ABBREVIATIONS

AB ANCHOR BOLT

ACC ACCESSIBLE

ACS ACCESS CONTROL SYSTEM

ACT ACOUSTICAL TILE

ADJ ADJACENT

AFF ABOVE FINISH FLOOR

AIB AIR INFILTRATION BARRIER

ALUM ALUMINUM

ANO ANODIZED

APPROX APPROXIMATE

ARCH ARCHITECT(URAL)

AT/FP ANTI-TERRORISM/FORCE

PROTECTION

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

BUR BUILT UP ROOF

CBU CEMENT BACKER UNIT

CDR CARD READER

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CG CORNER GUARD

CI CAST IRON

CIP CAST IN PLACE

CJ CONTROL JOINT

CL CLOSET

CLG CEILING

CLR CLEAR

CMT CERAMIC MOSAIC TILE

CMU CONCRETE MASONRY UNIT

COL COLUMN

COMM COMMUNICATIONS

COMP COMPENSATION

CONC CONCRETE

CONT CONTINUOUS/CONTINUE

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CORR CORRIDOR

CPT CARPET

CT CERAMIC TILE

CTR CENTER

D DRYER

DBL DOUBLE

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIM DIMENSION

DN DOWN

DR DOOR

DS DOWNSPOUT

DWG DRAWING

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC(AL)

EPT EXTERIOR PAINT

EPS EXPANDED POLYSTYRENE

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

FBM FACE BRICK MODULAR

FD FLOOR DRAIN

FDN FOUNDATION

FEB FIRE EXTINGUISHER BRACKET

FEC FIRE EXTINGUISHER CABINET

FED STD FEDERAL STANDARD

FF FINISH FLOOR

FG FINISH GRADE

FIN FINISH

FLR FLOOR

FOB FACE OF BRICK

FOC FACE OF CONCRETE

FOS FACE OF STUD FRAMING

FRR FIRE RESISTANCE RATED

FRP FIBER REINFORCED PLASTIC

FT FOOT

FTG FOOTING

HB HOSE BIB

HDPE HIGH DENSITY POLYETHYLENE

HDWD HARD WOOD

HDWR HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

HW-X HARDWARE SET NUMBER

HYD HYDRAULIC

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GFCI GOVERNMENT FURNISHED

CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED

GOVERNMENT INSTALLED

GL GRID LINE

GWB GYPSUM WALL BOARD

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

IGU INSULATED GLAZING UNIT

INSUL INSULATION

INT INTERIOR

JAN JANITOR

JT JOINT

KIT KITCHEN

KPL KICK PLATE

M MEN

MAT MATERIAL(S)

MAX MAXIMUM

MB MOISTURE BARRIER

MECH MECHANICAL

MTL METAL

MFR MANUFACTURER

MG MIRROR GLAZING

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MR MOISTURE RESISTANT

N/A NOT APPLICABLE

NO. NUMBER

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OA OVERALL

OBS OBSCURE GLAZING

OC ON CENTER

OCC OCCUPANT(S)

OD OUTSIDE DIAMETER

OD OVERFLOW DRAIN

OPEN'G OPENING

OPH OPPOSITE HAND

OPP OPPOSITE

OSB ORIENTED STRAND BOARD

OWSJ OPEN WEB STEEL JOIST

PC PRECAST CONCRETE

PL PLATE

PLYWD PLYWOOD

PLAM PLASTIC LAMINATE

PNT-X PAINT FINISH COLOR

PR PAIR

PT PAINT

PT PRESERVATIVE TREATED

PTD/WR PAPER TOWEL DISPENSER &

WASTE RECEPTACLE

P&S POLE AND SHELF

R RISER RADIUS

RAF RAISED ACCESS FLOOR

RB RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REFR REFRIGERATOR

REQD REQUIRED

RES RESILIENT

REV REVISION

RM ROOM

RO ROUGH OPENING

SAB SOUND ATTENUATION BLANKET

SASM SELF ADHERED SHEET MEMBRANE

SB SPLASH BLOCK

SCR SHOWER CURTAIN ROD

SCWD SOLID CORE WOOD DOOR

SD SOAP DISPENSER

SF SQUARE FEET

SGR SOAP/GRAB BAR COMBINATION

SH SOAP HOLDER

SHWR SHOWER

SIM SIMILAR

SIS SUSTAINABLE INFORMATION SIGN

SND SANITARY NAPKIN DISPOSER

SNTD SANITARY NAPKIN AND TAMPON

DISPENSER

SPEC SPECIFICATION(S)

SQ SQUARE

SS STAINLESS STEEL

SSB SHOU SUGI BAN WOOD PANELING

ST STEEL

STC SOUND TRANSMISSION CLASS

STD WT STANDARD WEIGHT

STOR STORAGE

STR STAIR

STRUCT STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

T TREAD

T&G TONGUE AND GROOVE

TB TOWEL BAR

TD TRENCH DRAIN

TEMP TEMPERED

TFP TRANSLUCENT FIBERGLASS PANEL

THK THICKNESS

TO TOP OF

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOF TOP OF FOOTING

TOP TOP OF PLATE

TOS. TOP OF STEEL

TPD TOILET PAPER DISPENSER

TRD TREAD

TSCD TOILET SEAT COVER DISPENSER

TS TUBE STEEL

TYP TYPICAL

U/C UNDER COUNTER

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

W WOMEN

W/ WITH

WC WATER CLOSET

W/D CLOTHES WASHER/DRYER

WD WOOD

WNDW WINDOW

WP WATER PROOFING

WR WATER RESISTANT

WRB WEATHER RESISTANT BARRIER

WWR WELDED WIRE REINFORCEMENT

SYMBOL

L ANGLE

& AND

@ AT

# NUMBER

CENTER LINE

ARCHITECTURAL SYMBOLS ARCHITECTURAL GENERAL NOTES

SHEET NUMBERING

A-001

DISCIPLINE:

A - ARCHITECTURE

SHEET NUMBER WITHIN SERIES

A-101

SIM

VIEW CALLOUTS

DIRECTION OF VIEW

DRAWING NUMBER ON SHEET

TEXT NOTE

SHEET NUMBER WHERE SECTION

OR DETAIL IS DRAWN

A-101

SIM

DIRECTION OF VIEW

DRAWING NUMBER ON SHEET

TEXT NOTE

SHEET NUMBER WHERE

ELEVATION IS DRAWN

REGION OF DETAIL OR ENLARGED VIEW

DRAWING NUMBER ON SHEET

TEXT NOTE

SHEET NUMBER WHERE DETAIL

OR ENLARGED VIEW IS DRAWN

A-101

SIM

ANNOTATION SYMBOLS

20A WALL TYPE DESIGNATOR, SEE WALL

SCHEDULES A-601 THROUGH A-602

WINDOW MARK, SEE WINDOW

SCHEDULE A-604

LV1

LOUVER MARK, SEE LOUVER

SCHEDULE A-604

CLG: UNDERSIDE

OF STRUCTURE

ROOM NAME

ROOM NAME

ROOM NUMBER

CEILING HEIGHT OR LOCATION

DOOR MARK, SEE DOOR

SCHEDULE A-603

GL

GRID NUMBER OR LETTER

GRID LINE

SHEET KEYNOTE, REFER TO

KEYNOTE LEGEND ON SHEET

WHERE ANNOTATION IS DRAWN

DIRECTION OF PLAN NORTH,

SEE CIVIL DRAWING FOR TRUE NORTH

T.O. SLAB

0'-0"

SURFACE DESCRIPTION

FINISH ELEVATION

1. REPETITIVE FEATURES NOTED TYPICAL ON THE DRAWINGS SHALL BE COMPLETELY PROVIDED AS IF DRAWN IN FULL. REPETITIVE FEATURES NOT NOTED ON THE DRAWINGS SHALL BE COMPLETELY PROVIDED

AS IF NOTED IN FULL.

2. DIMENSIONS ON ARCHITECTURAL DRAWINGS ARE INDICATED IN FEET AND INCHES.

3. DIMENSIONS ARE DRAWN TO THE FACE OF CMU, CONCRETE AND STEEL STUDS, UNLESS NOTED OTHERWISE. DIMENSIONS ARE DRAWN TO THE CENTERLINE OF STRUCTURAL STEEL, UNLESS NOTED OTHERWISE. GRID LINES INDICATE THE FACE OF CMU AND CONCRETE AND THE CENTERLINE OF INTERIOR

COLUMNS UNLESS NOTED OTHERWISE.

4. DIMENSIONS OF MASONRY COMPONENTS ARE MODULAR. MASONRY OPENINGS ARE INDICATED WITH

MODULAR DIMENSIONS AND NOTED AS "MO".

5. EXTERNAL CORNERS ON EXPOSED CONCRETE WALLS SHALL BE CHAMFERED 3/4" TYPICAL, UNLESS

NOTED OTHERWISE.

6. REPAIR OR REPLACE SURFACES DAMAGED DURING CONSTRUCTION TO MATCH ADJACENT FINISHED CONDITION. THE CONTRACTING OFFICER SHALL DETERMINE WHEN REPLACEMENT IS REQUIRED FOR

ACCEPTABLE APPEARANCE.

7. SELECTION OF EXTERIOR MATERIALS SHALL FOLLOW COLOR AND PATTERN MATCH REQUIREMENT

INDICATED. FLASHING COLOR SHALL MATCH ADJACENT WALL OR ROOF COLOR, UNO.

8. DOORS IN STUD WALLS NOT LOCATED BY DIMENSION ON FLOOR PLANS OR DETAIL DRAWINGS SHALL BE LOCATED 6 INCHES FROM SURFACE OF ADJACENT PERPENDICULAR WALL TO ROUGH OPENING OF DOOR

FRAME.

9. DOOR AND ROOM NUMBERS SHOWN ON DRAWINGS ARE FOR CONSTRUCTION PURPOSES. VERIFY

NUMBERING SCHEME WITH CONTRACTING OFFICER AND TENANT UNIT PRIOR TO FABRICATING PERMANENT

LABELS AND SIGNAGE.

10. WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESERVATIVE TREATED WOOD.

ISOLATE PRESERVATIVE TREATED WOOD FROM METALS.

11. SIZE FIRE EXTINGUISHER CABINETS AND BRACKETS TO HOUSE ONE, NFPA 10 COMPLIANT 2-A 10-BC

EXTINGUISHER, UNLESS NOTED OTHERWISE.

12. CONTRACTOR SHALL PROVIDE APPROPRIATE SHIMMING MATERIAL (WOOD, METAL, OR OTHER AS PERMITTED BY IBC) AS REQUIRED TO BRING CONSTRUCTION WITHIN SPECIFIED TOLERANCES AND DIMENSIONS. CONTRACTOR SHALL TRIM ITEMS TO FIT AND OTHERWISE ENSURE PROPER INSTALLATION OF

WORK.

13. THE CONTRACTOR IS RESPONSIBLE FOR ADVANCED REVIEW OF THE WORK REQUIRED IN THE CONSTRUCTION DOCUMENTS AND THE REQUIREMENTS FOR EXECUTING IT PROPERLY. IF THE CONTRACTOR FINDS DISCREPANCIES IN THE CONSTRUCTION DOCUMENTS OR SPECIFICATIONS, THEN THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY AND REQUEST RESOLUTION. THE CONTRACTOR

SHALL COORDINATE THE RESOLUTION OF DISCREPANCIES IN ADVANCE OF STARTING WORK.

14. FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL, TELECOMMUNICATIONS, CIVIL, AND STRUCTURAL FEATURES OR INFORMATION SHOWN ON ARCHITECTURAL DRAWINGS IS FOR COORDINATION AND LOCATION PURPOSES ONLY. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR SPECIFIC DESIGN

INFORMATION ON COMPONENTS AND SYSTEMS.

15. REFER TO THE SPECIFICATIONS FOR INFORMATION THAT SUPPLEMENTS THESE NOTES AND OTHER

DRAWING INFORMATION.

16. ARCHITECTURAL DETAILS ARE INTENDED TO SHOW THE GENERAL CHARACTER AND EXTENT OF THE PROJECT. THEY ARE NOT INTENDED TO SHOW EVERY DETAIL OF THE WORK. DETAILS NOTED "TYPICAL"

APPLY TO SIMILAR WORK THROUGHOUT THIS BUILDING, UNO.

17. ARCHITECTURAL DRAWINGS ARE FOR INFORMATION INCLUDING, BUT NOT LIMITED TO: DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND WINDOW OPENING, NON-BEARING WALLS, CURBS, DRAINS, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES AND OTHER NONSTRUCTURAL ITEMS.

18. WHERE CONFLICTS ARE IDENTIFIED BETWEEN THE CONSTRUCTION DOCUMENTS, REFERENCED STANDARDS AND THE GOVERNING CODES, THE CONTRACTING OFFICER WILL DETERMINE WHICH SHALL GOVERN. CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER AND

RESOLVED BEFORE PROCEEDING WITH THE WORK.

19. THE CONTRACTOR SHALL VERIFY DIMENSIONS, EXISTING UTILITIES, FIXTURES AND CONDITIONS AT THE SITE. CONFLICTS BETWEEN THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE

ATTENTION OF THE CONTRACTING OFFICER BEFORE PROCEEDING WITH THE WORK.

20. WORK SHALL COMPLY WITH IBC 2015, NFPA 101 (2015), AND UFC 3-600-01 AS DIRECTED BY UFC 1-200-01. WHEN CONFLICTS OCCUR BETWEEN UFC 3-600-01 AND OTHER CODES, STANDARDS AND CRITERIA, FOLLOW UFC 3-600-01. WHEN CONFLICTS OCCUR BETWEEN THE IBC AND NFPA 101, THE MOST

CONSERVATIVE REQUIREMENTS SHALL GOVERN.

21. PROVIDE ALL NECESSARY BLOCKING BACKING, FRAMING HANGERS OR OTHER SUPPORT FOR FIXTURES, EQUIPMENT CABINETRY, FURNISHINGS AND ANY ITEM REQUIRING THE SAME.

22. SEAL ALL PENETRATIONS THROUGH FLOORS, RATED WALLS, AND RATED CIELINGS WITH UL LISTED

ASSEMBLIES SUCH THAT FIRE AND SMOKE RATINGS ARE MAINTAINED.

12'-6"

LOCATION OF ELEVATION

MEASUREMENT

FINISH ELEVATION

AT TARGET

YD YARD

GRID LINES & CENTERLINES

EXPANSION JOINT

PLAN

NORTH

INTERIOR ELEVATION DRAWING NUMBER

PLATE NUMBER WHERE ELEVATION IS

DRAWN

DIRECTION OF VIEW

4A-101

AIR BARRIER

VAPOR RETARDER

SASM

DRAWING LINE TYPES

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:2

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-001

H

AL

E

AB

BR

EV

IA

T I

O N

S , S

YM

B O

LS

AN

D G

EN

ER

AL

N

O

TE

S

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

BUILDING AND LIFE SAFETY CODE SUMMARY

DESCRIPTIONCODE REFERENCEDESIGN ITEMTOPIC

BUILDING AND LIFE SAFETY CODE SUMMARY

DESCRIPTIONTOPIC DESIGN ITEM CODE REFERENCEINTERNATIONAL BUILDING CODE (IBC) - 2015

NATIONAL FIRE PREVENTION ASSOCIATION (NFPA) 101 “LIFE SAFETY CODE” - 2015

UFC 1-200-01 "GENERAL BUILDING REQUIREMENTS" - 20 JUNE 2016

UFC 3-600-01 “FIRE PROTECTION ENGINEERING FOR FACILITIES” - 28 NOV 2016, CHANGE 1

UFC 4-010-01 "ANTI-TERRORISM/FORCE PROTECTION (AT/FP)" - 01 OCT 2013, CHANGE 1

UFC 4-730-10 "FIRE STATIONS"

GOVERNING CODES

AND CRITERIA

OCCUPANCY (IBC) A-3 Assembly Assembly area, low density, without fixed seating.IBC Chapter 3

B Business Office and service type activities.

R-2 Residential Sleeping rooms, work related, permanent in nature (not transient lodging).

S-1 Storage Moderate hazard storage.

OCCUPANCY (NFPA101) NFPA occupancy classifications are similar to those of the IBC referenced above.Chapter 12New Assembly

New Business

New Hotel & Dormitory

Storage

Chapter 38

Chapter 28

Chapter 42

The building is designed with a mixture of separate and non-separated occupancies:

A one-hour fire barrier wall between the Apparatus Bay and the Business/Dormitory side of the facility is used to provide increased protection. Openings in this wall are 45-minute fire-rated. Separation is consistent with the provisions of Section 508.4

The Assembly/Business/Dormitory side employs the provisions of IBC Section 508.3 as non-separated occupancies. Code requirements are applied separately to each portion based on occupency group.

This building is sprinklered throughout, therefor additional fire barriers are only required where the code specifically requires them for non-exempted locations. These locations include the Dormitory Rooms (1/2 hour separation) and the Electrical room.

OCCUPANCY

SEPARATION (IBC)

IBC Section 508

Assembly, Business and Dorm Rooms

IBC 508.3

Storage (Apparatus Bays)

IBC 508.4

Construction Type II-B allows only non-combustible materials, with specific exceptions itemized in Section 603.

The primary structural frame, exterior and interior bearing walls, floor construction and associated secondary members, roof construction and associated secondary members are not required to be fire rated.

CONSTRUCTION TYPE IBC Chapter 6II-B

Using a Nonseparated approach, the most restrictive occupancy will govern the allowable floor area.

Per IBC Table 506.2, the allowable area for "A-3", Construction Type II-B, and single story is 38,000 SF. All other occupancies in this facility are less restrictive. Actual floor area is less than the allowable.

ALLOWABLE FLOOR

AREA

IBC TABLE 506.2A-3

(most restrictive occupancy)

Area modifications are not required since the allowable floor area exceeds the actual floor area of the building as designed.

MODIFIED

ALLOWABLE FLOOR

AREA

IBC 506Frontage & Sprinkler System

ACTUAL HEIGHT AND

STORIES

Tables 601 and 602 do not require fire resistance rated construction for Construction Type II B and the various occupancy groups in this facility. There is sufficient open space around the perimeter of the building to provide a fire separation distance in excess of 30 feet on all sides.

EXTERIOR WALL FIRE

RESISTANCE RATING

IBC 704.10,

705.5, Tables 601 and 602

The maximum area of unprotected or protected openings permitted in an exterior wall in any story is addressedt in IBC Table 705.8. Because the fire separation distance is greater than 30 feet on all sides, there is no limitation on the number and size of openings.

ALLOWABLE AREA

EXTERIOR OPENINGS

IBC 705.8,

Table 705.8

Per the cited UFC, all new construction facilities of Construction Type I or Type II with a floor area greater than 15,000 gross square feet must be protected by an Approved, Supervised Automatic Sprinkler System (ASASS) throughout the facility. The Fire Station falls within these criteria. The design of the sprinkler system must follow the "Area/Density Method of NFPA 13 and Table 9-3 of the UFC.

FIRE PROTECTION UFC 3-600-01,

Section 9-7.2 Table 9-3

Sprinkler System

No rating required for Construction Type II-B.FIRE RESISTANCE

RATING FOR

BUILDING ELEMENTS

IBC Table 601Primary structural frame, interior and exterior bearing walls, corridors, floor construction assembly, and roof assembly.

Not applicable, no stairways in this design.NFPA 101:

7.1.3.2.1 and 8.6.4

Stairway shafts

Dwelling units and sleeping units in buildings of Type II-B construction with ASASS are required to have 1/2 hour fire resistive separations between each other and between the units and the remainder of the building. Openings into units shall be 20 minute fire resistance rated door assemblies.

NFPA 101:

28.3.7.2 & Table 8.3.4.2

Dorm rooms

NFPA 90A:

5.3.4.3.1

Mechanical shafts

15 square feet per person, netOCCUPANT LOAD

FACTORS (NFPA)

NFPA 101

Table 7.3.1.2

Assembly, without fixed seats

100 square feet per person, gross

200 square feet per person, gross

200 square feet per person, gross; all other Storage at 500 square feet per person, gross

Business

Residential (Dorms)

Storage (garage)

The Assembly occupancy establishes the most restrictive requirements for dead-end corridors at 20 feet. The longest dead-end corridor in the building is 19'-10 1/2"

DEAD END CORRIDORS NFPA 101

12.2.5.1.3

COMMON PATH OF

TRAVEL

NFPA 101

12.2.5.1.2 28.2.5.4

The maximum travel distance to any exit is determined by occupancy. The most restrictive for any occupancy (Assembly) is 250 feet. The longest path in any occupancy is 168 feet.

TRAVEL DISTANCE TO

EXIT

NFPA 101

7.6 and Table A7.6

The maximum common path of travel distance is determined by occupancy. The most restrictive for any occupancy (Hotel & Dormitory) in this facility is 50 feet. MAX CPOT in Dorm area is 19'. MAX CPOT in assembly/business areas is 49' The next most restrictive is Assembly occupancy (maximum 50 occupants) at 75 feet. The longest common path of travel in an assembly occupancy is approximately 25 feet. The longest common path of travel in this building is approximately 49 feet.

Not applicable, single story facility with no stairs in the means of egress.CAPACITY MEANS OF

EGRESS

NFPA 101 - 7.3.3Stairways

Minimum required width is 44 inches and 0.2 inches per person. Maximum width of any corridor by number of occupants (egress from Day and Recreation Rooms is 126 persons times 0.2 inches = 26 inches. The minimum designed width of any corridor is 60 inches.

NFPA 101

7.3.4

Corridors

The min. clear width is 34 inches and 0.2 inches per person. The largest number of occupants at one door is 110 persons times 0.2 inches = 22 inches. The minimum designed width of any door is 34 inches.

NFPA 101

7.2.1.2.3

Doors

Portable fire extinguishers are not required in the business occupancy area or hazardous areas of other occupancies in accordance with UFC 3-600-01 (facility is fully protected with an automatic, supervised sprinkler system). The Apparatus Bay and equipment maintenance rooms are designated ordinary hazard areas. A single extinguisher will be located in the the kitchen as immediate protection against a range fire.

PORTABLE FIRE

EXTINGUISHERS

NFPA 101

9.7.4

NFPA 10

6.2.1

Not required in non-combustible construction without concealed spaces between floors and attic space.FIRE BLOCKING IBC - 718.2

Not required in attic and floor spaces of non-combustible construction.DRAFT STOPPING IBC - 718.4.3

Door assemblies including vision panels in 1/2 hour fire barriers require a 20 minute rating. Door assemblies in one hour fire barriers require a 45 minute rating.

DOOR ASSEMBLIES IBC

Table 716.5

Glazing assemblies for windows, side lights, and transom lights in 1/2 hour fire barriers require a 20 minute tested rating. Glazing assemblies in one hour fire barriers require a 45 minute tested rating.

GLAZING IBC

Table 716.5

Interior, Nonbearing walls construction must conform to NFPA 101 requirements (per UFC 3-600-01 3-3.1.1).

NFPA requirements shall be followed for any interior walls not forming area of occupancy separation per IBC.

NFPA 101, 8.3,

8.4, and 8.5

Interior non-bearing walls & partitions

29'-4" Single Story

Public areas of the facility are designed for compliance with ABA standards. Areas intended for use by fire department staff only have been designed for ABA compliance or are readily convertable if future uses incorporate more public access.

ARCHITECTURAL

BARRIERS ACT (ABA)

ABA Accessibility Standards

Facility is a "Primary Gathering" building due to the presence of "Billeting" (Dorm Rooms). The Apparatus Bays are considered a "Low Occupancy" portion of the building and are not required to meet ATFP criteria.

Exterior door and window glazing in all building areas except for the Apparatus Bays are required to be designed for blast loading resulting from Charge Weight II. Standoff distances are identified on the Civil drawings.

ANTITERRORISM/

FORCE PROTECTION

UFC 4-010-01

UFC 4-010-02

Dry Transformers over 112 1/2 kVA: Individual dry-type transformers installed indoors are rated more than 112 1/2 kVA rating shall be installed in a transformer room of fire-resistant construction. Wall construction for the electrical room has a fire rating of 1 hour, with walls running from F.F. to roof deck with fire stopped penetrations and appropriatly sealed to the roof deck.

NEC

450.21

Electrical Room

Fire Station = Risk Category "IV", Importance Factor I=1.5RISK CATEGORY ASCE 7-05

Per the cited UFC, other occupancies such as offices and shops must be separated from the storage area by a minimum of one-hour fire rated construction. The Apparatus Bay is separated from the remainder of the facility by a CMU wall providing at least a 1-hour rated fire barrier.

NOTE: Other storage occupancies with 8'-0" cielings are not considered "storage facilities" per UFC 3-600-01

STORAGE GROUP

SEPARATION

UFC 3-600-01,

Section 4-42.5.2.1

Fire Rated Separations

This is a mixed use facility and each occupancy group is classified per the IBC. Fire separation between occupancies must follow IBC and UFC 3-600-01 requirements. Fire resistance of interior, non-bearing partitions is compliant with NFPA 101 requirements.

ALLOWABLE HEIGHT

AND STORIES

IBC 504

Tables 504.3, 504.4

55 feet Three Stories

ACTUAL FLOOR AREA 30,027.5 GSF

Not applicable, no Mechanical shafts in this design.

SEISMIC DESIGN Yakima, WA - seismic design category "D"

APP BAY 11257

ADMIN/DORM 18750

1/2 EXT SPACE 20.5

Not Required

Not Applicable

Gross floor area is measured from exterior face to exterior face of enclosing perimeter walls. Exterior covered spaces are measured at 50 percent of actual coverage per Army standard methodology. Gross area of the building may not be consistent with floor area measured per the IBC.

The actual height and number of stories is less than the IBC allowable. No modifications to accommodate height are required.

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:2

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

D es ig ne r

BR

ES

H

EA

R S

A-002

C he ck er

LI

FE

S

AF

ET

Y

S U M

M A R

Y

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

7 8

C

H

MATCHLINE - ZONE B

MATCHLINE - ZONE C

M

AT

C H

LI

N

E

- Z

O N

E C

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E B

PROTECTIVE CLOTHING

LAUNDRY ROOM

SCBA

COMPRESSOR

ROOM

SCBA

MAINTENANCE

SOUTH CORR

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM

ROOM

DORM

ROOM

DORM

ROOM

RECYCLING

ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DAY/TRAINING

ROOM

RECREATION ROOM

WOMENS

RESTROOM

FITNESS ROOM

ELECTRICAL ROOM

MECHANICAL ROOM

HAZMAT/SAFETY

OFFICE

NORTH CORR

DEPARTMENT TRAINING

ROOM

TRAINING

OFFICER

TRAINING

STORAGE

116COMPUTER

TRAINING

ROOM

CHIEF'S DORM

CHIEF'S

BATH

DEP. CHIEFS

OFFICE

CHIEF'S OFFICE

MENS

RESTROOM

CONFERENCE

ROOM

ASSISTANT

CHIEF OF FP

EMS OFFICE

FIRE INSPECTORS

OFFICE

123CAPTAINS

DORM ROOM

BATHROOM

ASSISTANT CHIEF

DORM ROOM

ASSISTANT

CHIEF

STATION

CAPTAIN

HAZMAT

EQUIPMENT/CBRNE

STORAGE

147B

LAUNDRY

ROOM

148 JANITORS

CLOSET

WOMENS ABA

RESTROOM

MENS ABA

RESTROOM

DISPATCH

ROOM

103A

LOGISTICS

OFFICE

147A

EMT

STORAGE

147C

KITCHENETTE

103B

KITCHEN/DINING

ROOM

LOBBY

JANITORS

CLOSET

CLEAN UP ROOM

SPARE PPE STORAGE

PPE GEAR

STORAGE

E

A

B

D

F

G

I

J

119 12 13

141 2 3 4 5 6

MAINTENANCE/AGENT

STORAGE

EQUIPMENT

MAINTENANCE

WORKROOM

EQUIPMENT

WASH/

DISINFECT

TELECOMM

ROOM

CATV ROOM

GEN ADMIN

DISPATCH

BATHROOM

103C

UPS ROOM

CLEAN UP

ROOM BATH

VESTIBULE

VESTIBULE

VESTIBULE

VESTIBULE

VESTIBULE

PANTRY

APPARATUS BAY

CENTRAL

CORR

UNISEX BATH

UNISEX BATH

GENERAL NOTES

1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,

FIRE ALARM AND FIRE DETECTION SYSTEMS.

2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.

3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND

FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.

4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.

5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.

SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.

6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.

TRAVEL DISTANCE PATH

ONE HOUR FIRE BARRIER CONSTRUCTION

1/2 HOUR FIRE PARTITION CONSTRUCTION

LEGEND

SMOKE PARTITION CONSTRUCTION

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:3

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-003

H

AL

E

LI

FE

S

A F

ET

Y

PL

AN

3/32" = 1'-0"A-003

1 LIFE SAFETY PLAN

KEY PLAN

A B

C

SCALE:

3/32" = 1' - 0"

8' 8' 16' 24'

PLAN NORTH

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

GENERAL NOTES

1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,

FIRE ALARM AND FIRE DETECTION SYSTEMS.

2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.

3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND

FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.

4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.

5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.

SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.

6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.

7 8

C

H

E

B

D

F

G

I

J

1 2 3 4 5 6

M

AT

C H

LI

N

E

ZO

N E

C

M

AT

C H

LI

N

E

ZO

N E

A M

AT

C

H

LI

N E

- Z O

N E

A

M

AT

C H

LI

N

E

- Z

O N

E B

EGRESS PATH

101'-6"

10883

APPARATUS BAY

S-1 500

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

TRAVEL DISTANCE PATH

ONE HOUR FIRE BARRIER CONSTRUCTION

TOTAL OCCUPANTS EXITING

EXIT DOOR CAPACITY @ 0.2" PER PERSON

FEB

ROOM NAME & NUMBER

1/2 HOUR FIRE PARTITION CONSTRUCTION

APPARATUS BAY

S-2 500

OCCUPANCY & LOAD FACTOR

NET SQUARE FOOTAGE

OCCUPANTS

WALL MOUNTED FIRE EXTINGUISHER BRACKET

DEC = DEAD END CORRIDOR LENGTH

LEGEND

SMOKE PARTITION CONSTRUCTION

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:3

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-004

H

AL

E

EN

LA

R

G

ED

L

IF

E S A

FE

TY

P

LA

N Z O

N E

A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

PLAN NORTH

1/8" = 1'-0"A-004

1 ENLARGED LIFE SAFETY PLAN - ZONE B

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

H

E

D

F

G

I

J

119 12 13

MATCHLINE - ZONE B

MATCHLINE - ZONE C

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E B

PROTECTIVE

CLOTHING LAUNDRY

ROOM

S1 500

DAY/TRAINING

ROOM

A3 15

RECREATION ROOM

A3 15

WOMENS

RESTROOM

B 100

FITNESS ROOM

A3 15

ELECTRICAL ROOM

B 100

MECHANICAL ROOM

B 100

HAZMAT/SAFETY

OFFICE

B 100

NORTH CORR

B 100

DEPARTMENT

TRAINING ROOM

A3 15

TRAINING

OFFICER

B 100

TRAINING

STORAGE

S2 500

COMPUTER

TRAINING

ROOM

A3 15

CHIEF'S DORM

R2 50

CHIEF'S

BATH

R2 50

DEP. CHIEFS

OFFICE

B 100

CHIEF'S OFFICE

B 100

MENS

RESTROOM

B 100

CONFERENCE

ROOM

A3 15

ASSISTANT

CHIEF OF FP

B 100

EMS OFFICE

B 100

FIRE INSPECTORS

OFFICE

B 100

CAPTAINS

DORM ROOM

R2 50

BATHROOM

R2 50

ASSISTANT CHIEF

DORM ROOM

R2 50

ASSISTANT

CHIEF

B 100

STATION

CAPTAIN

B 100

HAZMAT

EQUIPMENT/CBRNE

STORAGE

147B

S1 500

LAUNDRY

ROOM

S1 500

JANITORS

CLOSET

B 100

WOMENS ABA

RESTROOM

B 100

MENS ABA

RESTROOM

B 100

DISPATCH

ROOM

103A

B 100

LOGISTICS

OFFICE

147A

B 100

EMT

STORAGE

147C

S1 500

KITCHENETTE

103B

B 100

LOBBY

B 100

JANITORS

CLOSET

B 100

CLEAN UP ROOM

S1 500

PPE GEAR

STORAGE

S1 500

EQUIPMENT

MAINTENANCE

WORKROOM

B 100

EQUIPMENT

WASH/

DISINFECT

B 100

TELECOMM

ROOM

B 100

CATV ROOM

B 100

GEN ADMIN

B 100

DISPATCH

BATHROOM

103C

B 100

UPS ROOM

B 100

CLEAN UP

ROOM BATH

S1 500

VESTIBULE

B 100

VESTIBULE

B 100

VESTIBULE

B 100

CENTRAL

CORR

B 100

RESTRICTED ACCESS DOOR FOR RESIDENT USE

ONLY. IF EXIT DEVICE IS PUSHED WITHOUT CODE,

ALARM WILL SOUND FOR 15 SECONDS BEFORE DOOR

OPENS. DURING EMERGENCIES DOOR WILL UNLOCK

AUTOMATICALLY.

EGRESS PATH 3'-0" EGRESS PATH 10'-8"

EGRESS PATH 29'-6"

EGRESS PATH 49'

EGRESS PATH

46'-4 7/8"

EGRESS PATH: 168'-0"

EGRESS PATH 140'-0"

EGRESS PATH

18'-6"

EXIT WIDTH / CAPACITY

68 INCHES : 340 OCCUPANTS

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

GENERAL NOTES

1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,

FIRE ALARM AND FIRE DETECTION SYSTEMS.

2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.

3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND

FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.

4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.

5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.

SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.

6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.

TRAVEL DISTANCE PATH

ONE HOUR FIRE BARRIER CONSTRUCTION

TOTAL OCCUPANTS EXITING

EXIT DOOR CAPACITY @ 0.2" PER PERSON

FEB

ROOM NAME & NUMBER

1/2 HOUR FIRE PARTITION CONSTRUCTION

APPARATUS BAY

S-2 500

OCCUPANCY & LOAD FACTOR

NET SQUARE FOOTAGE

OCCUPANTS

WALL MOUNTED FIRE EXTINGUISHER BRACKET

DEC = DEAD END CORRIDOR LENGTH

LEGEND

SMOKE PARTITION CONSTRUCTION

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:3

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-005

H

AL

E

EN

LA

R

G

ED

L

IF

E S A

FE

TY

P

LA

N Z O

N E

B

1/8" = 1'-0"A-005

1 ENLARGED LIFE SAFETY PLAN - ZONE B

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

PLAN NORTH

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

A

B

D

119 12 13

MATCHLINE - ZONE B

MATCHLINE - ZONE C

M

AT

C H

LI

N

E

- Z

O N

E C

M

AT

C H

LI

N

E

- Z

O N

E A

SCBA

COMPRESSOR

ROOM

S1 500

SCBA

MAINTENANCE

S1 500

SOUTH CORR

B 100

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM

ROOM

R2 50

DORM

ROOM

R2 50

DORM

ROOM

R2 50

RECYCLING

ROOM

S1 500

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

DORM ROOM

R2 50

KITCHEN/DINING

ROOM

A3 15

SPARE PPE

STORAGE

S1 500

MAINTENANCE/AGENT

STORAGE

S1 500

VESTIBULE

B 100

VESTIBULE

B 100

PANTRY

S2 500

UNISEX BATH

B 100

UNISEX BATH

B 100

EGRESS PATH 3'-0"

EGRESS PATH 10'-8"

EGRESS PATH: 140'-0"

EGRESS PATH

37'-8 1/8"

EGRESS PATH

18'-6"

EGRESS PATH: 102'-0 1/2"

FEB

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

EXIT WIDTH / CAPACITY

34 INCHES : 170 OCCUPANTS

GENERAL NOTES

1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,

FIRE ALARM AND FIRE DETECTION SYSTEMS.

2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.

3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND

FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.

4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.

5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.

SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.

6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.

TRAVEL DISTANCE PATH

ONE HOUR FIRE BARRIER CONSTRUCTION

TOTAL OCCUPANTS EXITING

EXIT DOOR CAPACITY @ 0.2" PER PERSON

FEB

ROOM NAME & NUMBER

1/2 HOUR FIRE PARTITION CONSTRUCTION

APPARATUS BAY

S-2 500

OCCUPANCY & LOAD FACTOR

NET SQUARE FOOTAGE

OCCUPANTS

WALL MOUNTED FIRE EXTINGUISHER BRACKET

DEC = DEAD END CORRIDOR LENGTH

LEGEND

SMOKE PARTITION CONSTRUCTION

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:4

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-006

H

AL

E

EN

LA

R

G

ED

L

IF

E S A

FE

TY

P

LA

N Z O

N E

C

1/8" = 1'-0"A-006

1 ENLARGED LIFE SAFETY PLAN - ZONE C

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

PLAN NORTH

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

H

E

A

B

D

F

G

I

J

119 12 13

141 2 3 4 5 6

A-008

A-008

A-008

LOCATIONS OF AIR BARRIER

REQUIRED TO BE TESTED

LOCATIONS OF AIR BARRIER

INSTALLED, BUT NOT TESTED

AIR BARRIER

GENERAL NOTES

1. SEE A-001 FOR SYMBOLS, ABBREVIATIONS, LEGENDS AND DRAWING CONVENTIONS.

2. FOR BUILDING PRESSURE TESTING REQUIREMENTS SEE SPECIFICATION SECTION 07 05 23.

FOR AIR BARRIER REQUIREMENTS SEE SPECIFICATION SECTIONS 07 27 10, AND 07 27 26.

3. SEAL PENETRATIONS OF THE AIR BARRIER AND VERIFY INTEGRITY PRIOR TO COVERING WITH

OTHER MATERIALS. PENETRATION SEAL DETAILING SHALL COMPLY WITH THE REQUIREMENTS

OF THE AIR BARRIER MFR AND THE PENETRATING COMPONENT.

4. BUILDING PLANS AND SECTIONS ARE SCHEMATIC AND CONVEY GENERAL EXTENT OF THE AIR

BARRIER. PROVIDE CONTINUOUS ENCLOSURE. PLEASE NOTE THAT THE IMP WALLS OF THE

APPARATUS BAY PROVIDE THEIR OWN AIR MOISTURE/BARRIER. OTHER WALL ASSEMBLIES

REQUIRE A SEPERATE AIRMOISTURE BARRIER TO BE APPLIED.

5. AS CONSTRUCTED SURFACE AREA OF THE AIR BARRIER MUST BE CONFIRMED BY THE

CONTRACTOR FOR USE IN TESTING CALCULATIONS.

APPROXIMATE AIR BARRIER SURFACE AREAS

(INCLUDES APPARATUS BAYS)

FLOOR 30,000 SF

WALLS 19,000 SF

ROOF 30,000 SF

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:4

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

D es ig ne r

BR

ES

H

EA

R S

A-007

C he ck er

AI

R

B

AR

R

IE

R F

IR

ST

F

LO

O R

P

LA

N

3/32" = 1'-0"1 AIR BARRIER FIRST FLOOR PLAN

KEY PLAN

A B

C

SCALE:

3/32" = 1' - 0"

8' 8' 16' 24'

PLAN NORTH

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

F.F.

0"

T.O.W. AT BAY

23' - 4"

TOF

-3' - 0"

T.O.R. AT BAY

20' - 0"

T.O.W. AT ADMIN

20' - 0"

7 8 10 141 2 3 4 5 6

A-008

____________________________________________________ 3 A-008

01 FLOOR

0"

F.F.

0"

T.O.W. AT BAY

23' - 4"

T.O.W. AT ADMIN

20' - 0"

CH E DFG

A-008

F.F.

0"

T.O.W. AT ADMIN

20' - 0"

T.O.W. AT DORM

14' - 0"

ABDFGI

A-008

LOCATIONS OF AIR BARRIER

REQUIRED TO BE TESTED

LOCATIONS OF AIR BARRIER

INSTALLED, BUT NOT TESTED

AIR BARRIER

GENERAL NOTES

1. SEE A-001 FOR SYMBOLS, ABBREVIATIONS, LEGENDS AND DRAWING CONVENTIONS.

2. FOR BUILDING PRESSURE TESTING REQUIREMENTS SEE SPECIFICATION SECTION 07 05 23.

FOR AIR BARRIER REQUIREMENTS SEE SPECIFICATION SECTIONS 07 27 10, AND 07 27 26.

3. SEAL PENETRATIONS OF THE AIR BARRIER AND VERIFY INTEGRITY PRIOR TO COVERING WITH

OTHER MATERIALS. PENETRATION SEAL DETAILING SHALL COMPLY WITH THE REQUIREMENTS

OF THE AIR BARRIER MFR AND THE PENETRATING COMPONENT.

4. BUILDING PLANS AND SECTIONS ARE SCHEMATIC AND CONVEY GENERAL EXTENT OF THE AIR

BARRIER. PROVIDE CONTINUOUS ENCLOSURE. PLEASE NOTE THAT THE IMP WALLS OF THE

APPARATUS BAY PROVIDE THEIR OWN AIR MOISTURE/BARRIER. OTHER WALL ASSEMBLIES

REQUIRE A SEPERATE AIRMOISTURE BARRIER TO BE APPLIED.

5. AS CONSTRUCTED SURFACE AREA OF THE AIR BARRIER MUST BE CONFIRMED BY THE

CONTRACTOR FOR USE IN TESTING CALCULATIONS.

APPROXIMATE AIR BARRIER SURFACE AREAS

(INCLUDES APPARATUS BAYS)

FLOOR 30,000 SF

WALLS 19,000 SF

ROOF 30,000 SF

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:4

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-008

H

AL

E

AI

R B

AR

R

IE

R

B U

IL

D

I N G

S E C

TI

O

N S

3/32" = 1'-0"A-008

1 AIR BARRIER CROSS SECTION

3/32" = 1'-0"A-008

2 AIR BARRIER BUILDING SECTION AT APPARATUS BAY

3/32" = 1'-0"A-008

3 AIR BARRIER BUILDING CROSS SECTION

SCALE:

3/32" = 1' - 0"

8' 8' 16' 24'

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

1. THE YTC FIRE STATION BUILDING IS REQUIRED TO HAVE A COMPREHENSIVE AIR BARRIER. AIR BARRIER PERFORMANCE MUST BE TESTED AND CONFIRMED. SEE SPECIFICATION SECTIONS 07 05 23, 07 27 10, AND 07 27 26 FOR AIR BARRIER INSTALLATION AND TESTING REQUIREMENTS. AIR BARRIER COMPONENTS SHALL BE

INCORPORATED IN WALL SYSTEM MOCK-UP CONSTRUCTION.

2. DETAILS ON THIS SHEET ARE A GENERIC REPRESENTATION OF AIR BARRIER DETAILING AT OPENINGS IN CMU WALLS. DETAILING AND MATERIALS MAY VARY DEPENDING ON THE AIR BARRIER MANUFACTURER AND SYSTEM

SELECTED.

3. SEAL AIR BARRIER MEMBRANE PENETRATIONS CAUSED BY FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL, AND TELECOMMUNICATIONS SYSTEMS AND COMPONENTS. PENETRATIONS THROUGH FLOOR, ROOF, AND WALL ASSEMBLIES SHALL BE SEALED TO CREATE A CONTINUOUS AIR BARRIER AND MEET FIRE

RESISTANCE CRITERIA OF RATED ASSEMBLIES.

4. AIR BARRIER MEMBRANES SHALL BE INTEGRATED WITH AND SEALED TO VAPOR RETARDER MEMBRANES AT COMMON EDGES AS DETAILED AND NOTED. SEALING TAPES AND MATERIALS MUST BE SPECIFICALLY LISTED AS

COMPATIBLE WITH SURFACES IN CONTACT.

5. VERIFY INTEGRITY AND PERFORMANCE OF AIR BARRIER PRIOR TO CONCEALING THE MEMBRANE WITH OTHER

MATERIALS AND SUBSEQUENT CONSTRUCTION.

AT THROUGH WALL PENETRATIONS

SELF ADHERED SHEET MEMBRANE

COVERES ALL TRANSITIONS

BETWEEN WALL AND FLUID APPLIED

AIR/MOISTURE BARRIER

OVERLAP FLUID APPLIED AIR/MOISTURE BARRIER

A MIN OF 2" AROUND THE ROUGH OPENING ON

THE INTERIOR.

EXTERIOR

INTERIOR

NO GAP IN CORNER

WINDOW

JAMB

SASM

WRONG SILL CORRECT

FRONT VIEW CORNER DETAIL

REMOVE FIRST PIECE OF RELEASE

PAPER, COVER HORIZONTAL SILL BY

ALIGNING EDGE OF SILL AND ADHERE

INTO ROUGH OPENING ALONG SILL

AND UP JAMBS (MIN 6" ON EACH SIDE).

REMOVE SECOND

RELEASE AT THE BOTTOM

CORNERS ONTO THE

FACE OF THE WALL.

SECURE THE EDGES OF SELF ADHERED SHEET

MEMBRANE WITH MECHANICAL FASTENERS, CAP NAILS,

WITH MFR RECOMMENDED CAPS. SECURE FASTENER

ALONG THE BOTTOM OUTER EDGE OF THE SELF

ADHERED SHEET MEMBRANE AT FIXED CORNERS.

FLUID APPLIED AIR/MOISTURE BARRIER IS

APPLIED ON THE SURFACE OF CMU

ALL PENETRATIONS THROUGH

THE AIR/MOISTURE BARRIER

ARE SEALED

SEE SHEET A-601 FOR WALL TYPE ASSEMBLIES

INTERIOR

(S)

SILL LENGTH

+12 INCHES

CUT SELF ADHERED SHEET MEMBRANE AT

LEAST 12" LONGER THAN WIDTH OF ROUGH

OPENING SILL.

INTERIOR(S)

CUT SELF ADHERED SHEET

MEMBRANE AT LEAST 12" LONGER

THAN WIDTH OF ROUGH OPENING SILL.

6"

MINIMUM DO NOT STRETCH

INTERIOR

2" MIN

APPLY SEALANT BETWEEN THE BACK EDGE OF THE SILL

PAN AND THE SILL OR JAMB

APPLY SEALANT BETWEEN THE

ROUGH OPENING AND THE JAMB,

6" ABOVE THE END CAPS.

BACKER ROD MAY BE NEEDED.

APPLY SEALANT

BETWEEN THE BACK

EDGE OF END CAPS

AND JAMB.

A CONTINOUS BEAD OF SEALANT PER SILL PAN MFR GUIDLINES AND

AIR BARRIER REQUIREMENTS

SEAL AROUND THE WINDOW OPENING AT

THE INTERIOR, USING APPROVED SEALANT

AND BACKER ROD AS NECESSARY.

CUT TWO PIECES OF SELF ADHERED

SHEET MEMBRANE FOR JAMB FLASHING,

EXTENDING 1" ABOVE THE WINDOW HEAD

FLANGE AND BELOW THE BOTTOM EDGE

OF SILL FLASHING. REMOVE RELEASE

PAPER AND PRESS TIGHTLY ALONG THE

SIDES OF THE WINDOW FRAME.

INSTALL WINDOW, SQUARE WINDOW AND CENTER

IN THE WINDOW OPENING PER WINDOW MFR.

CUT A PIECE OF SELF ADHERED SHEET MEMBRANE FOR HEAD

FLASHING, WHICH EXTENDS BEYOND THE OUTER EDGES OF JAMB

FLASHINGS. REMOVE RELEASE PAPER AND INSTALL

COMPLETELY,ADHERING TO THE EXPOSED SHEATHING OR

FRAMING MEMBERS.

APPLY CONTINUOUS 5/8" THICK BEAD OF APPROVED

ADHESIVE/SEALANT SELF AHDERED SHEET

MEMBRANE BELOW BOTTOM PLATE AND 6" ON THE

SIDES, APPROX 1/2" AWAY FROM THE ROUGH

OPENING.

SEAL VERTICAL LIP OF SILL

PAN TO THE SELF

ADHERED SHEET

MEMBRANE.

6"

EXTERIOR

TAPE ALONG ALL CUTS IN THE

VAPOR-BARRIER AND TAPE ACROSS

THE HEAD OF THE WINDOW WITH

SELF ADHERED SHEET MEMBRANE.

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:5

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-009

H

AL

E

AI

R B

AR

R

IE

R

O

PE

N

IN

G D

ET

AI

L S

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

A-201

A-201

A-201

A-201

APPARATUS BAY

EQUIPMENT

WASH/

DISINFECT

EQUIPMENT

MAINTENANCE

WORKROOM

PROTECTIVE CLOTHING

LAUNDRY ROOM

SCBA

COMPRESSOR

ROOM

SCBA

MAINTENANCE

SOUTH CORR

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM

ROOM

DORM

ROOM

DORM

ROOM

RECYCLING

ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DAY/TRAINING

ROOM

RECREATION ROOM

134WOMENS

RESTROOM

FITNESS ROOM

ELECTRICAL ROOM

MECHANICAL ROOM

HAZMAT/SAFETY

OFFICE

NORTH CORR

DEPARTMENT TRAINING

ROOM

TRAINING

OFFICER

TRAINING

STORAGE

116COMPUTER

TRAINING

ROOM

CHIEF'S DORM

CHIEF'S

BATH

DEP. CHIEFS

OFFICE

CHIEF'S OFFICE

MENS

RESTROOM

CONFERENCE

ROOM

ASSISTANT

CHIEF OF FP

EMS OFFICE

FIRE INSPECTORS

OFFICE

123CAPTAINS

DORM ROOM

BATHROOM

ASSISTANT CHIEF

DORM ROOM

ASSISTANT

CHIEF

STATION

CAPTAIN

HAZMAT

EQUIPMENT/CBRNE

STORAGE

147B

LAUNDRY

ROOM

JANITORS

CLOSET

WOMENS ABA

RESTROOM

MENS ABA

RESTROOM

DISPATCH

ROOM

103AUPS ROOM

LOGISTICS

OFFICE

147A

EMT

STORAGE

147C

KITCHENETTE

103B

KITCHEN/DINING

ROOM

LOBBY

A-301

A-301

JANITORS

CLOSET

CLEAN UP ROOM

SPARE PPE STORAGE

PPE GEAR

STORAGE

C

H

MATCHLINE - ZONE B

MATCHLINE - ZONE C

M

AT

C H

LI

N

E

- Z

O N

E C

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E B

A-404

TELECOMM

ROOM

CATV ROOM

VESTIBULE

VESTIBULE

PANTRY

A-302

E

A

B

D

F

G

I

J

119 12 13

141 2 3 4 5 6

CLEAN UP

ROOM BATH

DISPATCH

BATHROOM

103C

MAINTENANCE/AGENT

STORAGE

GEN ADMIN

UNISEX BATH

UNISEX BATH

CENTRAL

CORR

A-301

A-203 A-204

A-204

A-205

A-205

A-205

VESTIBULE

VESTIBULE

12" CARPETED

PLATFORM (SEE 3/A-509)

6" CARPETED PLATFORM

(SEE 3/A-509)

VESTIBULE

CANOPY ABOVE

WEST

CORR.

STORAGE

SOUTH

CORR

SOUTH

CORR

121' - 10" 24' - 8" 117' - 4"

0'

8"

8'

0"

13' - 4" 36' - 0" 28' - 8" 36' - 0" 28' - 0"

1' - 7" 23' - 9" 17' - 3" 18' - 0" 18' - 0" 17' - 3" 23' - 9"

2'

2"

2'

2"

23' - 9" 17' - 3" 18' - 0" 18' - 0" 17' - 3" 23' - 9"

FOM

FO

M

1' - 7"

FOM

FO

M

GENERAL NOTES

1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.

2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS

TYPES ARE INDICATED ON ENLARGED PLANS.

3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.

4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.

5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,

AND EXTERIOR FINISH SCHEDULE.

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:5

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-101

H

AL

E O

VE

R

A L L

FI

R

ST

F

LO

O

R P

LA

N

3/32" = 1'-0"A-101

1 OVERALL FIRST FLOOR PLAN

PLAN NORTH

KEY PLAN

A B

C

SCALE:

3/32" = 1' - 0"

8' 8' 16' 24'

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

SCBA

COMPRESSOR

ROOM

ASSISTANT

CHIEF

STATION

CAPTAIN

UPS ROOM

KITCHENETTE

103B

7 8

C

H

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E B

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E C

A-310

A-310

E

B

D

F

G

I

J

1 2 3 4 5 6

3B

JANITORS

CLOSET

MAINTENANCE/AGENT

STORAGE

PPE GEAR

STORAGE

146A

155A

3A

A-310

177A

1B

1C

W5

W4

W8B

W8B

4'

A-310

A-510

A-510

A-510

A-311

155B

DIMS TO FACE

OF CMU

6"

121' - 10"

A-501

A-510

A-501

9'

8" 4'

0" 1'

8"

4'

8"

1'

6'

8"

3'

4"

2'

0"

3'

4" 2'

8"

3'

0"

2'

8"

3'

0"

2'

8"

3'

4"

2'

8"

4'

8" 2'

0"

3'

4"

4'

0"

2'

0"

121' - 4"

APPARATUS BAY

101L 101M 101N 101P 101Q 101R

1D

176A

101K 101J 101H 101G 101F 101E 10 1A

3' - 7" 3' - 4" 1' - 8"

14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 2' - 0"3' - 4" 3' - 5"

1' - 7" 23' - 9" 17' - 3" 18' - 0" 18' - 0" 17' - 3" 23' - 9" 2' - 3"

2'

2"

2'

2"

3'

7'

0"

6" 3' - 0" 6"

6" 3' - 0" 6"

4' - 1" 3' - 4"

1' - 2"

14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 2' - 0"3' - 4" 3' - 5"

6"

A-511

A-510

GENERAL NOTES

1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.

2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS

TYPES ARE INDICATED ON ENLARGED PLANS.

3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.

4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.

5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,

AND EXTERIOR FINISH SCHEDULE.

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:0

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-102

H

AL

E

PA

R T I

AL

F

IR

ST

F

LO

O R

P

LA

N

ZO

N

E A

1/8" = 1'-0"1 PARTIAL FIRST FLOOR PLAN - ZONE A

PLAN NORTH

SHEET KEYNOTES

KEY NOTE

1 BOLLARD, 12" DIA. STEEL PIPE, CONC. FILLED, SEE STRUCTURAL

2 DOWNSPOUT

3 TRENCH DRAIN

4 RECESSED FLOOR GRATE (4/A-510)

5 PPE GEAR STORAGE LOCKER, 3-PACK (LK-1)

KEY PLAN

A B

C

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

5'

0"

EQUIPMENT

WASH/

DISINFECT

EQUIPMENT

MAINTENANCE

WORKROOM

PROTECTIVE CLOTHING

LAUNDRY ROOM

SOUTH CORR

DAY/TRAINING

ROOM

RECREATION ROOM

WOMENS

RESTROOM

FITNESS ROOM

ELECTRICAL ROOM

MECHANICAL ROOM

HAZMAT/SAFETY

OFFICE

NORTH CORR

DEPARTMENT TRAINING

ROOM

TRAINING

OFFICER

TRAINING

STORAGE

COMPUTER

TRAINING

ROOM

CHIEF'S DORM

CHIEF'S

BATH

DEP. CHIEFS

OFFICE

CHIEF'S OFFICE

MENS

RESTROOM

CONFERENCE

ROOM

126ASSISTANT

CHIEF OF FP

EMS OFFICE

FIRE INSPECTORS

OFFICE

CAPTAINS

DORM ROOM

BATHROOM

ASSISTANT CHIEF

DORM ROOM

ASSISTANT

CHIEF

STATION

CAPTAIN

HAZMAT

EQUIPMENT/CBRNE

STORAGE

147B

LAUNDRY

ROOM

JANITORS

CLOSET

WOMENS ABA

RESTROOM

MENS ABA

RESTROOM

DISPATCH

ROOM

103A

UPS ROOM

LOGISTICS

OFFICE

147A

EMT

STORAGE

147C

KITCHENETTE

103B

LOBBY

7 8

H

MATCHLINE - ZONE B

MATCHLINE - ZONE C

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E B

M

AT

C H

LI

N

E

- Z

O N

E A

M

AT

C H

LI

N

E

- Z

O N

E B

M

AT

C H

LI

N

E

- Z

O N

E C

CLEAN UP ROOM

A-310

A-311

A-401

A-402

A-403

A-401

18' - 8" 23' - 8" 11' - 8" 6' - 6 1/2" 25' - 6 3/8" 13' - 0" 17' - 9 1/2" 24' - 6"

6'

1/

2"

5'

3/ 4"

/8

/2

E

D

F

G

I

J

119 12 13

PPE GEAR

STORAGE

DISPATCH

BATHROOM

103C

4' - 4 1/8"

2'

6"

GEN ADMIN

TELECOMM

ROOM

CATV ROOM

22' - 0" 33' - 3 1/2"

5' - 5 1/2" 25' - 0 1/2" 12' - 0" 13' - 0" 5' - 8 7/8"

31' - 4 3/8"

13' - 0" 9' - 0" 8' - 9 1/2" 24' - 6"

JANITORS

CLOSET

5 5

7B

5B

175B 175A

3B

3A

177A 177B

147B

146B

146A

VESTIBULE

VESTIBULE

CENTRAL

CORR

VESTIBULE

CLEAN UP

ROOM BATH

1A

5' - 4" 19' - 0"

5' - 4" 20' - 0"

18' - 1 7/8"

14' - 4" 4' - 0"

6' - 3" 20' - 9" 6' - 3" 20' - 8"

/2

1/ 2"

/2 " 29

18B 18D 18C

18C

18C18B

14B 14B

18C 18C

18C

18C

18A 3B

13A

18E

18E18A

18E18E

18C

18A

18A

13A

13A

18D

18D 13A

13A

18A

18E

13A13A 13A

18A

18C18C18A 13A18A18A18B 18A

14A18A

18A

18A

A-405

8'

0"

W3W6W4W3W6W4

W1

W5

W2

M.O.

6' - 8" 1' - 4"

M.O.

4' - 0"

1' - 4"

M.O.

6' - 8" 10' - 4"

M.O.

6' - 8" 1' - 4"

M.O.

4' - 0"

1' - 4"

M.O.

6' - 8" 2' - 0"

6'

1/

2"

CANOPY ABOVE

11 6

W10

W10

W10

W10

A-508

A-508

3'

3/

4"

A-501

A-501

5'

5'

" 132A

12" CARPETED

PLATFORM (SEE

3/A-509)

6" CARPETED

PLATFORM (SEE

3/A-509)

176A 176B

80' - 8"

3B

W8A

W9A

A-515

A-515

5' - 0"

STORAGE

WEST

CORR.

W5

2'

0" M

.O

6'

8"

1'

4" M

.O

4'

0"

1'

4" M

.O

6'

8"

1'

4"

5'

4" 7'

8"

6'

8"

3'

4"

7'

8"

/4

5A

F. O. CMU

24' - 8" 117' - 4"

A-512

10' - 0" 8' - 0" 8' - 6" A-510

A-510

A-510

W9A

1B

137B 137A

GENERAL NOTES

1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.

2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS

TYPES ARE INDICATED ON ENLARGED PLANS.

3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.

4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.

5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,

AND EXTERIOR FINISH SCHEDULE.

SHEET

IDENTIFICATION

D W

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

D

AT

E:

C O

N

TR

AC

T

N O

SO

L I

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SE

AT

TL

E

D

IS

TR

IC

T

E

AS

T

M

AR

G

IN

AL

W

AY

S

O U

TH

SE

AT

TL

E, W

AS

H

IN

G

TO

N

C

KD

B

Y:

US Army Corps of Engineers

AN

S I

D

FI

LE

N U

M

BE

R

PL

O

T D

AT

E

/ T

IM

E:

1 2 3 4 5

D

C

B

A FY

P N

YT

FS

M

O D

IF

IE

D H

EA

D

Q U

AR

TE

R S

FI

R

E

ST

AT

IO

N

YA

KI

M

A

TR

AI

N

IN

G

C

EN

TE

R

, W

AS

H

IN

G

TO

N

SEATTLE DISTRICT

s/

0-

-0

J

U N

E

1 8

SC

O

TT

W

. L O

N G

RTA DESIGN SUBMITTAL

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

DESIGN FILE:

W

2D W

R

6/ 1/

1:

:0

AM

C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt

BR

ES

H

EA

R S

BR

ES

H

EA

R S

A-103

H

AL

E

PA

R T I

AL

F

IR

ST

F

LO

O R

P

LA

N

ZO

N

E B

1/8" = 1'-0"1 PARTIAL FIRST FLOOR PLAN - ZONE B

SHEET KEYNOTES

KEY NOTE

1 PPE GEAR STORAGE LOCKER, 3-PACK (LK-1)

2 STACK WASHER/DRYER (GFGI)

3 RECESSED FLOOR GRATE (4/A-510)

4 FOLDING PANEL PARTITION, MANUAL, SINGLE

5 DOWNSPOUT

6 FLOOR MOUNTED BENCH

7 LADDER SEE 3/A-506

8 SHOWER BASE AND WALLS

9 PPE WASHER EXTRACTOR

10 PPE DRYING CABINET

11 PRE-FABRICATED SHOWER STALL (SEE INTERIORS)

12 RECESSED CEILING MOUNTED PROJECTOR SCREEN (CFCI)

PLAN NORTH KEY PLAN

A B

C

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.

2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS

TYPES ARE INDICATED ON ENLARGED PLANS.

3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.

4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.

5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,

AND EXTERIOR FINISH SCHEDULE.

7 8

C

A-311

SCBA

COMPRESSOR

ROOM

SCBA

MAINTENANCE

SOUTH CORR

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM

ROOM

DORM

ROOM

DORM

ROOM

RECYCLING

ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

DORM ROOM

KITCHEN/DINING

ROOM

MATCHLINE - ZONE B

MATCHLINE - ZONE CZO

N

E

A ZO

N E

B

ZO

N E

C M

AT

C

H

LI

N E

- Z O

N E

C

M

AT

C H

LI

N

E

- Z

O N

E A

5' - 4" 20' - 0" 2' - 6 1/8" 20' - 2 7/8" 10' - 0 5/8" 10' - 0 5/8" 10' - 0 5/8" 11 7/8" 10' - 8" 2' - 11" 5' - 4 7/8" 6' - 0" 12' - 7 3/4"

VESTIBULE

VESTIBULE

A

B

D

119 12 13

UNISEX BATH

UNISEX BATH

7'

3/

4" 9'

/8

9'

/8

/4

3'

5/ 8"

5'

1/

2"

SPARE PPE STORAGE

MAINTENANCE/AGENT

STORAGE

5'

1/

2" 6'

/8

8'

3/ 4"

7'

1/

4" 9'

/8

9'

/8

/2

5'

0"

10' - 6" 17' - 7 3/4" 5' - 4 7/8" 2' - 0" 8' - 1 5/8" 4' - 4 3/4" 10' - 0 5/8" 10' - 0 5/8" 10' - 8 1/4" 11' - 0 1/4" 8' - 3 7/8" 10' - 1 3/8" 25' - 3 1/4" 7' - 9 1/8"

PANTRY

2'

8"

5'

4" 4'

8"

5'

4" 4'

8"

5'

4"

9'

4" 5'

4"

4'

8" 5'

4"

4'

8" 5'

4"

3'

4"

2' - 0" 5' - 4" 4' - 8" 5' - 4" 10' - 0" 1' - 4"

146A 146B 14

142 14

168B168A164A164B 172

5C

3B

3A

3A

/1 6"

9'

/8

9'

/8

7'

5/

7/ 8"

5'

1/

2"

2' - 8" 6' - 8" 4' - 0"

18A18A

18A

18A 18A

18B

18A

18A

13A

18A 18A11

18A

18A

18A

18A

18A 18A

18A

18A

18A

18A

18A

13A

18B

18A

18A

18C

18C

13A

18A

14A14A

13A

18C 18C

18C

18C13A 18A18A18A

18A

18B

18A

13A14A 14A

13A

14A

17 12 19 15

14A 14A 14A

13A

2'

8" 5'

4"

4'

8" 5'

4"

4'

8" 5'

4"

9'

4" 5'

4"

4'

8" 5'

4"

4'

8" 5'

4"

3'

4"

132B

A-405

W7W7W7

W7

W7

W7

W7

W7

W7

W7

W7

W7

W7

W7 W7

W7

W7

W7

A-501

A-508

A-511

A-501

A-501

A-501

142' - 0"

4' - 0" 4' - 8" 4' - 0" 16' - 0" 2' - 0" 5' - 4" 2' - 0" 5' - 4" 4' - 8"

19 19

VESTIBULE

SOUTH

CORR

SOUTH

CORR

13' - 4" 36' - 0" 28' - 8" 36' - 0" 28' - 0"

15' - 1 3/4" 5' - 4 7/8" 11' - 5 3/8" 4' - 0" 4' - 0" 11' - 5 3/8" 5' - 4 7/8" 15' - 1 3/4"

4'

0"

3' - 4" 5' - 4"…