This document provides details for a federal contract opportunity issued by the Department of the Army Corps of Engineers Engineering District Rock Island. The solicitation number is W912EK22R0008 for lock rehabilitation work at the Illinois River Basin Dresden Island Lock and Dam in Morris, Will County, Illinois. The base work includes installation of a government furnished miter gate, replacement of miter gate machinery, and electrical system replacement. An option for fairlead and checkpost replacement is also included. Bids are sought for lock chamber dewatering and other rehabilitation efforts. The opportunity type is listed as a solicitation.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

C O

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A N

S I

D

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

/0

/2

R O

C K

I S

L A

N D

IL

L

IN

IS

C K

I S

L A

N D

D

IS

T R

IC

T

C A

M P

B E

L

H

E E

T I

N D

E X

G-002

D

D

IL

L O

N

A

C A

M P

B E

L L

A P

R

M

N D

U P

D A

T E

D S

H E

E T

N U

M B

E R

A N

D A

D D

E D

S H

E E

B

IW

L D

B

R A

D T

K E

ELECTRICAL

W

E K

R

MECHANICAL SCHEDULE SWITCHBOARD BUILDING M-610

DETAIL - SWITCHBOARD BUILDING SUMP PUMPM-510

SECTION - DRAIN PIPE M-304

SECTION - DRAIN PIPE M-303

SECTION - DRAIN PIPE M-302

SECTION - DRAIN PIPE M-301

PLAN - SWITCHBOARD BUILDING MECHANICAL UNITSM-110

PLAN - DRAIN PIPE M-103

PLAN - DRAIN PIPE M-102

PLAN - DRAIN PIPE M-101

SWITCHBOARD BUILDING SECTIONS A-103

SWITCHBOARD BUILDING ELEVATIONS A-102

SWITCHBOARD BUILDING FLOOR PLAN A-101

DETAIL - MITER GATE AND SLIDE VALVE RECEPTACLES S-541

DETAIL - MITER GATE AND SLIDE VALVE RECEPTACLES ASSEMBLY S-540

DETAIL - WALL ARMOR AND TRENCH S-503

DETAIL - SWITCHBOARD BUILDING S-502

DETAIL - WALL ARMOR S-501

SECTION - EXISTING CROSSOVER DUCT BANK S-307

SECTION - SWITCHBOARD BUILDING S-306

SECTION - GALLERY AND UTILITY TRENCH S-305

SECTION - GALLERY AND UTILITY TRENCH S-304

SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS S-303

SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS S-302

SECTION - CROSSOVER DUCT BANK OVERALL S-301

ELEVATION - CROSSOVER DUCT BANK S-201

PLAN - I-WALL MANHOLE [Region4]S-105

PLAN - SWITCHBOARD BUILDING [Region4]S-104

PLAN - GALLERY AND UTILITY TRENCH S-103

PLAN - CROSSOVER DUCT BANK S-102

PLAN - OVERALL S-101

DETAILS - ELEMENTARY DIAGRAM - VALVE INTERLOK LADDER LOGIC DIAGRAME-709

DETAILS - ELEMENTARY DIAGRAM INTERLOCK AND SHUNT TRIP CONTROLSE-708

DETAILS - ELEMENTARY DIAGRAM LOWER TRAFFIC SIGNAL CONTROLSE-707

DETAILS - ELEMENTARY DIAGRAM UPPER TRAFFIC SIGNAL AND AIR HORN CONTROLSE-706

DETAILS - ELEMENTARY DIAGRAM UPPER RIGHT CONTROLSE-705

DETAILS - ELEMENTARY DIAGRAM LOWER RIGHT CONTROLSE-704

DETAILS - ELEMENTARY DIAGRAM UPPER LEFT CONTROLSE-703

DETAILS - ELEMENTARY DIARAM LOWER LEFT CONTROLSE-702

DETAILS - CONTROL INTERLOCK FLOW CHARTS E-701

SCHEDULES - CABLES E-629

SCHEDULES - CABLES E-628

SCHEDULES - CABLES E-627

SCHEDULES - CABLES E-626

SCHEDULES - CABLES E-625

SCHEDULES - NEW PANELBOARDS E-622

SCHEDULES - NEW PANELBOARD E-621

SCHEDULES - CONTROL CONSOLES E-611

GROUNDING DIAGRAM E-608

BUBBLER WIRING DIAGRAME-607

MOTOR WIRING DIAGRAMS E-606

ONE LINE DIAGRAM E-601

DETAILS - MITER GATE AND SLIDE VALVE RECEPTACLES E-540

DETAILS - DUCT BANKE-523

DETAILS - TRAFFIC CONTROL PANEL E-522

DETAILS - CONTROL POWER AND INTERLOCK CONTROL PANEL E-521

DETAILS - HIGH MAST LIGHTING CONTROLLER E-520

DETAILS - PANEL BOARD E-519

DETAILS - MAIN SWITCHBOARD "SB-1" E-518

DETAILS - JOYSTICK SELECTOR SWITCHES E-517

DETAILS - CONTROL CONSOLE SUBPANEL ELEVATIONSE-516

DETAILS - UPPER/LOWER RIGHT CONTROL CONSOLE E-513

DETAILS - UPPER/LOWER LEFT CONTROL CONSOLE E-512

DETAILS - NEW CONTROL CONSOLE E-511

DETAILS - INTERMEDIATE WALL RECESS PROXIMITY SWITCH AND MAGNETE-505

DETAILS - INTERMEDIATE WALL MITER PROXIMITY SWITCH AND MAGNETE-504

DETAILS - LAND WALL RECESS PROXIMITY SWITCH AND MAGNETE-503

DETAILS - LAND WALL MITER PROXIMITY SWITCH AND MAGNETE-502

DETAILS - MITER GATE LEAF ROTARY CAM LIMIT SWITCH INTERNAL PLANE-501

ELEVATION - NEW CROSSOVER DUCT BANK AND MANHOLES E-205

SWITCHBOARD BUILDING FLOOR PLAN E-150

PLAN - UPSTREAM MITER GATE AND SLIDE VALVE RECEPTACLESE-141

PLAN - DOWNSTREAM MITER GATE AND SLIDE VALVE RECEPTACLESE-140

PLAN - CENTRAL CONTROL BUILDING - FIRST FLOOR AND BASEMENTE-111

PLAN - UPSTREAM AND DOWNSTREAM GUIDE WALLSE-110

PLAN - DOWNSTREAM INTERMEDIATE WALL E-109

PLAN - CENTER INTERMEDIATE WALL E-108

PLAN - UPSTREAM INTERMEDIATE WALL E-107

PLAN - DOWNSTREAM LANDWALL E-106

PLAN - CENTER LAND WALL E-105

PLAN - UPSTREAM LAND WALL E-104

PLAN - ESPLANADE & SERVICE ENTRANCE E-103

MAIN LOCK ELECTRICAL PLAN E-102

OVERALL ELECTRICAL SITE PLAN E-101

GENERAL NOTES G-005

GENERAL NOTES AND SUGGESTED SEQUENCE OF WORK G-004

LEGEND AND ABBREVIATIONS G-003

SHEET INDEX G-002

COVER SHEET ELECTRICAL SYSTEM REPLACEMENT G-001

SHEET TITLESHEET ID

SHEET INDEX

SECTION - GALLERY AND UTILITY TRENCH DEMOLITIONSD305

SECTION - GALLERY AND UTILITY TRENCH DEMOLITIONSD304

SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS DEMOLITIONSD303

SECTION - CROSSOVER DUCT BANK CROSS-SECTIONS DEMOLITIONSD302

SECTION - CROSSOVER DUCT BANK OVERALL DEMOLITIONSD301

ELEVATIONS - CROSSOVER DUCT BANK DEMOLITION CROSSOVER DUCT BANKSD201

PLAN - UPSTREAM ELECTRICAL RECEPTACLES DEMOLITIONSD141

PLAN - DOWNSTREAM ELECTRICAL RECEPTACLES DEMOLITIONSD140

PLAN - GALLERY AND UTILITY TRENCH DEMOLITIONSD103

PLAN - CROSSOVER DUCTBANK DEMOLITIONSD102

PLAN - OVERALL DEMOLITIONSD101

EXISTING CABLE SCHEDULE DOWNSTREAM RIGHT DEMOLITIONED634

EXISTING CABLE SCHEDULE UPSTREAM RIGHT DEMOLITIONED633

EXISTING CABLE SCHEDULE DOWNSTREAM LEFT DEMOLITIONED632

EXISTING CABLE SCHEDULE UPSTREAM LEFT DEMOLITIONED631

EXISTING PANELBOARDS SCHEDULES DEMOLITION ED622

EXISTING PANELBOARDS SCHEDULES DEMOLITION ED621

EXISTING ONE LINE DIAGRAM DEMOLITION ED602

EXISTING ONE LINE DIAGRAM DEMOLITION ED601

CENTRAL CONTROL BUILDING PLAN DEMOLITION ED105

DOWNSTREAM PLAN DEMOLITION ED104

UPSTREAM PLAN DEMOLITION ED103

MAIN LOCK ELECTRICAL PLAN DEMOLITION ED102

OVERALL ELECTRICAL SITE PLAN DEMOLITION ED101

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A

C A

M P

B E

IN

L

O C

K E

L E

C T

R

IC

A L

P L

A N

E-102

T L

E E

C H

B P

A T

T S

C H

U

N D

A

D D

E D

A N

N O

T A

T

IO

N

IW

L D

B

R A

D T

K E

ELECTRICAL

A N

S I

X

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

W

E K

R

/0

/2

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

P R

LAND WALL

UPPER LEFT

ILLINOIS WATERWAY

FLOW

DRESDEN ISLAND MAIN LOCK CHAMBER

LAND WALL

INTERMEDIATE WALL (I-WALL)

GUIDEWALL

UPSTREAM

LAND WALL

LOWER LEFT

INTERMEDIATE WALL

LOWER RIGHT

STATION BUILDING

CENTRAL CONTROL

3 10

INTERMEDIATE WALL

UPPER RIGHT

TERMINATION OF PERMANENT GAUGE WELL EQUIPMENT.

EXISTING, INSTALLATION OF TEMPORARY, REMOVAL OF TEMPORARY, AND

COORDINATE WITH GOVERNMENT REGARDING DISCONNECTION OF

INSTRUMENTATION CONDUCTORS ON GAUGE WELL EQUIPMENT.

AND REMOVE TEMPORARY GAUGE WELL EQUIPMENT, AND TERMINATE

THE GOVERNMENT WILL UNTERMINATE INSTRUMENTATION CABLE, PROVIDE 3.

ELECTRICAL CABLES, AND CONNECTIONS.

SEE ED-DRAWINGS AND REFRENCE DRAWINGS FOR EXISTING STRUCTURE, 2.

SEE GENERAL ELECTRICAL NOTES ON SHEET E-00011.

GENERAL SHEET NOTES

SHEET KEYNOTES

FOUR.

ELECTRICAL CABLE FOR EXISTING FLOATING MOORING BITS. TYPICAL OF

PROVIDE NEW EMBEDDED CONDUIT TO NEW CABLE TRENCH AND NEW 8.

ELECTRICAL CABLES. TYPICAL OF ONE.

PROVIDE EXISTING AIR COMPRESSOR WITH NEW RACEWAYS AND NEW

RECONNECT AND REUSE EXISTING 150 HP BUBBLER AIR COMPRESSOR. 7.

TYPICAL OF TWO.

TOW HAULAGE UNITS WITH NEW RACEWAYS AND NEW ELECTRICAL CABLES.

REINSTALL AND REUSE EXISTING TOW HAULAGE UNITS. PROVIDE EXISTING 6.

ANCHORAGES (2 PER MITER GATE LEAF).

LOCATION OF EXISTING AND NEW CONCRETE EMBEDDED MITER GATE 5.

TYPICAL OF FOUR.

RACEWAYS AND NEW ELECTRICAL CABLES TO SLIDE VALVE EQUIPMENT.

REUSE EXISTING SLIDE VALVE MACHINERY AND CONTROLLERS. PROVIDE NEW

VALVE MACHINERY, AND HPU WITH INTEGRAL CONTROLLER. REINSTALL TO

LOCATION OF EXISTING HYDRAULICS SLIDE VALVE CONCRETE RECESS, SLIDE 4.

LOCATION OF NEW MITER GATE CONCRETE RECESS AND MACHINERY. 3.

OF FOUR.

ELECTRICAL EQUIPMENT INSIDE NEW CONTROL STAND STRUCTURE. TYPICAL

PROVIDE NEW CONTROL CONSOLE, POWER DISTRIBUTION, AND OTHER 2.

ASSEMBLY COVER. TYPICAL OF FOUR.

THE NEW GFE STRUT ARM BUFFER BOX INSIDE THE NEW GFE LIMIT SWITCH

SWITCH ACTUATORS AND PROVIDE FOUR NEW LIMIT SWITCHES INSTALLED ON

BOX COVERS SAME AS EXISTING. SALVAGE AND RELOCATE THE EXISTING

PROVIDE NEW STRUT ARM LIMIT SWITCH ASSEMBLY IN LOCATION ON BUFFER 1.

SHEETS.

PROVIDE NEW RACEWAYS AND ELECTRICAL CABLES. SEE APPLICABLE DETAIL

EXISTING TRAFFIC LIGHT FIXTURES (RED, YELLOW, & GREEN) FOR REUSE.

MAINTAIN AND PROTECT EXISTING TRAFFIC SIGNAL LIGHT POLES AND 18.

ELECTRICAL CABLES. SEE APPLICABLE DETAIL SHEETS.

ADDITIONAL NEW RACEWAYS, EXTEND TO EXISTING, AND PROVIDE NEW

EXISTING DAM PATH LIGHT RACEWAYS FOR THEIR REUSE. PROVIDE

MAINTAIN AND PROTECT EXISTING LIGHT POLES FOR REUSE. INTERCEPT 17.

CABLES. SEE APPLICABLE DETAIL SHEETS.

REFEED WITH NEW RACEWAYS, EXISTING RACEWAYS, AND NEW ELECTRICAL

(URDP-MCC-4) TO EXISTING TO SAFETY SWITCH LOCATED AT DAM ABUTMENT.

PROVIDE NEW DAM FEEDER CABLE ROUTED FROM POWER DISTRIBUTION 16.

GENERAL NOTE 3.

ELECTRICAL CABLES. PROVIDE ALL WORK FOR NEW POWER CABLE. ALSO SEE

EQUIPMENT EXCEPT CABLES AND RACEWAYS. PROVIDE NEW RACEWAYS AND

MAINTAIN AND PROTECT DOWNSTREAM POOL GAUGE JUNCTION BOX AND 15.

GENERAL NOTE 3.

ELECTRICAL CABLES. PROVIDE ALL WORK FOR NEW POWER CABLE. ALSO SEE

EQUIPMENT EXCEPT CABLES AND RACEWAYS. PROVIDE NEW RACEWAYS AND

MAINTAIN AND PROTECT UPSTREAM POOL GAUGE JUNCTION BOX AND 14.

FEEDER CONDUCTORS.

EXISTING ROUTE OF THE EXISTING 500KVA TRANSFORMER SECONDARY

CONDUCTORS ROUTE. TRACE, IDENTIFY, RECORD, AND REPORT THE

UNTERMINATED, BUT IT IS NOT KNOWN WHERE THE SECONDARY

BUT THE SECONDARY LOW VOLTAGE CONDUCTORS EXIST IN THE CABINET

PRIMARY WINDING. THE 500 KVA SECONDARY WINDINGS ARE DISCONNECTED,

DAISY CHAIN WHICH ROUTES TO THE 225 KVA SERVICE TRANSFORMER

TRANSFORMER. THE MEDIUM VOLTAGE CABLES PRIMARY CONNECTION IS A

LOCATION OF EXISTING UTILITY-OWNED 500 KVA, 480/277 VAC PAD-MOUNTED 13.

ELECTRICAL PAD-MOUNTED SERVICE TRANSFORMER.

LOCATION OF EXISTING UTILITY-OWNED 225 KVA, 480/277 VAC LOCK & DAM 12.

RACEWAYS AND NEW ELECTRICAL CABLES. TYPICAL OF TWO.

FIXTURES (RED, YELLOW, & GREEN) FOR REUSE. REFEED WITH NEW

MAINTAIN AND PROTECT EXISTING TRAFFIC SIGNAL LIGHT POLES AND TRAFFIC 11.

ON LOWER GUIDE WALL, AND ONE ON UPPER GUIDE WALL.

CABLES TO REFEED LIGHT POLES. TYPICAL OF FIVE ON THE MAIN LOCK, ONE

AND FIXTURES FOR REUSE. PROVIDE WITH NEW RACEWAYS AND ELECTRICAL

MAINTAIN AND PROTECT EXISTING 100 FEET TALL HIGH MAST LIGHT POLES 10.

CONTAIN OTHER UNKNOWN CABLES.

LOCATED IN ESPLANADE CONTAINS EXISTING HIGH MAST LIGHTS. MAY

APPROXIMATE LOCATION OF EXISTING FLUSH ELECTRICAL PULL BOXES 9.

SIGNAL LIGHT POLE

EXISTING TRAFFIC

A1

SCALE: 1"=30'-0"

SITE PLAN

30' 60'0

THIS SHEET)

NOT SHOWN ON

(OFF SHEET AND

POOL GAGE WELL

DOWNSTREAM

N

A M

N D

A

D D

E D

A N

N O

T A

T

IO

P

R

8 1

E-110

A1

A1

E-107

E-109

A1

E-106

A1

E-111

A1

A1

E-105

E-108

A1

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A N

S I

D

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

/0

/2

R O

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

C A

M P

B E

U

S T

R E

A M

L A

N D

W A

L L

P L

A N

E-104

T

L E

E C

H

B P

A T

T S

C H

U L

L

A P

R

IW

L D

B

R A

D T

K E

ELECTRICAL

W

E K

R

SCALE: 1/4"=1'-0"

PLAN - UPSTREAM LAND WALL

0 4' 8'2'

WALL

TO UPSTREAM GUIDE

LIGHT POLE

EXISTING HIGH MAST

NEW CABLE TRENCH

TOW HAULAGE UNIT

RELOCATED EXISTING

SHEET KEYNOTES

SERIES ELEMENTARY DIAGRAMS FOR WIRING.

PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E-700

TRENCH. PROVIDE 4 CONDUCTOR #10 AWG XHHW-2 CABLE FROM RECESS

PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE

PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 17.

FROM NEW CABLE TRENCH.

EXISTING GRAVEL TO PROVIDE NEW CONCRETE-EMBEDDED CONDUITS

DEMOLISH EXISTING CONCRETE AS WELL AS EXCAVATE AND TRENCH 16.

FROM NEW CABLE TRENCH TO RELOCATED TOW HAULAGE EQUIPMENT.

PROVIDE NEW 2" AND 1" CONCRETE ENCASED PVC-COATED RGS CONDUITS 15.

ABOVE TOP GUARDRAIL ELEVATION TO ALLOW DOOR TO FULLY OPEN.

GUIDE WALL PULLBOX. INSTALL BOTTOM OF NEW ENCLOSURE LOCATED

JUNCTION BOX. CORE-OUT AND REUSE EXISTING CONDUIT HOLES INTO

ENCLOSURE WILL REPLACE EXISTING RACEWAY AND ELIMINATES EXISTING

BOX LOCATED ON THE UPSTREAM GUIDE WALL. NEW CONDUITS AND

ON FACE OF LOCK WALL FROM THIS NEW ENCLOSURE TO THE FIRST PULL

ROUTE FOUR(4) NEW 4" PVC-COATED RGS CONDUITS SURFACE INSTALLED

LOCATE BOTTOM OF ENCLOSURE ABOVE TOP OF LOCK WALL ELEVATION.

PANEL, HINGED 3-PT LATCH OR HALF-TURN DOOR THREE NEMA 4X DRAINS.

STEEL, 60"HIGH X 36" WIDE X 24" DEEP ELECTRICAL ENCLOSURE WITH BACK

END OF THE NEW CABLE TRENCH TO A NEW NEMA 4X TYPE 316 STAINLESS

NEW CABLE TRENCH. PROVIDE THE FOUR NEW 4" CONDUITS FROM THE

CONDUITS TO EXISTING WATER ELEVATION GAGE STATION FROM END OF

SURFACE INSTALLED ON FACE OF LOCK WALL. PROVIDE THE TWO NEW 2"

PROVIDE TWO (2) NEW 2" AND FOUR(4) NEW 4" PVC-COATED RGS CONDUITS 14.

MAINTAIN AND PROTECT EXSTING STEEL WALKWAY.13.

POWER CABLES AND FIBER OPTIC CABLE.

HYRAULICS INSTRUMENTATION STATION. PROVIDE NEW ELECTRICAL

CONDUIT FOR EXISTING REUSED WATER GAUGE AND WEATHER EC-H

AND ONE FOR FIBER OPTIC) REDUCED TO 3/4" LIQUIDTIGHT FLEXIBLE METAL

PROVIDE NEW 2" EXPOSED PVC-COATED RGS CONDUITS (ONE FOR POWER 12.

RGS GROUNDING CONDUIT. PROVIDE NEW ELECTRICAL CABLES.

INTEGRAL SWITCHED POWER RECEPTACLE. PROVIDE NEW 1" PVC-COATED

FOR RELOCATED TOW HAULAGE UNIT. PROVIDE NEW TOW HAULAGE UNIT

PROVIDE NEW 2" EMBEDDED AND EXPOSED PVC-COATED RGS CONDUIT 11

GROUNDING CABLE.

ELECTRICAL CABLES FOR LIGHTING CABLE, RECEPTACLE CABLE, AND

PVC COATED CONDUIT TO EXTEND TO NEW CABLE TRENCH. PROVIDE NEW

INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVIDE NEW 10

SECURED BY TYPE 316 STAINLESS STEEL CHANNEL STRUT AND HARDWARE.

AND SURFACE INSTALLED PVC-COATED RGS CONDUITS AND FITTINGS

TRENCH ROUTED TO UPSTREAM LOADS. PROVIDE CONCRETE EMBEDDED

GALVANIZED STEEL CONDUITS EXTENDED FROM END OF NEW CABLE

PROVIDE NEW BURIED AND SURFACE INSTALLED PVC-COATED RIGID 9

ANIMALS (E.G. RODENTS AND SNAKES).

CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND

FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND

CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND

CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 8

CONDUCTORS FROM 20 AMP 1 POLE CIRCUIT BREAKERS.

CONDUITS TO TERMINATE TO PIPE HEATERS. PROVIDE NEW 10 AWG

RGS CONDUIT REDUCED FROM 2", AND 3/4" LIQUIDTIGHT FLEXIBLE METAL

AMPERE, 120 VOLT SWITCHES FOR PIPE HEATING CABLES, 3/4" PVC-COATED

STAND TO NEW EQUIPMENT. PROVIDE THREE NEW WEATHERPROOF 20

HEATER CIRCUITS. PROVIDE NEW ELECTRICAL CABLES FROM CONTROL

PVC-COATED RGS CONDUIT FROM MCC2 TO BUBBLER PIPE MANIFOLD FOR

LIQUIDTIGHT FLEXIBLE METAL CONDUITS. SPECIFICALLY, PROVIDE NEW 2"

WEATHERPROOF CONTROL SWITCHES, RGS CONDUITS AND FITTINGS, AND

PROVIDE NEW BUBBLER PIPE SELF-REGULATING HEAT TRACE CABLE, 7

CONDUITS.

TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION BOXES FOR ALL

BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE GROUNDING TYPE CONDUIT

COATED RGS CONDUIT. TERMINATE RMC WITH PVC-COATED RGS OR RGS

CONDUIT BEFORE THEY EXIT OUT OF CONCRETE TO BE EXPOSED PVC-

CONDUITS AND RMC CONDUITS MUST TRANSITION TO PVC-COATED RGS

GALVANIZED STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC

CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID

ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.

TRENCH.

TRENCH FOR BEST LAY, BEST EXIT, AND BEST ENTRANCE INTO CABLE

CABLES ONLY AS REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE

LOCATED ON BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL

INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW 2.

SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.

GENERAL SHEET NOTES

SHEET KEYNOTES

FROM CONTROL STAND TO NEW EQUIPMENT.

LIQUID-TIGHT FLEXIBLE METAL CONDUITS. PROVIDE NEW ELECTRICAL CABLES

RGS CONDUITS AND FITTINGS, TYPE 316 STAINLESS STEEL JUNCTION BOX, AND

PROVIDE NEW BUBBLER VALVE ACTUATOR HEATER AND OPEN/CLOSE CONTROLS, 6

MACHINERY.

FOR PRECEDING AND LOCATE ADJACENT TO THE NEW MITER GATE OPERATING

SPEED, MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW SUPPORT STAND

PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR HIGH 5

DEMOLITION) OPERATION.

MAKE PROPER LEVER-ARM ACTUATION TO MATCH EXISTING (PRIOR TO

MOUNTING PLATE WITH NEW LIMIT SWITCH BOLT PATTERNS AS REQUIRED TO

75°C WITH LOW TEMP OPTION CODE L40. FABRICATE NEW STAINLESS STEEL

ALLOY AND GOLD-PLATED CONTACT OPTION; OPERATING TEMPERATURES -40°C -

AND IP67 RATINGS; DPDT, SNAP ACTION, POSITIVE-BREAK CONTACTS, SILVER

HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH, ADJUSTABLE LEVER, NEMA 4

THE DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES REPLACEMENT IS:

MITER" PROXIMITY LIMIT SWITCH.

FROM BUFFER BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF

SWITCHES ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT

STAINLESS STEEL JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT

WITH CLAMP TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316

ACROSS THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED

PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS

EXTRA FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO

NOR THE CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF

CYCLES OF THE MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT

MITER GATE PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE

EXTRA FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE

WHERE IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2"

MITER GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS

PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW 4

NEMA 4X RATED CAPS FOR BOTH DEVICES.

MATING ACP PLUGS, 25 FEET LONG FOR CONNECTION TO MOTOR. PROVIDE

6AWG & 1/C-10 AWG GND, TYPE W OR G-GC ROUND, PROTABLE CORDS AND

ENCLOSED DISCONNECT SWITCH ON STRUCTURAL STAND. PROVIDE 3/C-

POWER: PROVIDE CROUSE HINDS WSR INTERLOCKED RECEPTACLE WITH

NEW HYDRAULIC SLIDE VALVE OPERATING MACHINERY. HYDRAULIC VALVE

AND SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE

PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, 3

FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL CABLE.

PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT FROM LIGHT

THE FLOATING MOORING BIT LIGHT FIXTURE. PROVIDE NEW 2" EMBEDDED

LOCATE AND INTERCEPT EXISTING EMBEDDED ELECTRICAL CONDUIT FOR 2

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1

EQUIPMENT

CONTROL STAND

CABLE TRENCH TO

FLOW

JUNCTION BOX

MITER GATE

MG LOW

MG HIGH

FLEET PR

1 9

UPSTREAM

LOCATION AND ROUTE

AT APPROXIMATELY AT THIS

EXPOSED CONDUITS START

WALKWAY

EXISTING

MITER PROXIMITY SWITCH

RECESS PROXIMITY SWITCH

MITER GATE MACHINERY

A M

N D

U P

D A

T E

D N

O T

E S

A N

D A

N N

O T

A T

IO

N

E-502

G1

E-503

G1

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A N

S I

D

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

/0

/2

R O

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

C A

M P

B E

N T

E R

L A

N D

W A

L L

P L

A N

E-105

T

L E

E C

H

B P

A T

T S

C H

U L

L

A P

R

N D

S

H E

E T

N U

M B

E R

R E

V

IS

D

IW

L D

B

R A

D T

K E

ELECTRICAL

W

E K

R

PLAN - CENTER LAND WALL

0 4' 8'2'

SHEET KEYNOTES

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH AND DUCTS.13.

TRENCH TO NEW 120V, 20A, GFCI WEATHERPROOF DUPLEX RECEPTACLE.

PROVIDE NEW 2" PVC COATED RGS CONDUIT EMBEDDED FROM NEW CABLE 12.

NEW SERVICE TRANSFORMER.

AND DAM ELECTRIC POWER SERVICE IS PERMANENTLY CHANGED OVER TO

CONSTRUCTION. REMOVE 225KVA SERVICE TRANSFORMER AFTER LOCK

TRANSFORMER OWNED AND MAINTAINED BY POWER COMPANY DURING

MAINTAIN AND PROTECT 225KVA ELECTRIC UTILITY SERVICE PAD-MOUNTED 11.

ELECTRICAL CLOSET TO THE NEW ELECTRICAL TRENCH.

DUCT BANK FROM CENTRAL CONTROL BUILDING BASEMENT EXISTING

PROVIDE NEW PVC-COATED RIGID GALVANIZED STEEL CONDUITS IN NEW 10.

GOVERNMENT.

BUILDING BASEMENT FOR FUTURE CONNECTION BY THE

ELEVATION EQUIPMENT. COIL 50 FEET OF CABLE INSIDE CENTRAL CONTROL

BUILDING TO THE UPSTREAM AND DOWNSTREAM GAGE WELLS WATER

PROVIDE NEW INSTRUMENTATION CABLE FROM THE CENTRAL CONTROL 9.

DOWNSTREAM HIGH MAST LIGHT CABLES INSIDE THE NEW CABLE TRENCH.

PLUG. DEMOLISH EXISTING ELECTRICAL CABLES. PROVIDE NEW

CONDUITS DUCT BANK. PLUG EACH END OF EACH DUCT WITH PVC CONDUIT

ABANDON THE EXISTING DOWNSTREAM HIGH MAST LIGHTS BURIED 8.

NEW SWITCHBOARD BUILDING

EXISTING VISITOR CENTER

EXISTING CENTRAL CONTROL BUILDING

DUCT BANK

NEW CROSSOVER

AIR COMPRESSOR

EXISTING BUBBLER

TRANSFORMER

EXISTING SERVICE

SET

EXISTING GENERATOR

NEW SERVICE TRANSFORMER

CONCRETE DUCT BANK TO

NEW 2X2 (4") REINFORCED

EXISTING IN-GROUND PULL BOX

BOXES

DUCT BANK AND PULL

ABANDON EXISTING

BOX

EXISTING JUNCTION

13 9 13NEW CABLE TRENCH13

HATCHES

NEW ACCESS

12 12

WITH PVC END BELLS OR PVC BUSHINGS.

WITHIN CABLE TRENCHES WHERE PVC CONDUITS MUST BE TERMINATED

AND BECOME EXPOSED MUST BE PVC COATED RGS CONDUITS EXCEPT

ALL EMBEDDED RMC CONDUITS WHICH PENETRATE OUT OF CONCRETE 3.

STRUCTURE, ELECTRICAL CABLES, AND CONNECTIONS.

SEE ED-DRAWINGS AND REFERENCE DRAWINGS FOR EXISTING 2.

SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.

GENERAL SHEET NOTES

SHEET KEYNOTES

NEW CABLE SCHEDULE FOR SIZES.

COMPRESSOR. PROVIDE NEW CONDUITS AND ELECTRICAL CABLES PER

TO EXISTING ELECTRICAL ENCLOSURE LOCATED ON OUTSIDE OF THE AIR

EMBEDDED AND EXPOSED CONDUITS ROUTED FROM NEW CABLE TRENCH

DEMOLISH AND REPLACE EXISTING CONDUITS WITH NEW CONCRETE

EXISTING 150 HP AIR COMPRESSOR POWER AND CONTROL CONDUITS. 7.

NEW CABLE TRENCH. SEE NEW CABLE SCHEDULE FOR SIZES.

EXISTING CONDUIT WITH EMBEDDED PVC40 IN NEW CONCRETE TO THE

FLOATING MOORING BIT LIGHT FIXTURE: LOCATE, INTERCEPT, AND EXTEND 6.

ENTRANCE CABLES. SEE NEW CABLE SCHEDULE FOR SIZES.

NEW CONCRETE EMBEDDED SERVICE ENTRANCE DUCT BANK AND SERVICE 5.

SWITCHBOARD AUTO TRANSFER SWITCH.

GENERATOR ENCLOSURE TO CENTRAL CONTROL BUILDING AND EXISTING

SCHEDULE. DEMOLISH EXISTING GENERATOR CABLE AND CONDUIT FROM

TRANSFER SWITCH INSIDE NEW SWITCHBOARD. SIZE PER NEW CABLE

ELECTRICAL CABLE FROM GENERATOR ENCLOSURE TO NEW AUTO

PROVIDE NEW JUNCTION BOX, CONCRETE EMBEDDED CONDUIT AND

EXISTING STANDBY GENERATOR ELECTRICAL FEEDER CABLE AND CONDUIT: 4.

CABLE SCHEDULE FOR SIZES.

EXTEND EXISTING EMBEDDED CONDUIT TO NEW CABLE TRENCH. SEE NEW

CENTRAL LAND WALL HIGH MAST LIGHT POLE: LOCATE, INTERCEPT, AND 3.

NEW CROSSOVER DUCT BANK AND ELECTRICAL CABLES.2.

AND FULLY OPERATIONAL.

ELECTRICAL CABLES UNTIL PERMANENT CABLES ARE INSTALLED, TESTED,

MAINTAIN AND PROTECT EXISTING CROSSOVER DUCT BANK AND 1.

BANK (NOT SHOWN)

CROSSOVER DUCT

EXISTING

E-150

A1

E-111

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

SHEET KEYNOTES

SERIES ELEMENTARY DIAGRAMS FOR WIRING.

PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E-700

TRENCH. PROVIDE 4 CONDUCTOR #10 AWG XHHW-2 CABLE FROM RECESS

PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE

PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 17

ABANDON THE EXISTING IN-GROUND PRECAST (QUAZITE) PULL BOXES.16

CABLE DOWNSTREAM FOR ITS REUSE.

MAST PULL BOX NEAR THE CONTROL STAND AND CAREFULLY REMOVE

DISCONNECT CABLE FROM EXISTING DOWNSTREAM LAND WALL HIGH

DOWNSTREAM GUIDE WALL HIGH MAST LIGHT POLE CIRCUIT: C.

AND CAREFULLY REMOVE CABLE DOWNSTREAM FOR ITS REUSE.

DISCONNECT CABLE FROM EXISTING DOWNSTREAM LAND WALL GALLERY

DOWNSTREAM GUIDE WALL CIRCUIT 40 FT. TALL LIGHT POLE CIRCUIT: B.

EXISTING ELECTRICAL CABLE DOWNSTREAM FOR ITS REUSE.

DOWNSTREAM LAND WALL CONTROL STAND AND CAREFULLY REMOVE

NAVIGATION LIGHT CIRCUIT: DISCONNECT CABLE FROM EXISTING A.

DOWNSTREAM GUIDE WALL CIRCUITS:

PROVIDE NEW CABLES SPLICED ON TERMINALS IN NEW JUNCTION BOX FOR 15

REUSE EXISTING CONDUIT HOLES INTO GUIDE WALL PULLBOX.

PULL BOX LOCATED ON THE DOWNSTREAM GUIDE WALL. CORE-OUT AND

COATED RGS CONDUITS IN NEW CONCRETE 2X2 DUCT BANK TO THE FIRST

GUIDE WALL CABLES TO NEW CABLES. PROVIDE FOUR(4) NEW 4" PVC-

DRAIN. PROVIDE TERMINAL BLOCKS TO SPLICE EXISTING DOWNSTREAM

ENCLOSURE WITH 3-PT LATCH HINGED DOOR, BACKPANEL, AND NEMA 4X

PROVIDE NEW 36"X36"X18" DEEP, NEMA 4X, TYPE 316 STAINLESS STEEL 14

CABLES AND FIBER OPTIC CABLE.

HYRAULICS INSTRUMENTATION STATION. PROVIDE NEW ELECTRICAL POWER

CONDUIT FOR EXISTING REUSED WATER GAUGE AND WEATHER EC-H

AND ONE FOR FIBER OPTIC) REDUCED TO 3/4" LIQUIDTIGHT FLEXIBLE METAL

PROVIDE NEW 2" EXPOSED PVC-COATED RGS CONDUITS (ONE FOR POWER 13

GROUNDING CONDUIT. PROVIDE NEW ELECTRICAL CABLES.

SWITCHED POWER RECEPTACLE. PROVIDE NEW 1" PVC-COATED RGS

RELOCATED TOW HAULAGE UNIT, NEW TOW HAULAGE UNIT INTEGRAL

PROVIDE NEW 2" EMBEDDED AND EXPOSED PVC-COATED RGS CONDUIT FOR 12

GROUNDING CABLE.

ELECTRICAL CABLES FOR LIGHTING CABLE, RECEPTACLE CABLE, AND

PVC-COATED CONDUIT TO EXTEND TO NEW CABLE TRENCH. PROVIDE NEW

INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVIDE NEW 3" 11

FITTINGS.

EMBEDDED AND SURFACE INSTALLED PVC-COATED RGS CONDUITS AND

NEW CABLE TRENCH ROUTED TO NEW JUNCTION BOX. PROVIDE CONCRETE

PVC-COATED RIGID GALVANIZED STEEL CONDUITS EXTENDED FROM END OF

PROVIDE TWO(2) 2", ONE(1) 1", AND FOUR(4) 4" NEW EMBEDDED AND EXPOSED 10

(E.G. RODENTS AND SNAKES).

CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND ANIMALS

FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND

CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND

CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 9

CONDUCTORS FROM 20 AMP 1 POLE CIRCUIT BREAKERS.

CONDUITS TO TERMINATE TO PIPE HEATERS. PROVIDE NEW 10 AWG

RGS CONDUIT REDUCED FROM 2", AND 3/4" LIQUIDTIGHT FLEXIBLE METAL

AMPERE, 120 VOLT SWITCHES FOR PIPE HEATING CABLES, 3/4" PVC-COATED

STAND TO NEW EQUIPMENT. PROVIDE THREE NEW WEATHERPROOF 20

HEATER CIRCUITS. PROVIDE NEW ELECTRICAL CABLES FROM CONTROL

PVC-COATED RGS CONDUIT FROM MCC2 TO BUBBLER PIPE MANIFOLD FOR

LIQUIDTIGHT FLEXIBLE METAL CONDUITS. SPECIFICALLY, PROVIDE NEW 2"

WEATHERPROOF CONTROL SWITCHES, RGS CONDUITS AND FITTINGS, AND

PROVIDE NEW BUBBLER PIPE SELF-REGULATING HEAT TRACE CABLE, 8

ELECTRICAL CABLES FROM CONTROL STAND TO NEW EQUIPMENT.

JUNCTION BOX, AND LIQUID-TIGHT FLEXIBLE METAL CONDUITS. PROVIDE NEW

CONTROLS RGS CONDUITS AND FITTINGS, TYPE 316 STAINLESS STEEL

PROVIDE NEW BUBBLER VALVE ACTUATOR HEATER AND OPEN/CLOSE 7

OPERATING MACHINERY.

STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW MITER GATE

SPEED, MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW SUPPORT

PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR HIGH 6

MATCH EXISTING (PRIOR TO DEMOLITION) OPERATION.

PATTERNS AS REQUIRED TO MAKE PROPER LEVER-ARM ACTUATION TO

NEW STAINLESS STEEL MOUNTING PLATE WITH NEW LIMIT SWITCH BOLT

TEMPERATURES -40°C - 75°C WITH LOW TEMP OPTION CODE L40. FABRICATE

SILVER ALLOY AND GOLD-PLATED CONTACT OPTION; OPERATING

4 AND IP67 RATINGS; DPDT, SNAP ACTION, POSITIVE-BREAK CONTACTS,

HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH, ADJUSTABLE LEVER, NEMA

DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES REPLACEMENT IS:

LIMIT SWITCH.

BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF MITER" PROXIMITY

ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT FROM BUFFER

JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT SWITCHES

TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316 STAINLESS STEEL

THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED WITH CLAMP

PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS ACROSS

FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO

CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF EXTRA

MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT NOR THE

PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE CYCLES OF THE

FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE MITER GATE

IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2" EXTRA

GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS WHERE

PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW MITER 5

CONNECTION TO MOTOR. PROVIDE NEMA 4X RATED CAPS FOR BOTH DEVICES.

ROUND, PROTABLE CORDS AND MATING ACP PLUGS, 25 FEET LONG FOR

STRUCTURAL STAND. PROVIDE 3/C-6AWG & 1/C-10 AWG GND, TYPE W OR G-GC

HINDS WSR INTERLOCKED RECEPTACLE WITH ENCLOSED DISCONNECT SWITCH ON

SLIDE VALVE OPERATING MACHINERY. HYDRAULIC VALVE POWER: PROVIDE CROUSE

SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW HYDRAULIC

PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, AND 4

INSIDE NEW STRUCTURAL SHELTER.

POWER DISTRIBUTION PANEL, AND NEW LOCK CONTROL CONSOLE LOCATED

DOWNSTREAM LAND WALL CONTROL STAND NEW MOTOR CONTROL CENTER, 3

FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL CABLE.

PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT FROM LIGHT

THE FLOATING MOORING BIT LIGHT FIXTURE. PROVIDE NEW 2" EMBEDDED

LOCATE AND INTERCEPT EXISTING EMBEDDED ELECTRICAL CONDUIT FOR 2

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1

PVC-COATED RGS SURFACE CONDUITS.

JOINTS. PROVIDE PVC-COATED RGS EXPANSION/CONTRACTION COUPLINGS FOR

CONDUITS ARE INSTALLED ACROSS LOCK CONCRETE MONOLITH EXPANSION

PROVIDE NEW EXPANSION/CONTRACTION CONDUIT COUPLINGS WHEREEVER 4.

BOXES FOR ALL CONDUITS.

GROUNDING TYPE CONDUIT TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION

WITH PVC-COATED RGS OR RGS BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE

OUT OF CONCRETE TO BE EXPOSED PVC-COATED RGS CONDUIT. TERMINATE RMC

CONDUITS MUST TRANSITION TO PVC-COATED RGS CONDUIT BEFORE THEY EXIT

STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC CONDUITS AND RMC

CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID GALVANIZED

ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.

EXIT, AND BEST ENTRANCE INTO CABLE TRENCH.

REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE TRENCH FOR BEST LAY, BEST

BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL CABLES ONLY AS

INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW LOCATED ON 2.

SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.

GENERAL SHEET NOTES

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

W

E K

R

/0

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

C A

M P

B E

W N

S T

R E

A M

L A

N D

W A

L L

P L

A N

E-106

T L

E E

C H

B P

A T

T S

C H

U

IW

L D

B

R A

D T

K E

ELECTRICAL

A N

S I

X

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

W

E K

R

SCALE: 3/32"=1'-0"

PLAN - DOWNSTREAM LANDWALL

NEW MITER GATE MACHINERY

EXISTING HIGH MAST LIGHT POLE

HAULAGE UNIT

EXISTING RELOCATED TOW

EQUIPMENT

TO EXISTING GAUGE WELL

EQUIPMENT

TO DOWNSTREAM GUIDE WALL

NEW CABLE TRENCH

DUCT BANK

START OF NEW DOWNSTREAM

END OF NEW CABLE TRENCH /

NEW JUNCTION BOX

EMBEDDED CONDUIT

EXISTING HIGH MAST LIGHTS

LOCATE, INTERCEPT, AND COUPLE TO

EXISTING SPEAKER POLE

0 8'4' 16'

SLIDE VALVE MACHINERY

BANK

NEW CONCRETE EMBEDDED DUCT

LIGHT FIXTURE UNDER GRATING

EXISTING FLOATING MOORING BIT

N

MITER PROXIMITY SWITCH

RECESSED PROXIMITY SWITCH 17

A P

R

A

M N

D

A D

D E

D A

N N

O T

A T

IO

N

S

A P

R

A

M N

D

A D

D E

D A

N N

O T

A T

IO

N

S

E-502

G1

E-502

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A N

S I

D

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

/0

/2

R O

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

C A

M P

B E

S T

R E

A M

I N

T E

R M

E D

IA

T

E W

A L

L

P L

A N

E-107

T

L E

E C

H

B P

A T

T S

C H

U

IW

L D

B

R A

D T

K E

ELECTRICAL

W

E K

R

SCALE: 3/16"=1'-0"

PLAN - UPSTREAM INTERMEDIATE WALL

EXISTING POLE BASE

NEW CABLE TRENCH

NEW CABLE TRENCH

EXISTING GUARD RAIL

SHEET KEYNOTES

ACTUATION TO MATCH EXISTING (PRIOR TO DEMOLITION) OPERATION.

LIMIT SWITCH BOLT PATTERNS AS REQUIRED TO MAKE PROPER LEVER-ARM

CODE L40. FABRICATE NEW STAINLESS STEEL MOUNTING PLATE WITH NEW

OPTION; OPERATING TEMPERATURES -40°C - 75°C WITH LOW TEMP OPTION

POSITIVE-BREAK CONTACTS, SILVER ALLOY AND GOLD-PLATED CONTACT

ADJUSTABLE LEVER, NEMA 4 AND IP67 RATINGS; DPDT, SNAP ACTION,

REPLACEMENT IS: HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH,

THE DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES

MITER" PROXIMITY LIMIT SWITCH.

FROM BUFFER BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF

SWITCHES ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT

STAINLESS STEEL JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT

WITH CLAMP TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316

ACROSS THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED

PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS

EXTRA FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO

NOR THE CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF

CYCLES OF THE MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT

MITER GATE PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE

EXTRA FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE

WHERE IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2"

MITER GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS

PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW 4

NEMA 4X RATED CAPS FOR BOTH DEVICES.

PLUGS, 25 FEET LONG FOR CONNECTION TO MOTOR WINDING. PROVIDE

10 AWG GND, TYPE W OR G-GC ROUND, PROTABLE CORDS AND MATING ACP

DISCONNECT SWITCH ON STRUCTURAL STAND. PROVIDE 3/C-6 AWG & 1/C-

CROUSE-HINDS WSR INTERLOCKED RECEPTACLE WITH ENCLOSED

SLIDE VALVE OPERATING MACHINERY. HYDRAULIC VALVE POWER: PROVIDE

AND SUPPORT STAND FOR AND LOCATE ADJACENT TO THE NEW HYDRAULIC

PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, 3

CABLE.

CABLES FOR LIGHTING CABLE, RECEPTACLE CABLE, AND GROUNDING

RGS CONDUIT TO TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL

PVC COATED CONDUIT TO EXTEND EXISTING CONDUIT WITH PVC-COATED

INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVID NEW 2

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1

SHEET KEYNOTES

SERIES ELEMENTARY DIAGRAMS FOR WIRING

PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E700

TRENCH. PROVIDE 4 CONDUCTOR #10AWG XHHW-2 CABLE FROM RECESS

PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE

PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 16

WALL AND TO THE SPILLWAY DAM.

COMMUNICATIONS CABLES) ROUTED ACROSS ARCH DAM TO THE RIVER

EXISTING RGS CONDUITS (DAM POWER FEEDER, DAM PATH LIGHTS, AND 15

EXISTING STAINLESS STEEL JUNCTION BOX.14

THE NEW CABLE TRENCH (NOT INTO THE BOTTOM).

NEW 3” PVC40 CONDUITS EXTENDED UPWARD TO THE END OF AND INTO

EXISTING CONDUIT WITH CONDUIT COUPLINGS AND PROVIDE THREE (3)

CONCRETE EMBEDDED CONDUITS INSIDE THE GALLERY. TRANSITION THE

SAWCUT AND CORE DRILL CONCRETE TO INTERCEPT THE EXISTING 13

EMBEDDED CONDUIT TRENCH WITH NEW CONCRETE.

EXISTING RGS CONDUIT, REPAIR AND RESTORE LOCK WALL NEW

EXTEND NEW PVC40 AND TRANSITION WITH COUPLING TO INTERCEPTED

EMBEDDED 2” PVC40 CONDUIT FROM NEW CABLE TRENCH TO FEED POLE.

EMBEDDED CONDUIT, SAWCUT CONCRETE TO PROVIDE A NEW CONCRETE

EXISTING I-WALL DAM PATH LIGHT POLE: INTERCEPT EXISTING CONCRETE 12

CABLE SCHEDULE.

CABLES, AND DAM COMMUNICATION CABLES IN NEW CABLE TRENCH. SEE

PROVIDE NEW CABLES FOR DAM POWER CABLE, PATH LIGHT CIRCUIT 11

FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL CABLE.

PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT FROM LIGHT

CONDUIT FOR NAVIGATION LIGHT FIXTURES. PROVIDE NEW 2" EMBEDDED

LOCATE AND INTERCEPT EXISTING CONCRETE EMBEDDED ELECTRICAL 10

CABLE.

FROM LIGHT FIXTURE TO NEW CABLE TRENCH. PROVIDE NEW ELECTRICAL

EMBEDDED PVC40 CONDUIT TO EXTEND EXISTING EMBEDDED CONDUIT

CONDUIT FOR TRAFFIC SIGNAL LIGHT FIXTURE. PROVIDE NEW 2"

LOCATE AND INTERCEPT EXISTING CONCRETE EMBEDDED ELECTRICAL 9

NAVIGATION LIGHT FIXTURES.

ROUTED UPSTREAM TO EXISTING TRAFFIC SIGNAL LIGHT FIXTURES AND

PROVIDE NEW PVC-COATED RGS CONDUITS FROM NEW CABLE TRENCH 8

ANIMALS (E.G. RODENTS AND SNAKES).

CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND

FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND

CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND

CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 7

MITER GATE OPERATING MACHINERY. SEE CABLE SCHEDULES.

SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW

HIGH SPEED, & MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW

PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR 6

CABLES.

PVC-COATED RGS CONDUITS FROM CABLE TRENCH AND NEW ELECTRICAL

DESIGN IS CROUSE-HINDS WSR. PROVIDE NEW CONCRETE EMBEDDED

AND SUPPORT STAND FOR TWO NEW "FLEET" RECEPTACLES. BASIS OF

PROVIDE NEW 100 AMP, 480 VOLTS INTERLOCKED POWER RECEPTACLES 5

COUPLINGS FOR PVC-COATED RGS SURFACE CONDUITS.

EXPANSION JOINTS. PROVIDE PVC COATED RGS EXPANSION/CONTRACTION

CONDUITS ARE INSTALLED ACROSS LOCK CONCRETE MONOLITH

PROVIDE NEW EXPANSION/CONTRACTION CONDUIT COUPLINGS WHEREVER 4.

CONDUITS.

TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION BOXES FOR ALL

BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE GROUNDING TYPE CONDUIT

COATED RGS CONDUIT. TERMINATE RMC WITH PVC-COATED RGS OR RGS

CONDUIT BEFORE THEY EXIT OUT OF CONCRETE TO BE EXPOSED PVC-

CONDUITS AND RMC CONDUITS MUST TRANSITION TO PVC-COATED RGS

GALVANIZED STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC

CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID

ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.

TRENCH.

TRENCH FOR BEST LAY, BEST EXIT, AND BEST ENTRANCE INTO CABLE

CABLES ONLY AS REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE

LOCATED ON BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL

INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW 2.

SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.

GENERAL SHEET NOTES

NEW CABLE TRENCH

LIGHTING POLE

EXISTING HIGH MAST

8'0 4' 16'

LEAF

MITER GATE

CABLE TRENCH

END OF NEW

N

1'-8" DEEP

1'-6" WIDE x

TRENCH

1'-8" DEEP

3'-2" WIDE x

TRENCH

LEAF

MITER GATE

SWITCH

PROXIMITY

RECESS

MACHINERY

MITER GATE

A P

R

A

M N

D

U P

D A

T E

D A

N N

O T

A T

IO

N

A

P R

PROXIMITY SWITCH CONNECTIONS

E-504

G1

E-505

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A N

S I

D

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

/0

/2

R O

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

C A

M P

B E

W N

S T

R E

A M

I N

T E

R M

E D

IA

T

E W

A L

L

P L

A N

E-109

T

L E

E C

H

B P

A T

T S

C H

U L

L

A P

R

N D

U P

D A

T E

D N

O T

E S

A N

D A

N N

O T

A T

IO

IW

L D

B

R A

D T

K E

ELECTRICAL

W

E K

R

PLAN - DOWNSTREAM INTERMEDIATE WALL

0 4' 8'2'

NEW CABLE TRENCH

CONDUITS.

EXPANSION/CONTRACTION COUPLINGS FOR PVC-COATED RGS SURFACE

MONOLITH EXPANSION JOINTS. PROVIDE PVC-COATED RGS

WHEREEVER CONDUITS ARE INSTALLED ACROSS LOCK CONCRETE

PROVIDE NEW EXPANSION/CONTRACTION CONDUIT COUPLINGS 4.

CONDUITS.

TERMINATION HUBS (E.G. MYERS HUBS) IN JUNCTION BOXES FOR ALL

BUSHINGS TO MATCH CONDUIT TYPE. PROVIDE GROUNDING TYPE CONDUIT

COATED RGS CONDUIT. TERMINATE RMC WITH PVC-COATED RGS OR RGS

CONDUIT BEFORE THEY EXIT OUT OF CONCRETE TO BE EXPOSED PVC-

CONDUITS AND RMC CONDUITS MUST TRANSITION TO PVC-COATED RGS

GALVANIZED STEEL (RGS) CONDUITS. ALL CONCRETE EMBEDDED PVC

CONCRETE AND BECOME EXPOSED MUST BE PVC COATED RIGID

ALL EMBEDDED RIGID METAL CONDUITS (RMC) WHICH PENETRATE OUT OF 3.

TRENCH.

TRENCH FOR BEST LAY, BEST EXIT, AND BEST ENTRANCE INTO CABLE

CABLES ONLY AS REQUIRED. ORGANIZE CABLE LOCATIONS IN CABLE

LOCATED ON BOTTOM OF TRENCH. STACK SECOND ROW OF ELECTRICAL

INSTALL ALL ELECTRICAL CABLES NEATLY SIDE-BY-SIDE IN ONE ROW 2.

SEE GENERAL ELECTRICAL NOTES ON SHEET E-001.1.

GENERAL SHEET NOTES SHEET KEYNOTES

SERIES ELEMENTARY DIAGRAMS FOR WIRING.

PROXIMITY LIMIT SWITCH ASSEMBLY TO CONTROL CONSOLE. SEE E700

TRENCH. PROVIDE 4 CONDUCTOR #10AWG XHHW-2 CABLE FROM RECESS

PROXIMITY LIMIT SWITCH ASSEMBLY THRU BULLGEAR RECESS TO CABLE

PROVIDE 1" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW RECESS 14

RECEPTACLE CABLE, AND GROUNDING CABLE.

TRENCH. PROVIDE NEW ELECTRICAL CABLES FOR LIGHTING CABLE,

PVC COATED CONDUIT AND NEW CORE DRILLTO EXTEND TO NEW CABLE

INTERCEPT EXISTING HIGH MAST LIGHT POLE CONDUIT AND PROVIDE NEW 13

ANIMALS (E.G. RODENTS AND SNAKES).

CABLES AS REQUIRED TO PREVENT ENTRY BY WATER, TRASH, AND

FOUNDATION WALL INTO THE CABLE CRAWL SPACE. PROVIDE SEAL AROUND

CABLE TRENCH AS CABLES PENETRATE UNDER THE CONTROL STAND

CONTROL STAND. PROPERLY SEAL THE ELECTRICAL CABLE ENTRIES IN THE

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH TO/FROM 12

CAPS FOR BOTH DEVICES

PLUGS, 25 FEET LONG FOR CONNECTION TO MOTOR. PROVIDE NEMA 4X RATED

1/C-10 AWG GND, TYPE W OR G-GC ROUND, PROTABLE CORDS AND MATING ACP

ENCLOSED DISCONNECT SWITCH ON STRUCTURAL STAND. PROVIDE 3/C-6AWG &

POWER: PROVIDE CROUSE HINDS WSR INTERLOCKED RECEPTACLE WITH

HYDRAULIC VALVE NEW HYDRAULIC SLIDE VALVE OPERATING MACHINERY.

AND SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE

PROVIDE NEW POWER RECEPTACLE (VALVE HPU POWER), JUNCTION BOX, 11

MITER GATE OPERATING MACHINERY. SEE CABLE SCHEDULES.

SUPPORT STAND FOR PRECEDING AND LOCATE ADJACENT TO THE NEW

HIGH SPEED, & MG MOTOR LOW SPEED), NEW JUNCTION BOX, AND NEW

PROVIDE NEW POWER RECEPTACLES (FLEET RECEPTACLE, MG MOTOR 10

ACTUATION TO MATCH EXISTING (PRIOR TO DEMOLITION) OPERATION.

LIMIT SWITCH BOLT PATTERNS AS REQUIRED TO MAKE PROPER LEVER-ARM

CODE L40. FABRICATE NEW STAINLESS STEEL MOUNTING PLATE WITH NEW

OPTION; OPERATING TEMPERATURES -40°C - 75°C WITH LOW TEMP OPTION

POSITIVE-BREAK CONTACTS, SILVER ALLOY AND GOLD-PLATED CONTACT

ADJUSTABLE LEVER, NEMA 4 AND IP67 RATINGS; DPDT, SNAP ACTION,

REPLACEMENT IS: HONEYWELL SZL-VL-S SIDE ROTARY LIMIT SWITCH,

THE DESIGN BASIS FOR THE NEW STRUT ARM LIMIT SWITCHES

MITER" PROXIMITY LIMIT SWITCH.

FROM BUFFER BOX NEW JUNCTION BOX TO NEW MITER GATE "PROOF OF

SWITCHES ASSEMBLY ON BUFFER BOX. PROVIDE NEW 3/4" RGS CONDUIT

STAINLESS STEEL JUNCTION BOX ADJACENT TO THE NEW STRUT ARM LIMIT

WITH CLAMP TYPE CONDUIT FASTENERS. ROUTE TO NEW TYPE 316

ACROSS THE TOP OF THE MITER GATE UNDER THE WALKWAY SECURED

PROPERLY CROSS THE PINTLE "HINGE" LOCATION. PROVIDE 2" RGS

EXTRA FLEXIBLE METAL CONDUIT ADJUSTED IN LENGTH AS NECESSARY TO

NOR THE CONDUCTORS INSIDE IT. PROVIDE APPROXIMATELY 6 FEET OF

CYCLES OF THE MITER GATE WILL NOT DAMAGE THE FLEXIBLE CONDUIT

MITER GATE PINTLE IN PROPER METHOD SO THAT THE OPEN AND CLOSE

EXTRA FLEXIBLE LIQUIDTIGHT FLEXIBLE METAL CONDUIT ACROSS THE

WHERE IT MUST BE SURFACE INSTALLED TO THE MITER GATE. PROVIDE 2"

MITER GATE JUNCTION BOX CONCRETE EMBEDDED TO BULLGEAR RECESS

PROVIDE NEW 2" RIGID GALVANIZED STEEL (RGS) CONDUIT FROM NEW 9

FOR FULL LENGTH OF DRILLED CORES.

FILL ANNULAR SPACE AROUND EACH CONDIUT WITH NON-SHRINK GROUT

CONDUITS TO THE NAVIGATION LIGHTS POLE AND ALSO TO THE CCTV POLE.

CONCRETE STAIRWAY TO ALLOW INSTALLATION OF NEW PVC-COATED RGS

PROVIDE TWO 3" DIAMETER CORE DRILLS THROUGH THE EXISTING 8

TO KEEP DISSIMILAR METALS SEPARATED.

SUPPORTS WITH 316 STAINLESS STEEL CLAMPS AND ISOLATING MATERIAL

PROVIDE NEW TYPE 316 STAINLESS STEEL CHANNEL STRUT CONDUIT 7

ELECTRICAL CABLES.

STAINLESS STEEL NEMA 4X JUNCTION BOX WITH DRAIN, AND NEW

REUSE EXISTING CCTV AND POLE. PROVIDE NEW CONDUIT, NEW TYPE 316 6

CONDUCTORS FROM JUNCTION BOX TO NAVIGATION LIGHT FIXTURES.

WEATHERPROOF SPLICE IN JUNCTION BOX TO PROVIDE INDIVIDUAL

NEMA 4X JUNCTION BOX TO NAVIGATION LIGHT FIXTURES POLE. PROVIDE

3/4" PVC-COATED RGS CONDUIT FROM NEW TYPE 316 STAINLESS STEEL

REUSE EXISTING NAVIGATION LIGHT FIXTURES AND POLE. PROVIDE NEW 5

LIGHTS FIXTURES.

INDIVIDUAL CONDUCTORS FROM JUNCTION BOX TO TRAFFIC SIGNAL

PROVIDE WEATHERPROOF SPLICE IN JUNCTION BOX TO PROVIDE

STEEL NEMA 4X JUNCTION BOX TO TRAFFIC SIGNAL LIGHTS FIXTURES POLE.

NEW 3/4" PVC-COATED RGS CONDUIT FROM NEW TYPE 316 STAINLESS

REUSE EXISTING TRAFFIC SIGNAL LIGHT FIXTURES AND POLE. PROVIDE 4

SHEET KEYNOTES

STRUT, HARDWARE, AND EXPOXY TYPE CONCRETE ANCHOR BOLTS.

ABOVE TOP OF GAURDRAIL SUPPORTED BY 316 STAINLESS STEEL CHANNEL

NEMA 4X DRAIN. LOCATE ENCLOSURE ABOVE TOP OF LOCK WALL AND

PROVIDE NEW TYPE 316 NEMA 4X STAINLESS STEEL ENCLOSURE WITH 3

CONCRETE ANCHOR BOLTS.

SECURE CHANNEL STUT WITH 316 STAINLESS STEEL EXPOXY TYPE

316 STAINLESS STEEL CHANNEL STRUT AND HARDWARE. FASTEN AND

INSTALLED PVC-COATED RGS CONDUITS AND FITTINGS SECURED BY TYPE

CAMERA POLE LOADS. PROVIDE CONCRETE EMBEDDED AND SURFACE

DOWNSTREAM TO TRAFFIC SIGNAL LIGHTS, NAVIGATION LIGHTS, AND CCTV

STEEL CONDUITS EXTENDED FROM END OF NEW CABLE TRENCH ROUTED

PROVIDE TWO NEW WALL-MOUNTED 2" PVC-COATED RIGID GALVANIZED 2

PROVIDE NEW ELECTRICAL CABLES IN NEW CABLE TRENCH. 1

STAND

CONTROL

NEW

MITER GATE LEAF

POLE

LIGHTS

NAVIGATION

EXISTING

POLE

SIGNAL LIGHTS

EXISTING TRAFFIC

ON TRI-AX POLE

EXISTING CCTV

POLE

HIGH MAST

EXISTING

EXPOSED CONDUIT

INTERCEPT EXISTING 8

AS SHOWN)

(TYPICAL QTY

1 11

N E

W C

A B

LE

T

R E N C

H

FLOW

MITER GATE MACHINERY

SLIDE VALVE MACHINERY

MITER PROXIMITY SWITCH

A P

R

A

M N

D

U P

D A

T E

D N

O T

E S

A N

D A

N N

O T

A T

IO

N

A

M N

D

U P

D A

T E

D N

O T

E S

A N

D A

N N

O T

A T

IO

N

A

P R

SWITCH

PROXIMITY

RECESS

E-504

G1

E-505

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A

C A

M P

B E

S T

R E

A M

A N

D D

O W

N S

T R

E A

M G

U

ID

E W

A L

L S

P L

A N

E-110

T L

E E

C H

B P

A T

T S

C H

U

N D

S

H E

E T

A D

D E

D T

O S

IW

L D

B

R A

D T

K E

ELECTRICAL

A N

S I

X

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

W

E K

R

/0

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

R

BRANDON ROAD LOCKS AND DAMS "HIGH MAST LIGHTING" PROJECT.

ALSO SEE REFRENCE DRAWINGS FROM THE DRESDEN ISLAND AND 4.

ELECTRICAL CABLES AND THEIR NEW SOURCES.

DOWNSTREAM GUIDE WALL EQUIPMENT AFTER CONNECTION TO NEW

VERIFY CORRECT ENERGIZATION AND OPERATION OF ALL UPSTREAM AND 3.

GUIDE WALLS.

MAINTAIN AND PROTECT EXISTING ELECTRICAL EQUIPMENT LOCATED ON 2.

TO SPLICE TO NEW ELECTRICAL CABLES INSTALLED ON THE MAIN LOCK.

WALL CABLES EXCEPT AS REQUIRED TO EXTEND TO NEW JUNCTION BOXES

MAINTAIN AND PROTECT EXISTING UPSTREAM AND DOWNSTREAM GUIDE 1.

GENERAL SHEET NOTES

SHEET KEYNOTES

ALSO SEE THE CABLE SCHEDULE.

BUILDING TO EXISTING UPSTREAM GUIDE WALL CCTV CAMERA.

CCTV CABLE "V2" FULL LENGTH FROM CENTRAL CONTROL

POLE-MOUNTED CCTV CAMERA: PROVIDE NEW ELECTRICAL 18

THE UPSTREAM LAND WALL PLAN ON SHEET E-104.

ELECTRICAL CABLES TO NEW ELECTRICAL CABLES. ALSO SEE

WALL IN WHICH TO SPLICE EXISTING UPSTREAM GUIDE WALL

PROVIDE NEW JUNCTION BOX ON UPSTREAM END OF LAND 17

SEE THE DOWNSTREAM LAND WALL PLAN ON SHEET E-106.

WALL ELECTRICAL CABLES TO NEW ELECTRICAL CABLES. ALSO

WALL IN WHICH TO SPLICE EXISTING DOWNSTREAM GUIDE

PROVIDE NEW JUNCTION BOX ON DOWNSTREAM END OF LAND 16

LAND WALL JUNCTION BOX.

TO EXTEND AND SPLICE CABLE IN THE NEW DOWNSTREAM

TERMINATE CABLE DP8 DOWNSTREAM WITH ENOUGH LENGTH

RECEPTACLE POWER CABLE DP8 ON THE GUIDE WALL.

MAINTAIN EXISTING ELECTRICAL 480 VOLTS, 3 PHASE, 15

CABLE IN THE NEW UPSTREAM LAND WALL JUNCTION BOX.

DOWNSTREAM WITH ENOUGH LENGTH TO EXTEND AND SPLICE

POWER CABLE DP1 ON THE GUIDE WALL. TERMINATE CABLE DP1

MAINTAIN EXISTING ELECTRICAL 120 VOLTS RECEPTACLE 14

CABLE IN THE NEW DOWNSTREAM LAND WALL JUNCTION BOX.

DP3 UPSTREAM WITH ENOUGH LENGTH TO EXTEND AND SPLICE

POWER CABLE DP3 ON THE GUIDE WALL. TERMINATE CABLE

MAINTAIN EXISTING ELECTRICAL 120 VOLTS RECEPTACLE 13

UPSTREAM LAND WALL JUNCTION BOX.

ENOUGH LENGTH TO EXTEND AND SPLICE CABLE IN THE NEW

GUIDE WALL. TERMINATE CABLE DL6 DOWNSTREAM WITH

MAINTAIN EXISTING ELECTRICAL LIGHTING CABLE DL6 ON THE 12

UPSTREAM LAND WALL JUNCTION BOX.

ENOUGH LENGTH TO EXTEND AND SPLICE CABLE IN THE NEW

GUIDE WALL. TERMINATE CABLE DL2 DOWNSTREAM WITH

MAINTAIN EXISTING ELECTRICAL LIGHTING CABLE DL2 ON THE 11

FLEET RECEPTACLE.

MAINTAIN AND RECONNECT THE EXISTING 480 VOLTS, 3 PHASE 10

WEATHERPROOF GFCI RECEPTACLES.

MAINTAIN AND RECONNECT THE EXISTING 120 VOLTS, 20 AMPS 9

WALL JUNCTION BOX.

EXTEND AND SPLICE CABLE IN THE NEW DOWNSTREAM LAND

TERMINATE CABLE DL5 UPSTREAM WITH ENOUGH LENGTH TO

ELECTRICAL LIGHTING CABLE DL5 ON THE GUIDE WALL.

EXISTING NAVIGATION LIGHT CABLE. MAINTAIN EXISTING 8

WALL JUNCTION BOX.

EXTEND AND SPLICE CABLE IN THE NEW DOWNSTREAM LAND

TERMINATE CABLE DL1 UPSTREAM WITH ENOUGH LENGTH TO

ELECTRICAL LIGHTING CABLE DL1 ON THE GUIDE WALL.

EXISTING 30 FT. TALL POLE LIGHTS CABLE. MAINTAIN EXISTING 7

DUCT AND CABLES WITHIN IN IT.

MAINTAIN EXISTING GUIDE WALL 3" CONCRETE-EMBEDDED 6

MAINTAIN THE EXISTING PULLBOX.5

POLE.

MAINTAIN AND RECONNECT THE EXISTING HIGH MAST LIGHT 4

DOWN LIGHT POLE.

MAINTAIN AND RECONNECT THE EXISTING 30 FEET TALL TIP-3

POLE.

MAINTAIN AND RECONNECT THE EXISTING NAVIGATION LIGHT 2

POLE.

MAINTAIN AND RECONNECT THE EXISTING WIND SOCK LIGHT 1

J8

PLAN - DOWNSTREAM RECEPTACLE POWER

SCALE: 1"=80'

J1

PLAN - DOWNSTREAM LIGHTING

SCALE: 1"=80'

FG

FE

LT

NAV

LT

SOCK

WIND

COLLINS RD & LOCK RDTO THE INTERSECTION OF

LOCK RD

FE

FG

LT

NAV

A1

PLAN - UPSTREAM LIGHTING

SCALE: 1"=80'

A10

PLAN - UPSTREAM RECEPTACLE POWER

SCALE: 1"=80'

8'0 4' 16' 8'0 4' 16'

8'0 4' 16'8'0 4' 16'

5(TYPICAL)

FLOW FLOW

5(TYPICAL)

9 13

FLOWFLOW

5(TYPICAL)

IN 1" RGS

11 12

5(TYPICAL)

11 12

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

N T

R A

C T

/T .O

N

O

P R

O J E

C T

C O

D E

M A

T O

C /I

D

IQ

C O

N T

R A

C T

N O

A

C A

M P

B E

L L

F

IR

S T

F L

O O

R A

N D

B A

S E

M E

N T

C E

N T

R A

L C

O N

T R

O L

B U

IL

D

IN

G

P L

A N

E-111

T L

E E

C H

B P

A T

T S

C H

U

N D

S

H E

E T

N U

M B

E R

R E

V

IS

IW

L D

B

R A

D T

K E

ELECTRICAL

A N

S I

X

S O

L

IC

IT

A

T

IO

N

L O

C K

R E

H A

B

IL

IT

A

T

IO

N

G R

U N

D Y

C O

U N

T Y

IL

D R

E S

D E

N I

S L

A N

D L

O C

K A

N D

D A

M

IL

L

IN

O

IS

R

IV

E

R B

A S

IN

W

E K

R

/0

C K

I S

L A

N D

IL

L

IN

C K

I S

L A

N D

D

IS

T R

R

EXISTING SUSPENDED CEILING WITH NEW SUSPENDED CEILING.

ELECTRICAL EQUIPMENT TO BE PROVIDED IN THE BASEMENT. REPLACE

EXISTING CEILING IN ITS ENTIRETY TO ALLOW REMOVAL AND NEW

THE BASEMENT CEILING IS A 2' X 2' SUSPENDED CEILING. DEMOLISH 2.

DAM BUSINESS.

PERSONNEL PRIOR TO AND DURING CONSTRUCTION CONDUCTING LOCK AND

BUILDING WILL STAY OCCUPIED BY GOVERNMENT LOCK AND DAM WORK

GOVERNMENT LOCK AND DAM PERSONNEL. THE CENTRAL CONTROL

ADJACENT TO THE CENTRAL CONTROL BUILDING WHICH MAY AFFECT

COORDINATE WITH THE GOVERNMENT REGARDING ALL WORK INSIDE OR 1.

GENERAL SHEET NOTES

SHEET KEYNOTES

EXISTING DEVICE.

PROVIDE NEW CONDUIT AND CONDUCTORS TO REFEED 6.

SCREW COVER IS NOT ACCEPTABLE.

WITH HANDLE OR 1/4-TURN LATCH. CLAMPED, BOLTED, OR

4X, 18"H X 18"W X 18"D, COVER MUST BE EITHER 3-POINT LATCH

SCHEDULE. PROVIDE NEW TYPE 316 STAINLESS STEEL, NEMA

CONNECTING INTO EXISTING EXITING RACEWAY. SEE CABLE

TRENCH TO EXISTING STANDBY DIESEL GENERATOR SET

PROVIDE NEW UNDERGROUND RACEWAY FROM NEW CABLE

SWITCHBOARD TO EXISTING STANDBY DIESEL GENERATOR SET.

PROVIDE NEW ELECTRICAL CABLE P3A FROM NEW 5.

CEILING.

DIPPED GALVANIZED THREADED ROD ANCHORED TO CONCRETE

SUSPENDED CEILING. SUPPORT NEW CABLE TRAY FROM HOT-

LADDER TYPE CABLE TRAY INSIDE BASEMENT ABOVE

PROVIDE NEW 12-INCH WIDE ALUMINUM, OPEN-BOTTOM, 4.

SCHEDULES.

CABLE TRENCH. SEE STRUCTURAL DRAWINGS AND CABLE

PROVIDE NEW DUCT BANK AND ELECTRICAL CABLES FROM 3.

MLP AND MLPA. SEE DETAIL ON SHEET E-622.

PROVIDE…