W912HN-18-B-3001_VOL2.pdf
PDF 28 MB Posted
- Solicitation number
- W912HN18B3001
About this file
DRAWINGS Vol 2
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B.01.02_Bid_Abstract_W912HN18B3001_ARCYBER_COF.xls | XLS spreadsheet | |
| Bid_Abstract_W912HN18B3001_ARCYBER_COF.pdf | ||
| 18B3001vol2.PDF | ||
| 18B3001vol1.PDF | ||
| amd7.pdf | ||
| amd6.pdf | ||
| 18B3001vol1.PDF | ||
| amd5.pdf | ||
| 18B3001vol1.PDF | ||
| 18B3001vol2.PDF | ||
| 18B3001vol4.PDF | ||
| 18B3001vol3.PDF | ||
| W912HN-18-B-3001_VOL2_AMD5.pdf | ||
| 18B3001vol1.pdf | ||
| 18B3001vol3.pdf | ||
| 18B3001vol4.pdf | ||
| W912HN-18-B-3001_VOL2_AMD4.pdf | ||
| 18B3001vol2.pdf | ||
| amd4.pdf | ||
| W912HN-18-B-3001_VOL2_AMD3.pdf | ||
| 18B3001vol1.pdf | ||
| amd3.pdf | ||
| W912HN-18-B-3001_VOL1_AMD3.pdf | ||
| 18B3001vol2.pdf | ||
| amd2.pdf | ||
| W912HN-18-B-3001_VOL1_AMD1.pdf | ||
| 18B3001vol4.pdf | ||
| W912HN-18-B-3001_VOL2_AMD2.pdf | ||
| 18B3001vol1.pdf | ||
| 18B3001vol1.pdf | ||
| amd1.pdf | ||
| 18B3001vol3.pdf | ||
| 18B3001vol4.pdf | ||
| 18B3001vol2.pdf | ||
| W912HN-18-B-3001_VOL1.pdf | ||
| 18B3001vol1.pdf |
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET ID. TITLE
INDEX OF DRAWINGS - VOLUME 2
SHEET ID. SHEET ID.TITLE TITLE
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENDKRW\Documents\FY17PN85794_PROJ_R18_K6ENDKRW.rvt
4/17/2018 7:19:04 AM
AP
R
IL
W
2H N
-1 8-
B-
XX
X
YY
Y
Au th or
XX
X
YY
Y
1-
-0
G-002
IN
D
EX
O
F D
R
AW
IN
G
S
Sa va nn ah
, G eo rg ia
Sa va nn ah
, G eo rg ia
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
XX
X
YY
Y
ISSUED FOR CONSTRUCTION
MI002 HVAC CONTROLS POINTS - SCHEDULING INSTRUCTIONS
MI801 AHU-1 CONTROL SCHEMATIC AND LADDER DIAGRAM
MI802 AHU-2 & 3 CONTROL SCHEMATIC AND LADDER DIAGRAM
MI803 AHU-4 CONTROL SCHEMATIC AND LADDER DIAGRAM
MI804 DOAS-1 CONTROL SCHEMATIC AND LADDER DIAGRAM
MI805 AHU-1 SEQUENCE-OF-OPERATION
MI806 AHU-2 & 3 SEQUENCE-OF-OPERATION
MI807 AHU-4 SEQUENCE-OF-OPERATION
MI808 DOAS-1 SEQUENCE-OF-OPERATION
MI809 CONTROL VALVE & CONTROL DAMPER SCHEDULES
MI810 AHU-1 CONTROL POINTS SCHEDULE
MI811 AHU-2 & 3 CONTROL POINTS SCHEDULE
MI812 AHU-4 CONTROL POINTS SCHEDULE
MI813 DOAS-1 CONTROL POINTS SCHEDULE
MI814 MISC CONTROL SCHEMATICS
MI815 MISC CONTROLS AND SEQUENCE-OF-OPERATION
MI816 VAV TERMINAL UNIT & UNIT HEATER CONTROL POINTS SCHEDULE
MI817 MISC CONTROL POINTS SCHEDULES
MI818 FCU-1 & 2 CONTROL POINTS SCHEDULE
MI819 HYDRONIC HEATING HOT WATER SYSTEM CONTROL SCHEMATIC AND SEQUENCE-OF-OPERATION
MI820 HYDRONIC CHILLED WATER SYSTEM CONTROL SCHEMATIC AND SEQUENCE-OF-OPERATION
MI821 HYDRONIC CHILLED WATER SYSTEM CONTROL POINTS SCHEDULE
MI822 HYDRONIC HEATING HOT WATER SYSTEM CONTROL POINTS SCHEDULE
MI823 DOMESTIC HOT WATER CTRL SCHEMATIC, SEQUENCE OF OP, AND CTRL POINTS SCHED
MP101 HVAC HYDRONIC PIPING PLAN
MP102 HVAC HYDRONIC PIPING PLAN - PARTS A & C
MP103 HVAC HYDRONIC PIPING PLAN - PARTS B & D
E-001 ELECTRICAL LEGEND & GENERAL NOTES
E-002 ELECTRICAL ABBREVIATIONS & MOUNTING DIAGRAM
EG101 LIGHTNING PROTECTION PLAN - PARTS A & C
EG102 LIGHTNING PROTECTION PLAN - PARTS B & D
EG103 GROUNDING PLAN - PARTS A & C
EG104 GROUNDING PLAN - PARTS B & D
EG501 LIGHTNING PROTECTION SYSTEM DETAILS
EG502 MISCELLANEOUS GROUNDING DETAILS
EL101 LIGHTING PLAN - PARTS A & C
EL102 LIGHTING PLAN - PARTS B & D
EL401 LIGHTING PLAN - ENLARGED MECHANICAL EQUIPMENT PLATFORM
EL501 LIGHT FIXTURE SCHEDULE AND DETAILS
EL502 LIGHT FIXTURE DETAILS
EL503 LIGHT FIXTURE DETAILS
EL504 LIGHTING CONTROL STRATEGY SCHEDULE
EP101 POWER PLAN - PARTS A & C
EP102 POWER PLAN - PARTS B & D
EP103 EQUIPMENT POWER PLAN - PARTS A & C
EP104 EQUIPMENT POWER PLAN - PARTS B & D
EP105 ROOF POWER PLAN - PARTS A & C
EP106 ROOF POWER PLAN - PARTS B & D
EP401 ENLARGED POWER PLANS
EP501 ELECTRICAL DETAILS
EP601 POWER ONE-LINE DIAGRAM
EP602 FEEDER & TRANSFORMER SCHEDULES
EP603 PANEL SCHEDULES
EP604 PANEL SCHEDULES
EP605 PANEL SCHEDULES
EP606 PANEL SCHEDULES
EP607 PANEL SCHEDULES
EY001 AUXILIARY SYSTEMS LEGEND & GENERAL NOTES
EY101 AUXILIARY SYSTEMS PLAN - PARTS A & C
EY102 AUXILIARY SYSTEMS PLAN - PARTS B & D
EY601 AUXILIARY SYSTEMS DIAGRAMS
T-001 TELECOMMUNICATIONS LEGEND & GENERAL NOTES
T-101 TELECOMMUNICATION PLAN - PARTS A & C
T-102 TELECOMMUNICATION PLAN - PARTS B & D
T-103 TELECOMMUNICATION NON-SECURE PATHWAY PLAN - PARTS A & C
T-104 TELECOMMUNICATION NON-SECURE PATHWAY PLAN - PARTS B & D
T-105 SIPRNET PATHWAY PLAN - PARTS A & C
T-106 SIPRNET PATHWAY PLAN - PARTS B & D
T-401 ENLARGED TELECOMMUNICATION PLANS
T-501 TELECOMMUNICATION DETAILS - CABLE TRAYS
T-502 TELECOMMUNICATION DETAILS - OUTLETS & LABELING
T-601 TELECOMMUNICATION ONE-LINE DIAGRAMS
T-602 TELECOMMUNICATION ELEVATION DIAGRAM - T.E.R. B103
T-603 TELECOMMUNICATION ELEVATION DIAGRAM - T.R. B116
T-604 TELECOMMUNICATION ELEVATION DIAGRAM - NERD SERVER C102
A-601A PARTITION TYPES
A-602 PARTITION TYPES
A-603 DOOR SCHEDULE AND DETAILS 1
A-604 DOOR SCHEDULE AND DETAILS 2
A-604A ESS DOOR DETAILS 1
A-604B ESS DOOR DETAILS 2
A-604C ESS DOOR DETAILS 3
A-605 DOOR DETAILS
A-606 DOOR DETAILS
A-607 DOOR DETAILS
A-608 WINDOW TYPES
A-609 WINDOW DETAILS 1
A-609A WINDOW DETAILS 2
A-610 LOUVER SCHEDULE AND LOUVER DETAILS
A-620 FINISH SCHEDULE
A-701 LIFE SAFETY PLAN
A-702 LIFE SAFETY ANALYSIS
A-800 AIR BARRIER BOUNDARY PLAN
A-801 AIR BARRIER SECTIONS
I-101A FURNITURE PLAN - AREA A
I-101B FURNITURE PLAN - AREA B
I-101C FURNITURE PLAN - AREA C
I-101D FURNITURE PLAN - AREA D
I-111A FINISH PLAN - AREA A
I-111B FINISH PLAN - AREA B
I-111C FINISH PLAN - AREA C
I-111D FINISH PLAN - AREA D
I-501 SIGNAGE SCHEDULE & DETAILS
I-511 SIGNAGE TYPICALS 1
I-512 SIGNAGE TYPICALS 2
I-601 ROOM FINISH SCHEDULE
I-611 FINISH LEGEND
I-612 FINISH DETAILS
FA001 FIRE ALARM LEGEND AND OPERATIONS MATRIX
FA101 FIRE ALARM & MASS NOTIFICATION SYSTEMS PLAN - PARTS A & C
FA102 FIRE ALARM & MASS NOTIFICATION SYSTEMS PLAN - PARTS B & D
FA601 FIRE ALARM & MNS ONE-LINE DIAGRAM
FX001 FIRE PROTECTION LEGEND AND GENERAL NOTES
FX101 FIRE PROTECTION FLOOR PLAN - OVERALL
FX102 FIRE PROTECTION FLOOR PLAN - AREA A
FX103 FIRE PROTECTION FLOOR PLAN - AREA B
FX104 FIRE PROTECTION FLOOR PLAN - AREA C
FX105 FIRE PROTECTION FLOOR PLAN - AREA D
FX501 FIRE PROTECTION DETAILS I
FX502 FIRE PROTECTION DETAILS II
FX503 FIRE PROTECTION DETAILS III
P-001 PLUMBING LEGEND
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-503 PLUMBING DETAILS
P-504 PLUMBING DETAILS
PL101 PLUMBING FLOOR PLAN - SANITARY SEWER
PL102 PLUMBING FLOOR PLAN - DOMESTIC WATER
PL103 PLUMBING FLOOR PLAN - ROOF DRAINAGE
PL601 PLUMBING SCHEDULES
M-001 HVAC LEGEND
MH101 HVAC FLOOR PLAN - OVERALL
MH102 HVAC FLOOR PLAN - PARTS A & C
MH103 HVAC FLOOR PLAN - PARTS B & D
MH104 HVAC FLOOR PLAN - PARTS A & C (AIRFLOWS & DEVICES)
MH105 HVAC FLOOR PLAN - PARTS B & D (AIRFLOWS & DEVICES)
MH106 HVAC ROOF PLAN
MH107 HVAC THERMOSTAT & SENSOR PLAN
MH301 HVAC SECTIONS
MH302 HVAC SECTIONS
MH303 HVAC SECTIONS
MH304 HVAC SECTIONS
MH305 HVAC SECTIONS
MH401 HVAC ENLARGED PLANS
MH501 HVAC DETAILS
MH502 HVAC DETAILS
MH503 HVAC DETAILS
MH504 HVAC DETAILS
MH505 HVAC DETAILS
MH506 HVAC BRACING DETAILS
MH507 HVAC DETAILS
MH601 MECHANICAL SCHEDULES
MH602 MECHANICAL SCHEDULES
MH603 MECHANICAL SCHEDULES
MH701 HOT AND CHILLED WATER PIPING SCHEMATIC
MI001 HVAC CONTROLS LEGEND
G-001 COVER SHEET
G-002 INDEX OF DRAWINGS
G-003 GENERAL NOTES, ABBREVIATIONS
S-001 GENERAL STRUCTURAL NOTES
S-002 GENERAL STRUCTURAL NOTES
S-003 GENERAL STRUCTURAL NOTES
SB101 COMPOSITE FOUNDATION PLAN
SB101A FOUNDATION PLAN - AREA A
SB101B FOUNDATION PLAN - AREA B
SB101C FOUNDATION PLAN - AREA C
SB101D FOUNDATION PLAN - AREA D
SB102 LOADING DOCK PLAN
SB103 PEDESTRIAN BRIDGE PLAN
SB301 FOUNDATION SECTIONS
SB302 FOUNDATION SECTIONS
SB303 FOUNDATION SECTIONS
SB501 FOUNDATION DETAILS
SB601 FOUNDATION SCHEDULES
SF101 COMPOSITE ROOF PLAN
SF101A ROOF PLAN - AREA A AND C
SF101B ROOF PLAN - AREA B AND D
SF201 FRAMING ELEVATIONS
SF202 FRAMING ELEVATIONS
SF203 FRAMING ELEVATIONS
SF204 FRAMING ELEVATIONS
SF205 FRAMING ELEVATIONS
SF206 FRAMING ELEVATIONS
SF207 FRAMING ELEVATIONS
SF208 FRAMING ELEVATIONS
SF301 FRAMING SECTIONS
SF302 FRAMING SECTIONS
SF303 FRAMING SECTIONS
SF304 FRAMING SECTIONS
SF305 FRAMING SECTIONS
SF501 FRAMING DETAILS
SF502 FRAMING DETAILS
SF601 COLUMN SCHEDULES
A-101 COMPOSITE FLOOR PLAN
A-101A FLOOR PLAN -AREA A
A-101B FLOOR PLAN -AREA B
A-101C FLOOR PLAN -AREA C
A-101D FLOOR PLAN -AREA D
A-101E FLOOR PLAN - MECHANICAL EQUIPMENT PLATFORMS AREA C & D
A-101F CLERESTORY PLAN
A-102 DIMENSION PLAN
A-102A DIMENSION PLAN- LATRINES/BREAKROOM
A-103 SECRET OPEN STORAGE AREA FLOOR PLAN
A-104 ROOF PLAN
A-105 REFLECTED CEILING PLAN -PART A
A-106 REFLECTED CEILING PLAN -PART B
A-107 REFLECTED CEILING PLAN -PART C
A-108 REFLECTED CEILING PLAN -PART D
A-109 REFLECTED CEILING PLAN - MECH. EQUIPMENT PLATFORM AREAS C & D
A-201 NORTH ELEVATIONS PART A AND B
A-202 SOUTH ELEVATIONS PART C AND D
A-203 EAST AND WEST ELEVATIONS
A-301 BUILDING CROSS SECTION
A-302 BUILDING LONGITUDINAL SECTION
A-310 WALL SECTIONS
A-311 WALL SECTIONS
A-312 WALL SECTIONS
A-313 WALL SECTIONS
A-314 WALL SECTIONS
A-315 WALL SECTIONS
A-316 WALL SECTIONS
A-317 WALL SECTIONS
A-400 ENLARGED PLANS & INTERIOR ELEVATIONS
A-401 ENLARGED PLANS & INTERIOR ELEVATIONS
A-500 ROOF DETAILS 1
A-501 ROOF DETAILS 2
A-502 ROOF DETAILS 3
A-503 ROOF DETAILS 4
A-504 ROOF DETAILS 5
A-520 CEILING DETAILS
A-521 INTERIOR DETAILS I
A-522 INTERIOR DETAILS 2
A-523 INTERIOR DETAILS 3
A-530 EXTERIOR DETAILS
A-531 EXTERIOR DETAILS 2
A-540 MISCELLANEOUS DETAILS
A-601 PARTITION TYPES
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET LOGICMATERIALS
EARTH
DRAWING ABBREVIATIONS GENERAL NOTES
C (cont) ---------------------
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE, CONTINUOUS
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED, EXPANSION
EXT EXTERIOR, EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FAS BD FASCIA BOARD
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FED FEDERAL
FF FINISH FLOOR
FFE FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED
GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC
FRTW FIRE RETARDANT
TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GEJ GUTTER EXPANSION JOINT
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GFRG GLASS-FIBER-
REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GUT GUTTER
GWB GYPSUM WALL BOARD
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H -------------
HB HOSE BIBB
HC HANDICAPPED
HDPE HIGH DENSITY
POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY
PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING
CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
JT JOINT
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LG LIGHT GAUGE
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTD MOUNTED
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE
WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE
PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION
COEFFICIENT
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL
JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GLPLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PLPUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PREFIN PREFINISHED
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER
AND RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK
MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
R (cont) --------------------
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL SHEET METAL
FLASH (FLASHING)
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS STAINLESS STEEL
SSMR STANDING SEAM METAL ROOF
ST STAIRS
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
STRUC STRUCTURAL
SUB FL SUBFLOOR
SUSP SUSPENDED
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
TH THICK
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
TYP TYPICAL
U --------------------
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER
LABORATORIES
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER
SYSTEM
V --------------------
VAV VARIABLE AIR VOLUME/UNIT
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VTR VENT THRU ROOF
W --------------------
W/ WITH
WC WATER CLOSET
WD WOOD
WDW WINDOW
W/O WITHOUT
WWF WELDED WIRE FABRIC
X --------------------
XFMRTRANSFORMER
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ABV ABOVE
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL
SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH
DISABILITIES ACT
ADJ ADJACENT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED
CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AWT ACOUSTICAL WALL
TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BD BOARD
BDRY BOUNDARY
BEJ BRICK EXPANSION JOINT
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE
MANUFACTURER'S
ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BSMTBASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER)
BOARD
CD CONSTRUCTION
DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CFCI CONTRACTOR
FURNISHED/CONTRACTOR
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL
FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
0 GRID/COLUM
N LINE
DESIGNATOR
INTERIOR ELEVATION
SECTION
ROOM
NAME/NUMBE
R
REVISION
TAG
PLAN, BLOW-UP
DETAIL
PLAN NORTH
NORTH ARROW
w/ TRUE NORTH
INDICATION
SPOT ELEVATION
Name Elevation REFERENCE LEVEL
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
A-101
SIM
EXTERIOR ELEVATION
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
A-101
SYMBOLS
INTERIOR ELEVATION
SYMBOL
EXTERIOR ELEVATION
SYMBOL
SECTION SYMBOL
CALLOUT SYMBOL
ELEVATION SYMBOL
LEVEL SYMBOL
GENERAL SYMBOLS
Room name
Room name
150 SF
ROOM
NAME/NUMBER
W/ AREA
CENTERLINE
INDICATOR
1/2 1 21
SCALE: 1"=1'-0"
SCALE BAR
1 View Name 1/8" = 1'-0"R101
MATCHLINE INDICATOR
VIEW TITLE BAR
1 / A-101
1 / A-102
REFERENCE
SHEETS
SAND
CONCRETE/ PRECAST
CONCRETE
STONE
BRICK
CMU
PLYWOOD
RIGID INSULATION
BATT INSULATION
GYPSUM BOARD,
PLASTER
EIFS
1. THESE LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE PERTINENT TO THE CONDITIONS
ON THIS SET OF DRAWINGS TO THE EXTENT APPLICABLE.
2. ADDITIONAL LEGENDS AND/OR ABBREVIATIONS MAY APPEAR IN THIS SET OF DRAWINGS TO INDICATE
SPECIFIC CONDITIONS IN LIEU OF SYMBOLS SHOWN ON THIS SHEET.
AE201
DISCIPLINE*:
G - GENERAL
C - CIVIL
L - LANDSCAPE
S - STRUCTURAL
A - ARCHITECTURE
DISCIPLINE DESIGNATOR
SHEET TYPE
DESIGNATOR
SHEET SEQUENCE
NUMBER
F- FIRE PROTECTION
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
T-
TELECOMMUNICATIONS
*ADDITIONAL DISCIPLINES MAY BE USED
IN THIS DRAWING SET.
DRAWING NAMING CONVENTION
SHEET ID
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENDKRW\Documents\FY17PN85794_PROJ_R18_K6ENDKRW.rvt
4/17/2018 7:01:19 AM
AP
R
IL
W
2H N
-1 8-
B-
XX
X
YY
Y
Au th or
XX
X
YY
Y
1-
-0
G-003
G
EN
ER
AL
N O
TE
S, A
BB
R
EV
IA
TI
O N
S
Sa va nn ah
, G eo rg ia
Sa va nn ah
, G eo rg ia
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
XX
X
YY
Y
ISSUED FOR CONSTRUCTION
M
AR
K D
ES
C
R
IP
TI
O
N D
GENERAL NOTES:
G-1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL OTHER DRAWINGS. COORDINATE THE WORK OF OTHER TRADES INCLUDING, BUT NOT LIMITED TO, THE REQUIREMENTS FOR SLEEVES, INSERTS, HOLES, HANGERS, AND ANCHORS.
G-2. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DIFFERENT DRAWINGS TO CONTRACTING OFFICER
PRIOR TO BEGINNING WORK IN AREAS THAT WILL BE AFFECTED.
G-3. DETAILS TITLED OR NOTED AS "TYPICAL" APPLY NOT ONLY WHERE SPECIFICALLY INDICATED OR REFERENCED, BUT ALSO IN ALL OTHER CASES WHERE THE NATURE OF THE CONSTRUCTION REQUIRES THEIR USE. DETERMINE APPLICABILITY OF TYPICAL DETAILS FROM DESCRIPTIVE TITLES OR FROM THE
SIMILARITY OF A CONSTRUCTION CONDITION TO ANOTHER CONDITION WHERE THE DETAIL IS
SPECIFICALLY INDICATED OR REFERENCED.
G-4. PROVIDE TEMPORARY BRACING AND SHORING OF THE STRUCTURE AND COMPONENTS UNTIL ALL COMPONENTS ARE ERECTED AND ALL CONNECTIONS ARE FULLY MADE, AS NECESSARY, TO ENSURE STABILITY DURING CONSTRUCTION. BRACE ALL WALLS DURING CONSTRUCTION AGAINST WIND AND/OR
CONSTRUCTION LOADS.
G-5. ELEVATIONS ON THE STRUCTURAL DRAWINGS ARE DENOTED AS [±X'-X"] REFERENCED TO THE FINISHED FIRST FLOOR ELEVATION DATUM [0'-0"]. SEE CIVIL DRAWINGS FOR ACTUAL DATUM ELEVATION.
G-6. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS UNDER ANY
CIRCUMSTANCE.
FOUNDATION AND SLAB NOTES:
F-1. FOUNDATIONS FOR THIS PROJECT HAVE BEEN DESIGNED IN ACCORDANCE WITH THE
RECOMMENDATIONS IN THE GEOTECHNICAL REPORT PREPARED BY THE SAVANNAH DISTRICT TITLED
"SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING REPORT, ARCYBER COMPANY
OPERATIONS FACILITY, FY 17, LI 85794, FT GORDON, GA", DATED NOVEMBER 2017.
F-2. FOUNDATIONS HAVE BEEN DESIGNED TO BEAR ON SOIL CAPABLE OF SUPPORTING AN ALLOWABLE BEARING PRESSURE OF 2500 PSF AS STATED IN THE GEOTECHNICAL REPORT REFERENCED ABOVE.
F-3. THE CONTRACTOR SHALL HIRE AN INDEPENDENT TESTING LABORATORY AND GEOTECHNICAL ENGINEER, REGISTERED AND LICENSED IN THE STATE WHERE THE WORK WILL BE ACCOMPLISHED, TO VERIFY THAT ALL OF THE REQUIREMENTS CONTAINED IN SPECIFICATION 31 00 00, EARTHWORK, HAVE
BEEN FOLLOWED AND ACCOMPLISHED.
F-4. ALL EXCAVATIONS SHALL BE PERFORMED SO THAT THE SITE AND THE AREA IMMEDIATELY SURROUNDING THE SITE WHICH AFFECTS CONSTRUCTION OPERATIONS WILL BE CONTINUALLY AND
EFFECTIVELY DRAINED. THE CONTRACTOR SHALL PROVIDE DRAINAGE AND DEWATERING AS
REQUIRED TO ENSURE THAT ALL FOOTING EXCAVATIONS ARE ACCOMPLISHED WITH THE SUBGRADE SOILS REMAINING DRY AND FIRM UNTIL AFTER FOOTINGS ARE PLACED AND BACKFILLED. REMOVAL OF
SURFACE WATER, GROUNDWATER, AND ANY PERCHED WATER CONDITIONS WHICH MIGHT BE
ENCOUNTERED DURING EXCAVATIONS, SHALL BE ACCOMPLISHED BY APPROVED MEANS. REFER TO SPECIFICATION SECTION 31 00 00, EARTHWORK, AND TO SHEET B-001 FOR ADDITIONAL EXCAVATION
REQUIREMENTS.
F-5. DO NOT PLACE FOUNDATION CONCRETE ON FROZEN OR SATURATED SUBGRADES.
F-6. ENSURE THAT EARTH-FORMED FOOTINGS CONFORM TO THE SHAPE, LINES, AND THICKNESSES INDICATED ON THE FOUNDATION PLAN, SECTIONS, AND FOOTING SCHEDULES. EXCAVATION WIDTHS
SHALL BE A MINIMUM OF 4" GREATER THAN DIMENSIONS INDICATED.
F-7. DO NOT INSTALL FOUNDATIONS UNTIL FOUNDATION WORK HAS BEEN COORDINATED WITH ADJACENT
UNDERGROUND UTILITIES.
F-8. FOOTINGS SHALL BE LOWERED AS REQUIRED TO PASS UNDER UTILITY LINES. STEP CONTINUOUS FOOTINGS DOWN AS SHOWN IN THE "TYPICAL STEPPED FOOTING DETAIL" ON SHEET SB301. SEE
"TYPICAL CONDUIT OPENING" DETAIL ON SHEET SB301.
F-9. PLACE 10 MIL VAPOR RETARDER AND 4" CAPILLARY WATER BARRIER UNDER ALL INTERIOR SLABS-ON- GRADE (TYPICAL). COORDINATE INSULATION SIZE AND TYPE WITH ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
CONCRETE CONSTRUCTION NOTES:
C-1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-14) AND THE SPECIFICATIONS FOR
STRUCTURAL CONCRETE (ACI 301-14) OF THE AMERICAN CONCRETE INSTITUTE (ACI).
C-2. ALL CAST-IN-PLACE CONCRETE SHALL ATTAIN MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF
4000 PSI.
C-3. CONCRETE DENSITY SHALL BE NORMAL WEIGHT WITH A DENSITY OF 140 PCF TO 150 PCF UNLESS
NOTED OTHERWISE ON PLANS.
C-4. CONCRETE REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60 AND SHALL HAVE FABRICATION TOLERANCES IN ACCORDANCE WITH ACI 315. SHOP
FABRICATE REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.
C-5. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185 OR ASTM A497. PROVIDE SHEET-TYPE WELDED
WIRE FABRIC. SHEET LAPS SHALL BE TIED AND LAPPED ONE FULL MESH SPACING PLUS 2".
C-6. CONCRETE REINFORCING STEEL SHALL BE CONTINUOUS UNLESS OTHERWISE INDICATED. CONTINUOUS
REINFORCING STEEL SHALL BE SPLICED AS SHOWN IN SCHEDULE ON SB601 UNO ON PLANS.
REINFORCING STEEL SHALL BE PLACED SO THAT SPACING IS GREATER THAN OR EQUAL TO 2X BAR
DIAMETER.
C-7. MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS INDICATED. IN NO CASE SHALL
REINFORCEMENT COVER BE LESS THAN THE REQUIREMENTS OF ACI 301.
A. CONCRETE DEPOSITED AGAINST THE GROUND 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER 2"
C. SLABS AND WALLS 1"
C-8. CONCRETE REINFORCING STEEL MARKED STANDARD HOOK SHALL HAVE A 90° HOOK A MINIMUM OF 12 BAR DIAMETERS IN LENGTH, UNLESS OTHERWISE NOTED. STIRRUPS, TIES, AND 180° HOOKS SHALL
CONFORM TO THE REQUIREMENTS OF ACI 318.
C-9. PROVIDE 1/2" THICK PRE-MOLDED JOINT FILLER MATERIAL WHERE SLABS ON GRADE ABUT VERTICAL
SURFACES.
C-10. ALL EMBEDDED ITEMS SHALL BE PROPERLY PLACED, ACCURATELY POSITIONED AND MAINTAINED
SECURELY IN PLACE PRIOR TO AND DURING CONCRETE PLACEMENT.
C-11. REINFORCING STEEL SHALL BE SPREAD AT SLEEVES, ANCHORS, RECESSES AND OTHER EMBEDDED
ITEMS UNLESS OTHERWISE INDICATED. REINFORCEMENT SHALL NOT BE CUT TO FACILITATE
PLACEMENT OF EMBEDDED ITEMS, UNLESS INDICATED.
C-12. NO CONCRETE SHALL BE PLACED UNTIL THE OWNER OR THE CONTRACTING OFFICER'S DESIGNATED
REPRESENTATIVE HAS INSPECTED ALL EMBEDDED WORK, INCLUDING REINFORCEMENT.
C-13. ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED 3/4" OR AS INDICATED.
C-14. ALUMINUM SHALL NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE UNLESS EFFECTIVELY COATED
OR COVERED TO PREVENT ALUMINUM-CONCRETE REACTION AND ELECTROLYTIC ACTION BETWEEN
ALUMINUM AND STEEL.
C-15. CONCRETE SLAB ON GRADE JOINTS INDICATED ARE DIAGRAMMATIC AND DO NOT REPRESENT ALL OF THE JOINTS REQUIRED FOR SLAB-ON-GRADE CONSTRUCTION. SLAB PANELS BETWEEN JOINTS SHALL BE SQUARE OR NEARLY SO AND SHALL NOT EXCEED AN ASPECT RATIO WITH PANEL LENGTH GREATER
THAN 1.5 TIMES THE PANEL WIDTH. SPACING SHALL NOT EXCEED 15 FEET O.C.
C-16. CONTRACTOR SHALL PROVIDE JOINTS AT ALL RE-ENTRANT CORNERS INCLUDING, BUT NOT LIMITED TO, COLUMNS AND SLAB RECESSES.
C-17. IN ADDITION, CONTRACTOR SHALL COORDINATE SLAB ON GRADE JOINT REQUIREMENTS WITH SLAB-ON-
GRADE CONSTRUCTION SEQUENCING. CONTRACTOR SHALL SHOW JOINT LAYOUT ON REINFORCING
SHOP DRAWING SUBMITTAL FOR APPROVAL.
STEEL CONSTRUCTION NOTES:
S-1. FABRICATION AND ERECTION OF STRUCTURAL STEEL AND DESIGN OF CONNECTIONS SHALL BE IN ACCORDANCE WITH AISC 360-10, "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" DATED JUNE 22, 2010 AND AISC 303-10, "CODE OF STANDARD PRACTICE FOR BUILDING AND BRIDGES" DATED
APRIL 14, 2010. THE STRUCTURAL STEEL MEMBERS SHOWN IN THESE DRAWINGS HAVE BEEN
ANALYZED AND DESIGNED USING AISC 360-10, LRFD METHOD.
S-2. UNLESS OTHERWISE NOTED, STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE ABOVE-
LISTED AISC SPECIFICATION AND THE FOLLOWING:
A. WIDE FLANGE SHAPES (50 KSI) ASTM A992, GRADE B
B. HSS HOLLOW SHAPES (46 KSI) ASTM A500, GRADE B
B. PLATES AND ANGLES ASTM A36
C. HIGH STRENGTH BOLTS ASTM A325
D. ANCHOR RODS W/ NUT AND WASHER ASTM F1554, GRADE 36
S-3. IT IS THE INTENTION OF THESE DESIGN DOCUMENTS TO DELEGATE THE DESIGN OF ALL STRUCTURAL
STEEL CONNECTIONS TO A QUALIFIED REGISTERED ENGINEER U.N.O. SIGNED AND SEALED
CALCULATIONS FOR CONNECTION DESIGNS SHALL BE SUBMITTED SIMULTANEOUSLY WITH
FABRICATION DRAWINGS FOR REVIEW. UNLESS NOTED OTHERWISE ON PLANS, ALL SHEAR
CONNECTIONS FOR SIMPLY SUPPORTED BEAMS SHALL BE DESIGNED TO DEVELOP THE REACTION OF
THE MAXIMUM ALLOWABLE UNIFORM LOAD CAPACITY FOR THE BEAM SIZE AND SPAN SHOWN,
ASSUMING FULL LATERAL SUPPORT, AS TABULATED IN THE ALLOWABLE UNIFORM LOAD TABLES OF
THE AISC MANUAL, 14TH EDITION.
S-4. ALL SHOP AND FIELD WELDING SHALL BE BY CERTIFIED WELDERS AND SHALL CONFORM TO AWS
STANDARDS. USE E70XX ELECTRODES UNLESS OTHERWISE NOTED. MINIMUM WELD SIZE FOR
STRUCTURAL STEEL IS 1/8 IN FILLET, UNLESS OTHERWISE NOTED. CURRENT AWS CERTIFICATIONS
SHALL BE AVAILABLE AT THE JOB SITE FOR REVIEW BY THE OWNERS' REPRESENTATIVE.
S-5. ALL BOLTED CONNECTIONS, UNLESS OTHERWISE NOTED, SHALL USE 3/4" DIAMETER HIGH STRENGTH
BOLTS WITH HARDENED CARBON STEEL WASHERS AS REQUIRED FOR THE CONNECTION LOADS.
S-6. ALL FIELD-BOLTED SHEAR CONNECTIONS SHALL BE SNUG TIGHT BEARING-TYPE CONNECTIONS, THREADS INCLUDED IN THE SHEAR PLANE.
S-7. FIELD CUTTING OF STRUCTURAL STEEL MEMBERS BY ANY TRADE IS NOT PERMITTED. BOLT HOLES
SHALL NOT BE CUT OR ENLARGED BY FLAME CUTTING IN THE FIELD.
S-8. THE CONTRACTOR SHALL SUBMIT FOR APPROVAL DRAWINGS AND DESIGN CALCULATIONS FOR ANY
ALTERNATE DETAILS AND MEMBER SPLICES.
S-9. SHOP OR FIELD SPLICES OF STRUCTURAL STEEL MEMBERS ARE PROHIBITED EXCEPT AS DETAILED ON THE DRAWINGS, PERMITTED IN THE SPECIFICATIONS, AS INDICATED ON APPROVED SUBMITTALS, AND AS SPECIFICALLY APPROVED ON SHOP DRAWINGS PRIOR TO FABRICATION.
S-10. PAINT ALL STEEL BELOW GRADE WITH BITUMINOUS COATING.
S-11. ALL STEEL EXPOSED TO WEATHER SHALL BE HOT-DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A123 FOR MEMBERS AND ASTM A153 FOR CONNECTION ELEMENTS, EXCEPT THAT ARCHITECTURALLY EXPOSED STRUCTURAL STEEL SHALL BE BLAST CLEANED AND COATED IN ACCORDANCE WITH THE
STRUCTURAL STEEL AND PAINT SPECIFICATIONS. COORDINATE ALL STEEL FINISHES WITH
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
MASONRY CONSTRUCTION NOTES:
M-1. ALL MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" (ACI 530-13/ASCE 5-13/TMS 402-13) AND "SPECIFICATION FOR MASONRY
STRUCTURES" (ACI 530.1-13/ASCE 6-13/TMS 602-13).
M-2. NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNITS SHALL BE A MINIMUM OF 2000 PSI.
M-3. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 AND BE MANUFACTURED WITH NORMAL
WEIGHT AGGREGATE.
M-4. GROUT SHALL CONFORM TO ASTM C476 AND SHALL NOT CONTAIN ADMIXTURES. GROUT SHALL ATTAIN
A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2000 PSI.
M-5. REINFORCEMENT SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60 AND
SHALL HAVE FABRICATION TOLERANCES IN ACCORDANCE WITH ACI 315. SHOP FABRICATE
REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.
M-6. LOCATE JOINT REINFORCEMENT 16 INCHES ON CENTER VERTICALLY AND ADDITIONALLY AT THE TOP OF ALL FOUNDATIONS AND IN THE TWO JOINTS IMMEDIATELY ABOVE AND BELOW ALL OPENINGS, EXTENDING A MINIMUM OF 24 INCHES BEYOND THE JAMB ON EACH SIDE.
M-7. PLACE PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH MASONRY IN STEEL OR PVC SLEEVES
OR CORED HOLES UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
M-8. ALUMINUM CONDUITS, PIPES, AND ACCESSORIES SHALL NOT BE EMBEDDED IN MASONRY GROUT, OR
MORTAR, UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CEMENT CHEMICAL
REACTION OR ELECTROLYTIC REACTION BETWEEN ALUMINUM AND STEEL.
M-9. UNLESS OTHERWISE NOTED OR DETAILED, CENTER WALL REINFORCEMENT IN BLOCK CELLS. USE
NONMETALLIC BAR POSITIONERS.
M-10. PROVIDE DOWEL REINFORCEMENT FROM WALLS INTO FOUNDATION OF SAME SIZE AND SPACING AS VERTICAL WALL REINFORCEMENT. LAP WALL REINFORCEMENT AS INDICATED IN SCHEDULE ON SB601.
STEEL DECK NOTES:
SD-1. ROOF DECK SHALL BE GALVANIZED STEEL CONFORMING TO ASTM A653 WITH A MINIMUM YIELD STRENGTH OF 33 KSI. STEEL ROOF DECK SHALL BE AS SHOWN ON DRAWINGS. ROOF DECK SHALL BE
FASTENED AS SHOWN SF501.
SD-2. PROVIDE ALL RIDGE PLATES, VALLEY PLATES, CLOSURE PLATES, POUR STOPS, AND ALL OTHER
ACCESSORIES REQUIRED FOR COMPLETE INSTALLATION IN ACCORDANCE WITH THE DECK
MANUFACTURER'S RECOMMENDATIONS.
SD-3. CONTRACTOR SHALL COORDINATE OPENINGS IN STEEL DECK WITH ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS PRIOR TO DECK PLACEMENT.
SD-4. HANGING LOADS DIRECTLY FROM ROOF DECK IS PROHIBITED.
SD-5. STEEL DECK SHALL SPAN CONTINUOUSLY OVER A MINIMUM OF 4 SUPPORTS (3 SPANS) UNO.
STEEL JOIST NOTES:
SJ-1. DESIGN, FABRICATION AND ERECTION OF JOISTS, JOIST EXTENSIONS AND JOIST SUBSTITUTES SHALL
BE IN ACCORDANCE WITH SJI SPECIFICATIONS.
SJ-2. JOISTS, JOIST EXTENSIONS AND JOIST SUBSTITUTES SHALL BE DESIGNED TO THE INDICATED SLOPES
AND FOLLOWING CRITERIA. ROOF JOISTS SIZES SHOWN ON DRAWINGS ARE PROVIDED FOR
ESTIMATING PURPOSES, HOWEVER SHALL BE MINIMUM REQUIRED AND ANY CHANGE REQUIRED SHALL
BE SUBJECT TO CONTRACTING OFFICER APPROVAL.
SJ-3. ALL ROOF JOISTS, JOIST EXTENSIONS AND JOIST SUBSTITUTES SHALL BE DESIGNED BY THE STEEL
JOIST FABRICATOR FOR THE DESIGN LOADS NOTED ON THE DRAWINGS INCLUDING:
1. COLLATERAL ROOF DEAD LOAD OF 15 PSF W/ 10 PSF TOP CHORD, 5 PSF BOTTOM CHORD
2. ROOF SNOW LOADS, INCLUDING DRIFT SURCHARGE AT ALL HEADWALLS
3. ROOF LIVE LOAD OF 20 PSF WITH LIVE LOAD DEFLECTION LESS THAN L/240
4. ROOF MOUNTED MECHANICAL EQUIPMENT, SEE SF502
5. ROOF MOUNTED SCREEN WALL, WITH DEAD LOAD OF 20 PLF
6. GROSS UPLIFT PRESSURES ARE INDICATED ON S-003, FOR NET UPLIFT
UTILIZE COLLATERAL ROOF DEAD OF 10 PSF PLUS SELF WEIGHT OF JOIST
SJ-4. JOISTS SHALL NOT SUPPORT GREATER THAN A 50 LB CONCENTRATED VERTICAL LOAD ON THE
BOTTOM CHORD BETWEEN PANEL POINTS WITHOUT ADEQUATE REINFORCING OF JOISTS. NO
VERTICAL LOAD SHALL BE IMPOSED ON BRIDGING. SEE SF502 FOR JOIST REINFORCING DETAIL.
SJ-5. PROVIDE TOP AND BOTTOM CHORD EXTENSIONS WHERE NOTED ON DRAWINGS.
SJ-6. JOIST DESIGN SHALL INCLUDE ALL REQUIRED JOIST BRIDGING. BRIDGING SHALL BE SIZED, SPACED, AND INSTALLED IN ACCORDANCE WITH SJI SPECIFICATIONS.
SJ-7. JOISTS SHALL BE CONNECTED TO THE SUPPORTING STEEL IN ACCORDANCE WITH SJI SPECIFICATIONS
AND PROJECT CRITERIA NOTED ON DRAWINGS.
SJ-8. CALCULATIONS AND DRAWINGS PREPARED AND SIGNED BY A REGISTERED ENGINEER SHALL BE
SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW PRIOR TO FABRICATION OF JOISTS.
FORCE PROTECTION NOTES:
FP-1. WINDOW AND DOOR FRAME CONNECTIONS TO STRUCTURAL ELEMENTS SHALL MEET UFC 4-010-01
AND UFC 4-010-02 REQUIREMENTS.
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXMLV\Documents\FY17PN85794_STRUC_R18_K6ENXMLV.rvt
4/16/2018 6:51:15 AM
AP
R
IL
W
2H N
-1 8-
B-
M . V
AN
D
ER
H
EY
D
EN
JA
W
C
AT
C O
D E
S-001
G
EN
ER
AL
S
TR
U C
TU
R
AL
N
O
TE
S
SA
VA
N N
AH
D
IS
TR
IC
T
SA
VA
N N
AH
, G
EO
R
G
IA
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
ISSUED FOR CONSTRUCTION
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
M-11. BOND BEAMS AT ROOF AND FLOOR LEVELS SHALL BE CONTINUOUS FOR LENGTH OF BOND BEAM, INCLUDING WALL INTERSECTIONS, AROUND CORNERS, AND THROUGH MASONRY CONTROLS JOINTS.
M-12. MASONRY WALLS NOT SPECIFICALLY DETAILED SHALL HAVE MINIMUM VERTICAL REINFORCING OF #5 BARS LOCATED 48" OC, INTERMEDIATE BOND BEAM LOCATED 6' - 8" AFF AND BOND BEAM AT TOP OF
WALL WITH (2) #5 BARS. HORIZONTAL JOINT REINFORCEMENT SHALL BE 16 INCHES OC.
STRUCTURAL ABBREVIATIONS
SYMBOL DESCRIPTION
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
APPROX APPROXIMATELY
ARCH ARCHITECTURAL
BOC BOTTOM OF CONCRETE
BOF BOTTOM OF FOOTING
BOM BOTTOM OF MASONRY
BOS BOTTOM OF STEEL
BOT BOTTOM
BRG BEARING
CJ CONSTRUCTION JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONN CONNECTION
CONC CONCRETE
CONT. CONTINUOUS
CONSTR CONSTRUCTION
DCJ DOWELED CONSTRUCTION JOINT
DEG DEGREE
DIA DIAMETER
DN DOWN
DWG(S) DRAWING(S)
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
EOS EDGE OF SLAB
EQ EQUAL
ERV ENERGY RECOVERY VENTILATOR
EW EACH WAY
FF FINISHED FLOOR
FTG FOOTING
GA GAGE
GALV GALVANIZED
GFGI GOVT
HORIZ HORIZONTAL
KIP (k) 1000 POUNDS
LG LONG
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MFR MANUFACTURER
MIN MINIMUM
NTS NOT TO SCALE
OC ON CENTER
OPP OPPOSITE
PEMB PRE-ENGINEERED METAL BUILDING
PJF PREMOLDED JOINT FILLER
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
REINF REINFORCEMENT
REQD REQUIRED
SCHED SCHEDULE
SJ SAWED CONTRACTION JOINT
SJI STEEL JOIST INSTITUTE
SIM SIMILAR
SL SLOPE(D)
SOG SLAB ON GRADE
STD STANDARD
T&B TOP AND BOTTOM
TO TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF SLAB
TS THICKENED SLAB
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VEF VEHICLE EXHAUST FAN
VERT VERTICAL
WP WORKING POINT
WWF WELDED WIRE FABRIC
STRUCTURAL LEGEND
SLOPE DIRECTION
INDICATES ELEVATION REFERENCED
TO FINISHED FLOOR
KEYED PLAN NOTE
COLUMN REFERENCE LINE
(CENTER LINE OF COLUMN)
SPOT ELEVATION
SLAB DEPRESSION
BRICK WALL
CONCRETE ELEMENT
EARTH FILL
GROUT
CONCRETE MASONRY UNIT (CMU)
POROUS FILL
WELDED WIRE FABRIC (WWF)
STEEL FRAMING REFERENCE
(XXK) WXxXX [XX] (XXK)
DN
X
[+/- X’-X”]
X
[+/- X’-X”]
BEAM
REACTION
AISC SHAPE
DESIGNATION
INDICATES # OF SHEAR STUDS
WELDED TO TOP FLANGE OF
BEAM PER GENERAL NOTES
HSSXxX
BPX
COLUMN SIZE
BASE PLATE SIZE
STEEL COLUMN
SPECIAL INSPECTION NOTES:
SI-1. INSPECTION OF FABRICATORS SHALL BE CONDUCTED IN ACCORDANCE WITH
IBC 2015, SECTION 1704.2.5.
SI-2. INSPECTION OF STEEL CONSTRUCTION SHALL BE CONDUCTED IN ACCORDANCE
WITH IBC 2015, SECTION 1705.2.
SI-3. INSPECTION OF CONCRETE CONSTRUCTION SHALL BE CONDUCTED IN ACCORDANCE
WITH IBC 2015, SECTION 1705.3 AND TABLE 1705.3.
SI-4 INSPECTION OF MASONRY CONSTRUCTION SHALL BE CONDUCTED IN ACCORDANCE
WITH IBC 2015, SECTION 1705.4.
SI-5. INSPECTIONS FOR SEISMIC RESISTANCE SHALL BE CONDUCTED IN ACCORDANCE
WITH IBC 2015, SECTION 1705.12.
SI-6. INCLUDE SPECIAL INSPECTIONS REQUIREMENTS IN CONTRACTOR'S QUALITY
CONTROL (CQC) PLAN.
SI-7. THE CONTRACTOR SHALL RETAIN THIRD PARTY QUALITY ASSURANCE AGENCIES
TO CONDUCT SPECIAL INSPECTIONS REQUIRED BY IBC. INSPECTING AGENCY
SHALL PROVIDE REPORTS OF SPECIAL INSPECTIONS DIRECTLY TO THE GOVERNMENT.
DESIGN CODE NOTES:
D-1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND
SPECIFICATIONS:
A. IBC 2015, INTERNATIONAL BUILDING CODE
B. ASCE 7-10, MINIMUM DESIGN LOADS FOR BUILDINGS AND STRUCTURES
C. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
D. ACI 530-13, BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
E. AISC 360-10, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
F. AISI S100-12, NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD
FORMED STEEL STRUCTURAL MEMBERS.
G. SDI, STEEL DECK INSTITUTE: DESIGN MANUAL FOR COMPOSITE DECK,
FORM DECK, & ROOF DECK
H. UFC 1-200-01, GENERAL BUILDING REQUIREMENTS, (1 FEB 2018)
I. UFC 3-301-01, STRUCTURAL ENGINEERING, (12 SEP 2016)
J. UFC 3-310-04, SEISMIC DESIGN OF BUILDINGS, (20 JUN 2016)
K. UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS,
(1 OCT 2013)
DESIGN LOAD CRITERIA:
D-2. FIRST FLOOR LIVE LOADS:
MECHANICAL/ELECTRICAL ROOMS 150 PSF
STORAGE ROOMS 125 PSF
RESTROOMS 60 PSF
OFFICES 50 PSF
AREAS NOT OTHERWISE SPECIFIED 100 PSF
D-3. ROOF LIVE LOAD: (REDUCIBLE) 20 PSF
D-4. SNOW LOADS:
RISK CATEGORY II
SNOW IMPORTANCE FACTOR, Is 1.0 MINIMUM GROUND SNOW LOAD, Pg 10 PSF SNOW EXPOSURE FACTOR, Ce 0.9 SNOW THERMAL FACTOR, Ct 1.0 ROOF SLOPE FACTOR, Cs 1.0
BALANCED SNOW LOADING:
MINIMUM LOW SLOPE ROOF SNOW LOAD, Pm 10 PSF SLOPED ROOF SNOW LOAD, Ps 6.3 PSF
RAIN ON SNOW LOAD 5 PSF
UNBALANCED SNOW LOADING:
DRIFT SURCHARGE LOAD (MAX INTENSITY) 30 PSF
DRIFT WIDTH (ABUTTING ALL HEADWALLS) 10 FT
D-5. WIND LOADS:
RISK CATEGORY II
WIND IMPORTANCE FACTOR, Iw 1.0
BASIC WIND SPEED, V 115 MPH
WIND EXPOSURE CATEGORY C
GUST EFFECT FACTOR, G 0.85
INTERNAL PRESSURE COEFFICIENTS, GCpi +/- 0.18
D-6. SEISMIC LOADS:
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR, Ie 1.0 MAPPED SPECTRAL RESPONSE ACCELERATION, Ss 0.27
MAPPED SPECTRAL RESPONSE ACCELERATION, S1 0.11
SITE CLASS D
DESIGN SPECTRAL RESPONSE ACCELERATION, Sds 0.285 DESIGN SPECTRAL RESPONSE ACCELERATION, Sd1 0.173
SEISMIC DESIGN CATEGORY C
SEISMIC ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
SEISMIC-FORCE RESISTING SYSTEM ORDINARY REINFORCED MASONRY
SHEAR WALLS
RESPONSE MODIFICATION FACTOR, R 2
SYSTEM OVERSTRENGTH FACTOR 2.5
DEFLECTION AMPLIFICATION FACTOR, Cd 2 SEISMIC RESPONSE COEFFICIENT, Cs 0.143
SEISMIC DESIGN BASE SHEAR 199.6 KIPS (LONGITUDINAL)
323.3 KIPS (TRANSVERSE)
D-7. ANTI-TERRORISM/FORCE PROTECTION CRITERIA:
NEW BUILDING LOCATION PARKING AND ROADWAYS WITHIN
A CONTROLLED PERIMETER
BUILDING CATEGORY PRIMARY GATHERING BUILDING
DESIGN LEVEL OF THREAT LOW
DESIGN LEVEL OF PROTECTION (LOP) LOW (VLOP)
CONVENTIONAL CONSTR STANDOFF DISTANCE 30 FT
APPLICABLE EXPLOSIVE WEIGHT CLASS II
STEEL DOORS AND FRAMES SPEC 08 11 13
ALUMINUM DOORS AND FRAMES SPEC 08 11 16
ALUMINUM WINDOWS SPEC 08 51 13
GLAZING SPEC 08 81 00
PROGRESSIVE COLLAPSE CRITERIA APPLIES NO (<3 STORIES)
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXMLV\Documents\FY17PN85794_STRUC_R18_K6ENXMLV.rvt
4/16/2018 6:51:41 AM
AP
R
IL
W
2H N
-1 8-
B-
M . V
AN
D
ER
H
EY
D
EN
JA
W
C
AT
C O
D E
S-002
G
EN
ER
AL
S
TR
U C
TU
R
AL
N
O
TE
S
SA
VA
N N
AH
D
IS
TR
IC
T
SA
VA
N N
AH
, G
EO
R
G
IA
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
ISSUED FOR CONSTRUCTION
M
AR
K D
ES
C
R
IP
TI
O
N D a = 11' - 8"
3'
3 2
3' 3'2'
2' 2'
4a 4a
2a
2a
3 32
HIGH MONOSLOPE ROOF AREA
HIGH MONOSLOPE ROOF AREA
DENOTES
LOW GABLE
ROOF
RIDGELINE
2a
2a 2a
OVERHANG AREA
3 2 2a
"a"
"a
LOW MONOSLOPE ROOF AREA
TRIBUTARY
AREA (SF)
TRIBUTARY
AREA (SF)
ZONE 1
MIDDLE
ZONE 2
EDGE/RIDGE
ZONE 3
CORNERS
ZONE 2
OVERHANG
ZONE 3
OVERHANG
-33.2
-32.6
-31.7
-30.3
-52.8
-55.6
-49.7
-41.9
-36.0
-83.7
-66.9
-44.4
-27.5
-83.7
-69.1
-50.0
-36.0
GABLE ROOF COMPONENT/CLADDING PRESSURES (PSF)
ROOF PRESSURES
TRIBUTARY
AREA (SF)
ZONE 4 ZONE 5
-36.0 -44.4
-41.3
-37.4
-34.6
-34.6
-32.6
-30.9
WALL COMPONENT/CLADDING PRESSURES (PSF)
500 -27.5-27.5
-52.0
-50.3
-50.0
TRIBUTARY
AREA (SF)
ZONE 1
MIDDLE
ZONE 2
EDGE/RIDGE
ZONE 3
CORNERS
-36.0 -41.6
-40.7
-39.3
-38.8
-55.6
-50.6
-43.8
-38.8
MONOSLOPE ROOF COMPONENT/CLADDING PRESSURES (PSF)
ROOF PRESSURES
ZONE 2'
EDGE/RIDGE
ZONE 3'
CORNERS
-50.0
-49.4
-47.8
-47.2
-78.1
-69.7
-58.4
-50.0
-36.0
-36.0
-36.0
5 4 5
"a" a = 11' - 8"
"a"
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXMLV\Documents\FY17PN85794_STRUC_R18_K6ENXMLV.rvt
4/16/2018 6:51:57 AM
AP
R
IL
W
2H N
-1 8-
B-
M . V
AN
D
ER
H
EY
D
EN
JA
W
C
AT
C O
D E
S-003
G
EN
ER
AL
S
TR
U C
TU
R
AL
N
O
TE
S
SA
VA
N N
AH
D
IS
TR
IC
T
SA
VA
N N
AH
, G
EO
R
G
IA
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
ISSUED FOR CONSTRUCTION
COMPONENT & CLADDING ROOF PLAN1
COMPONENT & CLADDING WIND PRESSURES3
COMPONENT & CLADDING WALL ELEVATION2 NO SCALENO SCALE
NO SCALE
M
AR
K D
ES
C
R
IP
TI
O
N D
MASONRY OUT-TO-OUT
341' - 8 3/4"
" C
M U
SH
EA
R W
AL
L
J
SH
EA
R W
AL
L
G
SH
EA
R W
AL
L
G
SH
EA
R W
AL
L
F
SH
EA
R W
AL
L
D
SH
EA
R
W
AL
L C
SH
EA
R W
AL
L
B
SH
EA
R W
AL
L
A
SHEARWALL 2
SHEARWALL 1A
SHEARWALL 1B
SHEARWALL 1
M
AS
O N
R Y
O U
T-
TO
-O U
T
5'
3/ 4"
SHEARWALL 3
SH
EA
R W
AL
L
H A
BO
VE
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXMLV\Documents\FY17PN85794_STRUC_R18_K6ENXMLV.rvt
4/16/2018 6:52:23 AM
AP
R
IL
W
2H N
-1 8-
B-
M . V
AN
D
ER
H
EY
D
EN
JA
W
C
AT
C O
D E
SB101
C O
M
PO
SI
TE
F O
U N
D
AT
IO
N
P
LA
N
SA
VA
N N
AH
D
IS
TR
IC
T
SA
VA
N N
AH
, G
EO
R
G
IA
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
ISSUED FOR CONSTRUCTION
COMPOSITE FOUNDATION PLAN1
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
8 16 3241216
SCALE: 1/16"=1'-0"
PLAN NORTH TRUE NORTH
NORTH ARROW
PART A PART B
PART
C
PART D
KEY PLAN
W F2
.5
WF3.0 WF3.0
WF2.5
B
A
2 86
C
D
SF201
SF201
SF205
SF206
CF4.0
CF6.0X10.0
SHEARWALL 2
SHEARWALL 3
SH
EA
R W
AL
L
J
SH
EA
R W
AL
L
G
C.J.
C .J
C .J
SB302
W F2
.0
C.J.
DEPRESSED SLAB
SEE ARCH FOR EXTENTS *
WF2.5
W F2
.0
WF2.0
C .J
C .J
C .J
W F2
.0
1 1
SB301
1 1 1
5' - 0 1/2"
TO FACE BRG WALL
10' - 0" 15' - 0"
TO FACE BRG WALL
10' - 0"
SB301
CF4.0
SB301
SB301
SB301
SB301
/4
15' - 4 7/8" *
* VERIFY DEPRESSD SLAB DIMENISONS
WITH ARCH DRAWINGS.
C .J
C .J
C .J
C .J
C .J
C.J.
C.J.
3' - 0"
CC18x18
HSS5X5X1/2
CC18x18
HSS5X5X1/2
HSS8X8X1/2
HSS8X8X1/2
CC21x37
CC18x184
SB303
(-6") (-6")(-6") (-6")
TYP @
MASONRY
PILASTERS
37' - 6"
1. FOR GENERAL STRUCTURAL NOTES AND ABBREVIATIONS,
SEE S-001 AND S-002.
2. SEE SF201 AND FOLLOWING FOR FRAMING ELEVATIONS.
3. SEE SB501 AND FOLLOWING FOR FOUNDATION SECTIONS
AND DETAILS.
4. TOP OF CONCRETE SLAB-ON-GRADE ELEVATION = 0'-0".
ALL ELEVATIONS INDICATED FROM THIS DATUM. SEE
CIVIL FOR EXACT ELEVATION.
5. ALL FOOTINGS SHALL BE CENTERED UNDER COLUMNS
AND WALLS, UNO.
6. CF-X INDICATES COLUMN FOOTING. SEE FOOTING
SCHEDULE ON SB601 FOR SIZE AND REINFORCEMENT.
7. WF-X INDICATES WALL FOOTING. SEE FOOTING
SCHEDULE ON SB601 FOR SIZE AND REINFORCEMENT.
8. TOP OF FTG. = (-) 2'- 0" UNO.
9. ALL INTERIOR MASONRY WALLS EXTEND TO THE
UNDERSIDE OF STRUCTURE ABOVE UNO.
10. SLAB-ON-GRADE AT ALL INTERIOR CONDITIONS SHALL BE
PLACED 10 MIL VAPOR RETARDER ON A 4" LAYER OF
COMPACTED GRANULAR FILL.
11. PROVIDE (2) #4 X 4'-0" LONG AT CENTER OF
SLAB-ON-GRADE AT ALL RE-ENTRANT CORNERS AND
WHERE A CONTRACTION JOINT TERMINATES AT A
CONTRACTION JOINT.
12. JOINT LOCATIONS DENOTED BY CJ ARE DIAGRAMMATIC
ONLY AND DO NOT REPRESENT ALL JOINTS REQUIRED
FOR SLAB CONSTRUCTION. CONTRACTOR SHALL
COORDINATE SLAB-ON-GRADE REQUIREMENTS WITH
SLAB-ON-GRADE CONSTRUCTION SEQUENCING AND SLAB
DETAILS ON SB501. JOINT SPACING SHALL NOT EXCEED
MAXIMUM JOINT SPACING PER ACI REQUIREMENTS.
13. COORDINATE UNDERGROUND UTILITY LINES WITH CIVIL,
PLUMBING, AND FIRE PROTECTION DRAWINGS PRIOR TO
CONSTRUCTION OF FOOTINGS AND SLABS-ON-GRADE.
SLAB-ON-GRADE SHALL CONSIST OF 4" THICK
CONCRETE REINFORCED WITH 6X6 W2.1XW2.1 WWF
LOCATED AT 1/3-DEPTH FROM TOP OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 6" THICK
CONCRETE REINFORCED WITH 6X6 W2.1XW2.1 WWF
LOCATED AT 1/3-DEPTH FROM TOP OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 8" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 9" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 12" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
6 8" THICK CONCRETE CAP OVERHEAD REINFORCED
WITH #5 BARS @ 12" OC EW, CENTERED IN CAP.
BOTTOM OF CAP AT 10' - 0" AFF.
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXMLV\Documents\FY17PN85794_STRUC_R18_K6ENXMLV.rvt
4/16/2018 6:52:41 AM
AP
R
IL
W
2H N
-1 8-
B-
M . V
AN
D
ER
H
EY
D
EN
JA
W
C
AT
C O
D E
SB101A
FO
U
N D
AT
IO
N P
LA
N
AR
EA
A
SA
VA
N N
AH
D
IS
TR
IC
T
SA
VA
N N
AH
, G
EO
R
G
IA
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
ISSUED FOR CONSTRUCTION
FOUNDATION PLAN - AREA A1 164 8268
SCALE: 1/8"=1'-0"
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
PLAN NORTH TRUE NORTH
NORTH ARROW
PART A PART B
PART
C
KEY PLANPLAN NOTES PLAN NOTES PLAN LEGEND PLAN LEGEND
WF3.0
F2
.5
WF2.5 WF2.5
WF3.0
B
A
128 96 10
C
SF208
SF202
SF202
SF205
SF206
CF4.0CF4.0
CF6.0X10.0 CF6.0X10.0
W F2
.0
SH
EA
R W
AL
L
D
SHEARWALL 3
SHEARWALL 2
SH
EA
R W
AL
L
A
C.J.
C .J
C.J.
C .J
C.J.
C.J. C.J.
DEPRESSED SLAB
SEE ARCH FOR EXTENTS *
SB302
SF207
SF207
DEPRESS SLAB 3/4" FOR
WALK OFF MAT, SEE ARCH
WF2.0
W F2
.0
1 1 1 1 1
TO FACE BRG WALL
15' - 0" 20' - 0"
TO FACE BRG WALL
15' - 0"
5' - 0 1/2" 19' - 11" 5' - 0 1/2"
/8
C .J
C .J
C .J
C .J
C .J
C .J
C .J
C .J
HAIRPIN H-2
HAIRPIN H-1
SB301
SB301
SB301
SB301
SB301
38' - 0"
SB301
6 6 6
1 1 1
/4
15' - 4 7/8" *
* VERIFY DEPRESSED SLAB DIMENSIONS
WITH ARCH DRAWINGS.
3' - 0" 3' - 0"
CF6.0 CF6.0
CC18x18
HSS8X8X1/2
CC18x18
HSS8X8X1/2
HSS8X8X1/2 HSS8X8X1/2
HSS8X8X1/2HSS8X8X1/2
CC21x37
CC18x18
CC21x37
CC18x18
CC18x18 CC18x18
HSS5X5X1/2 HSS5X5X1/2
(-6") (-6")
(-4") (-4")
(-4") (-4")
9'
0"
SB302
SB303
TYP @
MASONRY
PILASTERS
56' - 5 1/4"
C .J
C .J
C .J
C.J.C.J.
1. FOR GENERAL STRUCTURAL NOTES AND ABBREVIATIONS,
SEE S-001 AND S-002.
2. SEE SF201 AND FOLLOWING FOR FRAMING ELEVATIONS.
3. SEE SB501 AND FOLLOWING FOR FOUNDATION SECTIONS
AND DETAILS.
4. TOP OF CONCRETE SLAB-ON-GRADE ELEVATION = 0'-0".
ALL ELEVATIONS INDICATED FROM THIS DATUM. SEE
CIVIL FOR EXACT ELEVATION.
5. ALL FOOTINGS SHALL BE CENTERED UNDER COLUMNS
AND WALLS, UNO.
6. CF-X INDICATES COLUMN FOOTING. SEE FOOTING
SCHEDULE ON SB601 FOR SIZE AND REINFORCEMENT.
7. WF-X INDICATES WALL FOOTING. SEE FOOTING
SCHEDULE ON SB601 FOR SIZE AND REINFORCEMENT.
8. TOP OF FTG. = (-) 2'- 0" UNO.
9. ALL INTERIOR MASONRY WALLS EXTEND TO THE
UNDERSIDE OF STRUCTURE ABOVE UNO.
10. SLAB-ON-GRADE AT ALL INTERIOR CONDITIONS SHALL BE
PLACED 10 MIL VAPOR RETARDER ON A 4" LAYER OF
COMPACTED GRANULAR FILL.
11. PROVIDE (2) #4 X 4'-0" LONG AT CENTER OF
SLAB-ON-GRADE AT ALL RE-ENTRANT CORNERS AND
WHERE A CONTRACTION JOINT TERMINATES AT A
CONTRACTION JOINT.
12. JOINT LOCATIONS DENOTED BY CJ ARE DIAGRAMMATIC
ONLY AND DO NOT REPRESENT ALL JOINTS REQUIRED
FOR SLAB CONSTRUCTION. CONTRACTOR SHALL
COORDINATE SLAB-ON-GRADE REQUIREMENTS WITH
SLAB-ON-GRADE CONSTRUCTION SEQUENCING AND SLAB
DETAILS ON SB501. JOINT SPACING SHALL NOT EXCEED
MAXIMUM JOINT SPACING PER ACI REQUIREMENTS.
13. COORDINATE UNDERGROUND UTILITY LINES WITH CIVIL,
PLUMBING, AND FIRE PROTECTION DRAWINGS PRIOR TO
CONSTRUCTION OF FOOTINGS AND SLABS-ON-GRADE.
SLAB-ON-GRADE SHALL CONSIST OF 4" THICK
CONCRETE REINFORCED WITH 6X6 W2.1XW2.1 WWF
LOCATED AT 1/3-DEPTH FROM TOP OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 6" THICK
CONCRETE REINFORCED WITH 6X6 W2.1XW2.1 WWF
LOCATED AT 1/3-DEPTH FROM TOP OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 8" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 9" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 12" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
6 8" THICK CONCRETE CAP OVERHEAD REINFORCED
WITH #5 BARS @ 12" OC EW, CENTERED IN CAP.
BOTTOM OF CAP AT 10' - 0" AFF.
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXMLV\Documents\FY17PN85794_STRUC_R18_K6ENXMLV.rvt
4/16/2018 6:52:59 AM
AP
R
IL
W
2H N
-1 8-
B-
M . V
AN
D
ER
H
EY
D
EN
JA
W
C
AT
C O
D E
SB101B
FO
U
N D
AT
IO
N P
LA
N
AR
EA
B
SA
VA
N N
AH
D
IS
TR
IC
T
SA
VA
N N
AH
, G
EO
R
G
IA
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AR
C
YB
ER
C O
M
PA
N Y
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
PN
ISSUED FOR CONSTRUCTION
FOUNDATION PLAN - AREA B1
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
PLAN NORTH TRUE NORTH
NORTH ARROW
PART A PART B
PART
C
PART D
KEY PLAN
164 8268
SCALE: 1/8"=1'-0"
NORTH ARROW
PLAN NOTES PLAN NOTES PLAN LEGEND PLAN LEGEND
.5
WF3.0
W F2
.0
WF3.0
WF2.5
W F2
.0
CF4.0 CF4.0 CF4.0
E
G
F
4 5 7 10
D
SF201
SF201
SF201
SF201
SF303
/2
SF203 2
SF203
SF204 2
SF204
SF205
SF205
SB302
SB302
CF14.0
CF6.0
CF14.0
HAIRPIN H-1
HAIRPIN H-1
W24X68
HSS8X8X1/4
W24X68
" C
SH
EA
R W
AL
L
J
SH
EA
R W
AL
L
G
SH
EA
R W
AL
L
F
SHEARWALL 1B
SHEARWALL 1
SHEARWALL 2
W F2
.0
W F2
.0
WF3.5
W F2
.0 C
.J
C .J
C .J
BOLLARD, TYP
BOLLARD, TYP
/8
C.J.
WF2.0
CF4.0
C .J
C .J
C .J
C .J
C .J
C .J
C .J
C .J
C.J.
C.J.
C .J
C .J
C .J
WF3.0
W F2
.0
SB301
FACE OF CMU TO CL GRID LINE 1
47' - 8 3/8"4 4 4
4 4 4
1 1
3 3
2 2
27' - 8" 27' - 8" 27' - 8"
TO
F
AC
E
O F
M
AS
O N
R Y
/8
HSS4X4X1/4 HSS4X4X1/4 HSS4X4X1/4 HSS4X4X1/4
SB301
SB302
SB301
SB301
SB301
6 6 6
C.J.
C.J.
C .J
C .J
C .J
C .J
WF2.0
T/WALL 15' - 4" AFF
CC21x37CC21x37CC21x37CC21x37
SL
O
PE
/8 "/F
T
CC18x40
CC18x40
(-4")
(-4")
SB303
SB303
C .J
C .J
. W F2
.0
C .J
C .J
C.J.
C.J.
1. FOR GENERAL STRUCTURAL NOTES AND ABBREVIATIONS,
SEE S-001 AND S-002.
2. SEE SF201 AND FOLLOWING FOR FRAMING ELEVATIONS.
3. SEE SB501 AND FOLLOWING FOR FOUNDATION SECTIONS
AND DETAILS.
4. TOP OF CONCRETE SLAB-ON-GRADE ELEVATION = 0'-0".
ALL ELEVATIONS INDICATED FROM THIS DATUM. SEE
CIVIL FOR EXACT ELEVATION.
5. ALL FOOTINGS SHALL BE CENTERED UNDER COLUMNS
AND WALLS, UNO.
6. CF-X INDICATES COLUMN FOOTING. SEE FOOTING
SCHEDULE ON SB601 FOR SIZE AND REINFORCEMENT.
7. WF-X INDICATES WALL FOOTING. SEE FOOTING
SCHEDULE ON SB601 FOR SIZE AND REINFORCEMENT.
8. TOP OF FTG. = (-) 2'- 0" UNO.
9. ALL INTERIOR MASONRY WALLS EXTEND TO THE
UNDERSIDE OF STRUCTURE ABOVE UNO.
10. SLAB-ON-GRADE AT ALL INTERIOR CONDITIONS SHALL BE
PLACED 10 MIL VAPOR RETARDER ON A 4" LAYER OF
COMPACTED GRANULAR FILL.
11. PROVIDE (2) #4 X 4'-0" LONG AT CENTER OF
SLAB-ON-GRADE AT ALL RE-ENTRANT CORNERS AND
WHERE A CONTRACTION JOINT TERMINATES AT A
CONTRACTION JOINT.
12. JOINT LOCATIONS DENOTED BY CJ ARE DIAGRAMMATIC
ONLY AND DO NOT REPRESENT ALL JOINTS REQUIRED
FOR SLAB CONSTRUCTION. CONTRACTOR SHALL
COORDINATE SLAB-ON-GRADE REQUIREMENTS WITH
SLAB-ON-GRADE CONSTRUCTION SEQUENCING AND SLAB
DETAILS ON SB501. JOINT SPACING SHALL NOT EXCEED
MAXIMUM JOINT SPACING PER ACI REQUIREMENTS.
13. COORDINATE UNDERGROUND UTILITY LINES WITH CIVIL,
PLUMBING, AND FIRE PROTECTION DRAWINGS PRIOR TO
CONSTRUCTION OF FOOTINGS AND SLABS-ON-GRADE.
SLAB-ON-GRADE SHALL CONSIST OF 4" THICK
CONCRETE REINFORCED WITH 6X6 W2.1XW2.1 WWF
LOCATED AT 1/3-DEPTH FROM TOP OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 6" THICK
CONCRETE REINFORCED WITH 6X6 W2.1XW2.1 WWF
LOCATED AT 1/3-DEPTH FROM TOP OF SLAB.
SLAB-ON-GRADE SHALL CONSIST OF 8" THICK
CONCRETE REINFORCED WITH (2) LAYERS OF
4X4 W2.9XW2.9 WWF LOCATED AT 2" FROM TOP AND
BOTTOM OF SLAB.
SLAB-ON…