This document provides specifications for a federal construction contract opportunity. The project involves constructing a non-standard Battalion Operations Facility of approximately 92,000 square feet at Fort Benning, Georgia for a newly formed 75th Ranger Battalion. Primary facilities include administrative areas, an operations area with a Sensitive Compartmented Information Facility, a Ranger Operations Center, and Company Operations Facilities/Readiness Bays. Supporting facilities include site development, utilities, lighting, paving, parking, walks, curbs, gutters, storm drainage, information systems, landscaping and signage. The period of performance is 740 calendar days. The contract will be procured using Lowest Price Technically Acceptable with a value between $25 million and $100 million.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RTA SUBMITTAL
SPECIFICATIONS – Vol 4 of 5
SOF BATTALION HEADQUARTERS FACILITY
Fort Benning, Georgia
CONTRACT SOLICITATION NO. W912HN22R3004
B&V PROJECT NO. 043146
B&V FILE NO. 50.1000
PREPARED FOR
U.S. Army Corps of Engineers, Savannah District
21 JANUARY 2022
PREPARED BY:
BLACK & VEATCH SPECIAL PROJECTS
6800 WEST 115TH STREET
OVERLAND PARK, KANSAS 66211
B la c k
V e a tc h H o ld in g
C o m p a n y
A ll r ig h ts r e se rv e d
Ft. Benning SOF BN HQ Facility 43146
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 58 00 PROJECT IDENTIFICATION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 TOTAL BUILDING COMMISSIONING
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION and DECONSTRUCTION
DI VI SI ON 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 UNIT MASONRY
DI VI SI ON 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
05 72 00 DECORATIVE METAL SPECIALTIES
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
PROJECT TABLE OF CONTENTS Page 1 (Revised by Amendment 0003)
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 21 13 BOARD INSULATION
07 21 13.01 SPRAY FOAM INSULATION
07 21 16 BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 13 METAL WALL PANELS
07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 31 00 ACCESS DOORS AND PANELS
08 33 23 OVERHEAD COILING DOORS
08 34 59 VAULT DOORS AND DAY GATES
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DI VI SI ON 09 - FI NI SHES
09 22 00 SUPPORTS GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, PORCELAIN AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 66 23 RESINOUS MATRIX TERRAZZO FLOORING AND TERRAZZO TILE
09 68 00 CARPETING
09 69 13 RIGID GRID ACCESS FLOORING
09 72 00 WALLCOVERINGS
09 84 20 ACOUSTICAL WALL PANELS
09 90 00 PAINTS AND COATINGS
DI VI SI ON 10 - SPECI ALTI ES
10 11 00 VISUAL DISPLAY UNITS
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHER CABINETS
10 51 13 METAL LOCKERS
10 51 20 PHENOLIC LOCKERS
10 56 13 STEEL SHELVING
PROJECT TABLE OF CONTENTS Page 2 (Revised by Amendment 0003)
DI VI SI ON 11 - EQUI PMENT
11 11 37 ELECTRIC VEHICLE SUPPLY EQUIPMENT
DI VI SI ON 12 - FURNI SHI NGS
12 21 00 WINDOW BLINDS
12 24 13 ROLLER WINDOW SHADES
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
12 50 00.13 10 FURNITURE AND FURNITURE INSTALLATION
12 59 00 SYSTEMS FURNITURE
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 48 73 SEISMIC/ATFP CONTROL FOR MISCELLANEOUS EQUIPMENT/COMPONENTS
13 49 20.00 10 RF SHIELDING
DI VI SI ON 14 - CONVEYI NG EQUI PMENT
14 24 13 HYDRAULIC FREIGHT ELEVATORS
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
21 13 16 DRY PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
21 30 00 FIRE PUMPS
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBING, GENERAL PURPOSE
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 05 15 COMMON PIPING FOR HVAC
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.01 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER
BUILDING CONTROL SYSTEMS
23 11 20 FACILITY GAS PIPING
23 21 23 HYDRONIC PUMPS
23 30 00 HVAC AIR DISTRIBUTION
23 52 00 HEATING BOILERS
23 64 26 HOT AND CONDENSER WATER PIPING SYSTEMS
23 65 00 COOLING TOWERS
23 81 47 WATER-LOOP HEAT PUMP SYSTEMS
23 83 00.00 20 ELECTRIC SPACE HEATING EQUIPMENT
DI VI SI ON 25 - I NTEGRATED AUTOMATI ON
25 05 11.14 24 CYBERSECURITY FOR ELEVATOR CONTROL SYSTEM
25 05 11.21 CYBERSECURITY FOR FIRE AND LIFE SAFETY
25 05 11.21 03 CYBERSECURITY FOR FIRE PUMP CONTROL SYSTEM
25 05 11.23 CYBERSECURITY FOR BUILDING AUTOMATION SYSTEM
PROJECT TABLE OF CONTENTS Page 3 (Revised by Amendment 0003)
25 05 11.26 32 CYBERSECURITY FOR GENERATOR CONTROL SYSTEM
25 05 11.26 33 CYBERSECURITY FOR UPS CONTROL SYSTEM
25 05 11.26 34 CYBERSECURITY FOR VEHICLE CHARGING SYSTEM
25 05 11.26 36 CYBERSECURITY FOR ATS CONTROL SYSTEM
25 05 11.26 51 CYBERSECURITY FOR BUILDING LIGHTING CONTROL SYSTEM
25 08 10 ENERGY MONITORING AND CONTROL SYSTEM TESTING
25 10 10 ENERGY MONITORING AND CONTROL SYSTEM (EMCS) INTEGRATION
DI VI SI ON 26 - ELECTRI CAL
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00 LOW-VOLTAGE SWITCHGEAR
26 24 13 SWITCHBOARDS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS
26 32 15.00 NATURAL GAS ENGINE-GENERATOR SET STATIONARY 1000 KW, WITH
AUXILIARIES
26 33 53 STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
26 36 23 AUTOMATIC TRANSFER SWITCHES AND BY-PASS/ISOLATION SWITCH
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 52 24 AUDIO-VISUAL SYSTEM
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 08 10 ELECTRONIC SECURITY SYSTEM ACCEPTANCE TESTING
28 10 05 ELECTRONIC SECURITY SYSTEMS (ESS)
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM,
ADDRESSABLE
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19.13 GEOTEXTILES FOR EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 31 16.13 CHEMICAL TERMITE CONTROL
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENT
32 11 20 BASE COURSE FOR RIGID AND SUBBASES FOR FLEXIBLE PAVING
32 11 23 AGGREGATE BASE COURSES
32 11 23.23 BASE COURSE DRAINAGE LAYERS
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 32 23.13 SEGMENTAL CONCRETE BLOCK RETAINING WALL
32 35 00 PEDESTRIAN BRIDGE
PROJECT TABLE OF CONTENTS Page 4 (Revised by Amendment 0003)
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DI VI SI ON 33 - UTI LI TI ES
33 05 23.13 UTILITY HORIZONTAL DIRECTIONAL DRILLING
33 11 23 NATURAL GAS PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 47 13.01 BIORETENTION AREAS
33 49 23 UNDERGROUND DETENTION SYSTEM
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DI VI SI ON 46 - WATER AND WASTEWATER EQUI PMENT
46 25 14 COALESCING OIL-WATER SEPARATORS
*3
APPENDICES
APPENDIX B CONSTRUCTION SECURITY PLAN
APPENDIX C GEOTECHNICAL REPORT
APPENDIX D ENVIRONMENTAL PERMITS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 5 (Revised by Amendment 0003)
SECTION 23 09 13
INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
11/15
PART 1 GENERAL
1.1 SUMMARY
This section provides for the instrumentation control system components excluding direct digital controllers, network controllers, gateways etc.
that are necessary for a completely functional automatic control system.
When combined with a Direct Digital Control (DDC) system, the Instrumentation and Control Devices covered under this section must be a complete system suitable for the control of the heating, ventilating and air conditioning (HVAC) and other building-level systems as specified and indicated.
a. Install hardware to perform the control sequences as specified and indicated and to provide control of the equipment as specified and indicated.
b. Install hardware such that individual control equipment can be replaced by similar control equipment from other equipment manufacturers with no loss of system functionality.
c. Install and configure hardware such that the Government or their agents are able to perform repair, replacement, and upgrades of individual hardware without further interaction with the installing Contractor.
1.1.1 Verification of Dimensions
After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing any work.
1.1.2 Drawings
The Government will not indicate all offsets, fittings, and accessories that may be required on the drawings. Carefully investigate the mechanical, electrical, and finish conditions that could affect the work to be performed, arrange such work accordingly, and provide all work necessary to meet such conditions.
1.2 RELATED SECTIONS
Related work specified elsewhere.
Section 01 30 00 ADMINISTRATIVE REQUIREMENTS
Section 23 30 00 HVAC AIR DISTRIBUTION
Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
Section 23 09 23.01 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER
BUILDING CONTROL SYSTEMS
SECTION 23 09 13 Page 1
Section 23 21 23 HYDRONIC PUMPS
Section 23 52 00 HEATING BOILERS
Section 23 64 26 HOT AND CONDENSER WATER PIPING SYSTEMS
Section 23 65 00 COOLING TOWERS
Section 23 81 47 WATER-LOOP HEAT PUMP SYSTEMS
Section 23 83 00.00 20 ELECTRIC SPACE HEATING EQUIPMENT
Section 22 00 00 PLUMBING, GENERAL PURPOSE
Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. (AMCA)
AMCA 500-D (2018) Laboratory Methods of Testing Dampers for Rating
AMCA 511 (2010; R 2016) Certified Ratings Program for Air Control Devices
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B16.15 (2018) Cast Copper Alloy Threaded Fittings Classes 125 and 250
ASME B16.18 (2018) Cast Copper Alloy Solder Joint Pressure Fittings
ASME B16.22 (2018) Standard for Wrought Copper and Copper Alloy Solder Joint Pressure Fittings
ASME B16.26 (2018) Standard for Cast Copper Alloy Fittings for Flared Copper Tubes
ASME B16.34 (2017) Valves - Flanged, Threaded and Welding End
ASME B40.100 (2013) Pressure Gauges and Gauge Attachments
ASTM INTERNATIONAL (ASTM)
ASTM A269/A269M (2015; R 2019) Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service
ASTM A536 (1984; R 2019; E 2019) Standard Specification for Ductile Iron Castings
SECTION 23 09 13 Page 2
ASTM B32 (2008; R 2014) Standard Specification for Solder Metal
ASTM B75/B75M (2020) Standard Specification for Seamless Copper Tube
ASTM B88 (2020) Standard Specification for Seamless Copper Water Tube
ASTM D635 (2018) Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position
ASTM D638 (2014) Standard Test Method for Tensile Properties of Plastics
ASTM D792 (2013) Density and Specific Gravity (Relative Density) of Plastics by Displacement
ASTM D1238 (2013) Melt Flow Rates of Thermoplastics by Extrusion Plastometer
ASTM D1693 (2015) Standard Test Method for Environmental Stress-Cracking of Ethylene Plastics
FLUID CONTROLS INSTITUTE (FCI)
FCI 70-2 (2013) Control Valve Seat Leakage
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 142 (2007; Errata 2014) Recommended Practice for Grounding of Industrial and Commercial Power Systems - IEEE Green Book
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
NFPA 90A (2018) Standard for the Installation of Air Conditioning and Ventilating Systems
UNDERWRITERS LABORATORIES (UL)
UL 94 (2013; Reprint Sep 2017) UL Standard for Safety Tests for Flammability of Plastic Materials for Parts in Devices and Appliances
UL 1820 (2004; Reprint May 2013) UL Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics
UL 5085-3 (2006; Reprint Nov 20121) Low Voltage Transformers - Part 3: Class 2 and Class 3
SECTION 23 09 13 Page 3
Transformers
1.4 SUBMITTALS
Submittal requirements are specified in Section 23 09 00 INSTRUMENTATION
AND CONTROL FOR HVAC.
1.5 DELIVERY AND STORAGE
Store and protect products from the weather, humidity, and temperature variations, dirt and dust, and other contaminants, within the storage condition limits published by the equipment manufacturer.
1.6 INPUT MEASUREMENT ACCURACY
Select, install and configure sensors, transmitters and DDC Hardware such that the maximum error of the measured value at the input of the DDC hardware is less than the maximum allowable error specified for the sensor or instrumentation.
1.7 SUBCONTRACTOR SPECIAL REQUIREMENTS
Perform all work in this section in accordance with the paragraph entitled CONTRACTOR SPECIAL REQUIREMENTS in Section 01 30 00 ADMINISTRATIVE
REQUIREMENTS.
PART 2 PRODUCTS
2.1 EQUIPMENT
2.1.1 General Requirements
All products used to meet this specification must meet the indicated requirements, but not all products specified here will be required by every project. All products must meet the requirements both Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC and this Section.
2.1.2 Operation Environment Requirements
Unless otherwise specified, provide products rated for continuous operation under the following conditions:
2.1.2.1 Pressure
Pressure conditions normally encountered in the installed location.
2.1.2.2 Vibration
Vibration conditions normally encountered in the installed location.
2.1.2.3 Temperature
a. Products installed indoors: Ambient temperatures in the range of 32 to 112 degrees F and temperature conditions outside this range normally encountered at the installed location.
b. Products installed outdoors or in unconditioned indoor spaces: Ambient temperatures in the range of -35 to +151 degrees F and temperature conditions outside this range normally encountered at the installed
SECTION 23 09 13 Page 4 location.
2.1.2.4 Humidity
10 to 95 percent relative humidity, non-condensing and also humidity conditions outside this range normally encountered at the installed location.
2.2 WEATHERSHIELDS
Provide weathershields constructed of galvanized steel painted white, unpainted aluminum, aluminum painted white, or white PVC.
2.3 TUBING
2.3.1 Copper
Provide ASTM B75/B75M or ASTM B88 rated tubing meeting the following requirements:
a. For tubing 0.375 inch outside diameter and larger provide tubing with minimum wall thickness equal to ASTM B88, Type M
b. For tubing less than 0.375 inch outside diameter provide tubing with minimum wall thickness of 0.025 inch
c. For exposed tubing and tubing for working pressures greater than 30 psig provide hard copper tubing.
d. Provide fittings which are ASME B16.18 or ASME B16.22 solder type using ASTM B32 95-5 tin-antimony solder, or which are ASME B16.26 compression type.
2.3.2 Stainless Steel
For stainless steel tubing provide tubing conforming to ASTM A269/A269M
2.3.3 Plastic
Provide plastic tubing with the burning characteristics of linear low-density polyethylene tubing which is self-extinguishing when tested in accordance with ASTM D635, has UL 94 V-2 flammability classification or better, and which withstands stress cracking when tested in accordance with ASTM D1693. Provide plastic-tubing bundles with Mylar barrier and flame-retardant polyethylene jacket.
2.3.4 Polyethylene Tubing
Provide flame-resistant, multiple polyethylene tubing in flame-resistant protective sheath with mylar barrier, or unsheathed polyethylene tubing in rigid metal, intermediate metal, or electrical metallic tubing conduit for areas where tubing is exposed. Single, unsheathed, flame-resistant polyethylene tubing may be used where concealed in walls or above ceilings and within control panels. Do not provide polyethylene tubing for systems indicated as critical and smoke removal systems, or for systems with working pressures over 30 psig. Provide compression or brass barbed push-on type fittings. Provide extruded seamless polyethylene tubing conforming to the following:
SECTION 23 09 13 Page 5
a. Minimum Burst Pressure Requirements: 100 psig at 75 degrees F to 25 psig at 150 degrees F.
b. Stress Crack Resistance: ASTM D1693, 200 hours minimum.
c. Tensile Strength (Minimum): ASTM D638, 1100 psi.
d. Flow Rate (Average): ASTM D1238, 0.30 decigram per minute.
e. Density (Average): ASTM D792, 57.5 pounds per cubic feet.
f. Burn rate: ASTM D635
g. Flame Propagation: UL 1820 , less than 5 feet ASTM D635
h. Average Optical Density: UL 1820 , less than 0.15 ASTM D635
2.4 WIRE AND CABLE
Provide wire and cable meeting the requirements of NFPA 70 and NFPA 90A in addition to the requirements of this specification and referenced specifications.
2.4.1 Terminal Blocks
For terminal blocks which are not integral to other equipment, provide terminal blocks which are insulated, modular, feed-through, clamp style with recessed captive screw-type clamping mechanism, suitable for DIN rail mounting, and which have enclosed sides or end plates and partition plates for separation.
2.4.2 Control Wiring for Binary Signals
For Control Wiring for Binary Signals, provide 18 AWG copper or thicker wire rated for 300-volt service.
2.4.3 Control Wiring for Analog Signals
For Control Wiring for Analog Signals, provide 18 AWG or thicker, copper, single- or multiple-twisted wire meeting the following requirements:
a. minimum 2 inch lay of twist
b. 100 percent shielded pairs
c. at least 300-volt insulation
d. each pair has a 20 AWG tinned-copper drain wire and individual overall pair insulation
e. cables have an overall aluminum-polyester or tinned-copper cable-shield tape, overall 20 AWG tinned-copper cable drain wire, and overall cable insulation.
2.4.4 Power Wiring for Control Devices
For 24-volt circuits, provide insulated copper 18 AWG or thicker wire rated for 300 VAC service. For 120-volt circuits, provide 14 AWG or thicker stranded copper wire rated for 600-volt service.
SECTION 23 09 13 Page 6
2.4.5 Transformers
Provide UL 5085-3 approved transformers. Select transformers sized so that the connected load is no greater than 80 percent of the transformer rated capacity.
2.5 MOTOR OPERATED VALVES
Provide valves with stainless-steel stems and stuffing boxes with extended necks to clear the piping insulation. Provide valves with bodies meeting ASME B16.34 or ASME B16.15 pressure and temperature class ratings based on the design operating temperature and 150 percent of the system design operating pressure. Unless otherwise specified or indicated, provide valves meeting FCI 70-2 Class III leakage rating. Provide valves rated for modulating or two-position service as indicated, which close against a differential pressure indicated as the Close-Off pressure and which are Normally-Open, Normally-Closed, or Fail-In-Last-Position as indicated.
2.5.1 Valve Type
2.5.1.1 Liquid Service 150 Degrees F or Less
Use either globe valves or ball valves except that butterfly valves shall be used for sizes 4 inch and larger.
2.5.1.2 Liquid Service Above 150 Degrees F
a. Two-position valves: Use either globe valves or ball valves except use butterfly valves for sizes 4 inch and larger.
b. Modulating valves: Use globe valves except that butterfly valves shall be used for sizes 4 inch and larger.
2.5.2 Valve Flow Coefficient and Flow Characteristic
2.5.2.1 Two-Way Modulating Valves
Provide the valve coefficient (Cv) indicated. Provide equal-percentage flow characteristic for liquid service except for butterfly valves.
2.5.3 Two-Position Valves
Use full line size full port valves with maximum available (Cv).
2.5.4 Globe Valves
2.5.4.1 Liquid Service Not Exceeding 150 Degrees F
a. Valve body and body connections:
(1) valves 1-1/2 inches and smaller: brass or bronze body, with threaded or union ends
(2) valves from 2 inches to 3 inches inclusive: brass, bronze, or iron bodies. 2 inch valves with threaded connections; 2-1/2 to 3 inches valves with flanged connections
b. Internal valve trim: Brass or bronze.
SECTION 23 09 13 Page 7
c. Stems: Stainless steel.
2.5.4.2 Liquid Service Not Exceeding 250 Degrees F
a. Valve body and body connections:
(1) valves 1-1/2 inches and smaller: brass or bronze body, with threaded or union ends
(2) valves from 2 inches to 3 inches inclusive: brass, bronze, or iron bodies. 2 inch valves with threaded connections; 2-1/2 to 3 inches valves with flanged connections
b. Internal trim: Type 316 stainless steel including seats, seat rings, modulation plugs, valve stems, and springs.
c. Provide valves with non-metallic parts suitable for a minimum continuous operating temperature of 250 degrees F or 50 degrees F above the system design temperature, whichever is higher.
2.5.5 Ball Valves
2.5.5.1 Liquid Service Not Exceeding 150 Degrees F
a. Valve body and connections:
(1) valves 1-1/2 inches and smaller: bodies of brass or bronze, with threaded or union ends
(2) valves from 2 inches to 3 inches inclusive: bodies of brass, bronze, or iron. 2 inch valves with threaded connections; valves from 2-1/2 to 3 inches with flanged connections.
b. Ball: Stainless steel or nickel-plated brass or chrome-plated brass.
c. Seals: Reinforced Teflon seals and EPDM O-rings.
d. Stem: Stainless steel, blow-out proof.
e. Provide valves compatible with a solution of 50 percent ethylene or propylene glycol.
2.5.6 Butterfly Valves
Provide butterfly valves which are threaded lug type suitable for dead-end service and modulation to the fully-closed position, with carbon-steel bodies or with ductile iron bodies in accordance with ASTM A536. Provide butterfly valves with non-corrosive discs, stainless steel shafts supported by bearings, and EPDM seats suitable for temperatures from -20 to +250 degrees F. Provide valves meeting FCI 70-2 Class VI leakage rating.
2.5.7 Heat Pump Shutoff Valves
For WAHP and DOAS water coils provide motor operated on/off shutoff valves that are full-port ball valve type with screw type, flange, or solder-type ends. Valves shall be two-way or three-way as indicated in the drawings.
Provide maximum available valve coefficient (Cv).
SECTION 23 09 13 Page 8
2.6 DAMPERS
2.6.1 Damper Assembly
Provide single damper sections with blades no longer than 48 inches and which are no higher than 72 inches and damper blade width of 8 inches or less. When larger sizes are required, combine damper sections. Provide dampers made of steel, or other materials where indicated and with assembly frames constructed of 0.07 inch minimum thickness galvanized or stainless steel channels with mitered and welded corners. Steel channel frames constructed of 0.06 inch minimum thickness are acceptable provided the corners are reinforced.
a. Flat blades must be made rigid by folding the edges.
b. Damper axles must be 1/2 inch minimum, plated steel rods supported in the damper frame by stainless steel or bronze bearings. Blades mounted vertically must be supported by thrust bearings.
c. Provide dampers which do not exceed a pressure drop through the damper of 0.04 inches water gauge at 1000 ft/min in the wide-open position.
Provide dampers with frames not less than 2 inch in width. Provide dampers which have been tested in accordance with AMCA 500-D.
2.6.2 Operating Linkages
For operating links external to dampers, such as crank arms, connecting rods, and line shafting for transmitting motion from damper actuators to dampers, provide links able to withstand a load equal to at least 300 percent of the maximum required damper-operating force without deforming.
Rod lengths must be adjustable. Links must be brass, bronze, zinc-coated steel, or stainless steel. Working parts of joints and clevises must be brass, bronze, or stainless steel. Adjustments of crank arms must control the open and closed positions of dampers.
2.6.3 Damper Types
2.6.3.1 Flow Control Dampers
Provide parallel-blade or opposed blade type dampers for outside air, return air, relief air, exhaust, as indicated on the Damper Schedule.
Blades must have interlocking edges. The channel frames of the dampers must be provided with jamb seals to minimize air leakage. Air inlet and outlet dampers on the outside air unit must meet AMCA 511 Class 1A requirements. Unless otherwise indicated, all other dampers must meet AMCA 511 Class 2 requirements. Outside air damper seals must be suitable for an operating temperature range of -40 to +167 degrees F. Dampers must be rated at not less than 2000 ft/min air velocity.
2.7 SENSORS AND INSTRUMENTATION
Unless otherwise specified, provide sensors and instrumentation which incorporate an integral transmitter. Sensors and instrumentation, including their transmitters, must meet the specified accuracy and drift requirements at the input of the connected DDC Hardware's analog-to-digital conversion.
SECTION 23 09 13 Page 9
2.7.1 Analog and Binary Transmitters
Provide transmitters which match the characteristics of the sensor.
Transmitters providing analog values must produce a linear 4-20 mAdc, 0-10 Vdc signal corresponding to the required operating range and must have zero and span adjustment. Transmitters providing binary values must have dry contacts rated at 1A at 24 Volts AC.
2.7.2 Network Transmitters
Sensors and Instrumentation incorporating an integral network connection are considered DDC Hardware and must meet the DDC Hardware requirements of Section 23 09 23.01 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS when used in a Lonworks network.
2.7.3 Temperature Sensors
Use a single type of temperature sensor for all instances where the particular sensor type is sufficient to reliably accomplish the design intent indicated. Temperature sensors may be provided without transmitters. Where transmitters are used, the range must be the smallest available from the manufacturer and suitable for the application such that the range encompasses the expected range of temperatures to be measured.
The end to end accuracy includes the combined effect of sensitivity, hysteresis, linearity and repeatability between the measured variable and the end user interface (graphic presentation) including transmitters if used.
2.7.3.1 Sensor Accuracy and Stability of Control
2.7.3.1.1 Conditioned Space Temperature
Plus or minus 0.5 degree F over the operating range.
2.7.3.1.2 Unconditioned Space Temperature
a. Plus or minus 1 degree F over the range of 30 to 131 degrees F AND
b. Plus or minus 4 degrees F over the rest of the operating range.
2.7.3.1.3 Duct Temperature
Plus or minus 0.5 degree F
2.7.3.1.4 Outside Air Temperature
a. Plus or minus 2 degrees F over the range of -30 to +130 degrees F AND
b. Plus or minus 1 degree F over the range of 30 to 130 degrees F.
2.7.3.1.5 Condenser Water
Plus or minus 0.8 degrees F.
2.7.3.1.6 Heating Hot Water
Plus or minus 2 degrees F.
SECTION 23 09 13 Page 10
2.7.3.2 Transmitter Drift
The maximum allowable transmitter drift: 0.25 degrees F per year.
2.7.3.3 Point Temperature Sensors
Point Sensors must be encapsulated in epoxy, series 300 stainless steel, anodized aluminum, or copper.
2.7.3.4 Temperature Sensor Details
2.7.3.4.1 Room Type
Provide the sensing element components within a decorative protective cover suitable for surrounding decor.
2.7.3.4.2 Duct Probe Type
Ensure the probe is long enough to properly sense the air stream temperature.
2.7.3.4.3 Duct Averaging Type
Continuous averaging sensors must be one foot in length for each 1 square foot of duct cross-sectional area, and a minimum length of 5 feet.
2.7.3.4.4 Pipe Immersion Type
Provide minimum 3 inch immersion. Provide each sensor with a corresponding pipe-mounted sensor well, unless indicated otherwise.
Sensor wells must be stainless steel when used in steel piping, and brass when used in copper piping.
2.7.3.4.5 Outside Air Type
Provide the sensing element rated for outdoor use
2.7.4 Relative Humidity Sensor
Relative humidity sensors must use bulk polymer resistive or thin film capacitive type non-saturating sensing elements capable of withstanding a saturated condition without permanently affecting calibration or sustaining damage. The sensors must include removable protective membrane filters. Where required for exterior installation, sensors must be capable of surviving below freezing temperatures and direct contact with moisture without affecting sensor calibration. When used indoors, the sensor must be capable of being exposed to a condensing air stream (100 percent relative humidity) with no adverse effect to the sensor's calibration or other harm to the instrument. The sensor must be of the wall-mounted or duct-mounted type, as required by the application, and must be provided with any required accessories. Sensors used in duct high-limit applications must have a bulk polymer resistive sensing element. Duct-mounted sensors must be provided with a duct probe designed to protect the sensing element from dust accumulation and mechanical damage. Wall mount sensors for space humidity control may be included as integral with the temperature sensor as part of the space sensor module in accordance with the paragraph Space Sensor Module. Relative humidity (RH) sensors must measure relative humidity over a range of 0 percent to 100 percent with an accuracy of plus or minus 3 percent. RH sensors must
SECTION 23 09 13 Page 11 function over a temperature range of 40 to 135 degrees F and must not drift more than 1 percent per year.
2.7.5 Differential Pressure Instrumentation
2.7.5.1 Differential Pressure Sensors
Provide Differential Pressure Sensors with ranges as indicated or as required for the application. Pressure sensor ranges must not exceed the high end range indicated on the Points Schedule by more than 50 percent.
The over pressure rating must be a minimum of 150 percent of the highest design pressure of either input to the sensor. The accuracy must be plus or minus 1 percent of full scale. The sensor must have a maximum drift of 2 percent per year
2.7.5.2 Differential Pressure Switch
Provide differential pressure switches with a user-adjustable setpoint which are sized for the application such that the setpoint is between 25 percent and 75 percent of the full range. The over pressure rating must be a minimum of 150 percent of the highest design pressure of either input to the sensor. The switch must have two sets of contacts and each contact must have a rating greater than it's connected load. Contacts must open or close upon rise of pressure above the setpoint or drop of pressure below the setpoint as indicated.
2.7.6 Flow Sensors
2.7.6.1 Airflow Measurement Array (AFMA)
2.7.6.1.1 Airflow Straightener
Provide AFMAs which contain an airflow straightener. The straightener must be contained inside a flanged sheet metal casing, with the AFMA located as specified according to the published recommendation of the AFMA manufacturer. Air-flow straighteners, where required, must be constructed of 0.125 inch honeycomb and the depth of the straightener must not be less than 1.5 inches. In order to minimize turbulence AFMA must be installed at least 1 duct diameter downstream of 90 degree elbows with a turning vane, 3 duct diameters downstream of 90 degree elbows without turning vanes, and at least 1/6 duct length upstream of any duct transition.
2.7.6.1.2 Resistance to Airflow
The resistance to air flow through the AFMA, including the airflow straightener must not exceed 0.085 inch water gauge at an airflow of 2,000 fpm. AFMA construction must be suitable for operation at airflows of up to 5000 fpm over a temperature range of 40 to 120 degrees F.
2.7.6.1.3 Outside Air Temperature
In outside air measurement or in low-temperature air delivery applications, provide an AFMA certified by the manufacturer to be accurate as specified over a temperature range of 10 to +120 degrees F.
2.7.6.1.4 Electronic AFMA
Each electronic AFMA must consist of an array of velocity sensing elements of the resistance temperature detector (RTD) or thermistor type. The
SECTION 23 09 13 Page 12 sensing elements must be distributed across the duct cross section in the quantity and pattern specified or recommended by the published application data of the AFMA manufacturer. Electronic AFMAs must have an accuracy of plus or minus 5 percent over a range of 125 to 5,000 fpm and the output must be temperature compensated over a range of 32 to 212 degrees F.
2.7.6.1.5 Fan Inlet Measurement Devices
Fan inlet measurement devices cannot be used unless indicated on the drawings or schedules.
2.7.6.2 Ultrasonic Flow Meter
Provide Ultrasonic Flow Meters complete with matched transducers, self aligning installation hardware and transducer cables, and portable meter with display. Ultrasonic transducers must be optimized for the specific pipe and process conditions for the application. The flow meter accuracy must plus or minus 1 percent of rate from 0 to 40 ft/sec. The flowmeter must include either dry contact pulse outputs, 4-20mA, 0-10Vdc or 0-5Vdc output. The portable meter shall be hand-held; configurable based on pipe material, pipe OD, wall-thickness, and fluid; and display instantaneous flowrate, totalized flow, calibration menu, and daily flow report.
2.7.6.3 Flow Switch
Flow switch must have a repetitive accuracy of plus or minus 10 percent of actual flow setting. Switch actuation must be adjustable over the operating flow range, and must be sized for the application such that the setpoint is between 25 percent and 75 percent of the full range. The switch must have Form C snap-action contacts, rated for the application.
The flow switch must have non flexible paddle with magnetically actuated contacts and be rated for service at a pressure greater than the installed conditions. Flow switch for use in sewage system must be rated for use in corrosive environments encountered.
2.7.7 Electrical Instruments
Provide Electrical Instruments with an input range as indicated or sized for the application. Unless otherwise specified, AC instrumentation must be suitable for 60 Hz operation.
2.7.7.1 Current Transducers
Current transducers must accept an AC current input and must have an accuracy of plus or minus 2 percent of full scale. The device must have a means for calibration. Current transducers for variable frequency applications must be rated for variable frequency operation.
2.7.7.2 Current Sensing Relays (CSRs)
Current sensing relays (CSRs) must provide a normally-open contact with a voltage and amperage rating greater than its connected load. Current sensing relays must be of split-core design. The CSR must be rated for operation at 200 percent of the connected load. Voltage isolation must be a minimum of 600 volts. The CSR must auto-calibrate to the connected load or be adjustable and field calibrated. Current sensors for variable frequency applications must be rated for variable frequency operation.
SECTION 23 09 13 Page 13
2.7.7.3 Voltage Transducers
Voltage transducers must accept an AC voltage input and have an accuracy of plus or minus 0.25 percent of full scale. The device must have a means for calibration. Line side fuses for transducer protection must be provided.
2.7.7.4 Energy Metering
2.7.7.4.1 Watt or Watthour Transducers
Watt transducers must measure voltage and current and must output both kW and kWh as indicated. kW outputs must have an accuracy of plus or minus
0.5 percent over a power factor range of 0.1 to 1. kWh outputs must have an accuracy of plus or minus 0.5 percent over a power factor range of 0.1 to 1.
2.7.7.4.2 Hydronic BTU Meters
The BTU meter shall be the ultrasonic type, and shall come complete from the manufacturer with meter, ultrasonic transducers, temperature transmitters for the supply/return that can be installed remote from the ultrasonic transducers, and all cabling and instrumentation necessary for install and operation. The BTU meter is to be supplied with wall mount hardware and be capable of being installed remote from the flow meter. The BTU meter must include an LCD display for local indication of energy rate, flow rate, supply temperature, and return temperature; and for display of parameters and settings during configuration. Each BTU meter must be factory configured for its specific application and be completely field configurable by the user via a front panel keypad (no special interface device or computer required). The unit must output Energy Rate, Energy Total, Flow Rate, Supply Temperature, and Return Temperature. An integral transmitter is to provide a linear analog or configurable pulse output signal representing the energy rate; and the signal must be compatible with building automation system DDC Hardware to which the output is connected.
2.7.8 Occupancy Sensors
Occupancy sensors must have occupancy-sensing sensitivity adjustment and an adjustable off-delay timer with a setpoint of 15 minutes. Adjustments accessible from the face of the unit are preferred. Occupancy sensors must be rated for operation in ambient air temperatures ranging from 40 to 95 degrees F or temperatures normally encountered in the installed location. Sensors integral to wall mount on-off light switches must have an auto-off switch. Wall switch sensors must be decorator style and must fit behind a standard decorator type wall plate. All occupancy sensors, power packs, and slave packs must be UL listed. In addition to any outputs required for lighting control, the occupancy sensor must provide an output for the HVAC control system, or else include a separate occupancy sensor for connection to the HVAC control system.
2.7.8.1 Passive Infrared (PIR) Occupancy Sensors
PIR occupancy sensors must have a multi-level, multi-segmented viewing lens and a conical field of view with a viewing angle of 180 degrees and a detection of at least 20 feet unless otherwise indicated or specified.
PIR Sensors must provide field-adjustable background light-level adjustment with an adjustment range suitable to the light level in the
SECTION 23 09 13 Page 14 sensed area, room or space. PIR sensors must be immune to false triggering from RFI and EMI.
2.7.8.2 Ultrasonic Occupancy Sensors
Ultrasonic sensors must operate at a minimum frequency 32 kHz and must be designed to not interfere with hearing aids.
2.7.8.3 Dual-Technology Occupancy Sensor (PIR and Ultrasonic)
Dual-Technology Occupancy Sensors must meet the requirements of both PIR and Ultrasonic Occupancy Sensors.
2.7.9 Vibration Switch
Vibration switch must be provided and installed on the cooling tower and pumps by the manufacturer. Vibration switches shall function to protect the pumps and/or tower from damage caused by excessive vibration.
2.7.10 Conductivity Sensor
Sensor must include local indicating meter and must be suitable for measurement of conductivity of water in boilers, chilled water systems, condenser water systems, distillation systems, or potable water systems as indicated. Sensor must sense from 0 to 10 microSeimens per centimeter (µS/cm) for distillation systems, 0 to 100 µS/cm for boiler, chilled water, and potable water systems and 0 to 1000 µS/cm for condenser water systems. Contractor must field verify the ranges for particular applications and adjust the range as required. The output must be temperature compensated over a range of 32 to 212 degrees F. The accuracy must be plus or minus 2 percent of the full scale reading. Sensor must have automatic zeroing and must require no periodic maintenance or recalibration.
2.7.11 NOx Monitor
Monitor must continuously monitor and give local indication of boiler stack gas for NOx content. It must be a complete system designed to verify compliance with the Clean Air Act standards for NOx normalized to a 3 percent oxygen basis and must have a range of from 0 to 100 ppm. Sensor must be accurate to plus or minus 5 ppm. Sensor must output NOx and oxygen levels and binary output that changes state when the NOx level is above a locally adjustable NOx setpoint. Sensor must have normal, trouble and alarm lights. Sensor must have heat traced lines if the stack pickup is remote from the sensor. Sensor must be complete with automatic zero and span calibration using a timed calibration gas system, and must not require periodic maintenance or recalibration.
2.7.12 Turbidity Sensor
Sensor must include a local indicating meter and must be suitable for measurement of turbidity of water. Sensor must sense from 0 to 1000 Nephelometric Turbidity Units (NTU). Range must be field-verified for the particular application and adjusted as required. The output must be temperature compensated over a range of 32 to 212 degrees F. The accuracy must be plus or minus 5 percent of full scale reading. Sensor must have automatic zeroing and must not require periodic maintenance or recalibration.
SECTION 23 09 13 Page 15
2.7.13 Temperature Switch
2.7.13.1 Duct Mount Temperature Low Limit Safety Switch (Freezestat)
Duct mount temperature low limit switches (Freezestats) must be manual reset, low temperature safety switches at least 1 foot long per square foot of coverage which must respond to the coldest 18 inch segment with an accuracy of plus or minus 3.6 degrees F. The switch must have a field-adjustable setpoint with a range of at least 30 to 50 degrees F.
The switch must have two sets of contacts, and each contact must have a rating greater than its connected load. Contacts must open or close upon drop of temperature below setpoint as indicated and must remain in this state until reset.
2.7.13.2 Pipe Mount Temperature Limit Switch (Aquastat)
Pipe mount temperature limit switches (aquastats) must have a field-adjustable setpoint range appropriate for the temperature setpoints indicated in the sequence of operations, with, an accuracy of plus or minus
3.6 degrees F and a 10 degrees F fixed deadband. The switch must have two sets of contacts, and each contact must have a rating greater than its connected load. Contacts must open or close upon change of temperature above or below setpoint as indicated.
2.7.14 Damper End Switches
Each end switch must be a hermetically sealed switch with a trip lever and over-travel mechanism. The switch enclosure must be suitable for mounting on the duct exterior and must permit setting the position of the trip lever that actuates the switch. The trip lever must be aligned with the damper blade.
End switches integral to an electric damper actuator are allowed as long as at least one is adjustable over the travel of the actuator.
2.8 INDICATING DEVICES
All indicating devices must display readings in English (inch-pound) units.
2.8.1 Thermometers
Provide bi-metal type thermometers at locations indicated. Thermometers must have either 9 inch long scales or 3.5 inch diameter dials, with insertion, immersion, or averaging elements. Provide matching thermowells for pipe-mounted installations. Select scale ranges suitable for the intended service, with the normal operating temperature near the scale's midpoint. The thermometer's accuracy must be plus or minus 2 percent of the scale range.
2.8.1.1 Piping System Thermometers
Piping system thermometers must have brass, malleable iron or aluminum alloy case and frame, clear protective face, permanently stabilized glass tube with indicating-fluid column, white face, black numbers, and a 9 inch scale. Piping system thermometers must have an accuracy of plus or minus 1 percent of scale range. Thermometers for piping systems must have rigid stems with straight, angular, or inclined pattern. Thermometer stems must have expansion heads as required to prevent breakage at extreme temperatures. On rigid-stem thermometers, the space between bulb and stem
SECTION 23 09 13 Page 16 must be filled with a heat-transfer medium.
2.8.1.2 Air-Duct Thermometers
Air-duct thermometers must have perforated stem guards and 45-degree adjustable duct flanges with locking mechanism.
2.8.2 Pressure Gauges
Provide pipe-mounted pressure gauges at the locations indicated. Gauges must conform to ASME B40.100 and have a 4 inch diameter dial and shutoff cock. Select scale ranges suitable for the intended service, with the normal operating pressure near the scale's midpoint. The gauge's accuracy must be plus or minus 2 percent of the scale range.
Gauges must be suitable for field or panel mounting as required, must have black legend on white background, and must have a pointer traveling through a 270-degree arc. Gauge range must be suitable for the application with an upper end of the range not to exceed 150 percent of the design upper limit. Accuracy must be plus or minus 3 percent of scale range. Gauges must meet requirements of ASME B40.100 .
2.8.3 Low Differential Pressure Gauges
Gauges for low differential pressure measurements must be a minimum of 3.5 inch (nominal) size with two sets of pressure taps, and must have a diaphragm-actuated pointer, white dial with black figures, and pointer zero adjustment. Gauge range must be suitable for the application with an upper end of the range not to exceed 150 percent of the design upper limit. Accuracy must be plus or minus two percent of scale range.
2.9 OUTPUT DEVICES
2.9.1 Actuators
Actuators must be electric (electronic). All actuators must be normally open (NO), normally closed (NC) or fail-in-last-position (FILP) as indicated. Normally open and normally closed actuators must be of mechanical spring return type. Electric actuators must have an electronic cut off or other means to provide burnout protection if stalled.
Actuators must have a visible position indicator. Electric actuators must provide position feedback to the controller as indicated. Actuators must smoothly and fully open or close the devices to which they are applied.
Electric actuators must have a full stroke response time in both directions of 90 seconds or less at rated load. Electric actuators must be of the foot-mounted type with an oil-immersed gear train or the direct-coupled type. Where multiple electric actuators operate from a common signal, the actuators must provide an output signal identical to its input signal to the additional devices. All actuators must be rated for their operating environment. Actuators used outdoors must be designed and rated for outdoor use. Actuators under continuous exposure to water, such as those used in sumps, must be submersible.
Actuators incorporating an integral network connection are considered DDC Hardware and must meet the DDC Hardware requirements of Section 23 09 23.01
LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL
SYSTEMS.
SECTION 23 09 13 Page 17
2.9.1.1 Valve Actuators
Valve actuators must provide shutoff pressures and torques as indicated on the Valve Schedule.
2.9.1.2 Damper Actuators
Damper actuators must provide the torque necessary per damper manufacturer's instructions to modulate the dampers smoothly over its full range of operation and torque must be at least 6 inch-pounds/1 square foot of damper area for opposed blade dampers and 9 inch-pounds/1 square foot of damper area for parallel blade dampers.
2.9.1.3 Electric Actuators
Each actuator must have distinct markings indicating the full-open and full-closed position Each actuator must deliver the torque required for continuous uniform motion and must have internal end switches to limit the travel, or be capable of withstanding continuous stalling without damage.
Actuators must function properly within 85 to 110 percent of rated line voltage. Provide actuators with hardened steel running shafts and gears of steel or copper alloy. Fiber or reinforced nylon gears may be used for torques less than 16 inch-pounds.
a. Two-position actuators must be single direction, spring return, or reversing type. Two position actuator signals may either be the control power voltage or line voltage as needed for torque or appropriate interlock circuits.
b. Modulating actuators must be capable of stopping at any point in the cycle, and starting in either direction from any point. Actuators must be equipped with a switch for reversing direction, and a button to disengage the clutch to allow manual adjustments. Provide the actuator with a hand crank for manual adjustments, as applicable.
Modulating actuator input signals can either be a 4 to 20 mAdc or a 0-10 VDC signal.
2.9.2 Relays
Relays must have contacts rated for the intended application, indicator light, and dust proof enclosure. The indicator light must be lit when the coil is energized and off when coil is not energized.
Control relay contacts must have utilization category and ratings selected for the application. Each set of contacts must incorporate a normally open (NO), normally closed (NC) and common contact. Relays must be rated for a minimum life of one million operations.
2.10 USER INPUT DEVICES
User Input Devices, including potentiometers, switches and momentary contact push-buttons. Potentiometers must be of the thumb wheel or sliding bar type. Momentary Contact Push-Buttons may include an adjustable timer for their output. User input devices must be labeled for their function.
2.11 MULTIFUNCTION DEVICES
Multifunction devices are products which combine the functions of multiple
SECTION 23 09 13 Page 18 sensor, user input or output devices into a single product. Unless otherwise specified, the multifunction device must meet all requirements of each component device. Where the requirements for the component devices conflict, the multifunction device must meet the most stringent of the requirements.
2.11.1 Current Sensing Relay Command Switch
The Current Sensing Relay portion must meet all requirements…