. PROVIDE CONDUIT AND WIRING AS REQUIRED.

15. ALL NEW CIRCUIT BREAKERS INSTALLED IN EXISTING POWER PANELS SHALL MATCH THE EXISTING

TYPE FOR THAT PANEL. NEW LOADS SHALL BE LISTED ON THE PANEL DIRECTORIES.

16. CONDUIT SLEEVES SHALL PROTRUDE 1-2" INTO THE SPACE. ALL WALL AND FLOOR PENETRATIONS

SHALL MAINTAIN THE FIRE RATING OF THE STRUCTURE.

17. PROVIDE THE FOLLOWING CONDUCTOR COLOR CODING FOR ALL FEEDERS AND BRANCH CIRCUITS:

208 / 120 V

PHASE A BLACK

PHASE B RED

PHASE C BLUE

NEUTRAL WHITE

GROUND GREEN

18. CONDUIT ROUTING IS DIAGRAMMATIC. FIELD VERIFY EXACT ROUTING. PROVIDE PULL BOXES EVERY 270°.

GENERAL NOTES

L2

L2

L2

L1

LW4 LW4

(TYP.)

L3

L3

L3

LD1

LD1

LD1LD1

LD1

LD1

LD1

LD1 LT2

LT2 LT2

LT2

LS1 LS1

EXTEND EXISTING

CORRIDOR CIRCUIT

L3 L3

EBU

EBUEBU EBU

EBU

EBU

E4E4

EBUE4

E4

E4 E4

E4

L5 L5L5

L5

A1

A1

A1

A1 A1

A1

A1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text 127th WING/CIVIL ENGINEER

AutoCAD SHX Text Engineer/Consultants

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text

SELFRIDGE AIR

AutoCAD SHX Text

NATIONAL GUARD

AutoCAD SHX Text

BASE, MICHIGAN

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text Project Number:

AutoCAD SHX Text File:

AutoCAD SHX Text Drawn By:

AutoCAD SHX Text Designed By:

AutoCAD SHX Text Checked By:

AutoCAD SHX Text 60554155

AutoCAD SHX Text Mark

AutoCAD SHX Text Date

AutoCAD SHX Text Description

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text Scale:

AutoCAD SHX Text Date:

AutoCAD SHX Text

02/13/18 100%%% FINAL

AutoCAD SHX Text

SRS RJ

AutoCAD SHX Text

SRS JR

AutoCAD SHX Text

DNB

AutoCAD SHX Text 02-21-18

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 4'

AutoCAD SHX Text 12'

EX.RTU-1

EX.RTU-2

ETR36", ETRS,

ETR

36", ETR S,

ETR

EX. AP TO

REMAIN

ETR

M

EX. ACU

TO REMAIN

EX. CONDUIT

TO REMAIN

EX. LP-KITCHEN

TO REMAIN

EX. CABLES

TO REMAIN

EX. LP-C

TO REMAIN

FA

CP

EX. BOILER PANEL

EX. MDP

EX. MAIN SERVICE DISCONNECT

EX.

MAIN FIRE

ALARM

PANEL

ETR

ETR

M

B-24

B-22

FF

NEW

LP-B

NEW

WIREMOLD

AC

(RELOCATED)

44"

44"

C

C C

GARBAGE

DISPOSAL,

CKT 23

C

54"

9 9

9 9

2121 21 21 21 21

H

H

H

H H

H

H

H

FAMILY READINESS

OFFICE

AREA DEFENSE

COUNSEL

FAMILY READINESS

YELLOW RIBBON

FAMILY READINESS

ASSISTANT

MEN'S

TOILET

WOMEN'S

TOILET

KITCHENETTE

J.C.

I.T. CLOSET

TOUCHDOWN

OFFICE

VOLUNTEER

STORAGE

COMPUTER LAB

FAMILY READINESS

MULTI-PURPOSE ROOM

LECTURE HALL

MEN'S

TOILET

WOMEN'S

TOILET

AIRMEN'S

LOUNGE

DIRECTOR OF

PYSCH. HEALTH

VESTIBULE

VESTIBULE

STAIRS

SARC

OFFICE

SARC

WAITING

SARC

COUNSELING

VOLUNTEER

STORAGE

CORRIDOR

CORRIDOR

CHAPLAIN 1

CHAPLAIN 2

CHAPLAIN 3

CHAPLAIN

ASSASTANTS (3)

STAGE

BOILER RM

TOILET

STUDENT FLIGHT

CLASSROOM

H HH

H

H

EWC,

H

44"

44"

F

MOUNT ABOVE

DOOR

DISHWASHER

C

COFFEE

POT

MICROWAVE

RANGE,

25, 27

NEW

LP-B1

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

ELECTRICAL

POWER &

E201

SPECIAL

SYSTEMS PLAN

NORTH

FIRST FLOOR POWER &

SPECIAL SYSTEMS PLAN

RELOCATE GROUND BUS TO IT CLOSET 115 AND MOUNT 3'-0" AFF. PROVIDE INSULATED #6 WIRE TO

IDF CABINET. PROVIDE NEW GROUND CONDUCTOR FROM EXISTING GROUND ROD TO RELOCATED

GROUND BUS.

MOUNT EXISTING IDF CABINET TO NEW TELEPHONE BACKBOARD. COORDINATE WITH CONTRACTING OFFICER. RECONNECT EXISTING DATA AND COMMUNICATIONS WIRING TO RELOCATED IDF CABINET.

MOUNT MANUAL MOTOR STARTER SERVING RELOCATED HVAC UNIT, EXTEND CIRCUIT AS

REQUIRED. RECONNECT TO EXISTING EXTERIOR CONDENSING UNIT, EXTEND CIRCUIT AS

REQUIRED.

RELOCATED FIRE ALARM STROBE. PROVIDE NEW WIREMOLD, MATCH EXISTING.

RELOCATED FIRE ALARM PULL STATION. PROVIDE NEW WIREMOLD, MATCH EXISTING.

PROVIDE 2#6, 1#10GRD, 1"C. FROM A 50A, 2P CIRCUIT BREAKER IN PANEL LP-B. VERIFY RECEPTACLE

NEMA CONFIGURATION WITH THE CONTRACTING OFFICER PRIOR TO ROUGH-IN.

PROVIDE NEW GFCI RECEPTACLE FOR RELOCATED DISHWASHER. MOUNT BELOW COUNTER.

PROVIDE (1) EMPTY 2" DATA CONDUIT WITH PULL CORD AND (1) EMPTY 2" COMMUNICATION

CONDUIT WITH PULL CORD ABOVE CEILING FROM IT CLOSET 115 TO STUDENT FLIGHT CLASSROOM 119.

PROVIDE I2000 (IVORY) WIREMOLD RACEWAY WITH COVERS AND ALL REQUIRED FITTINGS MOUNTED

18" AFF. ROUTE CONDUIT DOWN FROM CORNER OF ROOM TO HORIZONTAL RACEWAY. PAINT

CONDUIT TO MATCH THE WALL. REFER TO ARCHITECTURAL DRAWINGS AND ELEVATIONS.

EXTEND THE EXISTING FEEDER AND ALL BRANCH CIRCUITS TO NEW PANEL LP-B. PROVIDE (4) EMPTY 1" CONDUITS WITH PULL CORDS STUBBED ABOVE THE ACCESSIBLE CEILING IN ROOM 110

FOR FUTURE USE. COORDINATE WITH THE OWNER IN ADVANCE ALL REQUIRED POWER

SHUTDOWNS. REFER TO DRAWING E300 FOR ONE-LINE DIAGRAM AND PANEL SCHEDULES.

RELOCATED HEAT DETECTOR. COORDINATE LOCATION WITH LIGHT FIXTURES AND MECHANICAL

SYSTEMS ABOVE CEILING.

RELOCATED DATA OUTLET IN EXISTING SURFACE MOUNTED RACEWAY.

CONNECT NEW RECEPTACLES TO EXISTING CIRCUIT, EXTEND WIRING AS REQUIRED.

MOUNT RECEPTACLE WITH LIGHT SWITCH IN 2-GANG BOX. COORDINATE LOCATION WITH THE

LIGHTING PLAN.

PROVIDE 3 #12, 1 #12GRD, 3/4"C FROM PANEL LP-B1. REFER TO DRAWING E300 FOR STARTER , CIRCUIT NUMBERS AND WIRING DIAGRAM INFORMATION.

CONNECT RELOCATED HEAT DETECTOR TO EXISTING FIRE ALARM SYSTEM. COORDINATE

LOCATION WITH LIGHT FIXTURES AND MECHANICAL SYSTEMS.

REFER TO DETAIL #1 ON E000, PROVIDE EMPTY COMMUNICATION CONDUIT AND A BLANK PLATE FOR

FUTURE USE..

E1

E2

E3

E4

E5

E6

E7

E8

E9

E10

E11

E12

E13

E14

E15

E16

E17

ELECTRICAL KEY NOTES

GENERAL NOTES

1. REFER TO DRAWING E000 FOR SYMBOL LIST AND E400 FOR PARTIAL ONE-LINE DIAGRAM AND PANEL

SCHEDULES.

2. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL. COORDINATE ALL FIRE ALARM

SYSTEM OUTAGES WITH THE OWNER.

3. ALL CIRCUITS ARE FED FROM PANEL LP-B1, CIRCUIT NUMBER INDICATED UNLESS NOTED OTHERWISE.

4. NOT USED

5. FOR ALL 20A, 120V/1PH CIRCUITS OF LENGTH 75FT. OR GREATER, PROVIDE 2#10, 1#10G, 3 4" C UNLESS

NOTED OTHERWISE.

6. COORDINATE ALL OUTLET LOCATIONS WITH ARCHITECTURAL INTERIOR ELEVATIONS PRIOR TO

ROUGH-IN.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE EXISTING ELECTRICAL WORK FOR POSSIBLE

INTERFERENCE WITH NEW WORK. EXISTING ELECTRICAL WORK INTERFERING WITH OR REQUIRING

MODIFICATION FOR NEW REQUIREMENTS SHALL BE DISCONNECTED, REMOVED OR REROUTED TO

SUIT FINAL INSTALLATION.

8. ADJACENT AREAS OF THE BUILDING ARE TO REMAIN FULLY OPERATIONAL. COORDINATE ALL

REQUIRED POWER AND/OR SYSTEMS SHUTDOWNS WITH THE OWNER.

9. WORK MAY BE REQUIRED TO BE PERFORMED ON "OFF" HOURS TO AVOID INTERFERING WITH THE

BUILDINGS OPERATION. COORDINATE WITH THE OWNER AND CONSTRUCTION MANAGER.

10. UNLESS NOTED OTHERWISE, ALL SINGLE PHASE BRANCH CIRCUITS FOR LIGHTING AND POWER RECEPTACLES SHALL BE (2) #12 AND (1) #12 GROUND IN 3/4" CONDUIT. CONDUCTORS SHALL BE 600

VOLT 90°C RATING AND TYPE THWN OR XHHW INSULATION.

11. CONDUIT IN FINISHED AREAS SHALL BE CONCEALED IN CEILING SPACES OR IN WALLS UNLESS NOTED

OTHERWISE.

12. PROVIDE UPDATED TYPEWRITTEN PANEL DIRECTORIES FOR EXISTING PANEL BOARDS WHERE LOADS

HAVE BEEN REMOVED OR ADDED.

13. LABEL ALL RECEPTACLES AND LIGHT SWITCHES WITH THE PANEL ID AND CIRCUIT NUMBER FROM WHICH THEY ARE FED. RECEPTACLES AND LIGHT SWITCH LABELS SHALL BE MADE USING A BRADY HANDHELD LABELING SYSTEM IDENTIFYING THE PANEL AND CIRCUIT NUMBER. NORMAL POWER BLACK WITH WHITE LETTER #TL52200 WITH LABEL PART # PTL-45-430, FONT SIZE 7 AND BRADY #LAM-3-103

CLEAR POLYESTER APPLIED OVER THE TOP OF THE LABEL.

14. WHEN RELOCATING OR REMOVING A LIGHTING FIXTURE, RECEPTACLE, OR OTHER ELECTRICAL DEVICE, BUT NOT OTHERS ON THE SAME CIRCUIT, THE CIRCUIT SHALL BE EXTENDED FOR CONTINUED

SERVICE TO REMAINING ITEMS. PROVIDE CONDUIT AND WIRING AS REQUIRED.

15. ALL NEW CIRCUIT BREAKERS INSTALLED IN EXISTING POWER PANELS SHALL MATCH THE EXISTING

TYPE FOR THAT PANEL. NEW LOADS SHALL BE LISTED ON THE PANEL DIRECTORIES.

16. CONDUIT SLEEVES SHALL PROTRUDE 1-2" INTO THE SPACE. ALL WALL AND FLOOR PENETRATIONS

SHALL MAINTAIN THE FIRE RATING OF THE STRUCTURE.

17. PROVIDE THE FOLLOWING CONDUCTOR COLOR CODING FOR ALL FEEDERS AND BRANCH CIRCUITS:

208 / 120 V

PHASE A BLACK

PHASE B RED

PHASE C BLUE

NEUTRAL WHITE

GROUND GREEN

18. CONDUIT ROUTING IS DIAGRAMMATIC. FIELD VERIFY EXACT ROUTING. PROVIDE PULL BOXES EVERY 270°.

E2

E1

E3

E4

E5

E6

E7

E8

E9

E10

E11

(TYP)

E17

E12

E13

E13E13

E14

E14

EF-1

E15

EF-1

E15

E16

E17

E17

A1

A1

A1

A1

A1

A1

A1 A1

A1

A1A1

A1

A1

A1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text 127th WING/CIVIL ENGINEER

AutoCAD SHX Text Engineer/Consultants

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text

SELFRIDGE AIR

AutoCAD SHX Text

NATIONAL GUARD

AutoCAD SHX Text

BASE, MICHIGAN

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text Project Number:

AutoCAD SHX Text File:

AutoCAD SHX Text Drawn By:

AutoCAD SHX Text Designed By:

AutoCAD SHX Text Checked By:

AutoCAD SHX Text 60554155

AutoCAD SHX Text Mark

AutoCAD SHX Text Date

AutoCAD SHX Text Description

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text Scale:

AutoCAD SHX Text Date:

AutoCAD SHX Text

02/13/18 100%%% FINAL

AutoCAD SHX Text

RJ

AutoCAD SHX Text

RJ PTC

AutoCAD SHX Text

DNB

AutoCAD SHX Text 02-21-18

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 4'

12'

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

PARTIAL

ONE-LINE

DIAGRAM

E300

EX. LP-B EX. LP-C

PARTIAL ONE-LINE DIAGRAM

NEW LP-B

J

200A 3P

200A 3P

EXISTING MDP

600A, MLO,

208/120V, 3PH, 4W

600A

MAIN SERVICE

DISCONNECT

4#3/0, 1#6GRD,

2-1/2"C.

3#12, 1 #12GRD,

3/4"C.

EF-1

(KITCHEN)

1/2HP

THREE PHASE MOTOR SCHEMATIC - EF-1

NO SCALE

OLS

MS

MS

480V OR 208V

120V

R

5 FU

MS

MS

HAND

AUTO

OFF

L3

L2

L1

3 FU

6 FU

4 FU

2 FU

1 FU

OLS

MOTOR

FAN RUNNING

LED - PUSH TO TEST

E201

AUTOMATIC CONTROL DEVICE BY

MECHANICAL CONTROLS

CONTRACTOR (DDC)

KEYED NOTES:

PROVIDE (4) EMPTY 1" CONDUITS WITH PULL CORDS STUBBED ABOVE THE ACCESSIBLE

CEILING IN ROOM 110. PROVIDE REQUIRED FIRE STOPPING AROUND WALL

PENETRATIONS.

PROVIDE A NEMA SIZE 1 COMBINATION STARTER WITH HAND-OFF-AUTO SELECTOR

SWITCH AND RED LED (PUSH-TO-TEST) RUNNING LIGHT. PROVIDE DUAL ELEMENT RK1

FUSES. FUSE AT 4.0A FOR 1/2HP FAN. STARTER SHALL BE SIMILAR TO SQUARE D

CLASS 8538, NEMA 1 ENCLOSURE WITH 120V FUSED CONTROL TRANSFORMER,

CATALOG # SCG14-V02 OR EQUAL BY EATON OR GENERAL ELECTRIC.

E1

E2

E2

30A-3P

(IT ROOM)

E1

NEW

LP-B1

4#1/0, 1#6GRD, 2"C.

E1

A1

A1

A1

A1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text 127th WING/CIVIL ENGINEER

AutoCAD SHX Text Engineer/Consultants

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text

SELFRIDGE AIR

AutoCAD SHX Text

NATIONAL GUARD

AutoCAD SHX Text

BASE, MICHIGAN

AutoCAD SHX Text

REVISIONS:

AutoCAD SHX Text Project Number:

AutoCAD SHX Text File:

AutoCAD SHX Text Drawn By:

AutoCAD SHX Text Designed By:

AutoCAD SHX Text Checked By:

AutoCAD SHX Text 60554155

AutoCAD SHX Text Mark

AutoCAD SHX Text Date

AutoCAD SHX Text Description

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text Scale:

AutoCAD SHX Text Date:

AutoCAD SHX Text

02/13/18 100%%% FINAL

AutoCAD SHX Text

RJ

AutoCAD SHX Text

RJ PTC

AutoCAD SHX Text

DNB

AutoCAD SHX Text 02-21-18

ADDENDUM #1