A22 - PLAN_SET_AMND-2022-04-14-AMND_0001_ELECTRICAL.pdf
PDF 10 MB Posted
- Attached to
- Illinois River Basin Dresden Island Lock and Dam; Morris, Will County, Illinois; Lock Rehabilitation
- Solicitation number
- W912EK22R0008
About this file
This document provides details for a federal contract opportunity issued by the Department of the Army Corps of Engineers Engineering District Rock Island. The solicitation number is W912EK22R0008 for lock rehabilitation work at the Illinois River Basin Dresden Island Lock and Dam in Morris, Will County, Illinois. The base work includes installation of a government furnished miter gate, replacement of miter gate machinery, and electrical system replacement. An option for fairlead and checkpost replacement is also included. Bids are sought for lock chamber dewatering and other rehabilitation efforts. The opportunity type is listed as a solicitation.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
C O
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A N
S I
D
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
/0
/2
R O
C K
I S
L A
N D
IL
L
IN
IS
C K
I S
L A
N D
D
IS
T R
IC
T
C A
M P
B E
L
H
E E
T I
N D
E X
G-002
D
D
IL
L O
N
A
C A
M P
B E
L L
A P
R
M
N D
U P
D A
T E
D S
H E
E T
N U
M B
E R
A N
D A
D D
E D
S H
E E
B
IW
L D
B
R A
D T
K E
ELECTRICAL
W
E K
R
MECHANICAL SCHEDULE SWITCHBOARD BUILDING M-610
DETAIL - SWITCHBOARD BUILDING SUMP PUMPM-510
SECTION - DRAIN PIPE M-304
SECTION - DRAIN PIPE M-303
SECTION - DRAIN PIPE M-302
SECTION - DRAIN PIPE M-301
PLAN - SWITCHBOARD BUILDING MECHANICAL UNITSM-110
PLAN - DRAIN PIPE M-103
PLAN - DRAIN PIPE M-102
PLAN - DRAIN PIPE M-101
SWITCHBOARD BUILDING SECTIONS A-103
SWITCHBOARD BUILDING ELEVATIONS A-102
SWITCHBOARD BUILDING FLOOR PLAN A-101
DETAIL - MITER GATE AND SLIDE VALVE RECEPTACLES S-541
DETAIL - MITER GATE AND SLIDE VALVE RECEPTACLES ASSEMBLY S-540
DETAIL - WALL ARMOR AND TRENCH S-503
DETAIL - SWITCHBOARD BUILDING S-502
DETAIL - WALL ARMOR S-501
SECTION - EXISTING CROSSOVER DUCT BANK S-307
SECTION - SWITCHBOARD BUILDING S-306
SECTION - GALLERY AND UTILITY TRENCH S-305
SECTION - GALLERY AND UTILITY TRENCH S-304
SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS S-303
SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS S-302
SECTION - CROSSOVER DUCT BANK OVERALL S-301
ELEVATION - CROSSOVER DUCT BANK S-201
PLAN - I-WALL MANHOLE [Region4]S-105
PLAN - SWITCHBOARD BUILDING [Region4]S-104
PLAN - GALLERY AND UTILITY TRENCH S-103
PLAN - CROSSOVER DUCT BANK S-102
PLAN - OVERALL S-101
DETAILS - ELEMENTARY DIAGRAM - VALVE INTERLOK LADDER LOGIC DIAGRAME-709
DETAILS - ELEMENTARY DIAGRAM INTERLOCK AND SHUNT TRIP CONTROLSE-708
DETAILS - ELEMENTARY DIAGRAM LOWER TRAFFIC SIGNAL CONTROLSE-707
DETAILS - ELEMENTARY DIAGRAM UPPER TRAFFIC SIGNAL AND AIR HORN CONTROLSE-706
DETAILS - ELEMENTARY DIAGRAM UPPER RIGHT CONTROLSE-705
DETAILS - ELEMENTARY DIAGRAM LOWER RIGHT CONTROLSE-704
DETAILS - ELEMENTARY DIAGRAM UPPER LEFT CONTROLSE-703
DETAILS - ELEMENTARY DIARAM LOWER LEFT CONTROLSE-702
DETAILS - CONTROL INTERLOCK FLOW CHARTS E-701
SCHEDULES - CABLES E-629
SCHEDULES - CABLES E-628
SCHEDULES - CABLES E-627
SCHEDULES - CABLES E-626
SCHEDULES - CABLES E-625
SCHEDULES - NEW PANELBOARDS E-622
SCHEDULES - NEW PANELBOARD E-621
SCHEDULES - CONTROL CONSOLES E-611
GROUNDING DIAGRAM E-608
BUBBLER WIRING DIAGRAME-607
MOTOR WIRING DIAGRAMS E-606
ONE LINE DIAGRAM E-601
DETAILS - MITER GATE AND SLIDE VALVE RECEPTACLES E-540
DETAILS - DUCT BANKE-523
DETAILS - TRAFFIC CONTROL PANEL E-522
DETAILS - CONTROL POWER AND INTERLOCK CONTROL PANEL E-521
DETAILS - HIGH MAST LIGHTING CONTROLLER E-520
DETAILS - PANEL BOARD E-519
DETAILS - MAIN SWITCHBOARD "SB-1" E-518
DETAILS - JOYSTICK SELECTOR SWITCHES E-517
DETAILS - CONTROL CONSOLE SUBPANEL ELEVATIONSE-516
DETAILS - UPPER/LOWER RIGHT CONTROL CONSOLE E-513
DETAILS - UPPER/LOWER LEFT CONTROL CONSOLE E-512
DETAILS - NEW CONTROL CONSOLE E-511
DETAILS - INTERMEDIATE WALL RECESS PROXIMITY SWITCH AND MAGNETE-505
DETAILS - INTERMEDIATE WALL MITER PROXIMITY SWITCH AND MAGNETE-504
DETAILS - LAND WALL RECESS PROXIMITY SWITCH AND MAGNETE-503
DETAILS - LAND WALL MITER PROXIMITY SWITCH AND MAGNETE-502
DETAILS - MITER GATE LEAF ROTARY CAM LIMIT SWITCH INTERNAL PLANE-501
ELEVATION - NEW CROSSOVER DUCT BANK AND MANHOLES E-205
SWITCHBOARD BUILDING FLOOR PLAN E-150
PLAN - UPSTREAM MITER GATE AND SLIDE VALVE RECEPTACLESE-141
PLAN - DOWNSTREAM MITER GATE AND SLIDE VALVE RECEPTACLESE-140
PLAN - CENTRAL CONTROL BUILDING - FIRST FLOOR AND BASEMENTE-111
PLAN - UPSTREAM AND DOWNSTREAM GUIDE WALLSE-110
PLAN - DOWNSTREAM INTERMEDIATE WALL E-109
PLAN - CENTER INTERMEDIATE WALL E-108
PLAN - UPSTREAM INTERMEDIATE WALL E-107
PLAN - DOWNSTREAM LANDWALL E-106
PLAN - CENTER LAND WALL E-105
PLAN - UPSTREAM LAND WALL E-104
PLAN - ESPLANADE & SERVICE ENTRANCE E-103
MAIN LOCK ELECTRICAL PLAN E-102
OVERALL ELECTRICAL SITE PLAN E-101
GENERAL NOTES G-005
GENERAL NOTES AND SUGGESTED SEQUENCE OF WORK G-004
LEGEND AND ABBREVIATIONS G-003
SHEET INDEX G-002
COVER SHEET ELECTRICAL SYSTEM REPLACEMENT G-001
SHEET TITLESHEET ID
SHEET INDEX
SECTION - GALLERY AND UTILITY TRENCH DEMOLITIONSD305
SECTION - GALLERY AND UTILITY TRENCH DEMOLITIONSD304
SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS DEMOLITIONSD303
SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS DEMOLITIONSD302
SECTION - CROSSOVER DUCT BANK OVERALL DEMOLITIONSD301
ELEVATIONS - CROSSOVER DUCT BANK DEMOLITION CROSSOVER DUCT BANKSD201
PLAN - UPSTREAM ELECTRICAL RECEPTACLES DEMOLITIONSD141
PLAN - DOWNSTREAM ELECTRICAL RECEPTACLES DEMOLITIONSD140
PLAN - GALLERY AND UTILITY TRENCH DEMOLITIONSD103
PLAN - CROSSOVER DUCTBANK DEMOLITIONSD102
PLAN - OVERALL DEMOLITIONSD101
EXISTING CABLE SCHEDULE DOWNSTREAM RIGHT DEMOLITIONED634
EXISTING CABLE SCHEDULE UPSTREAM RIGHT DEMOLITIONED633
EXISTING CABLE SCHEDULE DOWNSTREAM LEFT DEMOLITIONED632
EXISTING CABLE SCHEDULE UPSTREAM LEFT DEMOLITIONED631
EXISTING PANELBOARDS SCHEDULES DEMOLITION ED622
EXISTING PANELBOARDS SCHEDULES DEMOLITION ED621
EXISTING ONE LINE DIAGRAM DEMOLITION ED602
EXISTING ONE LINE DIAGRAM DEMOLITION ED601
CENTRAL CONTROL BUILDING PLAN DEMOLITION ED105
DOWNSTREAM PLAN DEMOLITION ED104
UPSTREAM PLAN DEMOLITION ED103
MAIN LOCK ELECTRICAL PLAN DEMOLITION ED102
OVERALL ELECTRICAL SITE PLAN DEMOLITION ED101
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A
C A
M P
B E
IN
L
O C
K E
L E
C T
R
IC
A L
P L
A N
E-102
T L
E E
C H
B P
A T
T S
C H
U
N D
A
D D
E D
A N
N O
T A
T
IO
N
IW
L D
B
R A
D T
K E
ELECTRICAL
A N
S I
X
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
W
E K
R
/0
/2
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
P R
LAND WALL
UPPER LEFT
ILLINOIS WATERWAY
FLOW
DRESDEN ISLAND MAIN LOCK CHAMBER
LAND WALL
INTERMEDIATE WALL (I-WALL)
GUIDEWALL
UPSTREAM
LAND WALL
LOWER LEFT
INTERMEDIATE WALL
LOWER RIGHT
STATION BUILDING
CENTRAL CONTROL
3 10
INTERMEDIATE WALL
UPPER RIGHT
TERMINATION OF PERMANENT GAUGE WELL EQUIPMENT.
EXISTING, INSTALLATION OF TEMPORARY, REMOVAL OF TEMPORARY, AND
COORDINATE WITH GOVERNMENT REGARDING DISCONNECTION OF
INSTRUMENTATION CONDUCTORS ON GAUGE WELL EQUIPMENT.
AND REMOVE TEMPORARY GAUGE WELL EQUIPMENT, AND TERMINATE
THE GOVERNMENT WILL UNTERMINATE INSTRUMENTATION CABLE, PROVIDE 3.
ELECTRICAL CABLES, AND CONNECTIONS.
SEE ED-DRAWINGS AND REFRENCE DRAWINGS FOR EXISTING STRUCTURE, 2.
SEE GENERAL ELECTRICAL NOTES ON SHEET E-00011.
GENERAL SHEET NOTES
SHEET KEYNOTES
FOUR.
ELECTRICAL CABLE FOR EXISTING FLOATING MOORING BITS. TYPICAL OF
PROVIDE NEW EMBEDDED CONDUIT TO NEW CABLE TRENCH AND NEW 8.
ELECTRICAL CABLES. TYPICAL OF ONE.
PROVIDE EXISTING AIR COMPRESSOR WITH NEW RACEWAYS AND NEW
RECONNECT AND REUSE EXISTING 150 HP BUBBLER AIR COMPRESSOR. 7.
TYPICAL OF TWO.
TOW HAULAGE UNITS WITH NEW RACEWAYS AND NEW ELECTRICAL CABLES.
REINSTALL AND REUSE EXISTING TOW HAULAGE UNITS. PROVIDE EXISTING 6.
ANCHORAGES (2 PER MITER GATE LEAF).
LOCATION OF EXISTING AND NEW CONCRETE EMBEDDED MITER GATE 5.
TYPICAL OF FOUR.
RACEWAYS AND NEW ELECTRICAL CABLES TO SLIDE VALVE EQUIPMENT.
REUSE EXISTING SLIDE VALVE MACHINERY AND CONTROLLERS. PROVIDE NEW
VALVE MACHINERY, AND HPU WITH INTEGRAL CONTROLLER. REINSTALL TO
LOCATION OF EXISTING HYDRAULICS SLIDE VALVE CONCRETE RECESS, SLIDE 4.
LOCATION OF NEW MITER GATE CONCRETE RECESS AND MACHINERY. 3.
OF FOUR.
ELECTRICAL EQUIPMENT INSIDE NEW CONTROL STAND STRUCTURE. TYPICAL
PROVIDE NEW CONTROL CONSOLE, POWER DISTRIBUTION, AND OTHER 2.
ASSEMBLY COVER. TYPICAL OF FOUR.
THE NEW GFE STRUT ARM BUFFER BOX INSIDE THE NEW GFE LIMIT SWITCH
SWITCH ACTUATORS AND PROVIDE FOUR NEW LIMIT SWITCHES INSTALLED ON
BOX COVERS SAME AS EXISTING. SALVAGE AND RELOCATE THE EXISTING
PROVIDE NEW STRUT ARM LIMIT SWITCH ASSEMBLY IN LOCATION ON BUFFER 1.
SHEETS.
PROVIDE NEW RACEWAYS AND ELECTRICAL CABLES. SEE APPLICABLE DETAIL
EXISTING TRAFFIC LIGHT FIXTURES (RED, YELLOW, & GREEN) FOR REUSE.
MAINTAIN AND PROTECT EXISTING TRAFFIC SIGNAL LIGHT POLES AND 18.
ELECTRICAL CABLES. SEE APPLICABLE DETAIL SHEETS.
ADDITIONAL NEW RACEWAYS, EXTEND TO EXISTING, AND PROVIDE NEW
EXISTING DAM PATH LIGHT RACEWAYS FOR THEIR REUSE. PROVIDE
MAINTAIN AND PROTECT EXISTING LIGHT POLES FOR REUSE. INTERCEPT 17.
CABLES. SEE APPLICABLE DETAIL SHEETS.
REFEED WITH NEW RACEWAYS, EXISTING RACEWAYS, AND NEW ELECTRICAL
(URDP-MCC-4) TO EXISTING TO SAFETY SWITCH LOCATED AT DAM ABUTMENT.
PROVIDE NEW DAM FEEDER CABLE ROUTED FROM POWER DISTRIBUTION 16.
GENERAL NOTE 3.
ELECTRICAL CABLES. PROVIDE ALL WORK FOR NEW POWER CABLE. ALSO SEE
EQUIPMENT EXCEPT CABLES AND RACEWAYS. PROVIDE NEW RACEWAYS AND
MAINTAIN AND PROTECT DOWNSTREAM POOL GAUGE JUNCTION BOX AND 15.
GENERAL NOTE 3.
ELECTRICAL CABLES. PROVIDE ALL WORK FOR NEW POWER CABLE. ALSO SEE
EQUIPMENT EXCEPT CABLES AND RACEWAYS. PROVIDE NEW RACEWAYS AND
MAINTAIN AND PROTECT UPSTREAM POOL GAUGE JUNCTION BOX AND 14.
FEEDER CONDUCTORS.
EXISTING ROUTE OF THE EXISTING 500KVA TRANSFORMER SECONDARY
CONDUCTORS ROUTE. TRACE, IDENTIFY, RECORD, AND REPORT THE
UNTERMINATED, BUT IT IS NOT KNOWN WHERE THE SECONDARY
BUT THE SECONDARY LOW VOLTAGE CONDUCTORS EXIST IN THE CABINET
PRIMARY WINDING. THE 500 KVA SECONDARY WINDINGS ARE DISCONNECTED,
DAISY CHAIN WHICH ROUTES TO THE 225 KVA SERVICE TRANSFORMER
TRANSFORMER. THE MEDIUM VOLTAGE CABLES PRIMARY CONNECTION IS A
LOCATION OF EXISTING UTILITY-OWNED 500 KVA, 480/277 VAC PAD-MOUNTED 13.
ELECTRICAL PAD-MOUNTED SERVICE TRANSFORMER.
LOCATION OF EXISTING UTILITY-OWNED 225 KVA, 480/277 VAC LOCK & DAM 12.
RACEWAYS AND NEW ELECTRICAL CABLES. TYPICAL OF TWO.
FIXTURES (RED, YELLOW, & GREEN) FOR REUSE. REFEED WITH NEW
MAINTAIN AND PROTECT EXISTING TRAFFIC SIGNAL LIGHT POLES AND TRAFFIC 11.
ON LOWER GUIDE WALL, AND ONE ON UPPER GUIDE WALL.
CABLES TO REFEED LIGHT POLES. TYPICAL OF FIVE ON THE MAIN LOCK, ONE
AND FIXTURES FOR REUSE. PROVIDE WITH NEW RACEWAYS AND ELECTRICAL
MAINTAIN AND PROTECT EXISTING 100 FEET TALL HIGH MAST LIGHT POLES 10.
CONTAIN OTHER UNKNOWN CABLES.
LOCATED IN ESPLANADE CONTAINS EXISTING HIGH MAST LIGHTS. MAY
APPROXIMATE LOCATION OF EXISTING FLUSH ELECTRICAL PULL BOXES 9.
SIGNAL LIGHT POLE
EXISTING TRAFFIC
A1
SCALE: 1"=30'-0"
SITE PLAN
30' 60'0
THIS SHEET)
NOT SHOWN ON
(OFF SHEET AND
POOL GAGE WELL
DOWNSTREAM
N
A M
N D
A
D D
E D
A N
N O
T A
T
IO
P
R
8 1
E-110
A1
A1
E-107
E-109
A1
E-106
A1
E-111
A1
A1
E-105
E-108
A1
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A N
S I
D
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
/0
/2
R O
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
C A
M P
B E
U
S T
R E
A M
L A
N D
W A
L L
P L
A N
E-104
T
L E
E C
H
B P
A T
T S
C H
U L
L
A P
R
IW
L D
B
R A
D T
K E
ELECTRICAL
W
E K
R
SCALE: 1/4"=1'-0"
PLAN - UPSTREAM LAND WALL
0 4' 8'2'
WALL
TO UPSTREAM GUIDE
LIGHT POLE
EXISTING HIGH MAST
NEW CABLE TRENCH
TOW HAULAGE UNIT
RELOCATED EXISTING
SHEET KEYNOTES
SERIES ELEMENTARY DIAGRAMS FOR WIRING.
PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E-700
TRENCH. PROVIDE 4 CONDUCTOR #10 AWG XHHW-2 CABLE FROM RECESS
PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE
PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 17.
FROM NEW CABLE TRENCH.
EXISTING GRAVEL TO PROVIDE NEW CONCRETE-EMBEDDED CONDUITS
DEMOLISH EXISTING CONCRETE AS WELL AS EXCAVATE AND TRENCH 16.
FROM NEW CABLE TRENCH TO RELOCATED TOW HAULAGE EQUIPMENT.
PROVIDE NEW 2" AND 1" CONCRETE ENCASED PVC-COATED RGS CONDUITS 15.
ABOVE TOP GUARDRAIL ELEVATION TO ALLOW DOOR TO FULLY OPEN.
GUIDE WALL PULLBOX. INSTALL BOTTOM OF NEW ENCLOSURE LOCATED
JUNCTION BOX. CORE-OUT AND REUSE EXISTING CONDUIT HOLES INTO
ENCLOSURE WILL REPLACE EXISTING RACEWAY AND ELIMINATES EXISTING
BOX LOCATED ON THE UPSTREAM GUIDE WALL. NEW CONDUITS AND
ON FACE OF LOCK WALL FROM THIS NEW ENCLOSURE TO THE FIRST PULL
ROUTE FOUR(4) NEW 4" PVC-COATED RGS CONDUITS SURFACE INSTALLED
LOCATE BOTTOM OF ENCLOSURE ABOVE TOP OF LOCK WALL ELEVATION.
PANEL, HINGED 3-PT LATCH OR HALF-TURN DOOR THREE NEMA 4X DRAINS.
STEEL, 60"HIGH X 36" WIDE X 24" DEEP ELECTRICAL ENCLOSURE WITH BACK
END OF THE NEW CABLE TRENCH TO A NEW NEMA 4X TYPE 316 STAINLESS
NEW CABLE TRENCH. PROVIDE THE FOUR NEW 4" CONDUITS FROM THE
CONDUITS TO EXISTING WATER ELEVATION GAGE STATION FROM END OF
SURFACE INSTALLED ON FACE OF LOCK WALL. PROVIDE THE TWO NEW 2"
PROVIDE TWO (2) NEW 2" AND FOUR(4) NEW 4" PVC-COATED RGS CONDUITS 14.
MAINTAIN AND PROTECT EXSTING STEEL WALKWAY.13.
POWER CABLES AND FIBER OPTIC CABLE.
HYRAULICS INSTRUMENTATION STATION. PROVIDE NEW ELECTRICAL
CONDUIT FOR EXISTING REUSED WATER GAUGE AND WEATHER EC-H
AND ONE FOR FIBER OPTIC) REDUCED TO 3/4" LIQUIDTIGHT FLEXIBLE METAL
PROVIDE NEW 2" EXPOSED PVC-COATED RGS CONDUITS (ONE FOR POWER 12.
RGS GROUNDING CONDUIT. PROVIDE NEW ELECTRICAL CABLES.
INTEGRAL SWITCHED POWER RECEPTACLE. PROVIDE NEW 1" PVC-COATED
FOR RELOCATED TOW HAULAGE UNIT. PROVIDE NEW TOW HAULAGE UNIT
PROVIDE NEW 2" EMBEDDED AND EXPOSED PVC-COATED RGS CONDUIT 11
GROUNDING CABLE.
ELECTRICAL CABLES FOR LIGHTING CABLE, RECEPTACLE CABLE, AND
PVC COATED CONDUIT TO EXTEND TO NEW CABLE TRENCH. PROVIDE NEW
INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVIDE NEW 10
SECURED BY TYPE 316 STAINLESS STEEL CHANNEL STRUT AND HARDWARE.
AND SURFACE INSTALLED PVC-COATED RGS CONDUITS AND FITTINGS
TRENCH ROUTED TO UPSTREAM LOADS. PROVIDE CONCRETE EMBEDDED
GALVANIZED STEEL CONDUITS EXTENDED FROM END OF NEW CABLE
PROVIDE NEW BURIED AND SURFACE INSTALLED PVC-COATED RIGID 9
ANIMALS (E.G. RODENTS AND SNAKES).
CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND
FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND
CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND
CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 8
CONDUCTORS FROM 20 AMP 1 POLE CIRCUIT BREAKERS.
CONDUITS TO TERMINATE TO PIPE HEATERS. PROVIDE NEW 10 AWG
RGS CONDUIT REDUCED FROM 2", AND 3/4" LIQUIDTIGHT FLEXIBLE METAL
AMPERE, 120 VOLT SWITCHES FOR PIPE HEATING CABLES, 3/4" PVC-COATED
STAND TO NEW EQUIPMENT. PROVIDE THREE NEW WEATHERPROOF 20
HEATER CIRCUITS. PROVIDE NEW ELECTRICAL CABLES FROM CONTROL
PVC-COATED RGS CONDUIT FROM MCC2 TO BUBBLER PIPE MANIFOLD FOR
LIQUIDTIGHT FLEXIBLE METAL CONDUITS. SPECIFICALLY, PROVIDE NEW 2"
WEATHERPROOF CONTROL SWITCHES, RGS CONDUITS AND FITTINGS, AND
PROVIDE NEW BUBBLER PIPE SELF-REGULATING HEAT TRACE CABLE, 7
CONDUITS.
TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION BOXES FOR ALL
BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE GROUNDING TYPE CONDUIT
COATED RGS CONDUIT. TERMINATE RMC WITH PVC-COATED RGS OR RGS
CONDUIT BEFORE THEY EXIT OUT OF CONCRETE TO BE EXPOSED PVC-
CONDUITS AND RMC CONDUITS MUST TRANSITION TO PVC-COATED RGS
GALVANIZED STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC
CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID
ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.
TRENCH.
TRENCH FOR BEST LAY, BEST EXIT, AND BEST ENTRANCE INTO CABLE
CABLES ONLY AS REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE
LOCATED ON BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL
INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW 2.
SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.
GENERAL SHEET NOTES
SHEET KEYNOTES
FROM CONTROL STAND TO NEW EQUIPMENT.
LIQUID-TIGHT FLEXIBLE METAL CONDUITS. PROVIDE NEW ELECTRICAL CABLES
RGS CONDUITS AND FITTINGS, TYPE 316 STAINLESS STEEL JUNCTION BOX, AND
PROVIDE NEW BUBBLER VALVE ACTUATOR HEATER AND OPEN/CLOSE CONTROLS, 6
MACHINERY.
FOR PRECEDING AND LOCATE ADJACENT TO THE NEW MITER GATE OPERATING
SPEED, MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW SUPPORT STAND
PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR HIGH 5
DEMOLITION) OPERATION.
MAKE PROPER LEVER-ARM ACTUATION TO MATCH EXISTING (PRIOR TO
MOUNTING PLATE WITH NEW LIMIT SWITCH BOLT PATTERNS AS REQUIRED TO
75°C WITH LOW TEMP OPTION CODE L40. FABRICATE NEW STAINLESS STEEL
ALLOY AND GOLD-PLATED CONTACT OPTION; OPERATING TEMPERATURES -40°C -
AND IP67 RATINGS; DPDT, SNAP ACTION, POSITIVE-BREAK CONTACTS, SILVER
HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH, ADJUSTABLE LEVER, NEMA 4
THE DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES REPLACEMENT IS:
MITER" PROXIMITY LIMIT SWITCH.
FROM BUFFER BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF
SWITCHES ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT
STAINLESS STEEL JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT
WITH CLAMP TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316
ACROSS THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED
PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS
EXTRA FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO
NOR THE CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF
CYCLES OF THE MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT
MITER GATE PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE
EXTRA FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE
WHERE IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2"
MITER GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS
PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW 4
NEMA 4X RATED CAPS FOR BOTH DEVICES.
MATING ACP PLUGS, 25 FEET LONG FOR CONNECTION TO MOTOR. PROVIDE
6AWG & 1/C-10 AWG GND, TYPE W OR G-GC ROUND, PROTABLE CORDS AND
ENCLOSED DISCONNECT SWITCH ON STRUCTURAL STAND. PROVIDE 3/C-
POWER: PROVIDE CROUSE HINDS WSR INTERLOCKED RECEPTACLE WITH
NEW HYDRAULIC SLIDE VALVE OPERATING MACHINERY. HYDRAULIC VALVE
AND SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE
PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, 3
FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL CABLE.
PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT FROM LIGHT
THE FLOATING MOORING BIT LIGHT FIXTURE. PROVIDE NEW 2" EMBEDDED
LOCATE AND INTERCEPT EXISTING EMBEDDED ELECTRICAL CONDUIT FOR 2
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1
EQUIPMENT
CONTROL STAND
CABLE TRENCH TO
FLOW
JUNCTION BOX
MITER GATE
MG LOW
MG HIGH
FLEET PR
1 9
UPSTREAM
LOCATION AND ROUTE
AT APPROXIMATELY AT THIS
EXPOSED CONDUITS START
WALKWAY
EXISTING
MITER PROXIMITY SWITCH
RECESS PROXIMITY SWITCH
MITER GATE MACHINERY
A M
N D
U P
D A
T E
D N
O T
E S
A N
D A
N N
O T
A T
IO
N
E-502
G1
E-503
G1
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A N
S I
D
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
/0
/2
R O
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
C A
M P
B E
N T
E R
L A
N D
W A
L L
P L
A N
E-105
T
L E
E C
H
B P
A T
T S
C H
U L
L
A P
R
N D
S
H E
E T
N U
M B
E R
R E
V
IS
D
IW
L D
B
R A
D T
K E
ELECTRICAL
W
E K
R
PLAN - CENTER LAND WALL
0 4' 8'2'
SHEET KEYNOTES
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH AND DUCTS.13.
TRENCH TO NEW 120V, 20A, GFCI WEATHERPROOF DUPLEX RECEPTACLE.
PROVIDE NEW 2" PVC COATED RGS CONDUIT EMBEDDED FROM NEW CABLE 12.
NEW SERVICE TRANSFORMER.
AND DAM ELECTRIC POWER SERVICE IS PERMANENTLY CHANGED OVER TO
CONSTRUCTION. REMOVE 225KVA SERVICE TRANSFORMER AFTER LOCK
TRANSFORMER OWNED AND MAINTAINED BY POWER COMPANY DURING
MAINTAIN AND PROTECT 225KVA ELECTRIC UTILITY SERVICE PAD-MOUNTED 11.
ELECTRICAL CLOSET TO THE NEW ELECTRICAL TRENCH.
DUCT BANK FROM CENTRAL CONTROL BUILDING BASEMENT EXISTING
PROVIDE NEW PVC-COATED RIGID GALVANIZED STEEL CONDUITS IN NEW 10.
GOVERNMENT.
BUILDING BASEMENT FOR FUTURE CONNECTION BY THE
ELEVATION EQUIPMENT. COIL 50 FEET OF CABLE INSIDE CENTRAL CONTROL
BUILDING TO THE UPSTREAM AND DOWNSTREAM GAGE WELLS WATER
PROVIDE NEW INSTRUMENTATION CABLE FROM THE CENTRAL CONTROL 9.
DOWNSTREAM HIGH MAST LIGHT CABLES INSIDE THE NEW CABLE TRENCH.
PLUG. DEMOLISH EXISTING ELECTRICAL CABLES. PROVIDE NEW
CONDUITS DUCT BANK. PLUG EACH END OF EACH DUCT WITH PVC CONDUIT
ABANDON THE EXISTING DOWNSTREAM HIGH MAST LIGHTS BURIED 8.
NEW SWITCHBOARD BUILDING
EXISTING VISITOR CENTER
EXISTING CENTRAL CONTROL BUILDING
DUCT BANK
NEW CROSSOVER
AIR COMPRESSOR
EXISTING BUBBLER
TRANSFORMER
EXISTING SERVICE
SET
EXISTING GENERATOR
NEW SERVICE TRANSFORMER
CONCRETE DUCT BANK TO
NEW 2X2 (4") REINFORCED
EXISTING IN-GROUND PULL BOX
BOXES
DUCT BANK AND PULL
ABANDON EXISTING
BOX
EXISTING JUNCTION
13 9 13NEW CABLE TRENCH13
HATCHES
NEW ACCESS
12 12
WITH PVC END BELLS OR PVC BUSHINGS.
WITHIN CABLE TRENCHES WHERE PVC CONDUITS MUST BE TERMINATED
AND BECOME EXPOSED MUST BE PVC COATED RGS CONDUITS EXCEPT
ALL EMBEDDED RMC CONDUITS WHICH PENETRATE OUT OF CONCRETE 3.
STRUCTURE, ELECTRICAL CABLES, AND CONNECTIONS.
SEE ED-DRAWINGS AND REFERENCE DRAWINGS FOR EXISTING 2.
SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.
GENERAL SHEET NOTES
SHEET KEYNOTES
NEW CABLE SCHEDULE FOR SIZES.
COMPRESSOR. PROVIDE NEW CONDUITS AND ELECTRICAL CABLES PER
TO EXISTING ELECTRICAL ENCLOSURE LOCATED ON OUTSIDE OF THE AIR
EMBEDDED AND EXPOSED CONDUITS ROUTED FROM NEW CABLE TRENCH
DEMOLISH AND REPLACE EXISTING CONDUITS WITH NEW CONCRETE
EXISTING 150 HP AIR COMPRESSOR POWER AND CONTROL CONDUITS. 7.
NEW CABLE TRENCH. SEE NEW CABLE SCHEDULE FOR SIZES.
EXISTING CONDUIT WITH EMBEDDED PVC40 IN NEW CONCRETE TO THE
FLOATING MOORING BIT LIGHT FIXTURE: LOCATE, INTERCEPT, AND EXTEND 6.
ENTRANCE CABLES. SEE NEW CABLE SCHEDULE FOR SIZES.
NEW CONCRETE EMBEDDED SERVICE ENTRANCE DUCT BANK AND SERVICE 5.
SWITCHBOARD AUTO TRANSFER SWITCH.
GENERATOR ENCLOSURE TO CENTRAL CONTROL BUILDING AND EXISTING
SCHEDULE. DEMOLISH EXISTING GENERATOR CABLE AND CONDUIT FROM
TRANSFER SWITCH INSIDE NEW SWITCHBOARD. SIZE PER NEW CABLE
ELECTRICAL CABLE FROM GENERATOR ENCLOSURE TO NEW AUTO
PROVIDE NEW JUNCTION BOX, CONCRETE EMBEDDED CONDUIT AND
EXISTING STANDBY GENERATOR ELECTRICAL FEEDER CABLE AND CONDUIT: 4.
CABLE SCHEDULE FOR SIZES.
EXTEND EXISTING EMBEDDED CONDUIT TO NEW CABLE TRENCH. SEE NEW
CENTRAL LAND WALL HIGH MAST LIGHT POLE: LOCATE, INTERCEPT, AND 3.
NEW CROSSOVER DUCT BANK AND ELECTRICAL CABLES.2.
AND FULLY OPERATIONAL.
ELECTRICAL CABLES UNTIL PERMANENT CABLES ARE INSTALLED, TESTED,
MAINTAIN AND PROTECT EXISTING CROSSOVER DUCT BANK AND 1.
BANK (NOT SHOWN)
CROSSOVER DUCT
EXISTING
E-150
A1
E-111
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
SHEET KEYNOTES
SERIES ELEMENTARY DIAGRAMS FOR WIRING.
PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E-700
TRENCH. PROVIDE 4 CONDUCTOR #10 AWG XHHW-2 CABLE FROM RECESS
PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE
PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 17
ABANDON THE EXISTING IN-GROUND PRECAST (QUAZITE) PULL BOXES.16
CABLE DOWNSTREAM FOR ITS REUSE.
MAST PULL BOX NEAR THE CONTROL STAND AND CAREFULLY REMOVE
DISCONNECT CABLE FROM EXISTING DOWNSTREAM LAND WALL HIGH
DOWNSTREAM GUIDE WALL HIGH MAST LIGHT POLE CIRCUIT: C.
AND CAREFULLY REMOVE CABLE DOWNSTREAM FOR ITS REUSE.
DISCONNECT CABLE FROM EXISTING DOWNSTREAM LAND WALL GALLERY
DOWNSTREAM GUIDE WALL CIRCUIT 40 FT. TALL LIGHT POLE CIRCUIT: B.
EXISTING ELECTRICAL CABLE DOWNSTREAM FOR ITS REUSE.
DOWNSTREAM LAND WALL CONTROL STAND AND CAREFULLY REMOVE
NAVIGATION LIGHT CIRCUIT: DISCONNECT CABLE FROM EXISTING A.
DOWNSTREAM GUIDE WALL CIRCUITS:
PROVIDE NEW CABLES SPLICED ON TERMINALS IN NEW JUNCTION BOX FOR 15
REUSE EXISTING CONDUIT HOLES INTO GUIDE WALL PULLBOX.
PULL BOX LOCATED ON THE DOWNSTREAM GUIDE WALL. CORE-OUT AND
COATED RGS CONDUITS IN NEW CONCRETE 2X2 DUCT BANK TO THE FIRST
GUIDE WALL CABLES TO NEW CABLES. PROVIDE FOUR(4) NEW 4" PVC-
DRAIN. PROVIDE TERMINAL BLOCKS TO SPLICE EXISTING DOWNSTREAM
ENCLOSURE WITH 3-PT LATCH HINGED DOOR, BACKPANEL, AND NEMA 4X
PROVIDE NEW 36"X36"X18" DEEP, NEMA 4X, TYPE 316 STAINLESS STEEL 14
CABLES AND FIBER OPTIC CABLE.
HYRAULICS INSTRUMENTATION STATION. PROVIDE NEW ELECTRICAL POWER
CONDUIT FOR EXISTING REUSED WATER GAUGE AND WEATHER EC-H
AND ONE FOR FIBER OPTIC) REDUCED TO 3/4" LIQUIDTIGHT FLEXIBLE METAL
PROVIDE NEW 2" EXPOSED PVC-COATED RGS CONDUITS (ONE FOR POWER 13
GROUNDING CONDUIT. PROVIDE NEW ELECTRICAL CABLES.
SWITCHED POWER RECEPTACLE. PROVIDE NEW 1" PVC-COATED RGS
RELOCATED TOW HAULAGE UNIT, NEW TOW HAULAGE UNIT INTEGRAL
PROVIDE NEW 2" EMBEDDED AND EXPOSED PVC-COATED RGS CONDUIT FOR 12
GROUNDING CABLE.
ELECTRICAL CABLES FOR LIGHTING CABLE, RECEPTACLE CABLE, AND
PVC-COATED CONDUIT TO EXTEND TO NEW CABLE TRENCH. PROVIDE NEW
INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVIDE NEW 3" 11
FITTINGS.
EMBEDDED AND SURFACE INSTALLED PVC-COATED RGS CONDUITS AND
NEW CABLE TRENCH ROUTED TO NEW JUNCTION BOX. PROVIDE CONCRETE
PVC-COATED RIGID GALVANIZED STEEL CONDUITS EXTENDED FROM END OF
PROVIDE TWO(2) 2", ONE(1) 1", AND FOUR(4) 4" NEW EMBEDDED AND EXPOSED 10
(E.G. RODENTS AND SNAKES).
CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND ANIMALS
FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND
CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND
CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 9
CONDUCTORS FROM 20 AMP 1 POLE CIRCUIT BREAKERS.
CONDUITS TO TERMINATE TO PIPE HEATERS. PROVIDE NEW 10 AWG
RGS CONDUIT REDUCED FROM 2", AND 3/4" LIQUIDTIGHT FLEXIBLE METAL
AMPERE, 120 VOLT SWITCHES FOR PIPE HEATING CABLES, 3/4" PVC-COATED
STAND TO NEW EQUIPMENT. PROVIDE THREE NEW WEATHERPROOF 20
HEATER CIRCUITS. PROVIDE NEW ELECTRICAL CABLES FROM CONTROL
PVC-COATED RGS CONDUIT FROM MCC2 TO BUBBLER PIPE MANIFOLD FOR
LIQUIDTIGHT FLEXIBLE METAL CONDUITS. SPECIFICALLY, PROVIDE NEW 2"
WEATHERPROOF CONTROL SWITCHES, RGS CONDUITS AND FITTINGS, AND
PROVIDE NEW BUBBLER PIPE SELF-REGULATING HEAT TRACE CABLE, 8
ELECTRICAL CABLES FROM CONTROL STAND TO NEW EQUIPMENT.
JUNCTION BOX, AND LIQUID-TIGHT FLEXIBLE METAL CONDUITS. PROVIDE NEW
CONTROLS RGS CONDUITS AND FITTINGS, TYPE 316 STAINLESS STEEL
PROVIDE NEW BUBBLER VALVE ACTUATOR HEATER AND OPEN/CLOSE 7
OPERATING MACHINERY.
STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW MITER GATE
SPEED, MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW SUPPORT
PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR HIGH 6
MATCH EXISTING (PRIOR TO DEMOLITION) OPERATION.
PATTERNS AS REQUIRED TO MAKE PROPER LEVER-ARM ACTUATION TO
NEW STAINLESS STEEL MOUNTING PLATE WITH NEW LIMIT SWITCH BOLT
TEMPERATURES -40°C - 75°C WITH LOW TEMP OPTION CODE L40. FABRICATE
SILVER ALLOY AND GOLD-PLATED CONTACT OPTION; OPERATING
4 AND IP67 RATINGS; DPDT, SNAP ACTION, POSITIVE-BREAK CONTACTS,
HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH, ADJUSTABLE LEVER, NEMA
DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES REPLACEMENT IS:
LIMIT SWITCH.
BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF MITER" PROXIMITY
ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT FROM BUFFER
JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT SWITCHES
TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316 STAINLESS STEEL
THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED WITH CLAMP
PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS ACROSS
FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO
CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF EXTRA
MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT NOR THE
PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE CYCLES OF THE
FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE MITER GATE
IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2" EXTRA
GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS WHERE
PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW MITER 5
CONNECTION TO MOTOR. PROVIDE NEMA 4X RATED CAPS FOR BOTH DEVICES.
ROUND, PROTABLE CORDS AND MATING ACP PLUGS, 25 FEET LONG FOR
STRUCTURAL STAND. PROVIDE 3/C-6AWG & 1/C-10 AWG GND, TYPE W OR G-GC
HINDS WSR INTERLOCKED RECEPTACLE WITH ENCLOSED DISCONNECT SWITCH ON
SLIDE VALVE OPERATING MACHINERY. HYDRAULIC VALVE POWER: PROVIDE CROUSE
SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW HYDRAULIC
PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, AND 4
INSIDE NEW STRUCTURAL SHELTER.
POWER DISTRIBUTION PANEL, AND NEW LOCK CONTROL CONSOLE LOCATED
DOWNSTREAM LAND WALL CONTROL STAND NEW MOTOR CONTROL CENTER, 3
FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL CABLE.
PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT FROM LIGHT
THE FLOATING MOORING BIT LIGHT FIXTURE. PROVIDE NEW 2" EMBEDDED
LOCATE AND INTERCEPT EXISTING EMBEDDED ELECTRICAL CONDUIT FOR 2
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1
PVC-COATED RGS SURFACE CONDUITS.
JOINTS. PROVIDE PVC-COATED RGS EXPANSION/CONTRACTION COUPLINGS FOR
CONDUITS ARE INSTALLED ACROSS LOCK CONCRETE MONOLITH EXPANSION
PROVIDE NEW EXPANSION/CONTRACTION CONDUIT COUPLINGS WHEREEVER 4.
BOXES FOR ALL CONDUITS.
GROUNDING TYPE CONDUIT TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION
WITH PVC-COATED RGS OR RGS BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE
OUT OF CONCRETE TO BE EXPOSED PVC-COATED RGS CONDUIT. TERMINATE RMC
CONDUITS MUST TRANSITION TO PVC-COATED RGS CONDUIT BEFORE THEY EXIT
STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC CONDUITS AND RMC
CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID GALVANIZED
ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.
EXIT, AND BEST ENTRANCE INTO CABLE TRENCH.
REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE TRENCH FOR BEST LAY, BEST
BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL CABLES ONLY AS
INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW LOCATED ON 2.
SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.
GENERAL SHEET NOTES
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
W
E K
R
/0
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
C A
M P
B E
W N
S T
R E
A M
L A
N D
W A
L L
P L
A N
E-106
T L
E E
C H
B P
A T
T S
C H
U
IW
L D
B
R A
D T
K E
ELECTRICAL
A N
S I
X
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
W
E K
R
SCALE: 3/32"=1'-0"
PLAN - DOWNSTREAM LANDWALL
NEW MITER GATE MACHINERY
EXISTING HIGH MAST LIGHT POLE
HAULAGE UNIT
EXISTING RELOCATED TOW
EQUIPMENT
TO EXISTING GAUGE WELL
EQUIPMENT
TO DOWNSTREAM GUIDE WALL
NEW CABLE TRENCH
DUCT BANK
START OF NEW DOWNSTREAM
END OF NEW CABLE TRENCH /
NEW JUNCTION BOX
EMBEDDED CONDUIT
EXISTING HIGH MAST LIGHTS
LOCATE, INTERCEPT, AND COUPLE TO
EXISTING SPEAKER POLE
0 8'4' 16'
SLIDE VALVE MACHINERY
BANK
NEW CONCRETE EMBEDDED DUCT
LIGHT FIXTURE UNDER GRATING
EXISTING FLOATING MOORING BIT
N
MITER PROXIMITY SWITCH
RECESSED PROXIMITY SWITCH 17
A P
R
A
M N
D
A D
D E
D A
N N
O T
A T
IO
N
S
A P
R
A
M N
D
A D
D E
D A
N N
O T
A T
IO
N
S
E-502
G1
E-502
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A N
S I
D
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
/0
/2
R O
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
C A
M P
B E
S T
R E
A M
I N
T E
R M
E D
IA
T
E W
A L
L
P L
A N
E-107
T
L E
E C
H
B P
A T
T S
C H
U
IW
L D
B
R A
D T
K E
ELECTRICAL
W
E K
R
SCALE: 3/16"=1'-0"
PLAN - UPSTREAM INTERMEDIATE WALL
EXISTING POLE BASE
NEW CABLE TRENCH
NEW CABLE TRENCH
EXISTING GUARD RAIL
SHEET KEYNOTES
ACTUATION TO MATCH EXISTING (PRIOR TO DEMOLITION) OPERATION.
LIMIT SWITCH BOLT PATTERNS AS REQUIRED TO MAKE PROPER LEVER-ARM
CODE L40. FABRICATE NEW STAINLESS STEEL MOUNTING PLATE WITH NEW
OPTION; OPERATING TEMPERATURES -40°C - 75°C WITH LOW TEMP OPTION
POSITIVE-BREAK CONTACTS, SILVER ALLOY AND GOLD-PLATED CONTACT
ADJUSTABLE LEVER, NEMA 4 AND IP67 RATINGS; DPDT, SNAP ACTION,
REPLACEMENT IS: HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH,
THE DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES
MITER" PROXIMITY LIMIT SWITCH.
FROM BUFFER BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF
SWITCHES ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT
STAINLESS STEEL JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT
WITH CLAMP TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316
ACROSS THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED
PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS
EXTRA FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO
NOR THE CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF
CYCLES OF THE MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT
MITER GATE PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE
EXTRA FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE
WHERE IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2"
MITER GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS
PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW 4
NEMA 4X RATED CAPS FOR BOTH DEVICES.
PLUGS, 25 FEET LONG FOR CONNECTION TO MOTOR WINDING. PROVIDE
10 AWG GND, TYPE W OR G-GC ROUND, PROTABLE CORDS AND MATING ACP
DISCONNECT SWITCH ON STRUCTURAL STAND. PROVIDE 3/C-6 AWG & 1/C-
CROUSE-HINDS WSR INTERLOCKED RECEPTACLE WITH ENCLOSED
SLIDE VALVE OPERATING MACHINERY. HYDRAULIC VALVE POWER: PROVIDE
AND SUPPORT STAND FOR AND LOCATE ADJACENT TO THE NEW HYDRAULIC
PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, 3
CABLE.
CABLES FOR LIGHTING CABLE, RECEPTACLE CABLE, AND GROUNDING
RGS CONDUIT TO TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL
PVC COATED CONDUIT TO EXTEND EXISTING CONDUIT WITH PVC-COATED
INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVID NEW 2
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1
SHEET KEYNOTES
SERIES ELEMENTARY DIAGRAMS FOR WIRING
PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E700
TRENCH. PROVIDE 4 CONDUCTOR #10AWG XHHW-2 CABLE FROM RECESS
PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE
PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 16
WALL AND TO THE SPILLWAY DAM.
COMMUNICATIONS CABLES) ROUTED ACROSS ARCH DAM TO THE RIVER
EXISTING RGS CONDUITS (DAM POWER FEEDER, DAM PATH LIGHTS, AND 15
EXISTING STAINLESS STEEL JUNCTION BOX.14
THE NEW CABLE TRENCH (NOT INTO THE BOTTOM).
NEW 3” PVC40 CONDUITS EXTENDED UPWARD TO THE END OF AND INTO
EXISTING CONDUIT WITH CONDUIT COUPLINGS AND PROVIDE THREE (3)
CONCRETE EMBEDDED CONDUITS INSIDE THE GALLERY. TRANSITION THE
SAWCUT AND CORE DRILL CONCRETE TO INTERCEPT THE EXISTING 13
EMBEDDED CONDUIT TRENCH WITH NEW CONCRETE.
EXISTING RGS CONDUIT, REPAIR AND RESTORE LOCK WALL NEW
EXTEND NEW PVC40 AND TRANSITION WITH COUPLING TO INTERCEPTED
EMBEDDED 2” PVC40 CONDUIT FROM NEW CABLE TRENCH TO FEED POLE.
EMBEDDED CONDUIT, SAWCUT CONCRETE TO PROVIDE A NEW CONCRETE
EXISTING I-WALL DAM PATH LIGHT POLE: INTERCEPT EXISTING CONCRETE 12
CABLE SCHEDULE.
CABLES, AND DAM COMMUNICATION CABLES IN NEW CABLE TRENCH. SEE
PROVIDE NEW CABLES FOR DAM POWER CABLE, PATH LIGHT CIRCUIT 11
FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL CABLE.
PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT FROM LIGHT
CONDUIT FOR NAVIGATION LIGHT FIXTURES. PROVIDE NEW 2" EMBEDDED
LOCATE AND INTERCEPT EXISTING CONCRETE EMBEDDED ELECTRICAL 10
CABLE.
FROM LIGHT FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL
EMBEDDED PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT
CONDUIT FOR TRAFFIC SIGNAL LIGHT FIXTURE. PROVIDE NEW 2"
LOCATE AND INTERCEPT EXISTING CONCRETE EMBEDDED ELECTRICAL 9
NAVIGATION LIGHT FIXTURES.
ROUTED UPSTREAM TO EXISTING TRAFFIC SIGNAL LIGHT FIXTURES AND
PROVIDE NEW PVC-COATED RGS CONDUITS FROM NEW CABLE TRENCH 8
ANIMALS (E.G. RODENTS AND SNAKES).
CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND
FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND
CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND
CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 7
MITER GATE OPERATING MACHINERY. SEE CABLE SCHEDULES.
SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW
HIGH SPEED, & MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW
PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR 6
CABLES.
PVC-COATED RGS CONDUITS FROM CABLE TRENCH AND NEW ELECTRICAL
DESIGN IS CROUSE-HINDS WSR. PROVIDE NEW CONCRETE EMBEDDED
AND SUPPORT STAND FOR TWO NEW "FLEET" RECEPTACLES. BASIS OF
PROVIDE NEW 100 AMP, 480 VOLTS INTERLOCKED POWER RECEPTACLES 5
COUPLINGS FOR PVC-COATED RGS SURFACE CONDUITS.
EXPANSION JOINTS. PROVIDE PVC COATED RGS EXPANSION/CONTRACTION
CONDUITS ARE INSTALLED ACROSS LOCK CONCRETE MONOLITH
PROVIDE NEW EXPANSION/CONTRACTION CONDUIT COUPLINGS WHEREVER 4.
CONDUITS.
TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION BOXES FOR ALL
BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE GROUNDING TYPE CONDUIT
COATED RGS CONDUIT. TERMINATE RMC WITH PVC-COATED RGS OR RGS
CONDUIT BEFORE THEY EXIT OUT OF CONCRETE TO BE EXPOSED PVC-
CONDUITS AND RMC CONDUITS MUST TRANSITION TO PVC-COATED RGS
GALVANIZED STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC
CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID
ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.
TRENCH.
TRENCH FOR BEST LAY, BEST EXIT, AND BEST ENTRANCE INTO CABLE
CABLES ONLY AS REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE
LOCATED ON BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL
INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW 2.
SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.
GENERAL SHEET NOTES
NEW CABLE TRENCH
LIGHTING POLE
EXISTING HIGH MAST
8'0 4' 16'
LEAF
MITER GATE
CABLE TRENCH
END OF NEW
N
1'-8" DEEP
1'-6" WIDE x
TRENCH
1'-8" DEEP
3'-2" WIDE x
TRENCH
LEAF
MITER GATE
SWITCH
PROXIMITY
RECESS
MACHINERY
MITER GATE
A P
R
A
M N
D
U P
D A
T E
D A
N N
O T
A T
IO
N
A
P R
PROXIMITY SWITCH CONNECTIONS
E-504
G1
E-505
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A N
S I
D
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
/0
/2
R O
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
C A
M P
B E
W N
S T
R E
A M
I N
T E
R M
E D
IA
T
E W
A L
L
P L
A N
E-109
T
L E
E C
H
B P
A T
T S
C H
U L
L
A P
R
N D
U P
D A
T E
D N
O T
E S
A N
D A
N N
O T
A T
IO
IW
L D
B
R A
D T
K E
ELECTRICAL
W
E K
R
PLAN - DOWNSTREAM INTERMEDIATE WALL
0 4' 8'2'
NEW CABLE TRENCH
CONDUITS.
EXPANSION/CONTRACTION COUPLINGS FOR PVC-COATED RGS SURFACE
MONOLITH EXPANSION JOINTS. PROVIDE PVC-COATED RGS
WHEREEVER CONDUITS ARE INSTALLED ACROSS LOCK CONCRETE
PROVIDE NEW EXPANSION/CONTRACTION CONDUIT COUPLINGS 4.
CONDUITS.
TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION BOXES FOR ALL
BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE GROUNDING TYPE CONDUIT
COATED RGS CONDUIT. TERMINATE RMC WITH PVC-COATED RGS OR RGS
CONDUIT BEFORE THEY EXIT OUT OF CONCRETE TO BE EXPOSED PVC-
CONDUITS AND RMC CONDUITS MUST TRANSITION TO PVC-COATED RGS
GALVANIZED STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC
CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID
ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.
TRENCH.
TRENCH FOR BEST LAY, BEST EXIT, AND BEST ENTRANCE INTO CABLE
CABLES ONLY AS REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE
LOCATED ON BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL
INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW 2.
SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.
GENERAL SHEET NOTES SHEET KEYNOTES
SERIES ELEMENTARY DIAGRAMS FOR WIRING.
PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E700
TRENCH. PROVIDE 4 CONDUCTOR #10AWG XHHW-2 CABLE FROM RECESS
PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE
PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 14
RECEPTACLE CABLE, AND GROUNDING CABLE.
TRENCH. PROVIDE NEW ELECTRICAL CABLES FOR LIGHTING CABLE,
PVC COATED CONDUIT AND NEW CORE DRILLTO EXTEND TO NEW CABLE
INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVIDE NEW 13
ANIMALS (E.G. RODENTS AND SNAKES).
CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND
FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND
CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND
CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 12
CAPS FOR BOTH DEVICES
PLUGS, 25 FEET LONG FOR CONNECTION TO MOTOR. PROVIDE NEMA 4X RATED
1/C-10 AWG GND, TYPE W OR G-GC ROUND, PROTABLE CORDS AND MATING ACP
ENCLOSED DISCONNECT SWITCH ON STRUCTURAL STAND. PROVIDE 3/C-6AWG &
POWER: PROVIDE CROUSE HINDS WSR INTERLOCKED RECEPTACLE WITH
HYDRAULIC VALVE NEW HYDRAULIC SLIDE VALVE OPERATING MACHINERY.
AND SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE
PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, 11
MITER GATE OPERATING MACHINERY. SEE CABLE SCHEDULES.
SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW
HIGH SPEED, & MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW
PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR 10
ACTUATION TO MATCH EXISTING (PRIOR TO DEMOLITION) OPERATION.
LIMIT SWITCH BOLT PATTERNS AS REQUIRED TO MAKE PROPER LEVER-ARM
CODE L40. FABRICATE NEW STAINLESS STEEL MOUNTING PLATE WITH NEW
OPTION; OPERATING TEMPERATURES -40°C - 75°C WITH LOW TEMP OPTION
POSITIVE-BREAK CONTACTS, SILVER ALLOY AND GOLD-PLATED CONTACT
ADJUSTABLE LEVER, NEMA 4 AND IP67 RATINGS; DPDT, SNAP ACTION,
REPLACEMENT IS: HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH,
THE DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES
MITER" PROXIMITY LIMIT SWITCH.
FROM BUFFER BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF
SWITCHES ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT
STAINLESS STEEL JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT
WITH CLAMP TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316
ACROSS THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED
PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS
EXTRA FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO
NOR THE CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF
CYCLES OF THE MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT
MITER GATE PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE
EXTRA FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE
WHERE IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2"
MITER GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS
PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW 9
FOR FULL LENGTH OF DRILLED CORES.
FILL ANNULAR SPACE AROUND EACH CONDIUT WITH NON-SHRINK GROUT
CONDUITS TO THE NAVIGATION LIGHTS POLE AND ALSO TO THE CCTV POLE.
CONCRETE STAIRWAY TO ALLOW INSTALLATION OF NEW PVC-COATED RGS
PROVIDE TWO 3" DIAMETER CORE DRILLS THROUGH THE EXISTING 8
TO KEEP DISSIMILAR METALS SEPARATED.
SUPPORTS WITH 316 STAINLESS STEEL CLAMPS AND ISOLATING MATERIAL
PROVIDE NEW TYPE 316 STAINLESS STEEL CHANNEL STRUT CONDUIT 7
ELECTRICAL CABLES.
STAINLESS STEEL NEMA 4X JUNCTION BOX WITH DRAIN, AND NEW
REUSE EXISTING CCTV AND POLE. PROVIDE NEW CONDUIT, NEW TYPE 316 6
CONDUCTORS FROM JUNCTION BOX TO NAVIGATION LIGHT FIXTURES.
WEATHERPROOF SPLICE IN JUNCTION BOX TO PROVIDE INDIVIDUAL
NEMA 4X JUNCTION BOX TO NAVIGATION LIGHT FIXTURES POLE. PROVIDE
3/4" PVC-COATED RGS CONDUIT FROM NEW TYPE 316 STAINLESS STEEL
REUSE EXISTING NAVIGATION LIGHT FIXTURES AND POLE. PROVIDE NEW 5
LIGHTS FIXTURES.
INDIVIDUAL CONDUCTORS FROM JUNCTION BOX TO TRAFFIC SIGNAL
PROVIDE WEATHERPROOF SPLICE IN JUNCTION BOX TO PROVIDE
STEEL NEMA 4X JUNCTION BOX TO TRAFFIC SIGNAL LIGHTS FIXTURES POLE.
NEW 3/4" PVC-COATED RGS CONDUIT FROM NEW TYPE 316 STAINLESS
REUSE EXISTING TRAFFIC SIGNAL LIGHT FIXTURES AND POLE. PROVIDE 4
SHEET KEYNOTES
STRUT, HARDWARE, AND EXPOXY TYPE CONCRETE ANCHOR BOLTS.
ABOVE TOP OF GAURDRAIL SUPPORTED BY 316 STAINLESS STEEL CHANNEL
NEMA 4X DRAIN. LOCATE ENCLOSURE ABOVE TOP OF LOCK WALL AND
PROVIDE NEW TYPE 316 NEMA 4X STAINLESS STEEL ENCLOSURE WITH 3
CONCRETE ANCHOR BOLTS.
SECURE CHANNEL STUT WITH 316 STAINLESS STEEL EXPOXY TYPE
316 STAINLESS STEEL CHANNEL STRUT AND HARDWARE. FASTEN AND
INSTALLED PVC-COATED RGS CONDUITS AND FITTINGS SECURED BY TYPE
CAMERA POLE LOADS. PROVIDE CONCRETE EMBEDDED AND SURFACE
DOWNSTREAM TO TRAFFIC SIGNAL LIGHTS, NAVIGATION LIGHTS, AND CCTV
STEEL CONDUITS EXTENDED FROM END OF NEW CABLE TRENCH ROUTED
PROVIDE TWO NEW WALL-MOUNTED 2" PVC-COATED RIGID GALVANIZED 2
PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1
STAND
CONTROL
NEW
MITER GATE LEAF
POLE
LIGHTS
NAVIGATION
EXISTING
POLE
SIGNAL LIGHTS
EXISTING TRAFFIC
ON TRI-AX POLE
EXISTING CCTV
POLE
HIGH MAST
EXISTING
EXPOSED CONDUIT
INTERCEPT EXISTING 8
AS SHOWN)
(TYPICAL QTY
1 11
N E
W C
A B
LE
T
R E N C
H
FLOW
MITER GATE MACHINERY
SLIDE VALVE MACHINERY
MITER PROXIMITY SWITCH
A P
R
A
M N
D
U P
D A
T E
D N
O T
E S
A N
D A
N N
O T
A T
IO
N
A
M N
D
U P
D A
T E
D N
O T
E S
A N
D A
N N
O T
A T
IO
N
A
P R
SWITCH
PROXIMITY
RECESS
E-504
G1
E-505
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A
C A
M P
B E
S T
R E
A M
A N
D D
O W
N S
T R
E A
M G
U
ID
E W
A L
L S
P L
A N
E-110
T L
E E
C H
B P
A T
T S
C H
U
N D
S
H E
E T
A D
D E
D T
O S
IW
L D
B
R A
D T
K E
ELECTRICAL
A N
S I
X
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
W
E K
R
/0
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
R
BRANDON ROAD LOCKS AND DAMS "HIGH MAST LIGHTING" PROJECT.
ALSO SEE REFRENCE DRAWINGS FROM THE DRESDEN ISLAND AND 4.
ELECTRICAL CABLES AND THEIR NEW SOURCES.
DOWNSTREAM GUIDE WALL EQUIPMENT AFTER CONNECTION TO NEW
VERIFY CORRECT ENERGIZATION AND OPERATION OF ALL UPSTREAM AND 3.
GUIDE WALLS.
MAINTAIN AND PROTECT EXISTING ELECTRICAL EQUIPMENT LOCATED ON 2.
TO SPLICE TO NEW ELECTRICAL CABLES INSTALLED ON THE MAIN LOCK.
WALL CABLES EXCEPT AS REQUIRED TO EXTEND TO NEW JUNCTION BOXES
MAINTAIN AND PROTECT EXISTING UPSTREAM AND DOWNSTREAM GUIDE 1.
GENERAL SHEET NOTES
SHEET KEYNOTES
ALSO SEE THE CABLE SCHEDULE.
BUILDING TO EXISTING UPSTREAM GUIDE WALL CCTV CAMERA.
CCTV CABLE "V2" FULL LENGTH FROM CENTRAL CONTROL
POLE-MOUNTED CCTV CAMERA: PROVIDE NEW ELECTRICAL 18
THE UPSTREAM LAND WALL PLAN ON SHEET E-104.
ELECTRICAL CABLES TO NEW ELECTRICAL CABLES. ALSO SEE
WALL IN WHICH TO SPLICE EXISTING UPSTREAM GUIDE WALL
PROVIDE NEW JUNCTION BOX ON UPSTREAM END OF LAND 17
SEE THE DOWNSTREAM LAND WALL PLAN ON SHEET E-106.
WALL ELECTRICAL CABLES TO NEW ELECTRICAL CABLES. ALSO
WALL IN WHICH TO SPLICE EXISTING DOWNSTREAM GUIDE
PROVIDE NEW JUNCTION BOX ON DOWNSTREAM END OF LAND 16
LAND WALL JUNCTION BOX.
TO EXTEND AND SPLICE CABLE IN THE NEW DOWNSTREAM
TERMINATE CABLE DP8 DOWNSTREAM WITH ENOUGH LENGTH
RECEPTACLE POWER CABLE DP8 ON THE GUIDE WALL.
MAINTAIN EXISTING ELECTRICAL 480 VOLTS, 3 PHASE, 15
CABLE IN THE NEW UPSTREAM LAND WALL JUNCTION BOX.
DOWNSTREAM WITH ENOUGH LENGTH TO EXTEND AND SPLICE
POWER CABLE DP1 ON THE GUIDE WALL. TERMINATE CABLE DP1
MAINTAIN EXISTING ELECTRICAL 120 VOLTS RECEPTACLE 14
CABLE IN THE NEW DOWNSTREAM LAND WALL JUNCTION BOX.
DP3 UPSTREAM WITH ENOUGH LENGTH TO EXTEND AND SPLICE
POWER CABLE DP3 ON THE GUIDE WALL. TERMINATE CABLE
MAINTAIN EXISTING ELECTRICAL 120 VOLTS RECEPTACLE 13
UPSTREAM LAND WALL JUNCTION BOX.
ENOUGH LENGTH TO EXTEND AND SPLICE CABLE IN THE NEW
GUIDE WALL. TERMINATE CABLE DL6 DOWNSTREAM WITH
MAINTAIN EXISTING ELECTRICAL LIGHTING CABLE DL6 ON THE 12
UPSTREAM LAND WALL JUNCTION BOX.
ENOUGH LENGTH TO EXTEND AND SPLICE CABLE IN THE NEW
GUIDE WALL. TERMINATE CABLE DL2 DOWNSTREAM WITH
MAINTAIN EXISTING ELECTRICAL LIGHTING CABLE DL2 ON THE 11
FLEET RECEPTACLE.
MAINTAIN AND RECONNECT THE EXISTING 480 VOLTS, 3 PHASE 10
WEATHERPROOF GFCI RECEPTACLES.
MAINTAIN AND RECONNECT THE EXISTING 120 VOLTS, 20 AMPS 9
WALL JUNCTION BOX.
EXTEND AND SPLICE CABLE IN THE NEW DOWNSTREAM LAND
TERMINATE CABLE DL5 UPSTREAM WITH ENOUGH LENGTH TO
ELECTRICAL LIGHTING CABLE DL5 ON THE GUIDE WALL.
EXISTING NAVIGATION LIGHT CABLE. MAINTAIN EXISTING 8
WALL JUNCTION BOX.
EXTEND AND SPLICE CABLE IN THE NEW DOWNSTREAM LAND
TERMINATE CABLE DL1 UPSTREAM WITH ENOUGH LENGTH TO
ELECTRICAL LIGHTING CABLE DL1 ON THE GUIDE WALL.
EXISTING 30 FT. TALL POLE LIGHTS CABLE. MAINTAIN EXISTING 7
DUCT AND CABLES WITHIN IN IT.
MAINTAIN EXISTING GUIDE WALL 3" CONCRETE-EMBEDDED 6
MAINTAIN THE EXISTING PULLBOX.5
POLE.
MAINTAIN AND RECONNECT THE EXISTING HIGH MAST LIGHT 4
DOWN LIGHT POLE.
MAINTAIN AND RECONNECT THE EXISTING 30 FEET TALL TIP-3
POLE.
MAINTAIN AND RECONNECT THE EXISTING NAVIGATION LIGHT 2
POLE.
MAINTAIN AND RECONNECT THE EXISTING WIND SOCK LIGHT 1
J8
PLAN - DOWNSTREAM RECEPTACLE POWER
SCALE: 1"=80'
J1
PLAN - DOWNSTREAM LIGHTING
SCALE: 1"=80'
FG
FE
LT
NAV
LT
SOCK
WIND
COLLINS RD & LOCK RDTO THE INTERSECTION OF
LOCK RD
FE
FG
LT
NAV
A1
PLAN - UPSTREAM LIGHTING
SCALE: 1"=80'
A10
PLAN - UPSTREAM RECEPTACLE POWER
SCALE: 1"=80'
8'0 4' 16' 8'0 4' 16'
8'0 4' 16'8'0 4' 16'
5(TYPICAL)
FLOW FLOW
5(TYPICAL)
9 13
FLOWFLOW
5(TYPICAL)
IN 1" RGS
11 12
5(TYPICAL)
11 12
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
N T
R A
C T
/T .O
N
O
P R
O J E
C T
C O
D E
M A
T O
C /I
D
IQ
C O
N T
R A
C T
N O
A
C A
M P
B E
L L
F
IR
S T
F L
O O
R A
N D
B A
S E
M E
N T
C E
N T
R A
L C
O N
T R
O L
B U
IL
D
IN
G
P L
A N
E-111
T L
E E
C H
B P
A T
T S
C H
U
N D
S
H E
E T
N U
M B
E R
R E
V
IS
IW
L D
B
R A
D T
K E
ELECTRICAL
A N
S I
X
S O
L
IC
IT
A
T
IO
N
L O
C K
R E
H A
B
IL
IT
A
T
IO
N
G R
U N
D Y
C O
U N
T Y
IL
D R
E S
D E
N I
S L
A N
D L
O C
K A
N D
D A
M
IL
L
IN
O
IS
R
IV
E
R B
A S
IN
W
E K
R
/0
C K
I S
L A
N D
IL
L
IN
C K
I S
L A
N D
D
IS
T R
R
EXISTING SUSPENDED CEILING WITH NEW SUSPENDED CEILING.
ELECTRICAL EQUIPMENT TO BE PROVIDED IN THE BASEMENT. REPLACE
EXISTING CEILING IN ITS ENTIRETY TO ALLOW REMOVAL AND NEW
THE BASEMENT CEILING IS A 2' X 2' SUSPENDED CEILING. DEMOLISH 2.
DAM BUSINESS.
PERSONNEL PRIOR TO AND DURING CONSTRUCTION CONDUCTING LOCK AND
BUILDING WILL STAY OCCUPIED BY GOVERNMENT LOCK AND DAM WORK
GOVERNMENT LOCK AND DAM PERSONNEL. THE CENTRAL CONTROL
ADJACENT TO THE CENTRAL CONTROL BUILDING WHICH MAY AFFECT
COORDINATE WITH THE GOVERNMENT REGARDING ALL WORK INSIDE OR 1.
GENERAL SHEET NOTES
SHEET KEYNOTES
EXISTING DEVICE.
PROVIDE NEW CONDUIT AND CONDUCTORS TO REFEED 6.
SCREW COVER IS NOT ACCEPTABLE.
WITH HANDLE OR 1/4-TURN LATCH. CLAMPED, BOLTED, OR
4X, 18"H X 18"W X 18"D, COVER MUST BE EITHER 3-POINT LATCH
SCHEDULE. PROVIDE NEW TYPE 316 STAINLESS STEEL, NEMA
CONNECTING INTO EXISTING EXITING RACEWAY. SEE CABLE
TRENCH TO EXISTING STANDBY DIESEL GENERATOR SET
PROVIDE NEW UNDERGROUND RACEWAY FROM NEW CABLE
SWITCHBOARD TO EXISTING STANDBY DIESEL GENERATOR SET.
PROVIDE NEW ELECTRICAL CABLE P3A FROM NEW 5.
CEILING.
DIPPED GALVANIZED THREADED ROD ANCHORED TO CONCRETE
SUSPENDED CEILING. SUPPORT NEW CABLE TRAY FROM HOT-
LADDER TYPE CABLE TRAY INSIDE BASEMENT ABOVE
PROVIDE NEW 12-INCH WIDE ALUMINUM, OPEN-BOTTOM, 4.
SCHEDULES.
CABLE TRENCH. SEE STRUCTURAL DRAWINGS AND CABLE
PROVIDE NEW DUCT BANK AND ELECTRICAL CABLES FROM 3.
MLP AND MLPA. SEE DETAIL ON SHEET E-622.
PROVIDE…