ERDC Elevator Maintenance and Repair Services Elevator Maintenance Discrepancy Questions and Answers.docx
DOCX document 16 KB Posted
- Attached to
- ERDC Elevator Maintenance and Repair Services
- Solicitation number
- W912HZ23R0011
About this file
This document contains questions and answers regarding elevator maintenance and testing requirements for a federal solicitation. The solicitation is for elevator maintenance and repair services at the U.S. Army Engineer Research and Development Center in Vicksburg, Mississippi. The period of performance is a multiple year contract with one base year and four option years plus an additional six month option period. The contract will be awarded on a firm-fixed price basis. The questions and answers clarify that five-year elevator testing and inspections will be required in accordance with Mississippi state codes, even though federal regulations apply, and that any additional preexisting issues found during testing would be addressed separately.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amended_PWS TECHNICAL_EXHIBIT_3_ITM May 2023.docx | DOCX document | |
| Revised_ ERDC Elevator Maintenance and Repair Services Elevator Maintenance Discrepancy Questions and Answers.pdf | ||
| ERDC Elevator Maintenance and Repair Services Site Visit Questions and Answers.pdf | ||
| SITE VISIT2.pdf | ||
| SITE VISIT.docx | DOCX document | |
| SITE VISIT.pdf | ||
| PWS TECHNICAL_EXHIBIT_1_QASP_2022.docx | DOCX document | |
| PWS TECHNICAL EXHIBIT_ 2 List of Systems 2022.docx | DOCX document | |
| PWS TECHNICAL_EXHIBIT_4__CDRL_2022.docx | DOCX document | |
| PWS TECHNICAL_EXHIBIT_3_ITM_2022.docx | DOCX document | |
| W912HZ23R0011 Solicitation for ERDC Elevator Maintenance and Repair.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ERDC ELEVATOR MAINTENANCE AND REPAIR
QUESTIONS AND ANSWERS
*Noted Elevator Maintenance Discrepancy on System #3 Kone
Question
1. The last 5-year test was done in 2010 for System-3 (Kone EcoSpace) or B-3270 (ELHQ) and is currently 8 years overdue. The elevator will need to be weight tested to check elevator brakes, governor, and safeties. All safety switches, limits, door switches, and all other code compliant devices will also be checked during testing procedure.
Hydraulic Units Rupture Valve Test – On each unit that is equipped with a rupture valve, it will require a full load test. Test weights will be put on the elevator, the unit is to be ran greater than contract speed in the down direction in order to set the valve and ensure it will stop the elevator while also holding the capacity. The state of Mississippi has adopted the 2019 elevator code and this test is required on all rupture valves every 5 years. The valves have to be tagged with proper identification showing the test dates per 2019 code.
a. Response: The 5-year test is required; all bids should be submitted accordingly.
Once the contract is awarded, we will not entertain any additional quote/proposal for this specific issue.
Question
1. It is not mandatory in the State of Mississippi that the test be witnessed by an elevator inspection service. Due to the language of the bid documents, we are including the inspection fees in our proposal for witnessed testing on all these units. If you decide that you would like another proposal without the inspection fees included, please contact us so we can revise pricing.
1. Response: Even though we are the federal government, we are adhering to the State of MS mandates and requiring the elevator inspections per their statutes.
Question
1. If a contractor is awarded the contract, do the 5-year test, and then find other issues that were preexisting they would do that separately at that time, using the guaranteed labor rates for straight rate labor per hour, included in the maintenance proposal.
2. Response: We should wait and see if this ever comes to pass. The elevator has had regular maintenance from a Kone technician and has been in service for a while now without any major issues.