18B3001vol3.pdf

PDF 2 MB Posted

Attached to
ARCYBER Company Operations Facility, Fort Gordon, GA
Solicitation number
W912HN18B3001
Issued by

About this file

SPECS Vol 3

View the file

Other files

File Type Posted
B.01.02_Bid_Abstract_W912HN18B3001_ARCYBER_COF.xls XLS spreadsheet
Bid_Abstract_W912HN18B3001_ARCYBER_COF.pdf PDF
18B3001vol2.PDF PDF
18B3001vol1.PDF PDF
amd7.pdf PDF
amd6.pdf PDF
18B3001vol1.PDF PDF
amd5.pdf PDF
18B3001vol1.PDF PDF
18B3001vol2.PDF PDF
18B3001vol4.PDF PDF
18B3001vol3.PDF PDF
W912HN-18-B-3001_VOL2_AMD5.pdf PDF
18B3001vol1.pdf PDF
18B3001vol3.pdf PDF
18B3001vol4.pdf PDF
W912HN-18-B-3001_VOL2_AMD4.pdf PDF
18B3001vol2.pdf PDF
amd4.pdf PDF
W912HN-18-B-3001_VOL2_AMD3.pdf PDF
18B3001vol1.pdf PDF
amd3.pdf PDF
W912HN-18-B-3001_VOL1_AMD3.pdf PDF
18B3001vol2.pdf PDF
amd2.pdf PDF
W912HN-18-B-3001_VOL1_AMD1.pdf PDF
18B3001vol4.pdf PDF
W912HN-18-B-3001_VOL2_AMD2.pdf PDF
18B3001vol1.pdf PDF
18B3001vol1.pdf PDF
amd1.pdf PDF
18B3001vol4.pdf PDF
18B3001vol2.pdf PDF
W912HN-18-B-3001_VOL1.pdf PDF
W912HN-18-B-3001_VOL2.pdf PDF
18B3001vol1.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fort Gordon, Georgia

Solicitation Number

W912HN-18-B-3001

ARCYBER COF

Volume 3 of 4: Specification Divisions 10 - 23

PN 85794

May 2018

U.S. ARMY ENGINEER DISTRICT, SAVANNAH

CORPS OF ENGINEERS

100 WEST OGLETHORPE AVENUE

SAVANNAH, GEORGIA 31401-3640

US Army Corps of Engineers Savannah District

ARCYBER COF GO85794

Ft . Gor don, GA

PROJECT TABLE OF CONTENTS

DI VI SI ON 01 - GENERAL REQUI REMENTS

01 11 00 SUMMARY OF WORK

01 32 01. 00 37 PROJECT SCHEDULE

01 33 00 SUBMI TTAL PROCEDURES

01 33 29 SUSTAI NABI LI TY REPORTI NG

01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS

01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS

01 45 00. 00 10 QUALI TY CONTROL

01 45 00. 15 10 RESI DENT MANAGEMENT SYSTEM CONTRACTOR MODE ( RMS CM)

01 45 35 SPECI AL I NSPECTI ONS

01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS

01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS

01 74 19. 00 37 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT

01 78 00 CLOSEOUT SUBMI TTALS

01 78 23 OPERATI ON AND MAI NTENANCE DATA

01 91 00. 15 TOTAL BUI LDI NG COMMI SSI ONI NG

DI VI SI ON 03 - CONCRETE

03 20 00. 00 10 CONCRETE REI NFORCI NG

03 30 00. 00 10 CAST- I N- PLACE CONCRETE

03 35 00. 00 10 CONCRETE FI NI SHI NG

DI VI SI ON 04 - MASONRY

04 20 00 UNI T MASONRY

DI VI SI ON 05 - METALS

05 05 23. 16 STRUCTURAL WELDI NG

05 12 00 STRUCTURAL STEEL

05 21 00 STEEL JOI ST FRAMI NG

05 30 00 STEEL DECKS

05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS

05 51 33 METAL LADDERS

05 52 00 METAL RAI LI NGS

DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES

06 10 00 ROUGH CARPENTRY

06 20 00 FI NI SH CARPENTRY

06 41 16. 00 10 PLASTI C- LAMI NATE- CLAD ARCHI TECTURAL CABI NETS

06 61 16 SOLI D SURFACI NG FABRI CATI ONS

DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON

07 05 23 PRESSURE TESTI NG AN AI R BARRI ER SYSTEM FOR AI R TI GHTNESS

07 21 13 BOARD AND BLOCK I NSULATI ON

07 22 00 ROOF AND DECK I NSULATI ON

07 27 10. 00 10 BUI LDI NG AI R BARRI ER SYSTEM

07 41 13 METAL ROOF PANELS

07 42 63 FABRI CATED WALL PANEL ASSEMBLI ES

07 54 19 POLYVI NYL- CHLORI DE ROOFI NG

07 60 00 FLASHI NG AND SHEET METAL

07 84 00 FIRESTOPPING

07 92 00 JOI NT SEALANTS

PROJECT TABLE OF CONTENTS Page 1

DI VI SI ON 08 - OPENI NGS

08 11 13 STEEL DOORS AND FRAMES

08 11 16 ALUMI NUM DOORS AND FRAMES

08 34 59 VAULT DOORS AND DAY GATES

08 34 73 SOUND CONTROL DOOR ASSEMBLI ES

08 41 13 ALUMI NUM- FRAMED ENTRANCES AND STOREFRONTS

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 91 00 METAL WALL AND DOOR LOUVERS

DI VI SI ON 09 - FI NI SHES

09 06 00 SCHEDULES FOR FI NI SHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 30 10 CERAMI C, QUARRY, AND GLASS TI LI NG

09 51 00 ACOUSTI CAL CEI LI NGS

09 65 00 RESI LI ENT FLOORI NG

09 68 00 CARPETING

09 69 13 RI GI D GRI D ACCESS FLOORI NG

09 90 00 PAI NTS AND COATI NGS

DI VI SI ON 10 - SPECI ALTI ES

10 11 00 VI SUAL DI SPLAY UNI TS

10 14 00. 10 EXTERI OR SI GNAGE

10 14 00. 20 I NTERI OR SI GNAGE

10 21 13 TOI LET COMPARTMENTS

10 22 13 WI RE MESH PARTI TI ONS

10 26 00 WALL AND DOOR PROTECTI ON

10 28 13 TOI LET ACCESSORI ES

10 44 43. 00 37 FI RE EXTI NGUI SHER ACCESSORI ES

10 51 13 METAL LOCKERS

DI VI SI ON 12 - FURNI SHI NGS

12 24 13 ROLLER WI NDOW SHADES

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

DI VI SI ON 13 - SPECI AL CONSTRUCTI ON

13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT

13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT

DI VI SI ON 21 - FI RE SUPPRESSI ON

21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON

DI VI SI ON 22 - PLUMBI NG

22 00 00 PLUMBI NG, GENERAL PURPOSE

DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)

23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

23 05 15 COMMON PI PI NG FOR HVAC

23 05 48. 00 40 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC PI PI NG AND

PROJECT TABLE OF CONTENTS Page 2

EQUIPMENT

23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC

23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS

23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC

23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC

23 09 93 SEQUENCES OF OPERATI ON FOR HVAC CONTROL

23 11 25 FACI LI TY GAS PI PI NG

23 23 00 REFRI GERANT PI PI NG

23 52 00 HEATI NG BOI LERS

23 64 10 WATER CHI LLERS, VAPOR COMPRESSI ON TYPE

23 64 26 CHI LLED WATER PI PI NG SYSTEMS

23 82 02. 00 10 UNI TARY HEATI NG AND COOLI NG EQUI PMENT

DI VI SI ON 25 - I NTEGRATED AUTOMATI ON

25 05 11 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS

DI VI SI ON 26 - ELECTRI CAL

26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT

26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM

26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON

26 41 00 LI GHTNI NG PROTECTI ON SYSTEM

26 51 00 I NTERI OR LI GHTI NG

DI VI SI ON 27 - COMMUNI CATI ONS

27 05 14. 00 10 CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM

27 05 29. 00 10 PROTECTI VE DI STRI BUTI ON SYSTEM ( PDS) FOR SI PRNET

COMMUNI CATI ON SYSTEMS

27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM

DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY

28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM

DI VI SI ON 31 - EARTHWORK

31 00 00 EARTHWORK

31 11 00 CLEARI NG AND GRUBBI NG

31 31 16. 13 CHEMI CAL TERMI TE CONTROL

31 32 11 SOI L SURFACE EROSI ON CONTROL

DI VI SI ON 32 - EXTERI OR I MPROVEMENTS

32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D

PAVEMENTS

32 05 33 LANDSCAPE ESTABLI SHMENT

32 11 16 BASE COURSE FOR RI GI D PAVI NG

32 11 23 AGGREGATE AND/ OR GRADED- CRUSHED AGGREGATE BASE COURSE

32 12 10 BI TUMI NOUS TACK AND PRI ME COATS

32 12 17 HOT MI X BI TUMI NOUS PAVEMENT

32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE

FACILITIES

32 16 13 CONCRETE SI DEWALKS AND CURBS AND GUTTERS

32 17 24. 00 10 PAVEMENT MARKI NGS

32 92 19 SEEDING

32 92 23 SODDING

PROJECT TABLE OF CONTENTS Page 3

DI VI SI ON 33 - UTI LI TI ES

33 40 00 STORM DRAI NAGE UTI LI TI ES

33 61 13. 13 PREFABRI CATED UNDERGROUND HYDRONI C ENERGY DI STRI BUTI ON

33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON

33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)

APPENDICES

Appendi x A Ft . Gor don BACNET DDC For HVAC

- - End of Pr oj ect Tabl e of Cont ent s - -

PROJECT TABLE OF CONTENTS Page 4

ARCYBER COF 18B3001

Ft. Gordon, GA

SECTION TABLE OF CONTENTS

DIVISION 10 - SPECIALTIES

SECTION 10 11 00

VISUAL DISPLAY UNITS

08/17

PART 1 GENERAL

1.1 REFERENCES

1.2 DEFINITIONS OR ADMINISTRATIVE REQUIREMENTS

1.3 SUBMITTALS

1.4 DELIVERY, STORAGE, AND HANDLING

1.5 WARRANTY

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Cork

2.1.1.1 Colored Cork

2.1.1.2 Natural Cork

2.1.2 Woven Fabric

2.1.3 Non-Woven Fabric

2.1.4 Aluminum

2.1.5 Glass

2.2 Marker Board

2.3 Bulletin Boards

2.3.1 Cork

2.3.2 Fabric Covered

2.4 COLOR

PART 3 EXECUTION

3.1 PLACEMENT SCHEDULE

3.2 INSTALLATION

3.3 CLEANING

-- End of Section Table of Contents --

SECTION 10 11 00 Page 1

SECTION 10 11 00

VISUAL DISPLAY UNITS

08/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test

ASTM INTERNATIONAL (ASTM)

ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM C1048 (2012; E 2012) Standard Specification for Heat-Strengthened and Fully Tempered Flat Glass

ASTM E84 (2017) Standard Test Method for Surface Burning Characteristics of Building Materials

ASTM F148 (2013) Binder Durability of Cork Composition Gasket Materials

ASTM F152 (1995; R 2009) Tension Testing of Nonmetallic Gasket Materials

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS SCS Global Services (SCS)Indoor Advantage

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

SECTION 10 11 00 Page 2

1.2 DEFINITIONS OR ADMINISTRATIVE REQUIREMENTS

The term visual display board when used herein includes , marker boards, bulletin boards,submit manufacturer's descriptive data and catalog cuts plus manufacturer's installation instructions, and cleaning and maintenance instructions. Visual display boards must be from manufacturer's standard product line. Submit certificate of compliance signed by Contractor attesting that visual display boards conform to the requirements specified.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Visual Display Board; G, RO

SD-04 Samples

Materials; G, RO

SD-11 Closeout Submittals

Bulletin Boards; S

1.4 DELIVERY, STORAGE, AND HANDLING

Deliver materials to the building site in the manufacturer's original unopened containers and store them in a clean dry area with temperature maintained above 50 degrees F. Stack materials according to manufacturer's recommendations. Visual display boards must be allowed to acclimate to the building temperature for 24 hours prior to installation.

1.5 WARRANTY

Provide manufacturer's standard performance guarantees or warranties that extend beyond a one year period.

PART 2 PRODUCTS

2.1 MATERIALS

Submit section of core material showing the lamination of colored cork, natural cork, woven fabric, non-woven fabric. Submit sample of hardwood and plastic laminate finish, and glass type. Samples must be minimum 4 by 4 inches and show range of color.

2.1.1 Cork

Cork must be a continuous resilient sheet made from soft, clean, granulated cork relatively free from hardback and dust and bonded with a binder suitable for the purpose intended. The wearing surface must be free from streaks, spots, cracks or other imperfections that would impair its

SECTION 10 11 00 Page 3 usefulness or appearance. The material must be seasoned, and a clean cut made not less than 1/2 inch from the edge must show no evidence of soft sticky binder.

2.1.1.1 Colored Cork

Provide colored cork composed of pure cork and natural color pigments that are combined under heat and pressure with linseed oil. Colored cork must be colored throughout and must be washable. The burlap backing must be deeply imbedded and keyed to the work sheet being partially concealed in it and meeting the requirements of ASTM F148.

2.1.1.2 Natural Cork

Material must be a single layer of pure grain natural cork without backing or facing. The color must be light tan. The cork sheet must have a tensile strength of not less than 40 psi when tested in accordance with

ASTM F152.

2.1.2 Woven Fabric

Provide plain weave fabric. Fiber content must be 100 percent polyester .

Minimum total weight must be 16 oz. plus or minus 0.5 oz. per lineal yard.

Fabric must have a Class A flame spread rating of 0-50 and smoke development rating of 0-450 in accordance with ASTM E84.

2.1.3 Non-Woven Fabric

Fabric must be non-woven and hooktape compatible. Fiber content must be 100 percent polyester, 100 percent polyolefin or 100 percent nylon , backed.

Minimum total weight must be 11 oz. plus or minus 0.5 oz. per lineal yard for 60 inch wide fabric. Fabric must have a Class A flame spread rating of 0-50 and smoke development rating of 0-450 in accordance with ASTM E84.

2.1.4 Aluminum

Aluminum frame extrusions must be alloy 6063-T5 or 6063-T6, conform to ASTM B221, and be a minimum 0.06 inches thick. Exposed aluminum must have an anodized, satin finish. Straight, single lengths must be used wherever possible. Joints must be kept to a minimum. Corners must be mitered and must have a hairline closure.

2.1.5 Glass

Glass must be comprised of tempered glass in accordance with ANSI Z97.1 and must conform to ASTM C1048, Kind FT (fully tempered), Condition A (uncoated), Type I, Class I (clear), thickness as specified.

2.2 Marker Board

Markerboard must have a tempered glass writing, magnetic, surface and no frame. Markerboard must be a factory assembled unit complete in one piece, without joints whenever possible. Dry erase markings must be removable with a felt eraser or dry cloth without ghosting. Each unit must come complete with an eraser and four different color compatible dry erase markers and holder. The size must be as shown in paragraph PLACEMENT SCHEDULEand in the drawings. Provide markerboards that meet the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type).

SECTION 10 11 00 Page 4

2.3 Bulletin Boards

Provide bulletin boards that meet the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type).

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body.

2.3.1 Cork

Bulletin board must consist of a minimum 1/8 inch thick colored cork with burlap backing laminated to a minimum 3/8 inch thick insulation board or fiber board 1/8 inch thick natural cork laminated to a minimum 3/8 inch thick insulation board or fiber board, and must have an aluminum frame.

The size must be as shown in paragraph PLACEMENT SCHEDULEand in the drawings.

2.3.2 Fabric Covered

Bulletin boards must have a woven fabric covering laminated to a minimum 1/8 inch thick cork laminated to a minimum 3/8 inch thick insulation board or fiberboard, and must have an aluminum frame. The size must be as shown on the Placement Scheduleand in the drawings.

2.4 COLOR

Finish colors for required items must be as specified in Section 09 06 00

SCHEDULES FOR FINISHES.

PART 3 EXECUTION

3.1 PLACEMENT SCHEDULE

Location and mounting height of visual display boards must be as shown on the drawings and visual display boards must be provided as follows:

SECTION 10 11 00 Page 5

Room Name and Number

Board Type Board Size Wall Location Mounting Height

A100

A102

A103

A104

A108

A109

B107

B114

B115

B117

B118

B119

B120

B123

B124

MARKER

MARKER

MARKER

MARKER

MARKER

MARKER

MARKER

BULLETIN

MARKER

MARKER

MARKER

MARKER

MARKER

MARKER

MARKER

MARKER

3' X 4'

3' X 4'

3' X 4'

3' X 4'

4' X 10'

4' X 10'

4' X 6' 4' X 6'

3' X 4'

3' X 4'

3' X 4'

4' X 10'

3' X 4'

3' X 4'

3' X 4'

3' X 4'

SOUTH WALL

SOUTH WALL

NORTHWALL

NORTH WALL

WEST WALL

NORTH WALL

SOUTH WALL

SOUTH WALL

SOUTH WALL

NORTH WALL

NORTH WALL

EAST WALL

SOUTH WALL

NORTH WALL

SOUTH WALL

WEST WALL

6'6"

6'6"

6'6"

6'6"

7'6"

7'6"

7'6" 7'6"

6'6"

6'6"

6'6"

7'6"

6'6"

6'6"

6'6"

6'6"

Mounting height is defined as distance from finished floor to top of the display board frame.

3.2 INSTALLATION

Do not install items that show visual evidence of biological growth.

Perform installation and assembly in accordance with manufacturer's printed instructions. Use concealed fasteners. Visual display boards must be attached to the walls with suitable devices to anchor each unit. furnish and install trim items, accessories and miscellaneous items in total, including but not limited to hardware, grounds, clips, backing materials, adhesives, brackets, and anchorages incidental to or necessary for a sound, secure, complete and finished installation. Installation must not be initiated until completion of room painting and finishing operations.

Visual display boards must be installed in locations and at mounting heights indicated. Visual display boards must be installed level and plumb, and if applicable doors must be aligned and hardware must be adjusted. Damaged units must be repaired or replaced as directed by the Contracting Officer.

3.3 CLEANING

Writing surfaces must be cleaned in accordance with manufacturer's instructions.

SECTION 10 11 00 Page 6

-- End of Section --

SECTION 10 11 00 Page 7

SECTION TABLE OF CONTENTS

DIVISION 10 - SPECIALTIES

SECTION 10 14 00.10

EXTERIOR SIGNAGE

08/17

PART 1 GENERAL

1.1 REFERENCES

1.2 GENERAL REQUIREMENTS

1.2.1 Wind Load Requirements

1.2.2 Character Proportions and Heights

1.3 SUBMITTALS

1.4 QUALIFICATIONS

1.5 DELIVERY AND STORAGE

1.6 WARRANTY

PART 2 PRODUCTS

2.1 MODULAR EXTERIOR SIGNAGE SYSTEM

2.2 DIMENSIONAL BUILDING LETTERS

2.2.1 Fabrication

2.2.2 Typeface

2.2.3 Size

2.2.4 Finish

2.2.5 Mounting

2.3 ALUMINUM ALLOY PRODUCTS

2.4 ANCHORS AND FASTENERS

2.5 SHOP FABRICATION AND MANUFACTURE

2.5.1 Factory Workmanship

2.5.2 Dissimilar Materials

2.5.3 Shop Painting

2.6 COLOR, FINISH, AND CONTRAST

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Anchorage

3.1.2 Protection and Cleaning

SECTION 10 14 00.10 Page 1

SECTION 10 14 00.10

EXTERIOR SIGNAGE

08/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN WELDING SOCIETY (AWS)

AWS C1.1M/C1.1 (2012) Recommended Practices for Resistance Welding

AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel

ASTM INTERNATIONAL (ASTM)

ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM A653/A653M (2017) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM A924/A924M (2017a) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process

ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

1.2 GENERAL REQUIREMENTS

All exterior signage must be provided by a single manufacturer. Exterior signage must be of the design, detail, sizes, types, and message content shown on the drawings, must conform to the requirements specified, and must be provided at the locations indicated. Submit exterior signage schedule in electronic media with spread sheet format. Spread sheet must include sign location, sign type, and message. Signs must be complete with lettering, framing as detailed, and related components for a complete installation. Each sample must consist of a complete sign panel with letters and symbols. Samples may be installed in the work, provided each sample is identified and location recorded. Submit three color samples for each material requiring color and 12 inch square sample of sign face color sample.

SECTION 10 14 00.10 Page 2

1.2.1 Wind Load Requirements

Exterior signage must be designed to withstand 115____ mph windload.

Submit design analysis and supporting calculations performed in support of specified signage.

1.2.2 Character Proportions and Heights

Letters and numbers on indicated signs for handicapped-accessible buildings must have a width-to-height ratio between 3:5 and 1:1 and a stroke-width-to-height ratio between 1:5 and 1:10. Characters and numbers on indicated signs must be sized according to the viewing distance from which they are to be read. The minimum height is measured using an upper case letter "X". Lower case characters are permitted.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Approved Detail Drawings; G, RO_____

SD-03 Product Data

Modular Exterior Signage System

Installation

Exterior Signage; G, RO_____

Wind Load Requirements

SD-04 Samples

Exterior Signage; G, RO_____

SD-10 Operation and Maintenance Data

Protection and Cleaning; G, RO_____

1.4 QUALIFICATIONS

Signs, plaques, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of the products. Items of equipment must essentially duplicate equipment that has been in satisfactory use at least 2 years prior to bid opening.

1.5 DELIVERY AND STORAGE

Materials must be wrapped for shipment and storage, delivered to the jobsite in manufacturer's original packaging, and stored in a clean, dry area in accordance with manufacturer's instructions.

SECTION 10 14 00.10 Page 3

1.6 WARRANTY

Manufacturer's standard performance guarantees or warranties that extend beyond a one year period must be provided.

PART 2 PRODUCTS

2.1 MODULAR EXTERIOR SIGNAGE SYSTEM

Exterior signage must consist of a system of coordinated directional, identification, and regulatory type signs located where shown. Dimensions, details, materials, message content, and design of signage must be as shown. Submit manufacturer's descriptive data and catalog cuts.

2.2 DIMENSIONAL BUILDING LETTERS

2.2.1 Fabrication

Letters must be fabricated from 0.125 inch aluminum sheet. Letters must be cleaned by chemical etching or cleaned ultrasonically in a special degreasing bath. Letters must be packaged for protection until installation.Building number is "81400".

2.2.2 Typeface

Typeface must be helvetica medium.

2.2.3 Size

Letter size must be 12 INCHES Capital letter size.

2.2.4 Finish

Baked enamel or two-component acrylic polyurethane finish must be provided.

2.2.5 Mounting

Steel U-bracket, cap screws, and expansion bolts of number and size as recommended by manufacturer, must be used for concealed anchorage. Letters which project from the building line must have stud spacer sleeves.

Letters, studs, and sleeves must be of the same material. Supply templates for mounting.

2.3 ALUMINUM ALLOY PRODUCTS

Aluminum alloy products must conform to ASTM B209 for sheet or plate.

Welding for aluminum products must conform to AWS C1.1M/C1.1.

2.4 ANCHORS AND FASTENERS

Exposed anchor and fastener materials must be compatible with metal to which applied and must match in color and finish and must be non-rusting, non-corroding, and non-staining. Exposed fasteners must be tamper-proof.

SECTION 10 14 00.10 Page 4

2.5 SHOP FABRICATION AND MANUFACTURE

2.5.1 Factory Workmanship

Work must be assembled in the shop, as far as practical, ready for installation at the site. Work that cannot be shop assembled must be given a trial fit in the shop to ensure proper field assembly. Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Welding to or on structural steel must be in accordance with AWS D1.1/D1.1M. Welding must be continuous along the entire area of contact. Exposed welds must be ground smooth. Exposed surfaces of work must have a smooth finish and exposed riveting must be flush. Fastenings must be concealed where practical. Items specified to be galvanized must be by hot-dip process after fabrication if practical.

Galvanization must be in accordance with ASTM A123/A123M and ASTM A653/A653M, as applicable. Other metallic coatings of steel sheet must be in accordance with ASTM A924/A924M. Joints exposed to the weather must be formed to exclude water. Drainage and weep holes must be included as required to prevent condensation buildup.

2.5.2 Dissimilar Materials

Where dissimilar metals are in contact, or where aluminum is in contact with concrete, mortar, masonry, wet or pressure-treated wood, or absorptive materials subject to wetting, the surfaces must be protected with a coat of asphalt varnish or a coat of zinc-molybdate primer to prevent galvanic or corrosive action.

2.5.3 Shop Painting

Surfaces of miscellaneous metal work, except nonferrous metal, corrosion resisting steel, and zinc-coated work, must be given one coat of zinc-molybdate primer or an approved rust-resisting treatment and metallic primer in accordance with manufacturer's standard practice. Surfaces of items to be embedded in concrete must not be painted. Upon completion of work, damaged surfaces must be recoated.

2.6 COLOR, FINISH, AND CONTRAST

Color must be in accordance with Section 09 06 00 SCHEDULES FOR FINISHES.

PART 3 EXECUTION

3.1 INSTALLATION

Signs, plaques, or dimensional letters must be installed in accordance with approved manufacturer's instructions at locations shown on the approved detail drawings; submit drawings showing elevations of each type of sign;

dimensions, details, and methods of mounting or anchoring; shape and thickness of materials; and details of construction. Signs must be installed plumb and true at mounting heights indicated, and by method shown or specified. Signs mounted on other surfaces must not be installed until finishes on such surfaces have been completed. Submit manufacturer's installation instructions and cleaning instructions.

3.1.1 Anchorage

Anchorage and fastener materials must be in accordance with approved

SECTION 10 14 00.10 Page 5 manufacturer's instructions for the indicated substrate. Anchorage not otherwise specified or indicated must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood.

3.1.2 Protection and Cleaning

The work must be protected against damage during construction. Hardware must be adjusted for proper operation. sign surfaces must be cleaned in accordance with manufacturer's instructions. After signs are completed and inspected, cover all project identification, directional, and other signs which may mislead the public. Covering must be maintained until instructed to be removed by the Contracting Officer or until the facility is to be opened for business. Submit three_____ copies of maintenance instructions listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guides. The instructions must include simplified diagrams for the equipment as installed. Signs must be cleaned, as required, at time of cover removal.

SECTION 10 14 00.10 Page 6

SECTION TABLE OF CONTENTS

DIVISION 10 - SPECIALTIES

SECTION 10 14 00.20

INTERIOR SIGNAGE

08/17

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 EXTRA MATERIALS

1.4 QUALITY ASSURANCE

1.4.1 Samples

1.4.2 Detail Drawings

1.5 DELIVERY, STORAGE, AND HANDLING

1.6 WARRANTY

PART 2 PRODUCTS

2.1 STANDARD PRODUCTS

2.2 ROOM IDENTIFICATION/DIRECTIONAL SIGNAGE SYSTEM

2.2.1 Standard Room Signs

2.2.2 Changeable Message Strip Signs

2.2.3 Type of Mounting For Signs

2.2.4 Graphics

2.2.4.1 Surface Applied Photopolymer

2.2.5 Character Proportions and Heights

2.2.6 Tactile Letters, Symbols and Braille

2.3 BUILDING DIRECTORIES

2.3.1 Header Panel

2.3.2 Fabrication

2.3.3 Non-Illuminated Unit

2.4 ALUMINUM ALLOY PRODUCTS

2.5 ANODIC COATING

2.6 ORGANIC COATING

2.7 FABRICATION AND MANUFACTURE

2.7.1 Factory Workmanship

2.7.2 Dissimilar Materials

2.8 COLOR, FINISH, AND CONTRAST

2.9 TYPEFACE

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Anchorage

3.1.2 Protection and Cleaning

SECTION 10 14 00.20 Page 1

SECTION 10 14 00.20

INTERIOR SIGNAGE

08/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.

ALUMINUM ASSOCIATION (AA)

AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes

AA PK-1 (2015) Pink Sheets: Designations and Chemical Composition Limits for Aluminum Alloys in the Form of Castings & Ingot

AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)

AAMA 2604 (2017a) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels

AMERICAN WELDING SOCIETY (AWS)

AWS D1.2/D1.2M (2014) Structural Welding Code - Aluminum

ASTM INTERNATIONAL (ASTM)

ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are forinformation only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to

SECTION 10 14 00.20 Page 2

Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Detail Drawings; G, _RO____

SD-03 Product Data

Installation; G, __RO___

Warranty; G, __RO___

SD-04 Samples

Interior Signage; G, __RO___

Software; G, __RO___

SD-10 Operation and Maintenance Data

Approved Manufacturer's Instructions; G, __RO___

Protection and Cleaning; G, __RO___

1.3 EXTRA MATERIALS

Provide 10 extra frames and extra stock of the following: 10 blank plates of each color and size for sign type F.Provide 25 paper inserts and one copy of the software for user produced signs and inserts after project completion.

1.4 QUALITY ASSURANCE

1.4.1 Samples

Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: Directional sign, Standard Room sign, and Changeable message strip sign. The samples may be installed in the work, provided each sample is identified and location recorded.

1.4.2 Detail Drawings

Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.

1.5 DELIVERY, STORAGE, AND HANDLING

Materials must be packaged to prevent damage and deterioration during shipment, handling, storage and installation. Product must be delivered to the jobsite in manufacturer's original packaging and stored in a clean, dry area in accordance with manufacturer's instructions.

1.6 WARRANTY

Warrant the interior signage for a period of 2 years against defective workmanship and material. Warranties must be signed by the authorized

SECTION 10 14 00.20 Page 3 representative of the manufacturer. Submit warranty accompanied by the document authenticating the signer as an authorized representative of the guarantor. Guarantee that the signage products and the installation are free from any defects in material and workmanship from the date of delivery.

PART 2 PRODUCTS

2.1 STANDARD PRODUCTS

Signs, plaques, directories, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letterforms and graphics true and clean.

2.2 ROOM IDENTIFICATION/DIRECTIONAL SIGNAGE SYSTEM

2.2.1 Standard Room Signs

Signs must consist of 6063-T5 extruded aluminum in accordance with ASTM B221 and ASTM B209 and must conform to the following:

a. Frames must be aluminum, radius 1/4 inch thick.

b. End caps must be aluminum with square style corners.

c. Inserts shall be 0.090-inch extruded ABS plastic core with 0.003-inch UV-resistant acrylic cap bonded during extrusion/texturing process.

Insert color is integral..

2.2.2 Changeable Message Strip Signs

Changeable message strip signs must be of same construction as standard room signs to include a clear sleeve that will accept a paper or plastic insert identifying changeable text. The insert must be prepared typewritten message. Provide paper and software for creating text and symbols for computers identified by owner for Owner production of paper inserts after project completion. Furnish one suction device to assist in removing face sheet.

2.2.3 Type of Mounting For Signs

Provide extruded aluminum brackets for hanging, projecting, and double-sided signs. Mounting for framed, hanging, and projecting signs must be by mechanical fasteners. Surface mounted signs must be mounted with 1/16 inch thick closed cell vinyl foam with adhesive backing.

Adhesive must be transparent, long aging, high tech formulation on two sides of the vinyl foam fabricated from materials that are not corrosive to sign material and mounting surface.

2.2.4 Graphics

Signage graphics for modular signs must conform to the following:

2.2.4.1 Surface Applied Photopolymer

Integral graphics and Braille achieved by photomechanical stratification processes. Photopolymer used for ADA compliant graphics must be of the

SECTION 10 14 00.20 Page 4 type that has a minimum durometer reading of 90. Tactile graphics must be raised 1/32 inch from the first surface of plaque by photomechanical stratification process.

2.2.5 Character Proportions and Heights

Letters and numbers on signs conform to 36 CFR 1191.

2.2.6 Tactile Letters, Symbols and Braille

Raised letters and numbers on signs must conform to 36 CFR 1191.

2.3 BUILDING DIRECTORIES

Building directories must be lobby directories or floor directories, and must be provided with a changeable directory listing consisting of the areas, offices and personnel located within the facility. Dimensions, details, and materials of sign and message content must be as shown on the drawings.

2.3.1 Header Panel

Header panel must have background metal to match frame.

2.3.2 Fabrication

Extruded aluminum frames and trim must be assembled with corners reinforced and mitered to a hairline fit, with no exposed fasteners.

2.3.3 Non-Illuminated Unit

Directory must consist of a non-illuminated unit with machine or laser engraved copy in interchangeable acrylic, metal, or high-pressure plastic laminate strips. Design of unit must be as shown in the drawings.

2.4 ALUMINUM ALLOY PRODUCTS

Aluminum extrusions must be at least 1/8 inch thick, and aluminum plate or sheet must be at least 0.0508 inch thick. Extrusions must conform to ASTM B221; plate and sheet must conform to ASTM B209. Where anodic coatings are specified, alloy must conform to AA PK-1 alloy designation

514.0. Exposed anodized aluminum finishes must be as shown. Welding for aluminum products must conform to AWS D1.2/D1.2M.

2.5 ANODIC COATING

Anodized finish must conform to AA DAF45 as follows:

a. Clear (natural) designation AA-M10-C22-A31, Architectural Class II 0.4 mil or thicker.; Or

b. Integral color anodized designation AA-M10-C22-A32, Architectural Class

0.4 to 0.7 mil.

2.6 ORGANIC COATING

Organic coating must conform to AAMA 2604, with total dry film thickness

SECTION 10 14 00.20 Page 5 not less than 1.2 mils.

2.7 FABRICATION AND MANUFACTURE

2.7.1 Factory Workmanship

Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Exposed surfaces of work must have a smooth finish and exposed riveting must be flush.

Fastenings must be concealed where practicable.

2.7.2 Dissimilar Materials

Where dissimilar metals are in contact, the surfaces will be protected to prevent galvanic or corrosive action.

2.8 COLOR, FINISH, AND CONTRAST

Color must be in accordance with Section 09 06 00 SCHEDULES FOR FINISHES.

Finish of all signs must be eggshell, matte, or other non-glare finish as required in handicapped-accessible buildings.

2.9 TYPEFACE

ADA-ABA compliant font for Room Signs.

PART 3 EXECUTION

3.1 INSTALLATION

Signs must be installed plumb and true and in accordance with approved manufacturer's instructions at locations shown on the detail drawings.

Submit two copies of operating instructions outlining the step-by-step procedures required for system operation. The instructions must include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Each set must be permanently bound and must have a hard cover. The following identification must be inscribed on the covers: the words "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Mounting height and mounting location must conform to 36 CFR 1191. Required blocking must be installed. Signs on doors or other surfaces must not be installed until finishes on such surfaces have been installed. Signs installed on glass surfaces must be installed with matching blank back-up plates in accordance with manufacturer's instructions.

3.1.1 Anchorage

Anchorage must be in accordance with approved manufacturer's instructions.

Anchorage not otherwise specified or shown must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete;

toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Exposed anchor and fastener materials must be compatible with metal to which applied and must have matching color and finish.

SECTION 10 14 00.20 Page 6

a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.

b. Mount signs mounted to lay-in ceiling grids with clip connections to ceiling tees.

c. Install signs mounted on metal surfaces with magnetic tape.

d. Install signs mounted on fabric surfaces with hook and loop tape or pin mount.

3.1.2 Protection and Cleaning

Protect the work against damage during construction. Hardware and electrical equipment must be adjusted for proper operation. Glass, frames, and other sign surfaces must be cleaned at completion of sign installation in accordance with the manufacturer's approved instructions and the requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA, Package

1. Submit two copies of maintenance instructions listing routine procedures, repairs, and guides.

SECTION 10 14 00.20 Page 7

SECTION TABLE OF CONTENTS

DIVISION 10 - SPECIALTIES

SECTION 10 21 13

TOILET COMPARTMENTS

08/17

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 CERTIFICATIONS

1.3.1 Indoor Air Quality

1.3.1.1 Solid Phenolic Products

1.4 REGULATORY REQUIREMENTS

1.5 DELIVERY, STORAGE, AND HANDLING

1.6 WARRANTY

PART 2 PRODUCTS

2.1 SYSTEM REQUIREMENTS

2.2 MATERIALS

2.2.1 Galvanized Steel Sheet

2.2.2 Sound-Deadening Cores

2.2.3 Anchoring Devices and Fasteners

2.2.4 Brackets

2.2.5 Hardware and Fittings

2.2.5.1 General Requirements

2.2.5.2 Finishes

2.2.6 Door Hardware

2.2.6.1 Hinges

2.2.6.2 Latch and Pull

2.2.6.3 Coat Hooks

2.3 PARTITION PANELS AND DOORS

2.3.1 Toilet Enclosures

2.3.2 Urinal Screens

2.4 FLOOR-ANCHORED PARTITIONS

2.5 PILASTER SHOES

2.6 HARDWARE

2.7 COLORS AND FINISHES

2.7.1 Colors

2.7.2 Finishes No.4 and No. 5

PART 3 EXECUTION

3.1 PREPARATION

3.2 INSTALLATION

3.3 FLOOR-ANCHORED PARTITIONS

3.4 FINAL ADJUSTMENT

3.5 CLEANING

SECTION 10 21 13 Page 1

SECTION 10 21 13

TOILET COMPARTMENTS

08/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip

ASTM A336/A336M (2015) Standard Specification for Alloy Steel Forgings for Pressure and High-Temperature Parts

ASTM A385/A385M (2017) Standard Practice for Providing High-Quality Zinc Coatings (Hot-Dip)

ASTM A653/A653M (2017) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM B36/B36M (2013) Standard Specification for Brass Plate, Sheet, Strip, and Rolled Bar

ASTM B86 (2013) Standard Specification for Zinc and Zinc-Aluminum (ZA) Alloy Foundry and Die Castings

ASTM D6386 (2016) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers

SECTION 10 21 13 Page 2

INTERNATIONAL CODE COUNCIL (ICC)

ICC A117.1 COMM (2017) Standard And Commentary Accessible and Usable Buildings and Facilities

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS SCS Global Services (SCS)Indoor Advantage

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

CID A-A-60003 (Basic) Partitions, Toilet, Complete

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Fabrication Drawings

SD-03 Product Data

Cleaning and Maintenance Instructions

Colors And Finishes

Galvanized Steel Sheet

Sound-Deadening Cores

Anchoring Devices and Fasteners

Hardware and Fittings

Brackets

Door Hardware

SECTION 10 21 13 Page 3

Pilaster Shoes

Finishes; G, RO

SD-04 Samples

Colors and Finishes; G, RO

Hardware and Fittings

Anchoring Devices and Fasteners

SD-07 Certificates

Warranty

Indoor Air Quality

SD-11 Closeout Submittals

Indoor air quality for solid phenolic, black core partitions and screens; S

1.3 CERTIFICATIONS

1.3.1 Indoor Air Quality

1.3.1.1 Solid Phenolic Products

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body.

1.4 REGULATORY REQUIREMENTS

Conform to ICC A117.1 COMM code for access for the handicapped operation of toilet compartment door and hardware.

1.5 DELIVERY, STORAGE, AND HANDLING

Deliver materials in the manufacturer's original unopened packages with the brand, item identification, and project reference clearly marked. Store components in a dry location that is adequately ventilated; free from dust, water, other contaminants, and damage during delivery, storage, and construction.

1.6 WARRANTY

Provide certification or warranties that toilet partitions will be free of defects in materials, fabrication, finish, and installation and will remain so for a period of not less than 2 years after completion.

PART 2 PRODUCTS

2.1 SYSTEM REQUIREMENTS

Provide a complete and usable toilet partition system, including toilet

SECTION 10 21 13 Page 4 enclosures, room entrance screens, urinal screens, system of panels, hardware, and support components. Furnish the partition system from a single manufacturer, with a standard product as shown in the most recent catalog data. Submit Fabrication Drawings for metal toilet partitions and urinal screens consisting of fabrication and assembly details to be performed in the factory. Submit manufacturer's Cleaning and Maintenance Instructions with Fabrication Drawings for review.

2.2 MATERIALS

2.2.1 Galvanized Steel Sheet

Provide galvanized steel sheet cold-rolled, stretcher-level, commercial quality material, conforming to ASTM A653/A653M. Conform surface preparation of material for painting to ASTM D6386, Method A.

2.2.2 Sound-Deadening Cores

Provide sound deadening consisting of treated kraft paper honeycomb cores with a cell size of not more than 1 inch. Resin-material content must weigh not less than 11 percent of the finished core weight. Expanded cores must be faced on both sides with kraft paper.

2.2.3 Anchoring Devices and Fasteners

Provide steel anchoring devices and fasteners hot-dipped galvanized after fabrication, in conformance with ASTM A385/A385M and ASTM A123/A123M.

Conceal all galvanized anchoring devices.

2.2.4 Brackets

Wall brackets must be two-ear panel brackets, T-style, 1-inch stock.

Provide stirrup style panel-to-pilaster brackets.

2.2.5 Hardware and Fittings

2.2.5.1 General Requirements

Conform hardware for the toilet partition system to CID A-A-60003 for the specified type and style of partitions. Provide hardware finish highly resistant to alkalis, urine, and other common toilet room acids. Comply latching devices and hinges for handicap compartments with 36 CFR 1191;

provide stainless steel devices and hinges with door latches that operate without either tight grasping or twisting of the wrist of the operator.

Submit three samples of each item, including anchoring devices and fasteners. Approved hardware samples may be installed in the work if properly identified.

Material Conformance Standard

Cold-rolled sheet steel ASTM A336/A336M, commercial quality

Zinc-base alloy ASTM B86, Alloy AC41-A

Brass ASTM B36/B36M, Alloy C26800

Aluminum ASTM B221

SECTION 10 21 13 Page 5

Corrosion-resistant steel ASTM A167, Type 304

2.2.5.2 Finishes

a. Corrosion-resistant steel must have a No. 4 finish.

b. Exposed fasteners must match the hardware and fittings.

2.2.6 Door Hardware

2.2.6.1 Hinges

Hinges must be adjustable to hold in-swinging doors open at any angle up to 90 degrees and outswinging doors to 10 degrees. Provide self-lubricating hinges with the indicated swing. Hinges must be the surface-mounted type.

have the following type of return movement:

a. Gravity return movement

2.2.6.2 Latch and Pull

Latch and pull must be a combination rubber-faced door strike and keeper equipped with emergency access.

2.2.6.3 Coat Hooks

Coat hooks must be combination units with hooks and rubber tipped pins.

2.3 PARTITION PANELS AND DOORS

Fabricate partition panels and doors not less than 1 inch thick with face sheets not less than 0.0396 inch thick.

Provide solid phenolic toilet partitions and urinal screens to meet the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type). Provide certification of indoor air quality for solid phenolic, black core partitions and screens.

2.3.1 Toilet Enclosures

Provide and conform toilet enclosures to CID A-A-60003, Type I, Style A, floor supported. Furnish width, length, and height of toilet enclosures as shown. Finish surface of panels must be solid phenolic, color through the core Finish 4A; water resistant; graffiti resistant; non-absorbent; .

Reinforce panels indicated to receive toilet paper holders or grab bars for mounting of the items required. Provide grab bars to withstand a bending stress, shear stress, shear force, and a tensile force induced by 250 lbf.

Grab bars must not rotate within their fittings.

2.3.2 Urinal Screens

Provide and conform urinal screens to CID A-A-60003, Type III, Style A, floor supported. Provide finish for surface of screens as solid phenolic, SECTION 10 21 13 Page 6 color through the core Finish 4A; water resistant; graffiti resistant;

non-absorbent; . Furnish width and height of urinal screens as shown.

Secure wall hung urinal screens with a minimum of three wall stirrup brackets. Fabricate screens from the same types of panels and pilasters as the toilet partitions. Use corrosion-resistant steel fittings and fasteners.

2.4 FLOOR-ANCHORED PARTITIONS

Pilasters must be not less than 1-1/4 inch thick with face sheets not less than 0.0635 inch thick. Provide anchoring device at the bottom of the pilaster consisting of a steel bar not less than 1/2 by 7/8 inch welded to the reinforced face sheets and having not less than two 3/8 inch round anchorage devices for securing to the floor slab. Provide anchorage devices complete with threaded rods, expansion shields, lock washers, and leveling-adjustment nuts. Trim piece at the floor must be 3 inch high and fabricated from not less than 0.030 inch thick corrosion-resistant steel.

2.5 PILASTER SHOES

Provide shoes at pilasters to conceal floor-mounted anchorage. Pilaster shoes must be stainless steel. Height must be 3 inches.

2.6 HARDWARE

Provide hardware for the toilet partition system that conforms to CID A-A-60003 for the specified type and style of partitions. Provide hardware pre-drilled by manufacturer. Use a hardware finish that is highly resistant to alkalis, urine, and other common toilet room acids. Hardware includes: chrome plated non ferrous cast pivot hinges, gravity type, adjustable for door close positioning; nylon bearings; chrome plated aluminum door latch; door strike and keeper with rubber bumper; and cast alloy chrome plated coat hook and bumper, . Provide latching devices and hinges for handicap compartments complying with 36 CFR 1191 and stainless steel door latches that operate without either tight grasping or twisting of the wrist of the operator. Use stainless steel, tamper proof type screws and bolts. Wall mounting brackets must be continuous, full height, stainless steel, in accordance with toilet compartment manufacturer's instructions. Provide floor-mounted anchorage consisting of corrosion-resistant anchoring assemblies with threaded rods, lock washers, and leveling adjustment nuts at pilasters for structural connection to floor.

2.7 COLORS AND FINISHES

2.7.1 Colors

Provide manufacturer's standard color charts for color of finishes for toilet partition system components. Submit three samples showing a finished edge on two adjacent sides and core construction, each not less than 12-inch square

2.7.2 Finishes No.4 and No. 5

Provide solid plastic fabricated of solid phenolic core with…