This solicitation document describes a construction project for Berkeley Gate at Seymour Johnson Air Force Base in North Carolina. The project involves demolishing existing wedge vehicle barriers, pavement, curbs and sidewalks, and constructing a new entry control point that meets security requirements. The new construction will include a roadway with turnaround points and lighting, concrete curbing and sidewalks, active vehicle barrier net and passive brick knee wall systems, a privately operated vehicle search area with shelter and vertical screens, and an overwatch facility with a parking spot for a security forces vehicle. Bids are due by the date specified in the solicitation. The selected contractor will be required to complete the project in accordance with the specifications.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Seymour Johnson AFB, North Carolina
Solicitation Number
W912HN-21-B-3004
Berkeley Gate Entry Control Point Volume 2 of 3: Specification Divisions 10 – 34
PN VKAG1073433
March 2021
U.S. ARMY ENGINEER DISTRICT, SAVANNAH
CORPS OF ENGINEERS
100 WEST OGLETHORPE AVENUE
SAVANNAH, GEORGIA 31401-3640
US Army Corps Of Engineers Savannah District
Berkeley Gate Entry Control Point c21B3004 Seymour Johnson AFB, NC
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00 QUALITY CONTROL
01 45 00.15 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION
DI VI SI ON 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
03 45 00 PRECAST ARCHITECTURAL CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 UNIT MASONRY
DI VI SI ON 05 - METALS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 51 00 METAL STAIRS
05 52 00 METAL RAILINGS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 61 16 SOLID SURFACING FABRICATIONS
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 21 13 BOARD AND BLOCK INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 60 00 FLASHING AND SHEET METAL
07 61 14 STEEL STANDING SEAM ROOFING
07 92 00 JOINT SEALANTS
PROJECT TABLE OF CONTENTS Page 1
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS AND FRAMES
08 31 00 ACCESS DOORS AND PANELS
08 34 02 BULLET-RESISTANT COMPONENTS
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
DI VI SI ON 09 - FI NI SHES
09 06 00 SCHEDULES FOR FINISHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 90 00 PAINTS AND COATINGS
DI VI SI ON 10 - SPECI ALTI ES
10 14 00.10 EXTERIOR SIGNAGE
10 14 53 TRAFFIC SIGNAGE
10 26 00 WALL AND DOOR PROTECTION
10 44 16 FIRE EXTINGUISHERS
DI VI SI ON 12 - FURNI SHI NGS
12 24 13 ROLLER WINDOW SHADES
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 23 00 REFRIGERANT PIPING
23 30 00 HVAC AIR DISTRIBUTION
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
DI VI SI ON 25 - I NTEGRATED AUTOMATI ON
25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
DI VI SI ON 26 - ELECTRI CAL
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 28 01 COORDINATED POWER SYSTEM PROTECTION
26 32 15 ENGINE-GENERATOR SET STATIONARY 15-2500 KW, WITH
AUXILIARIES
26 36 23 AUTOMATIC TRANSFER SWITCHES
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
PROJECT TABLE OF CONTENTS Page 2
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 05 22 GEOTEXTILES USED AS FILTERS
31 11 00 CLEARING AND GRUBBING
31 31 16.13 CHEMICAL TERMITE CONTROL
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 01 16.71 COLD MILLING ASPHALT PAVING
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 11 23.23 BASE COURSE DRAINAGE LAYERS
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DI VI SI ON 33 - UTI LI TI ES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DI VI SI ON 34 - TRANSPORTATI ON
34 71 13.19 CRASH RATED ACTIVE VEHICLE BARRIERS AND CONTROLS
APPENDICES
APPENDIX A STANDARD FORMS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 3
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 14 00.10
EXTERIOR SIGNAGE
08/17
PART 1 GENERAL
1.1 REFERENCES
1.2 GENERAL REQUIREMENTS
1.2.1 Character Proportions and Heights
1.3 SUBMITTALS
1.4 QUALIFICATIONS
1.5 DELIVERY AND STORAGE
1.6 WARRANTY
2.1 GRAPHICS FOR EXTERIOR SIGNAGE SYSTEMS
2.1.1 Graphics
2.1.2 Messages
2.2 DIMENSIONAL BUILDING LETTERS
2.2.1 Fabrication
2.2.2 Typeface
2.2.3 Size
2.2.4 Finish
2.2.5 Mounting
2.3 CAST BRONZE
2.4 ANCHORS AND FASTENERS
2.5 SHOP FABRICATION AND MANUFACTURE
2.5.1 Factory Workmanship
2.5.2 Dissimilar Materials
2.5.3 Shop Painting
2.6 EXTERIOR LED DIGITAL DISPLAY SIGN
2.6.1 Housing
2.6.2 Display
2.6.3 Communications
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Anchorage
3.1.2 Protection and Cleaning
3.1.3 LED Digital Display Sign Installation
3.2 FIELD PAINTED FINISH
-- End of Section Table of Contents --
SECTION 10 14 00.10 Page 1 (Revised by Amendment 0001)
SECTION 10 14 00.10
EXTERIOR SIGNAGE
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A653/A653M (2019) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A924/A924M (2018) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B62 (2017) Standard Specification for Composition Bronze or Ounce Metal Castings
1.2 GENERAL REQUIREMENTS
All exterior signage must be provided by a single manufacturer. Exterior signage must be of the design, detail, sizes, types, and message content shown on the drawings, must conform to the requirements specified, and must be provided at the locations indicated. Submit exterior signage schedule in electronic media with spread sheet format. Spread sheet must include sign location, sign type, and message. Signs must be complete with lettering, framing as detailed, and related components for a complete installation. Each sample must consist of a complete sign panel with letters and symbols.
1.2.1 Character Proportions and Heights
Letters and numbers on indicated signs for handicapped-accessible buildings must have a width-to-height ratio between 3:5 and 1:1 and a stroke-width-to-height ratio between 1:5 and 1:10. Characters and numbers on indicated signs must be sized according to the viewing distance from which they are to be read. The minimum height is measured using an upper case letter "X". Lower case characters are permitted.
SECTION 10 14 00.10 Page 2 (Revised by Amendment 0001)
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Approved Detail Drawings
SD-03 Product Data
Installation
Exterior Signage ;
Exterior Led Digital Display Sign ; G
SD-04 Samples
Exterior Signage ;
SD-10 Operation and Maintenance Data
Protection and Cleaning ;
1.4 QUALIFICATIONS
Signs, plaques, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of the products. Items of equipment must essentially duplicate equipment that has been in satisfactory use at least 2 years prior to bid opening.
1.5 DELIVERY AND STORAGE
Materials must be wrapped for shipment and storage, delivered to the jobsite in manufacturer's original packaging, and stored in a clean, dry area in accordance with manufacturer's instructions.
1.6 WARRANTY
Manufacturer's standard performance guarantees or warranties that extend beyond a one year period must be provided.
SECTION 10 14 00.10 Page 3 (Revised by Amendment 0001)
PART 2 PRODUCTS
*1
2.0 EXTERIOR LED SIGN
Provide Exterior LED Sign to be installed on new brick Sign Monument Wall as shown on drawings. See Civil drawings for location of Sign Monument Wall. LED Sign to be approximately 9'-6"x 5'-6" x 8" to 10" deep. Dimensions to are maximum. Dimensions may vary if it is confirmed that any variation will fit within the panel area of the new Sign Monument Wall. Finish color to be selected from manufacturers standard colors. All other requirments of this section apply as they relate to Exterior LED Signage.
2.1 GRAPHICS FOR EXTERIOR SIGNAGE SYSTEMS
2.1.1 Graphics
Signage graphics must conform to the following:
a. Custom fabricated dark bronze non-ferrous,must be provided and fastened to the message panel with concealed fasteners. Letters must project a minimum of 3/8 inches from face of brick.
2.1.2 Messages
See drawings for message content. Typeface: Helvetica medium. Type size 6" size for bidding purposes. Lettering size shall match existing Berkeley Village sign.
2.2 DIMENSIONAL BUILDING LETTERS
2.2.1 Fabrication
Letters must be fabricated from dark bronze nonferrous material to match existing Berkeley Village sign.. Letters must be cleaned by chemical etching or cleaned ultrasonically in a special degreasing bath. Letters must be packaged for protection until installation.
2.2.2 Typeface
Typeface must be helvetica medium.
2.2.3 Size
Letter size must be as indicated on plans.
2.2.4 Finish
Oxidized bronze with clear coat finish must be provided.
2.2.5 Mounting
Threaded studs of number and size as recommended by manufacturer, must be used for concealed anchorage. Letters which project from the building line must have stud spacer sleeves. Letters, studs, and sleeves must be of the same material. Supply templates for mounting.
2.3 CAST BRONZE
Fabricate components with sharp corners, flat faces, and accurate
SECTION 10 14 00.10 Page 4 (Revised by Amendment 0001) profiles. Remove and polish burrs and rough spots. Finish faces to a uniform high luster. Cast bronze must be in accordance with ASTM B62.
2.4 ANCHORS AND FASTENERS
Exposed anchor and fastener materials must be compatible with metal to which applied and must match in color and finish and must be non-rusting, non-corroding, and non-staining. Exposed fasteners must be tamper-proof.
2.5 SHOP FABRICATION AND MANUFACTURE
2.5.1 Factory Workmanship
Work must be assembled in the shop, as far as practical, ready for installation at the site. Work that cannot be shop assembled must be given a trial fit in the shop to ensure proper field assembly. Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Welding to or on structural steel must be in accordance with AWS D1.1/D1.1M . Welding must be continuous along the entire area of contact. Exposed welds must be ground smooth.
Exposed surfaces of work must have a smooth finish and exposed riveting must be flush. Fastenings must be concealed where practical. Items specified to be galvanized must be by hot-dip process after fabrication if practical. Galvanization must be in accordance with ASTM A123/A123M and ASTM A653/A653M , as applicable. Other metallic coatings of steel sheet must be in accordance with ASTM A924/A924M . Joints exposed to the weather must be formed to exclude water. Drainage and weep holes must be included as required to prevent condensation buildup.
2.5.2 Dissimilar Materials
Where dissimilar metals are in contact, or where aluminum is in contact with concrete, mortar, masonry, wet or pressure-treated wood, or absorptive materials subject to wetting, the surfaces must be protected with a coat of asphalt varnish or a coat of zinc-molybdate primer to prevent galvanic or corrosive action.
2.5.3 Shop Painting
Surfaces of miscellaneous metal work, except nonferrous metal, corrosion resisting steel, and zinc-coated work, must be given one coat of zinc-molybdate primer or an approved rust-resisting treatment and metallic primer in accordance with manufacturer's standard practice. Surfaces of items to be embedded in concrete must not be painted. Upon completion of work, damaged surfaces must be recoated.
*1
2.6 EXTERIOR LED DIGITAL DISPLAY SIGN
Provide exterior LED digital display sign on the new brick Electronic Message Board Monument, as shown. Locate the Electronic Message Board Monument as indicated. LED digital display sign must have a 5-year manufacturer's warranty.
2.6.1 Housing
LED digital display sign must have an all-metal, weather-resistant, LED cabinet. Sign size shall be 9.5 feet wide by 5.5 feet high. Dimensions are nominal and actual sign must fit on the face of the monument with a minimum of 12 inches of space on each side of the monument pillars and 12
SECTION 10 14 00.10 Page 5 (Revised by Amendment 0001) inches of space from the top of the monument to the top of the sign. The housing finish must be a dark color selected from the manufacturer's standard finish color set.
2.6.2 Display
Display must be modular. Modules must be weather-resistant, quick release panels. Service and replacement of LED panels must be from the front side of the housing. LED's must be full-color and panel resolution must be 8 millimeter pixel pitch. LED's life-span must be rated for a minimum of 100,000 hours. Brightness must be minumum 8,500 NITS. Display must operate in ambient temperature from -20 degrees F to +130 degrees F . The display must be capable of displaying text, pictures and video in .JPG, .PNG, .MP4, .AVI and .MOV formats.
2.6.3 Communications
Communications between the display sign and the imagery source must be via Ethernet network signal. The method of communication must be by Transmission Control Protocol/Internet Protocol (TCP/IP). The display sign must have an ethernet input that will accept TCP/IP signalling and display the content. The medium of communication must be either CAT6 copper ethernet cable or single-mode fiber optic cable or a combination of both, using media converters for the copper to fiber interface. The communications connection and medium must be complete from end to end.
PART 3 EXECUTION
3.1 INSTALLATION
Signs, plaques, or dimensional letters must be installed in accordance with approved manufacturer's instructions at locations shown on the approved detail drawings ; submit drawings showing elevations of each type of sign; dimensions, details, and methods of mounting or anchoring; shape and thickness of materials; and details of construction. A schedule showing the location, each sign type, and message must be included.
Circuits installed underground must conform to the requirements of Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION. Steel conduits installed underground and illuminated signage mounted directly on buildings must be in conformance with the requirements of Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Signs must be installed plumb and true at mounting heights indicated, and by method shown or specified. Signs mounted on other surfaces must not be installed until finishes on such surfaces have been completed. Submit manufacturer's installation instructions and cleaning instructions.
3.1.1 Anchorage
Anchorage and fastener materials must be in accordance with approved manufacturer's instructions for the indicated substrate. Anchorage not otherwise specified or indicated must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood.
3.1.2 Protection and Cleaning
The work must be protected against damage during construction. Hardware and electrical equipment must be adjusted for proper operation. Glass, SECTION 10 14 00.10 Page 6 (Revised by Amendment 0001) frames, and other sign surfaces must be cleaned in accordance with manufacturer's instructions. After signs are completed and inspected, cover all project identification, directional, and other signs which may mislead the public. Covering must be maintained until instructed to be removed by the Contracting Officer or until the facility is to be opened for business. Submitsixcopies of maintenance instructions listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guides. The instructions must include simplified diagrams for the equipment as installed. Signs must be cleaned, as required, at time of cover removal.
*1
3.1.3 LED Digital Display Sign Installation
Install the digital display sign on the Electronic Message Board Monument in accordance with the manufacturer's instructions. Connections to electrical power service and communications service must be at the points indicated. Text
3.2 FIELD PAINTED FINISH
Miscellaneous metals and frames must be field painted in accordance with Section 09 90 00 PAINTS AND COATINGS. Anodized metals, masonry, and glass must be protected from paint. Finish must be free of scratches or other blemishes.
-- End of Section --
SECTION 10 14 00.10 Page 7 (Revised by Amendment 0001)
Berkeley Gate Entry Control Point C21B3004
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 14 53
TRAFFIC SIGNAGE
02/15
PART 1 GENERAL
1.1 REFERENCES
1.2 GENERAL
1.3 SUBMITTALS
PART 2 PRODUCTS
2.1 TRAFFIC SIGN POSTS
2.1.1 Steel Flanged Channel Section (U-Shape)
2.1.2 Perforated Steel Tube
2.1.3 Steel Tube
2.1.4 Wood
2.2 FLAT ALUMINUM SIGN PANELS
2.3 TRAFFIC SIGN RETROREFLECTIVE SHEETING
2.3.1 Legend and Border
2.3.2 Screen Printed Transparent Colored Areas
2.3.3 Adhesive Performance
2.4 LETTERS, NUMERALS, ARROWS, SYMBOLS, AND BORDERS
2.5 DELINEATOR POSTS
2.5.1 Steel Posts
2.5.2 Flexible Posts
2.6 DELINEATOR RETROREFLECTORS
2.6.1 Circular Prismatic Reflectors
2.6.2 Retroreflective Sheeting
2.7 HARDWARE
2.8 CONCRETE
PART 3 EXECUTION
3.1 SIGN POSTS
3.1.1 Steel Flanged Channel Section
3.1.2 Structural Steel H Section Posts
3.1.3 Wood
3.2 SIGN PANELS
3.3 DELINEATORS
3.4 LOCATION AND POSITION OF SIGNS
SECTION 10 14 53 Page 1
SECTION 10 14 53
TRAFFIC SIGNAGE
02/15
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO M 133 (2012; R 2016) Standard Specification for Preservatives and Pressure Treatment Processes for Timber
AASHTO M 168 (2007; R 2012) Standard Specification for Wood Products
AASHTO M 268 (2014) Standard Specification for Retroreflective Sheeting for Flat and Vertical Traffic Control Applications
AMERICAN WOOD PROTECTION ASSOCIATION (AWPA)
AWPA T1 (2019) Use Category System: Processing and Treatment Standard
AWPA U1 (2019) Use Category System: User Specification for Treated Wood
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A499 (2015) Standard Specification for Steel Bars and Shapes, Carbon Rolled from "T" Rails
ASTM A500/A500M (2018) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A653/A653M (2019) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
SECTION 10 14 53 Page 2
ASTM A1011/A1011M (2018a) Standard Specification for Steel Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM C94/C94M (2018) Standard Specification for Ready-Mixed Concrete
ASTM D4956 (2013) Standard Specification for Retroreflective Sheeting for Traffic Control
U.S. FEDERAL HIGHWAY ADMINISTRATION (FHWA)
FHWA SHS (2004; Supplement 2012) Standard Highway Signs
MUTCD (2015) Manual on Uniform Traffic Control Devices
1.2 GENERAL
Signs must be in accordance with the MUTCD. Signs not detailed on the Drawings must be in accordance with the FHWA SHS.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-03 Product Data
Traffic Sign Posts
Traffic Sign Retroreflective Sheeting
SD-04 Samples
Flexible Posts
PART 2 PRODUCTS
2.1 TRAFFIC SIGN POSTS
2.1.1 Steel Flanged Channel Section (U-Shape)
Fabricate steel posts from steel conforming to ASTM A36/A36M or ASTM A499 and with a minimum yield strength of 30 ksi and a minimum tensile strength of 50 ksi . Punch or drill 5/16 to 3/8 inch diameter holes spaced at 1 or 2 inch centers along the centerline of the web prior to galvanizing for the entire length of the post. Galvanize posts after punching in accordance with ASTM A123/A123M .
SECTION 10 14 53 Page 3
2.1.2 Perforated Steel Tube
Fabricate steel posts from steel conforming to either ASTM A653/A653M , structural steel, Grade 50 , Class 1, coating designation G90 or ASTM A1011/A1011M , structural steel, Grade 50 , hot-dip galvanized after punching in accordance with ASTM A123/A123M . Prepunch holes approximately 7/16 inch in diameter spaced at approximately 1 inch centers along each side of the tube for the entire length of the post.
2.1.3 Steel Tube
Conform to ASTM A500/A500M , Grade B or C, and hot-dip galvanized in accordance with ASTM A123/A123M .
2.1.4 Wood
Wood posts must be dry No. 1 grade Douglas fir, southern or Ponderosa pine, hemlock, spruce, or western larch conforming to AASHTO M 168. Treat the posts with water-borne preservative according to AASHTO M 133, AWPA T1 and AWPA U1.
2.2 FLAT ALUMINUM SIGN PANELS
Aluminum sign panels must conform to ASTM B209, alloy-temper 6061-T6 or 5052-H38. The blanks must be free from laminations, blisters, open seams, pits, holes, other defects that may affect their appearance or use. The thickness must be uniform and the blank commercially flat.
2.3 TRAFFIC SIGN RETROREFLECTIVE SHEETING
All background sheeting applied to flat sheet signs must be in accordance with ASTM D4956, Type III, IV, VII, VIII, IX or XI retroreflective sheeting and must have Class 1, 3, or 4 adhesive backing. Retroreflective sheeting must be high intensity that is an unmetallized micro prismatic reflective material.
Retroreflective sheeting must have sufficient adhesion, strength and flexibility such that the sheeting can be handled, processed and applied according to the manufacturer's recommendations without appreciable stretching, tearing, cracking or other damage.
2.3.1 Legend and Border
Apply retroreflective sheeting as legend and border in accordance with ASTM D4956, Type IX, XI, or AASHTO M 268 Type C or D, Class 1.
Retroreflective sheeting must be an unmetallized cube corner microprismatic reflective material. Retroreflective sheeting applied as legend and border for specific signing applications, without a datum mark on the surface of the sheeting, must be evaluated for rotational sensitivity in accordance with AASHTO M 268, Section 3.3.1 and fabricated in accordance with AASHTO M 268, Section 3.3.2.
2.3.2 Screen Printed Transparent Colored Areas
For screen printed transparent colored areas or transparent colored overlay films on white sheeting, the coefficient of retroreflection (RA) must be no less than 70 percent of the original values for the corresponding color.
SECTION 10 14 53 Page 4
2.3.3 Adhesive Performance
Adhesive performance for retroreflective sheeting must be in accordance with ASTM D4956. The sheeting surface must be in condition to be readily screen processed and compatible with transparent overlay films, plus recommended transparent and opaque screen process colors. Furnish manufacturer's information as to the type of solvent or solvents that may be used to clean the surface of the sheeting without detrimental loss of performance and durability.
2.4 LETTERS, NUMERALS, ARROWS, SYMBOLS, AND BORDERS
Apply letters, numerals, arrows, symbols, and borders on the retroreflective sheeting or opaque background of the sign using the direct or reverse screen process. Apply messages and borders of a color darker than the background to the paint or the retroreflective sheeting using the direct process. Messages and borders must be of a color lighter than the sign background and applied using the reverse screen process. Use opaque or transparent colors, inks, and paints of the type and quality recommended by the retroreflective sheeting manufacturer in the screen process. Perform the screening in a manner that results in a uniform color and tone, with sharply defined edges of legends and borders and without blemishes on the sign background that will affect intended use.
Air dry or bake the signs after screening according to the manufacturer's recommendations to provide a smooth hard finish. Reject any signs with blister's or other blemishes.
2.5 DELINEATOR POSTS
2.5.1 Steel Posts
Fabricate posts from steel conforming to ASTM A36/A36M or ASTM A499 and having a minimum yield strength of 30 ksi and a minimum tensile strength of 50 ksi . Galvanize posts after punching in accordance with ASTM A123/A123M .
2.5.2 Flexible Posts
Provide one-piece driveableflexible posts. Posts must be impact-resistant, integrally colored UV stabilized polymer or polycarbonate extrusion or fiberglass reinforced composite material.
Other materials are subject to approval by the Contracting Officer's Representative. Include a retroreflective sheeting plate with each post as indicated.
2.6 DELINEATOR RETROREFLECTORS
2.6.1 Circular Prismatic Reflectors
Retroreflectors attached to steel posts must be a 3-inch minimum diameter acrylic plastic lens with prismatic optical elements and a smooth, clear, transparent face. Fabricate the back from similar material and fuse to the lens around the entire perimeter to form a homogeneous unit.
Permanently seal the units against the intrusion of dust, water, or air.
Mount the retroreflector unit in a housing fabricated from 0.063-inch aluminum alloy or similar, or from cold-rolled, hot dip, galvanized steel, having a thickness of 0.064 inches . Provide the indicated color.
SECTION 10 14 53 Page 5
2.6.2 Retroreflective Sheeting
A retroreflective sheeting plate must be applied to each flexible post by the post manufacturer and must be in accordance with ASTM D4956, Type III, IV, V, VII, VIII, IX or XI retroreflective sheeting. Retroreflective sheeting must be high intensity that is an unmetallized cube corner micro prismatic reflective material. Provide the size and color of the retroreflective sheeting plate as indicated.
2.7 HARDWARE
Bolts, nuts, post clips, lock and flat washers must be either aluminum alloy or commercial quality stainless steel, hot-dip galvanized or cadmium plated after fabrication. Bolts/nuts must be an approved tamper resistant design. Provide fiber washers of commercial quality.
2.8 CONCRETE
ASTM C94/C94M, using 3/4 inch maximum aggregate, and having minimum compressive strength of 3,000 psi at 28 days.
PART 3 EXECUTION
3.1 SIGN POSTS
3.1.1 Steel Flanged Channel Section
Sign posts consist of a base post and sign post. Drive steel sign base posts with a suitable driving head. Attach sign posts to base posts.
Replace any base posts damaged during driving or otherwise at no additional cost to the Government. Embed steel sign base posts in concrete as indicated.
3.1.2 Structural Steel H Section Posts
Tighten all breakaway assembly bolts in a systematic manner to the prescribed torque indicated. Loosen each breakaway assembly bolt and re-tighten to the required torque in the same order as the initial tightening. Burr the threads at the nut using a center punch to prevent the nut from loosening. Tighten nuts on hinge plate bolts to the required minimum bolt tension values indicated.
3.1.3 Wood
Drill holes in the post as indicated.
3.2 SIGN PANELS
Clean, degrease and etch the face of metal panels using methods recommended by the retroreflective sheeting manufacturer. After cleaning and degreasing, apply retroreflective sheeting material to the sign panels as recommended by the manufacturer. Perform shearing, cutting and punching prior to preparing the blanks for application of reflective material. Do not field drill holes in any part of the panel. Use nylon washers recommended by the sign sheeting manufacturer between the bolt heads and sign faces on flat sheet aluminum signs. Replace any damaged sign panels at no additional cost to the Government.
SECTION 10 14 53 Page 6
3.3 DELINEATORS
Drive steel delineator posts into the ground in a manner that will not damage the post. Attach flexible delineator posts to steel anchors or drive into the soil in accordance with the manufacturer's instructions.
Demonstrate the method of installation for the Contracting Officer's Representative to verify that posts will be installed without being damaged.
3.4 LOCATION AND POSITION OF SIGNS
Locate and erect all signs in accordance with the drawings and MUTCD.
Vertically mount signs at right angles to the direction of, and facing, the traffic that they are intended to serve. Where mirror reflection from the sign face is encountered to such a degree as to reduce legibility, turn the sign slightly away from the road. Turn signs that are placed 30 feet or more from the pavement edge toward the road. On curved alignments, determine the angle of placement by the direction of approaching traffic rather than by the roadway edge at the point where the sign is located. Mounted signs must present a smooth flat surface varying no more than 3/8 inch from a 4-foot straightedge placed in any position on the face of the sign after erection. Mount signs on traffic signal posts with strap or clamp type sign supports. Each installed sign will be inspected by the Contracting Officer's representative prior to acceptance by the Government.
SECTION 10 14 53 Page 7
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 26 00
WALL AND DOOR PROTECTION
08/10
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 SUSTAINABLE DESIGN CERTIFICATION
1.4 DELIVERY, STORAGE, AND HANDLING
1.5 WARRANTY
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
2.1.1 Resilient Material
2.1.1.1 Minimum Impact Resistance
2.1.1.2 Fire Rating
2.1.1.3 Integral Color
2.1.1.4 Chemical and Stain Resistance
2.1.1.5 Fungal and Bacterial Resistance
2.2 CORNER GUARDS
2.3 WALL COVERING/PANELS
2.4 TRIM, FASTENERS AND ANCHORS
2.5 FINISH
2.5.1 Stainless Steel Finish
2.6 ADHESIVES
2.7 COLOR
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Corner Guards and Wall Guards (Bumper Guards)
3.1.2 Door, Door Frame Protectors, and Wall Panels
3.1.3 Stainless Steel Guards
SECTION 10 26 00 Page 1
SECTION 10 26 00
WALL AND DOOR PROTECTION
08/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM D256 (2010; R 2018) Standard Test Methods for Determining the Izod Pendulum Impact Resistance of Plastics
ASTM D543 (2014) Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents
ASTM D635 (2018) Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position
ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM G21 (2015) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 80 (2016; TIA 16-1) Standard for Fire Doors and Other Opening Protectives
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J1545 (2005; R 2014) Instrumental Color Difference Measurement for Exterior Finishes, Textiles and Colored Trim
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
SECTION 10 26 00 Page 2 submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Corner Guards ; G
SD-03 Product Data
Corner Guards ; G
SD-04 Samples
Finish ; G
SD-06 Test Reports
Corner Guards
SD-07 Certificates
Corner Guards ; S
1.3 SUSTAINABLE DESIGN CERTIFICATION
Product shall be third party certified in accordance with LEED or other third party program equal. Certification shall be performed annually and shall be current.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and trademarks intact. Keep materials dry, protected from weather and damage, and stored under cover.
Materials shall be stored at approximately 70 degrees F for at least 48 hours prior to installation.
1.5 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
To the maximum extent possible, corner guards, door and door frame protectors, wall guards (bumper guards), wall panels and wall covering shall be the standard products of a single manufacturer and shall be furnished as detailed. Drawings show general configuration of products required, and items differing in minor details from those shown will be acceptable.
2.1.1 Resilient Material
Provide resilient material consisting of high impact resistant extruded
SECTION 10 26 00 Page 3 acrylic vinyl, polyvinyl chloride, or injection molded thermal plastic conforming to the following:
2.1.1.1 Minimum Impact Resistance
Minimum impact resistance shall be 18 ft-lbs/sq. inch when tested in accordance with ASTM D256, (Izod impact, ft-lbs per sq inch notched).
2.1.1.2 Fire Rating
Fire rating shall be Class 1 when tested in accordance with ASTM E84, having a maximum flame spread of 25 and a smoke developed rating of 450 or less. Material shall be rated self extinguishing when tested in accordance with ASTM D635. Material shall be labeled and tested by an approved nationally known testing laboratory. Resilient material used for protection on fire rated doors and frames shall be listed by the testing laboratory performing the tests. Resilient material installed on fire rated wood/steel door and frame assemblies shall have been tested on similar type assemblies. Test results of material tested on any other combination of door/frame assembly will not be acceptable.
2.1.1.3 Integral Color
Colored components shall have integral color and shall be matched in accordance with SAE J1545 to within plus or minus 1.0 on the CIE-LCH scales.
2.1.1.4 Chemical and Stain Resistance
Materials shall be resistant to chemicals and stains reagents in accordance with ASTM D543.
2.1.1.5 Fungal and Bacterial Resistance
Materials shall be resistant to fungi and bacteria in accordance with ASTM G21, as applicable.
2.2 CORNER GUARDS
Stainless steel corner guards shall be fabricated of 16 gauge thick material conforming to ASTM A167, type 302 or 304. Corner guards shall extend from floor to 6 feet high. Corner guard shall be formed to dimensions shown.
2.3 WALL COVERING/PANELS
Provide wall covering/panels consisting of high impact rigid steel material. Panel sizes shall be to a height of four feet . Finish to be Tread Pattern.
2.4 TRIM, FASTENERS AND ANCHORS
Provide vinyl trim, fasteners and anchors for each specific installation as shown.
2.5 FINISH
Submit samples indicating color and texture of materials requiring color and finish.
SECTION 10 26 00 Page 4
2.5.1 Stainless Steel Finish
Finish for stainless steel shall be in accordance with ASTM A167, Type 302 or 304 NAAMM AMP 500, finish number 4 satin brushed.
2.6 ADHESIVES
Adhesive for resilient material shall be in accordance with manufacturers recommendations.
2.7 COLOR
Color shall be as selected from manufacturers standard colors.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Corner Guards and Wall Guards (Bumper Guards)
Material shall be mounted at location indicated in accordance with manufacturer's recommendations.
3.1.2 Door, Door Frame Protectors, and Wall Panels
Surfaces to receive protection shall be clean, smooth, and free of obstructions. Protectors shall be installed after frames are in place, but prior to hanging of doors, in accordance with manufacturer's specific instructions. Adhesives shall be applied in controlled environment in accordance with manufacturer's recommendations. Protection for fire doors and frames shall be installed in accordance with NFPA 80 .
3.1.3 Stainless Steel Guards
a. Mount guards on external corners of interior walls, partitions and columns in accordance with manufacturer's recommendations.
b. Where corner guards are installed on walls, partitions or columns finished with plaster or ceramic tile, provide continuous 16 gage thick, perforated, galvanized z-shape steel anchors welded to back edges of corner guards and expansion bolted to concrete or masonry with four 3/8 inch diameter bolts, spaced 16 inches on centers. Coat back surfaces of corner guards, where shown, with a non-flammable, sound deadening material. Corner guards shall overlap finish plaster surfaces.
c. Where corner guards are installed on exposed structural glazed facing tile units or masonry wall, partitions or columns, anchor corner guards to existing walls with 1/4 inch oval head stainless steel countersunk expansion or toggle bolts. Grout spaces solid between guards and backing with portland cement and sand mortar.
d. Where corner guards are installed on gypsum board, clean surfaces and anchor guards with a neoprene solvent-type contact adhesive specifically manufactured for use on gypsum board construction.
Remove excess adhesive from the guard edges and allow to cure undisturbed for 24 hours.
SECTION 10 26 00 Page 5
e. For wall guards, space brackets at no more than 3 feet on centers and anchor to the wall in accordance with the manufacturer's installation instructions.
SECTION 10 26 00 Page 6
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 44 16
FIRE EXTINGUISHERS
05/15
PART 1 GENERAL
1.1 SUBMITTALS
1.2 DELIVERY, STORAGE, AND HANDLING
1.2.1 Samples
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.1.1 Material
2.1.2 Extinguishers
2.2 EQUIPMENT
2.2.1 Cabinets
2.2.1.1 Material
2.2.1.2 Type
2.2.1.3 Size
PART 3 EXECUTION
3.1 INSTALLATION
3.2 PROTECTION
3.2.1 Repairing
3.2.2 Cleaning
SECTION 10 44 16 Page 1
SECTION 10 44 16
FIRE EXTINGUISHERS
05/15
PART 1 GENERAL
1.1 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Cabinets ; G
SD-03 Product Data
Cabinets ; G
Replacement Parts List ; G
SD-04 Samples
Cabinet ; G
1.2 DELIVERY, STORAGE, AND HANDLING
Protect materials from weather, soil, and damage during delivery, storage, and construction.
Deliver materials in their original packages, containers, or bundles bearing the brand name and the name and type of the material.
1.2.1 Samples
Provide the following samples: one full-sized sample of each type of cabinet being installed.
Use approved samples for installation, with proper identification and storage.
PART 2 PRODUCTS
Submit fabrication drawings consisting of fabrication and assembly details performed in the factory and product data for the following items:
Accessories and cabinets .
SECTION 10 44 16 Page 2
2.1 SYSTEM DESCRIPTION
2.1.1 Material
Provide aluminum extinguisher shell.
2.1.2 Extinguishers
Type K fire extinguishers shall be provided at the locations indicated on the drawings. Extinguishers shall be two-gallon capacity.
2.2 EQUIPMENT
2.2.1 Cabinets
2.2.1.1 Material
Provide enameled steel cabinets.
2.2.1.2 Type
Provide recessed type cabinets.
Provide semi-recessed cabinet for a 6-inch wall.
2.2.1.3 Size
Dimension cabinets suitable for a 20-lb class ABC to fit two-gallon extinguishers.
PART 3 EXECUTION
3.1 INSTALLATION
Comply with the manufacturer's recommendations for all installations.
3.2 PROTECTION
3.2.1 Repairing
Remove and replace damaged and unacceptable portions of completed work with new work at no additional cost to the Government.
Submit replacement parts list indicating specified items replacement part, replacement cost, and name, address and contact for replacement parts distributor.
3.2.2 Cleaning
Clean all surfaces of the work, and adjacent surfaces which are soiled as a result of the work. Remove from the site all construction equipment, tools, surplus materials and rubbish resulting from the work.
SECTION 10 44 16 Page 3
SECTION TABLE OF CONTENTS
DIVISION 12 - FURNISHINGS
SECTION 12 24 13
ROLLER WINDOW SHADES
08/17
PART 1 GENERAL
1.1 GENERAL REQUIREMENTS
1.2 REFERENCES
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Qualifications
1.4.1.1 Manufacturer's Qualifications
1.4.1.2 Installer's Qualifications
1.4.2 Flammability Requirements
1.4.3 Electrical Requirements
1.4.4 Anti-Microbial Requirements
1.5 DELIVERY, STORAGE, AND HANDLING
1.6 WARRANTY
PART 2 PRODUCTS
2.1 WINDOW SHADES
2.1.1 Light Filtering Shades
2.2 COLOR
PART 3 EXECUTION
3.1 FIELD MEASUREMENTS
3.2 INSTALLATION
3.3 CLEAN-UP
SECTION 12 24 13 Page 1
SECTION 12 24 13
ROLLER WINDOW SHADES
08/17
PART 1 GENERAL
1.1 GENERAL REQUIREMENTS
Provide roller window shades, complete with necessary brackets, fittings, and hardware as indicated. Mount and operate equipment in accordance with manufacturer's instructions. Windows to receive a shade must be completely covered.
a. Submit drawings showing plans, elevations, sections, product details, installation details, operational clearances, wiring diagrams and relationship to adjacent work. Include the use of same room designations as indicated on the drawings.
b. Provide manufacturer's data composed of catalog cuts, brochures, product information, and operating and maintenance instructions on each product to be used. Include styles, profiles and features.
c. Furnish samples of each type and color of roller shade fabric and roller shade channel. Shade material shall be minimum 6 by 6 inch in size. Mark face of material to indicate interior faces.
d. Mock up: Install shade in area designated by Contracting Officer. Do not proceed with remaining work until the Contracting Officer approves workmanship and operation. Re-work mock-up as required to produce acceptable work. The approved shade can be used in installation.
e. Submit fire resistance data, flame spread and smoke contribution data.
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM G21 (2015) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 701 (2019) Standard Methods of Fire Tests for Flame Propagation of Textiles and Films
UNDERWRITERS LABORATORIES (UL)
UL 325 (2017) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems
SECTION 12 24 13 Page 2
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES
SD-02 Shop Drawings
Installation ; G
SD-03 Product Data
Window Shades ; G
SD-04 Samples
Window Shades ; G
SD-06 Test Reports
Window Shades
SD-08 Manufacturer's Instructions
Window Shades
SD-10 Operation and Maintenance Data
Window Shades
SD-11 Closeout Submittals
Recycled Content for various fiber components ; S
Warranty ; G
1.4 QUALITY ASSURANCE
1.4.1 Qualifications
1.4.1.1 Manufacturer's Qualifications
Obtain motor-controlled roller shades through one source from a single manufacturer with a minimum of twenty years experience and minimum of three projects of similar scope and size in manufacturing products comparable to those specified in this section.
1.4.1.2 Installer's Qualifications
Installer trained and certified by the manufacturer with a minimum of ten years experience in installing products comparable to those specified in this section.
1.4.2 Flammability Requirements
Passes in accordance with NFPA 701 small and large-scale vertical burn.
SECTION 12 24 13 Page 3
Materials tested must be identical to products proposed for use.
1.4.3 Electrical Requirements
NFPA Article 100 listed and labeled in accordance with UL 325 or other testing agency acceptable to authorities having jurisdiction, marked for intended use, and tested as a system. Individual testing of components will not be acceptable in lieu of system testing.
1.4.4 Anti-Microbial Requirements
'No Growth' per ASTM G21 results for fungi ATCC9642, ATCC 9644, ATCC9645.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver components to the jobsite in the manufacturer's original packaging with the brand or company name, item identification, and project reference clearly marked. Store components in a dry location that is adequately ventilated and free from dust, water, or other contaminants and has easy access for inspection and handling. Store materials flat in a clean dry area with temperature maintained above 50 degrees F . Do not open containers until needed for installation unless verification inspection is required.
1.6 WARRANTY
Provide 10 year minimum limited warranty.
PART 2 PRODUCTS
2.1 WINDOW SHADES
Roller tube must operate smoothly and be of sufficient diameter and thickness to prevent excessive deflection. Provide brackets that are appropriate for inside mount. The shade cloth must meet the performance described in NFPA 701 , small scale test. Treat steel features for corrosion resistance.
Provide Various Fiber Components with a minimum of 60 percent recycled content. Provide data identifying percentage of recycled content for various fiber components .
2.1.1 Light Filtering Shades
Provide light filtering window shades to conform with the following:
a. Roller tube must be extruded aluminum or steel. Diameter, wall thickness, and material to be selected by the manufacturer to accommodate the shade size. Provide roller idler assembly of molded nylon and zinc-plated steel pin. Sliding pin must allow easy installation and removal of roller. Fabric must be connected to the roller tube with double sided adhesive specifically developed to attach coated textiles to metal to eliminate horizontal impressions in fabric or attached with a spline lock system.
b. Fascia must be L-shaped aluminum extrusion to conceal shade roller and hardware that snaps onto end caps without requiring exposed fasteners of any kind. Fascia can be mounted continuously across two or more shade bands.
SECTION 12 24 13 Page 4
c. End caps must be stamped steel with universal design suitable for mounting to window mullions. Provide size compatible with roller size. End cap covers must match fascia/headbox finish.
d. Provide hardware that allows for field adjustment or removal of shade roller tube and other operable hardware component without requiring removal of brackets and end or center supports. Provide hardware system that allows for operation of multiple shade bands by a single operator. Connectors must be offset to assure alignment from the first to the last shade band. Provide shade hardware constructed of minimum 1/8 inch thick plated steel or heavier as required to support 150 percent of the full weight of each shade.
e. Manual Operated Chain Drive Hardware must provide for universal, regular and offset drive capacity, allowing drive chain to fall at front, rear or non-offset for all shade drive end brackets. Universal offset must be adjustable for future change. Provide positive mechanical engagement of drive mechanism to shade roller tube. The drive bracket must be fully integrated with all accessories. Drive chain must be #10 stainless steel chain rated to 90 lb. minimum breaking strength.
f. Operating function: Stop and hold shade at any position .
2.2 COLOR
Provide color, pattern and texture for metal and shade fabric in accordance with Section 09 06 00 SCHEDULES FOR FINISHES. . Color listed is not intended to limit the selection of equal colors from other manufacturers. Openness factor of shade fabric must be 5 percent.
PART 3 EXECUTION
3.1 FIELD MEASUREMENTS
After becoming familiar with details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing the work.
3.2 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth.
Perform installation in accordance with the approved detail drawings and manufacturer's installation instructions. Install units level, plumb, secure, and at proper height and location relative to window units.
Provide and install supplementary or miscellaneous items in total, including clips, brackets, or anchorages incidental to or necessary for a sound, secure, and complete installation. Do not start installation until completion of room painting and finishing operations.
SECTION 12 24 13 Page 5
3.3 CLEAN-UP
Upon completion of the installation, clean window treatments and adjust them for…