ABBREVIATIONS
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS ACCESS CONTROL SYSTEM
ACT ACOUSTICAL TILE
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
AIB AIR INFILTRATION BARRIER
ALUM ALUMINUM
ANO ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
AT/FP ANTI-TERRORISM/FORCE
PROTECTION
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRKT BRACKET
BTWN BETWEEN
BUR BUILT UP ROOF
CBU CEMENT BACKER UNIT
CDR CARD READER
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CLOSET
CLG CEILING
CLR CLEAR
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMM COMMUNICATIONS
COMP COMPENSATION
CONC CONCRETE
CONT CONTINUOUS/CONTINUE
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTR CENTER
D DRYER
DBL DOUBLE
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DR DOOR
DS DOWNSPOUT
DWG DRAWING
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
EPT EXTERIOR PAINT
EPS EXPANDED POLYSTYRENE
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FBM FACE BRICK MODULAR
FD FLOOR DRAIN
FDN FOUNDATION
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTINGUISHER CABINET
FED STD FEDERAL STANDARD
FF FINISH FLOOR
FG FINISH GRADE
FIN FINISH
FLR FLOOR
FOB FACE OF BRICK
FOC FACE OF CONCRETE
FOS FACE OF STUD FRAMING
FRR FIRE RESISTANCE RATED
FRP FIBER REINFORCED PLASTIC
FT FOOT
FTG FOOTING
HB HOSE BIB
HDPE HIGH DENSITY POLYETHYLENE
HDWD HARD WOOD
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HW-X HARDWARE SET NUMBER
HYD HYDRAULIC
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GL GRID LINE
GWB GYPSUM WALL BOARD
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IGU INSULATED GLAZING UNIT
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
KIT KITCHEN
KPL KICK PLATE
M MEN
MAT MATERIAL(S)
MAX MAXIMUM
MB MOISTURE BARRIER
MECH MECHANICAL
MTL METAL
MFR MANUFACTURER
MG MIRROR GLAZING
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MR MOISTURE RESISTANT
N/A NOT APPLICABLE
NO. NUMBER
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OA OVERALL
OBS OBSCURE GLAZING
OC ON CENTER
OCC OCCUPANT(S)
OD OUTSIDE DIAMETER
OD OVERFLOW DRAIN
OPEN'G OPENING
OPH OPPOSITE HAND
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
OWSJ OPEN WEB STEEL JOIST
PC PRECAST CONCRETE
PL PLATE
PLYWD PLYWOOD
PLAM PLASTIC LAMINATE
PNT-X PAINT FINISH COLOR
PR PAIR
PT PAINT
PT PRESERVATIVE TREATED
PTD/WR PAPER TOWEL DISPENSER &
WASTE RECEPTACLE
P&S POLE AND SHELF
R RISER RADIUS
RAF RAISED ACCESS FLOOR
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REFR REFRIGERATOR
REQD REQUIRED
RES RESILIENT
REV REVISION
RM ROOM
RO ROUGH OPENING
SAB SOUND ATTENUATION BLANKET
SASM SELF ADHERED SHEET MEMBRANE
SB SPLASH BLOCK
SCR SHOWER CURTAIN ROD
SCWD SOLID CORE WOOD DOOR
SD SOAP DISPENSER
SF SQUARE FEET
SGR SOAP/GRAB BAR COMBINATION
SH SOAP HOLDER
SHWR SHOWER
SIM SIMILAR
SIS SUSTAINABLE INFORMATION SIGN
SND SANITARY NAPKIN DISPOSER
SNTD SANITARY NAPKIN AND TAMPON
DISPENSER
SPEC SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
SSB SHOU SUGI BAN WOOD PANELING
ST STEEL
STC SOUND TRANSMISSION CLASS
STD WT STANDARD WEIGHT
STOR STORAGE
STR STAIR
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
T TREAD
T&G TONGUE AND GROOVE
TB TOWEL BAR
TD TRENCH DRAIN
TEMP TEMPERED
TFP TRANSLUCENT FIBERGLASS PANEL
THK THICKNESS
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOP TOP OF PLATE
TOS. TOP OF STEEL
TPD TOILET PAPER DISPENSER
TRD TREAD
TSCD TOILET SEAT COVER DISPENSER
TS TUBE STEEL
TYP TYPICAL
U/C UNDER COUNTER
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VR VAPOR RETARDER
VTR VENT THROUGH ROOF
W WOMEN
W/ WITH
WC WATER CLOSET
W/D CLOTHES WASHER/DRYER
WD WOOD
WNDW WINDOW
WP WATER PROOFING
WR WATER RESISTANT
WRB WEATHER RESISTANT BARRIER
WWR WELDED WIRE REINFORCEMENT
SYMBOL
L ANGLE
& AND
@ AT
# NUMBER
CENTER LINE
ARCHITECTURAL SYMBOLS ARCHITECTURAL GENERAL NOTES
SHEET NUMBERING
A-001
DISCIPLINE:
A - ARCHITECTURE
SHEET NUMBER WITHIN SERIES
A-101
SIM
VIEW CALLOUTS
DIRECTION OF VIEW
DRAWING NUMBER ON SHEET
TEXT NOTE
SHEET NUMBER WHERE SECTION
OR DETAIL IS DRAWN
A-101
SIM
DIRECTION OF VIEW
DRAWING NUMBER ON SHEET
TEXT NOTE
SHEET NUMBER WHERE
ELEVATION IS DRAWN
REGION OF DETAIL OR ENLARGED VIEW
DRAWING NUMBER ON SHEET
TEXT NOTE
SHEET NUMBER WHERE DETAIL
OR ENLARGED VIEW IS DRAWN
A-101
SIM
ANNOTATION SYMBOLS
20A WALL TYPE DESIGNATOR, SEE WALL
SCHEDULES A-601 THROUGH A-602
WINDOW MARK, SEE WINDOW
SCHEDULE A-604
LV1
LOUVER MARK, SEE LOUVER
SCHEDULE A-604
CLG: UNDERSIDE
OF STRUCTURE
ROOM NAME
ROOM NAME
ROOM NUMBER
CEILING HEIGHT OR LOCATION
DOOR MARK, SEE DOOR
SCHEDULE A-603
GL
GRID NUMBER OR LETTER
GRID LINE
SHEET KEYNOTE, REFER TO
KEYNOTE LEGEND ON SHEET
WHERE ANNOTATION IS DRAWN
DIRECTION OF PLAN NORTH,
SEE CIVIL DRAWING FOR TRUE NORTH
T.O. SLAB
0'-0"
SURFACE DESCRIPTION
FINISH ELEVATION
1. REPETITIVE FEATURES NOTED TYPICAL ON THE DRAWINGS SHALL BE COMPLETELY PROVIDED AS IF DRAWN IN FULL. REPETITIVE FEATURES NOT NOTED ON THE DRAWINGS SHALL BE COMPLETELY PROVIDED
AS IF NOTED IN FULL.
2. DIMENSIONS ON ARCHITECTURAL DRAWINGS ARE INDICATED IN FEET AND INCHES.
3. DIMENSIONS ARE DRAWN TO THE FACE OF CMU, CONCRETE AND STEEL STUDS, UNLESS NOTED OTHERWISE. DIMENSIONS ARE DRAWN TO THE CENTERLINE OF STRUCTURAL STEEL, UNLESS NOTED OTHERWISE. GRID LINES INDICATE THE FACE OF CMU AND CONCRETE AND THE CENTERLINE OF INTERIOR
COLUMNS UNLESS NOTED OTHERWISE.
4. DIMENSIONS OF MASONRY COMPONENTS ARE MODULAR. MASONRY OPENINGS ARE INDICATED WITH
MODULAR DIMENSIONS AND NOTED AS "MO".
5. EXTERNAL CORNERS ON EXPOSED CONCRETE WALLS SHALL BE CHAMFERED 3/4" TYPICAL, UNLESS
NOTED OTHERWISE.
6. REPAIR OR REPLACE SURFACES DAMAGED DURING CONSTRUCTION TO MATCH ADJACENT FINISHED CONDITION. THE CONTRACTING OFFICER SHALL DETERMINE WHEN REPLACEMENT IS REQUIRED FOR
ACCEPTABLE APPEARANCE.
7. SELECTION OF EXTERIOR MATERIALS SHALL FOLLOW COLOR AND PATTERN MATCH REQUIREMENT
INDICATED. FLASHING COLOR SHALL MATCH ADJACENT WALL OR ROOF COLOR, UNO.
8. DOORS IN STUD WALLS NOT LOCATED BY DIMENSION ON FLOOR PLANS OR DETAIL DRAWINGS SHALL BE LOCATED 6 INCHES FROM SURFACE OF ADJACENT PERPENDICULAR WALL TO ROUGH OPENING OF DOOR
FRAME.
9. DOOR AND ROOM NUMBERS SHOWN ON DRAWINGS ARE FOR CONSTRUCTION PURPOSES. VERIFY
NUMBERING SCHEME WITH CONTRACTING OFFICER AND TENANT UNIT PRIOR TO FABRICATING PERMANENT
LABELS AND SIGNAGE.
10. WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESERVATIVE TREATED WOOD.
ISOLATE PRESERVATIVE TREATED WOOD FROM METALS.
11. SIZE FIRE EXTINGUISHER CABINETS AND BRACKETS TO HOUSE ONE, NFPA 10 COMPLIANT 2-A 10-BC
EXTINGUISHER, UNLESS NOTED OTHERWISE.
12. CONTRACTOR SHALL PROVIDE APPROPRIATE SHIMMING MATERIAL (WOOD, METAL, OR OTHER AS PERMITTED BY IBC) AS REQUIRED TO BRING CONSTRUCTION WITHIN SPECIFIED TOLERANCES AND DIMENSIONS. CONTRACTOR SHALL TRIM ITEMS TO FIT AND OTHERWISE ENSURE PROPER INSTALLATION OF
WORK.
13. THE CONTRACTOR IS RESPONSIBLE FOR ADVANCED REVIEW OF THE WORK REQUIRED IN THE CONSTRUCTION DOCUMENTS AND THE REQUIREMENTS FOR EXECUTING IT PROPERLY. IF THE CONTRACTOR FINDS DISCREPANCIES IN THE CONSTRUCTION DOCUMENTS OR SPECIFICATIONS, THEN THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY AND REQUEST RESOLUTION. THE CONTRACTOR
SHALL COORDINATE THE RESOLUTION OF DISCREPANCIES IN ADVANCE OF STARTING WORK.
14. FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL, TELECOMMUNICATIONS, CIVIL, AND STRUCTURAL FEATURES OR INFORMATION SHOWN ON ARCHITECTURAL DRAWINGS IS FOR COORDINATION AND LOCATION PURPOSES ONLY. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR SPECIFIC DESIGN
INFORMATION ON COMPONENTS AND SYSTEMS.
15. REFER TO THE SPECIFICATIONS FOR INFORMATION THAT SUPPLEMENTS THESE NOTES AND OTHER
DRAWING INFORMATION.
16. ARCHITECTURAL DETAILS ARE INTENDED TO SHOW THE GENERAL CHARACTER AND EXTENT OF THE PROJECT. THEY ARE NOT INTENDED TO SHOW EVERY DETAIL OF THE WORK. DETAILS NOTED "TYPICAL"
APPLY TO SIMILAR WORK THROUGHOUT THIS BUILDING, UNO.
17. ARCHITECTURAL DRAWINGS ARE FOR INFORMATION INCLUDING, BUT NOT LIMITED TO: DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND WINDOW OPENING, NON-BEARING WALLS, CURBS, DRAINS, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES AND OTHER NONSTRUCTURAL ITEMS.
18. WHERE CONFLICTS ARE IDENTIFIED BETWEEN THE CONSTRUCTION DOCUMENTS, REFERENCED STANDARDS AND THE GOVERNING CODES, THE CONTRACTING OFFICER WILL DETERMINE WHICH SHALL GOVERN. CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER AND
RESOLVED BEFORE PROCEEDING WITH THE WORK.
19. THE CONTRACTOR SHALL VERIFY DIMENSIONS, EXISTING UTILITIES, FIXTURES AND CONDITIONS AT THE SITE. CONFLICTS BETWEEN THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE CONTRACTING OFFICER BEFORE PROCEEDING WITH THE WORK.
20. WORK SHALL COMPLY WITH IBC 2015, NFPA 101 (2015), AND UFC 3-600-01 AS DIRECTED BY UFC 1-200-01. WHEN CONFLICTS OCCUR BETWEEN UFC 3-600-01 AND OTHER CODES, STANDARDS AND CRITERIA, FOLLOW UFC 3-600-01. WHEN CONFLICTS OCCUR BETWEEN THE IBC AND NFPA 101, THE MOST
CONSERVATIVE REQUIREMENTS SHALL GOVERN.
21. PROVIDE ALL NECESSARY BLOCKING BACKING, FRAMING HANGERS OR OTHER SUPPORT FOR FIXTURES, EQUIPMENT CABINETRY, FURNISHINGS AND ANY ITEM REQUIRING THE SAME.
22. SEAL ALL PENETRATIONS THROUGH FLOORS, RATED WALLS, AND RATED CIELINGS WITH UL LISTED
ASSEMBLIES SUCH THAT FIRE AND SMOKE RATINGS ARE MAINTAINED.
12'-6"
LOCATION OF ELEVATION
MEASUREMENT
FINISH ELEVATION
AT TARGET
YD YARD
GRID LINES & CENTERLINES
EXPANSION JOINT
PLAN
NORTH
INTERIOR ELEVATION DRAWING NUMBER
PLATE NUMBER WHERE ELEVATION IS
DRAWN
DIRECTION OF VIEW
4A-101
AIR BARRIER
VAPOR RETARDER
SASM
DRAWING LINE TYPES
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:2
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-001
H
AL
E
AB
BR
EV
IA
T I
O N
S , S
YM
B O
LS
AN
D G
EN
ER
AL
N
O
TE
S
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
BUILDING AND LIFE SAFETY CODE SUMMARY
DESCRIPTIONCODE REFERENCEDESIGN ITEMTOPIC
BUILDING AND LIFE SAFETY CODE SUMMARY
DESCRIPTIONTOPIC DESIGN ITEM CODE REFERENCEINTERNATIONAL BUILDING CODE (IBC) - 2015
NATIONAL FIRE PREVENTION ASSOCIATION (NFPA) 101 “LIFE SAFETY CODE” - 2015
UFC 1-200-01 "GENERAL BUILDING REQUIREMENTS" - 20 JUNE 2016
UFC 3-600-01 “FIRE PROTECTION ENGINEERING FOR FACILITIES” - 28 NOV 2016, CHANGE 1
UFC 4-010-01 "ANTI-TERRORISM/FORCE PROTECTION (AT/FP)" - 01 OCT 2013, CHANGE 1
UFC 4-730-10 "FIRE STATIONS"
GOVERNING CODES
AND CRITERIA
OCCUPANCY (IBC) A-3 Assembly Assembly area, low density, without fixed seating.IBC Chapter 3
B Business Office and service type activities.
R-2 Residential Sleeping rooms, work related, permanent in nature (not transient lodging).
S-1 Storage Moderate hazard storage.
OCCUPANCY (NFPA101) NFPA occupancy classifications are similar to those of the IBC referenced above.Chapter 12New Assembly
New Business
New Hotel & Dormitory
Storage
Chapter 38
Chapter 28
Chapter 42
The building is designed with a mixture of separate and non-separated occupancies:
A one-hour fire barrier wall between the Apparatus Bay and the Business/Dormitory side of the facility is used to provide increased protection. Openings in this wall are 45-minute fire-rated. Separation is consistent with the provisions of Section 508.4
The Assembly/Business/Dormitory side employs the provisions of IBC Section 508.3 as non-separated occupancies. Code requirements are applied separately to each portion based on occupency group.
This building is sprinklered throughout, therefor additional fire barriers are only required where the code specifically requires them for non-exempted locations. These locations include the Dormitory Rooms (1/2 hour separation) and the Electrical room.
OCCUPANCY
SEPARATION (IBC)
IBC Section 508
Assembly, Business and Dorm Rooms
IBC 508.3
Storage (Apparatus Bays)
IBC 508.4
Construction Type II-B allows only non-combustible materials, with specific exceptions itemized in Section 603.
The primary structural frame, exterior and interior bearing walls, floor construction and associated secondary members, roof construction and associated secondary members are not required to be fire rated.
CONSTRUCTION TYPE IBC Chapter 6II-B
Using a Nonseparated approach, the most restrictive occupancy will govern the allowable floor area.
Per IBC Table 506.2, the allowable area for "A-3", Construction Type II-B, and single story is 38,000 SF. All other occupancies in this facility are less restrictive. Actual floor area is less than the allowable.
ALLOWABLE FLOOR
AREA
IBC TABLE 506.2A-3
(most restrictive occupancy)
Area modifications are not required since the allowable floor area exceeds the actual floor area of the building as designed.
MODIFIED
ALLOWABLE FLOOR
AREA
IBC 506Frontage & Sprinkler System
ACTUAL HEIGHT AND
STORIES
Tables 601 and 602 do not require fire resistance rated construction for Construction Type II B and the various occupancy groups in this facility. There is sufficient open space around the perimeter of the building to provide a fire separation distance in excess of 30 feet on all sides.
EXTERIOR WALL FIRE
RESISTANCE RATING
IBC 704.10,
705.5, Tables 601 and 602
The maximum area of unprotected or protected openings permitted in an exterior wall in any story is addressedt in IBC Table 705.8. Because the fire separation distance is greater than 30 feet on all sides, there is no limitation on the number and size of openings.
ALLOWABLE AREA
EXTERIOR OPENINGS
IBC 705.8,
Table 705.8
Per the cited UFC, all new construction facilities of Construction Type I or Type II with a floor area greater than 15,000 gross square feet must be protected by an Approved, Supervised Automatic Sprinkler System (ASASS) throughout the facility. The Fire Station falls within these criteria. The design of the sprinkler system must follow the "Area/Density Method of NFPA 13 and Table 9-3 of the UFC.
FIRE PROTECTION UFC 3-600-01,
Section 9-7.2 Table 9-3
Sprinkler System
No rating required for Construction Type II-B.FIRE RESISTANCE
RATING FOR
BUILDING ELEMENTS
IBC Table 601Primary structural frame, interior and exterior bearing walls, corridors, floor construction assembly, and roof assembly.
Not applicable, no stairways in this design.NFPA 101:
7.1.3.2.1 and 8.6.4
Stairway shafts
Dwelling units and sleeping units in buildings of Type II-B construction with ASASS are required to have 1/2 hour fire resistive separations between each other and between the units and the remainder of the building. Openings into units shall be 20 minute fire resistance rated door assemblies.
NFPA 101:
28.3.7.2 & Table 8.3.4.2
Dorm rooms
NFPA 90A:
5.3.4.3.1
Mechanical shafts
15 square feet per person, netOCCUPANT LOAD
FACTORS (NFPA)
NFPA 101
Table 7.3.1.2
Assembly, without fixed seats
100 square feet per person, gross
200 square feet per person, gross
200 square feet per person, gross; all other Storage at 500 square feet per person, gross
Business
Residential (Dorms)
Storage (garage)
The Assembly occupancy establishes the most restrictive requirements for dead-end corridors at 20 feet. The longest dead-end corridor in the building is 19'-10 1/2"
DEAD END CORRIDORS NFPA 101
12.2.5.1.3
COMMON PATH OF
TRAVEL
NFPA 101
12.2.5.1.2 28.2.5.4
The maximum travel distance to any exit is determined by occupancy. The most restrictive for any occupancy (Assembly) is 250 feet. The longest path in any occupancy is 168 feet.
TRAVEL DISTANCE TO
EXIT
NFPA 101
7.6 and Table A7.6
The maximum common path of travel distance is determined by occupancy. The most restrictive for any occupancy (Hotel & Dormitory) in this facility is 50 feet. MAX CPOT in Dorm area is 19'. MAX CPOT in assembly/business areas is 49' The next most restrictive is Assembly occupancy (maximum 50 occupants) at 75 feet. The longest common path of travel in an assembly occupancy is approximately 25 feet. The longest common path of travel in this building is approximately 49 feet.
Not applicable, single story facility with no stairs in the means of egress.CAPACITY MEANS OF
EGRESS
NFPA 101 - 7.3.3Stairways
Minimum required width is 44 inches and 0.2 inches per person. Maximum width of any corridor by number of occupants (egress from Day and Recreation Rooms is 126 persons times 0.2 inches = 26 inches. The minimum designed width of any corridor is 60 inches.
NFPA 101
7.3.4
Corridors
The min. clear width is 34 inches and 0.2 inches per person. The largest number of occupants at one door is 110 persons times 0.2 inches = 22 inches. The minimum designed width of any door is 34 inches.
NFPA 101
7.2.1.2.3
Doors
Portable fire extinguishers are not required in the business occupancy area or hazardous areas of other occupancies in accordance with UFC 3-600-01 (facility is fully protected with an automatic, supervised sprinkler system). The Apparatus Bay and equipment maintenance rooms are designated ordinary hazard areas. A single extinguisher will be located in the the kitchen as immediate protection against a range fire.
PORTABLE FIRE
EXTINGUISHERS
NFPA 101
9.7.4
NFPA 10
6.2.1
Not required in non-combustible construction without concealed spaces between floors and attic space.FIRE BLOCKING IBC - 718.2
Not required in attic and floor spaces of non-combustible construction.DRAFT STOPPING IBC - 718.4.3
Door assemblies including vision panels in 1/2 hour fire barriers require a 20 minute rating. Door assemblies in one hour fire barriers require a 45 minute rating.
DOOR ASSEMBLIES IBC
Table 716.5
Glazing assemblies for windows, side lights, and transom lights in 1/2 hour fire barriers require a 20 minute tested rating. Glazing assemblies in one hour fire barriers require a 45 minute tested rating.
GLAZING IBC
Table 716.5
Interior, Nonbearing walls construction must conform to NFPA 101 requirements (per UFC 3-600-01 3-3.1.1).
NFPA requirements shall be followed for any interior walls not forming area of occupancy separation per IBC.
NFPA 101, 8.3,
8.4, and 8.5
Interior non-bearing walls & partitions
29'-4" Single Story
Public areas of the facility are designed for compliance with ABA standards. Areas intended for use by fire department staff only have been designed for ABA compliance or are readily convertable if future uses incorporate more public access.
ARCHITECTURAL
BARRIERS ACT (ABA)
ABA Accessibility Standards
Facility is a "Primary Gathering" building due to the presence of "Billeting" (Dorm Rooms). The Apparatus Bays are considered a "Low Occupancy" portion of the building and are not required to meet ATFP criteria.
Exterior door and window glazing in all building areas except for the Apparatus Bays are required to be designed for blast loading resulting from Charge Weight II. Standoff distances are identified on the Civil drawings.
ANTITERRORISM/
FORCE PROTECTION
UFC 4-010-01
UFC 4-010-02
Dry Transformers over 112 1/2 kVA: Individual dry-type transformers installed indoors are rated more than 112 1/2 kVA rating shall be installed in a transformer room of fire-resistant construction. Wall construction for the electrical room has a fire rating of 1 hour, with walls running from F.F. to roof deck with fire stopped penetrations and appropriatly sealed to the roof deck.
NEC
450.21
Electrical Room
Fire Station = Risk Category "IV", Importance Factor I=1.5RISK CATEGORY ASCE 7-05
Per the cited UFC, other occupancies such as offices and shops must be separated from the storage area by a minimum of one-hour fire rated construction. The Apparatus Bay is separated from the remainder of the facility by a CMU wall providing at least a 1-hour rated fire barrier.
NOTE: Other storage occupancies with 8'-0" cielings are not considered "storage facilities" per UFC 3-600-01
STORAGE GROUP
SEPARATION
UFC 3-600-01,
Section 4-42.5.2.1
Fire Rated Separations
This is a mixed use facility and each occupancy group is classified per the IBC. Fire separation between occupancies must follow IBC and UFC 3-600-01 requirements. Fire resistance of interior, non-bearing partitions is compliant with NFPA 101 requirements.
ALLOWABLE HEIGHT
AND STORIES
IBC 504
Tables 504.3, 504.4
55 feet Three Stories
ACTUAL FLOOR AREA 30,027.5 GSF
Not applicable, no Mechanical shafts in this design.
SEISMIC DESIGN Yakima, WA - seismic design category "D"
APP BAY 11257
ADMIN/DORM 18750
1/2 EXT SPACE 20.5
Not Required
Not Applicable
Gross floor area is measured from exterior face to exterior face of enclosing perimeter walls. Exterior covered spaces are measured at 50 percent of actual coverage per Army standard methodology. Gross area of the building may not be consistent with floor area measured per the IBC.
The actual height and number of stories is less than the IBC allowable. No modifications to accommodate height are required.
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:2
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
D es ig ne r
BR
ES
H
EA
R S
A-002
C he ck er
LI
FE
S
AF
ET
Y
S U M
M A R
Y
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
7 8
C
H
MATCHLINE - ZONE B
MATCHLINE - ZONE C
M
AT
C H
LI
N
E
- Z
O N
E C
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E B
PROTECTIVE CLOTHING
LAUNDRY ROOM
SCBA
COMPRESSOR
ROOM
SCBA
MAINTENANCE
SOUTH CORR
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM
ROOM
DORM
ROOM
DORM
ROOM
RECYCLING
ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DAY/TRAINING
ROOM
RECREATION ROOM
WOMENS
RESTROOM
FITNESS ROOM
ELECTRICAL ROOM
MECHANICAL ROOM
HAZMAT/SAFETY
OFFICE
NORTH CORR
DEPARTMENT TRAINING
ROOM
TRAINING
OFFICER
TRAINING
STORAGE
116COMPUTER
TRAINING
ROOM
CHIEF'S DORM
CHIEF'S
BATH
DEP. CHIEFS
OFFICE
CHIEF'S OFFICE
MENS
RESTROOM
CONFERENCE
ROOM
ASSISTANT
CHIEF OF FP
EMS OFFICE
FIRE INSPECTORS
OFFICE
123CAPTAINS
DORM ROOM
BATHROOM
ASSISTANT CHIEF
DORM ROOM
ASSISTANT
CHIEF
STATION
CAPTAIN
HAZMAT
EQUIPMENT/CBRNE
STORAGE
147B
LAUNDRY
ROOM
148 JANITORS
CLOSET
WOMENS ABA
RESTROOM
MENS ABA
RESTROOM
DISPATCH
ROOM
103A
LOGISTICS
OFFICE
147A
EMT
STORAGE
147C
KITCHENETTE
103B
KITCHEN/DINING
ROOM
LOBBY
JANITORS
CLOSET
CLEAN UP ROOM
SPARE PPE STORAGE
PPE GEAR
STORAGE
E
A
B
D
F
G
I
J
119 12 13
141 2 3 4 5 6
MAINTENANCE/AGENT
STORAGE
EQUIPMENT
MAINTENANCE
WORKROOM
EQUIPMENT
WASH/
DISINFECT
TELECOMM
ROOM
CATV ROOM
GEN ADMIN
DISPATCH
BATHROOM
103C
UPS ROOM
CLEAN UP
ROOM BATH
VESTIBULE
VESTIBULE
VESTIBULE
VESTIBULE
VESTIBULE
PANTRY
APPARATUS BAY
CENTRAL
CORR
UNISEX BATH
UNISEX BATH
GENERAL NOTES
1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,
FIRE ALARM AND FIRE DETECTION SYSTEMS.
2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.
3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND
FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.
4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.
5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.
SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.
6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.
TRAVEL DISTANCE PATH
ONE HOUR FIRE BARRIER CONSTRUCTION
1/2 HOUR FIRE PARTITION CONSTRUCTION
LEGEND
SMOKE PARTITION CONSTRUCTION
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:3
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-003
H
AL
E
LI
FE
S
A F
ET
Y
PL
AN
3/32" = 1'-0"A-003
1 LIFE SAFETY PLAN
KEY PLAN
A B
C
SCALE:
3/32" = 1' - 0"
8' 8' 16' 24'
PLAN NORTH
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
GENERAL NOTES
1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,
FIRE ALARM AND FIRE DETECTION SYSTEMS.
2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.
3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND
FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.
4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.
5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.
SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.
6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.
7 8
C
H
E
B
D
F
G
I
J
1 2 3 4 5 6
M
AT
C H
LI
N
E
ZO
N E
C
M
AT
C H
LI
N
E
ZO
N E
A M
AT
C
H
LI
N E
- Z O
N E
A
M
AT
C H
LI
N
E
- Z
O N
E B
EGRESS PATH
101'-6"
10883
APPARATUS BAY
S-1 500
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
TRAVEL DISTANCE PATH
ONE HOUR FIRE BARRIER CONSTRUCTION
TOTAL OCCUPANTS EXITING
EXIT DOOR CAPACITY @ 0.2" PER PERSON
FEB
ROOM NAME & NUMBER
1/2 HOUR FIRE PARTITION CONSTRUCTION
APPARATUS BAY
S-2 500
OCCUPANCY & LOAD FACTOR
NET SQUARE FOOTAGE
OCCUPANTS
WALL MOUNTED FIRE EXTINGUISHER BRACKET
DEC = DEAD END CORRIDOR LENGTH
LEGEND
SMOKE PARTITION CONSTRUCTION
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:3
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-004
H
AL
E
EN
LA
R
G
ED
L
IF
E S A
FE
TY
P
LA
N Z O
N E
A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
PLAN NORTH
1/8" = 1'-0"A-004
1 ENLARGED LIFE SAFETY PLAN - ZONE B
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
H
E
D
F
G
I
J
119 12 13
MATCHLINE - ZONE B
MATCHLINE - ZONE C
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E B
PROTECTIVE
CLOTHING LAUNDRY
ROOM
S1 500
DAY/TRAINING
ROOM
A3 15
RECREATION ROOM
A3 15
WOMENS
RESTROOM
B 100
FITNESS ROOM
A3 15
ELECTRICAL ROOM
B 100
MECHANICAL ROOM
B 100
HAZMAT/SAFETY
OFFICE
B 100
NORTH CORR
B 100
DEPARTMENT
TRAINING ROOM
A3 15
TRAINING
OFFICER
B 100
TRAINING
STORAGE
S2 500
COMPUTER
TRAINING
ROOM
A3 15
CHIEF'S DORM
R2 50
CHIEF'S
BATH
R2 50
DEP. CHIEFS
OFFICE
B 100
CHIEF'S OFFICE
B 100
MENS
RESTROOM
B 100
CONFERENCE
ROOM
A3 15
ASSISTANT
CHIEF OF FP
B 100
EMS OFFICE
B 100
FIRE INSPECTORS
OFFICE
B 100
CAPTAINS
DORM ROOM
R2 50
BATHROOM
R2 50
ASSISTANT CHIEF
DORM ROOM
R2 50
ASSISTANT
CHIEF
B 100
STATION
CAPTAIN
B 100
HAZMAT
EQUIPMENT/CBRNE
STORAGE
147B
S1 500
LAUNDRY
ROOM
S1 500
JANITORS
CLOSET
B 100
WOMENS ABA
RESTROOM
B 100
MENS ABA
RESTROOM
B 100
DISPATCH
ROOM
103A
B 100
LOGISTICS
OFFICE
147A
B 100
EMT
STORAGE
147C
S1 500
KITCHENETTE
103B
B 100
LOBBY
B 100
JANITORS
CLOSET
B 100
CLEAN UP ROOM
S1 500
PPE GEAR
STORAGE
S1 500
EQUIPMENT
MAINTENANCE
WORKROOM
B 100
EQUIPMENT
WASH/
DISINFECT
B 100
TELECOMM
ROOM
B 100
CATV ROOM
B 100
GEN ADMIN
B 100
DISPATCH
BATHROOM
103C
B 100
UPS ROOM
B 100
CLEAN UP
ROOM BATH
S1 500
VESTIBULE
B 100
VESTIBULE
B 100
VESTIBULE
B 100
CENTRAL
CORR
B 100
RESTRICTED ACCESS DOOR FOR RESIDENT USE
ONLY. IF EXIT DEVICE IS PUSHED WITHOUT CODE,
ALARM WILL SOUND FOR 15 SECONDS BEFORE DOOR
OPENS. DURING EMERGENCIES DOOR WILL UNLOCK
AUTOMATICALLY.
EGRESS PATH 3'-0" EGRESS PATH 10'-8"
EGRESS PATH 29'-6"
EGRESS PATH 49'
EGRESS PATH
46'-4 7/8"
EGRESS PATH: 168'-0"
EGRESS PATH 140'-0"
EGRESS PATH
18'-6"
EXIT WIDTH / CAPACITY
68 INCHES : 340 OCCUPANTS
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
GENERAL NOTES
1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,
FIRE ALARM AND FIRE DETECTION SYSTEMS.
2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.
3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND
FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.
4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.
5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.
SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.
6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.
TRAVEL DISTANCE PATH
ONE HOUR FIRE BARRIER CONSTRUCTION
TOTAL OCCUPANTS EXITING
EXIT DOOR CAPACITY @ 0.2" PER PERSON
FEB
ROOM NAME & NUMBER
1/2 HOUR FIRE PARTITION CONSTRUCTION
APPARATUS BAY
S-2 500
OCCUPANCY & LOAD FACTOR
NET SQUARE FOOTAGE
OCCUPANTS
WALL MOUNTED FIRE EXTINGUISHER BRACKET
DEC = DEAD END CORRIDOR LENGTH
LEGEND
SMOKE PARTITION CONSTRUCTION
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:3
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-005
H
AL
E
EN
LA
R
G
ED
L
IF
E S A
FE
TY
P
LA
N Z O
N E
B
1/8" = 1'-0"A-005
1 ENLARGED LIFE SAFETY PLAN - ZONE B
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
PLAN NORTH
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
A
B
D
119 12 13
MATCHLINE - ZONE B
MATCHLINE - ZONE C
M
AT
C H
LI
N
E
- Z
O N
E C
M
AT
C H
LI
N
E
- Z
O N
E A
SCBA
COMPRESSOR
ROOM
S1 500
SCBA
MAINTENANCE
S1 500
SOUTH CORR
B 100
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM
ROOM
R2 50
DORM
ROOM
R2 50
DORM
ROOM
R2 50
RECYCLING
ROOM
S1 500
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
DORM ROOM
R2 50
KITCHEN/DINING
ROOM
A3 15
SPARE PPE
STORAGE
S1 500
MAINTENANCE/AGENT
STORAGE
S1 500
VESTIBULE
B 100
VESTIBULE
B 100
PANTRY
S2 500
UNISEX BATH
B 100
UNISEX BATH
B 100
EGRESS PATH 3'-0"
EGRESS PATH 10'-8"
EGRESS PATH: 140'-0"
EGRESS PATH
37'-8 1/8"
EGRESS PATH
18'-6"
EGRESS PATH: 102'-0 1/2"
FEB
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
EXIT WIDTH / CAPACITY
34 INCHES : 170 OCCUPANTS
GENERAL NOTES
1. SEE FIRE ALARM AND FIRE PROTECTION DRAWINGS FOR AUTOMATIC SPRINKER,
FIRE ALARM AND FIRE DETECTION SYSTEMS.
2. SEE ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING AND EXIT LIGHTING INFORMATION.
3. SEE DOOR (A-603) AND WINDOW (A-604) SCHEDULES FOR LISTING OF FIRE RATED DOORS AND
FRAMES WITH REQUIRED MINIMUM PROTECTION RATING.
4. SEE SHEET A-002 FOR SUMMARY OF BUILDING CODE AND LIFE SAFETY CODE ANALYSIS.
5. FIRE EXTINGUISHER CABINET AND BRACKET LOCATIONS SHOWN ARE SCHEMATIC.
SEE FLOOR PLAN DRAWINGS FOR DETAILED LOCATIONS.
6. SEE FLOOR PLANS AND WALL TYPE SCHEDULES FOR FIRE RESISTIVE WALL ASSEMBLIES.
TRAVEL DISTANCE PATH
ONE HOUR FIRE BARRIER CONSTRUCTION
TOTAL OCCUPANTS EXITING
EXIT DOOR CAPACITY @ 0.2" PER PERSON
FEB
ROOM NAME & NUMBER
1/2 HOUR FIRE PARTITION CONSTRUCTION
APPARATUS BAY
S-2 500
OCCUPANCY & LOAD FACTOR
NET SQUARE FOOTAGE
OCCUPANTS
WALL MOUNTED FIRE EXTINGUISHER BRACKET
DEC = DEAD END CORRIDOR LENGTH
LEGEND
SMOKE PARTITION CONSTRUCTION
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:4
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-006
H
AL
E
EN
LA
R
G
ED
L
IF
E S A
FE
TY
P
LA
N Z O
N E
C
1/8" = 1'-0"A-006
1 ENLARGED LIFE SAFETY PLAN - ZONE C
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
PLAN NORTH
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
H
E
A
B
D
F
G
I
J
119 12 13
141 2 3 4 5 6
A-008
A-008
A-008
LOCATIONS OF AIR BARRIER
REQUIRED TO BE TESTED
LOCATIONS OF AIR BARRIER
INSTALLED, BUT NOT TESTED
AIR BARRIER
GENERAL NOTES
1. SEE A-001 FOR SYMBOLS, ABBREVIATIONS, LEGENDS AND DRAWING CONVENTIONS.
2. FOR BUILDING PRESSURE TESTING REQUIREMENTS SEE SPECIFICATION SECTION 07 05 23.
FOR AIR BARRIER REQUIREMENTS SEE SPECIFICATION SECTIONS 07 27 10, AND 07 27 26.
3. SEAL PENETRATIONS OF THE AIR BARRIER AND VERIFY INTEGRITY PRIOR TO COVERING WITH
OTHER MATERIALS. PENETRATION SEAL DETAILING SHALL COMPLY WITH THE REQUIREMENTS
OF THE AIR BARRIER MFR AND THE PENETRATING COMPONENT.
4. BUILDING PLANS AND SECTIONS ARE SCHEMATIC AND CONVEY GENERAL EXTENT OF THE AIR
BARRIER. PROVIDE CONTINUOUS ENCLOSURE. PLEASE NOTE THAT THE IMP WALLS OF THE
APPARATUS BAY PROVIDE THEIR OWN AIR MOISTURE/BARRIER. OTHER WALL ASSEMBLIES
REQUIRE A SEPERATE AIRMOISTURE BARRIER TO BE APPLIED.
5. AS CONSTRUCTED SURFACE AREA OF THE AIR BARRIER MUST BE CONFIRMED BY THE
CONTRACTOR FOR USE IN TESTING CALCULATIONS.
APPROXIMATE AIR BARRIER SURFACE AREAS
(INCLUDES APPARATUS BAYS)
FLOOR 30,000 SF
WALLS 19,000 SF
ROOF 30,000 SF
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:4
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
D es ig ne r
BR
ES
H
EA
R S
A-007
C he ck er
AI
R
B
AR
R
IE
R F
IR
ST
F
LO
O R
P
LA
N
3/32" = 1'-0"1 AIR BARRIER FIRST FLOOR PLAN
KEY PLAN
A B
C
SCALE:
3/32" = 1' - 0"
8' 8' 16' 24'
PLAN NORTH
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
F.F.
0"
T.O.W. AT BAY
23' - 4"
TOF
-3' - 0"
T.O.R. AT BAY
20' - 0"
T.O.W. AT ADMIN
20' - 0"
7 8 10 141 2 3 4 5 6
A-008
____________________________________________________ 3 A-008
01 FLOOR
0"
F.F.
0"
T.O.W. AT BAY
23' - 4"
T.O.W. AT ADMIN
20' - 0"
CH E DFG
A-008
F.F.
0"
T.O.W. AT ADMIN
20' - 0"
T.O.W. AT DORM
14' - 0"
ABDFGI
A-008
LOCATIONS OF AIR BARRIER
REQUIRED TO BE TESTED
LOCATIONS OF AIR BARRIER
INSTALLED, BUT NOT TESTED
AIR BARRIER
GENERAL NOTES
1. SEE A-001 FOR SYMBOLS, ABBREVIATIONS, LEGENDS AND DRAWING CONVENTIONS.
2. FOR BUILDING PRESSURE TESTING REQUIREMENTS SEE SPECIFICATION SECTION 07 05 23.
FOR AIR BARRIER REQUIREMENTS SEE SPECIFICATION SECTIONS 07 27 10, AND 07 27 26.
3. SEAL PENETRATIONS OF THE AIR BARRIER AND VERIFY INTEGRITY PRIOR TO COVERING WITH
OTHER MATERIALS. PENETRATION SEAL DETAILING SHALL COMPLY WITH THE REQUIREMENTS
OF THE AIR BARRIER MFR AND THE PENETRATING COMPONENT.
4. BUILDING PLANS AND SECTIONS ARE SCHEMATIC AND CONVEY GENERAL EXTENT OF THE AIR
BARRIER. PROVIDE CONTINUOUS ENCLOSURE. PLEASE NOTE THAT THE IMP WALLS OF THE
APPARATUS BAY PROVIDE THEIR OWN AIR MOISTURE/BARRIER. OTHER WALL ASSEMBLIES
REQUIRE A SEPERATE AIRMOISTURE BARRIER TO BE APPLIED.
5. AS CONSTRUCTED SURFACE AREA OF THE AIR BARRIER MUST BE CONFIRMED BY THE
CONTRACTOR FOR USE IN TESTING CALCULATIONS.
APPROXIMATE AIR BARRIER SURFACE AREAS
(INCLUDES APPARATUS BAYS)
FLOOR 30,000 SF
WALLS 19,000 SF
ROOF 30,000 SF
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:4
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-008
H
AL
E
AI
R B
AR
R
IE
R
B U
IL
D
I N G
S E C
TI
O
N S
3/32" = 1'-0"A-008
1 AIR BARRIER CROSS SECTION
3/32" = 1'-0"A-008
2 AIR BARRIER BUILDING SECTION AT APPARATUS BAY
3/32" = 1'-0"A-008
3 AIR BARRIER BUILDING CROSS SECTION
SCALE:
3/32" = 1' - 0"
8' 8' 16' 24'
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
1. THE YTC FIRE STATION BUILDING IS REQUIRED TO HAVE A COMPREHENSIVE AIR BARRIER. AIR BARRIER PERFORMANCE MUST BE TESTED AND CONFIRMED. SEE SPECIFICATION SECTIONS 07 05 23, 07 27 10, AND 07 27 26 FOR AIR BARRIER INSTALLATION AND TESTING REQUIREMENTS. AIR BARRIER COMPONENTS SHALL BE
INCORPORATED IN WALL SYSTEM MOCK-UP CONSTRUCTION.
2. DETAILS ON THIS SHEET ARE A GENERIC REPRESENTATION OF AIR BARRIER DETAILING AT OPENINGS IN CMU WALLS. DETAILING AND MATERIALS MAY VARY DEPENDING ON THE AIR BARRIER MANUFACTURER AND SYSTEM
SELECTED.
3. SEAL AIR BARRIER MEMBRANE PENETRATIONS CAUSED BY FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL, AND TELECOMMUNICATIONS SYSTEMS AND COMPONENTS. PENETRATIONS THROUGH FLOOR, ROOF, AND WALL ASSEMBLIES SHALL BE SEALED TO CREATE A CONTINUOUS AIR BARRIER AND MEET FIRE
RESISTANCE CRITERIA OF RATED ASSEMBLIES.
4. AIR BARRIER MEMBRANES SHALL BE INTEGRATED WITH AND SEALED TO VAPOR RETARDER MEMBRANES AT COMMON EDGES AS DETAILED AND NOTED. SEALING TAPES AND MATERIALS MUST BE SPECIFICALLY LISTED AS
COMPATIBLE WITH SURFACES IN CONTACT.
5. VERIFY INTEGRITY AND PERFORMANCE OF AIR BARRIER PRIOR TO CONCEALING THE MEMBRANE WITH OTHER
MATERIALS AND SUBSEQUENT CONSTRUCTION.
AT THROUGH WALL PENETRATIONS
SELF ADHERED SHEET MEMBRANE
COVERES ALL TRANSITIONS
BETWEEN WALL AND FLUID APPLIED
AIR/MOISTURE BARRIER
OVERLAP FLUID APPLIED AIR/MOISTURE BARRIER
A MIN OF 2" AROUND THE ROUGH OPENING ON
THE INTERIOR.
EXTERIOR
INTERIOR
NO GAP IN CORNER
WINDOW
JAMB
SASM
WRONG SILL CORRECT
FRONT VIEW CORNER DETAIL
REMOVE FIRST PIECE OF RELEASE
PAPER, COVER HORIZONTAL SILL BY
ALIGNING EDGE OF SILL AND ADHERE
INTO ROUGH OPENING ALONG SILL
AND UP JAMBS (MIN 6" ON EACH SIDE).
REMOVE SECOND
RELEASE AT THE BOTTOM
CORNERS ONTO THE
FACE OF THE WALL.
SECURE THE EDGES OF SELF ADHERED SHEET
MEMBRANE WITH MECHANICAL FASTENERS, CAP NAILS,
WITH MFR RECOMMENDED CAPS. SECURE FASTENER
ALONG THE BOTTOM OUTER EDGE OF THE SELF
ADHERED SHEET MEMBRANE AT FIXED CORNERS.
FLUID APPLIED AIR/MOISTURE BARRIER IS
APPLIED ON THE SURFACE OF CMU
ALL PENETRATIONS THROUGH
THE AIR/MOISTURE BARRIER
ARE SEALED
SEE SHEET A-601 FOR WALL TYPE ASSEMBLIES
INTERIOR
(S)
SILL LENGTH
+12 INCHES
CUT SELF ADHERED SHEET MEMBRANE AT
LEAST 12" LONGER THAN WIDTH OF ROUGH
OPENING SILL.
INTERIOR(S)
CUT SELF ADHERED SHEET
MEMBRANE AT LEAST 12" LONGER
THAN WIDTH OF ROUGH OPENING SILL.
6"
MINIMUM DO NOT STRETCH
INTERIOR
2" MIN
APPLY SEALANT BETWEEN THE BACK EDGE OF THE SILL
PAN AND THE SILL OR JAMB
APPLY SEALANT BETWEEN THE
ROUGH OPENING AND THE JAMB,
6" ABOVE THE END CAPS.
BACKER ROD MAY BE NEEDED.
APPLY SEALANT
BETWEEN THE BACK
EDGE OF END CAPS
AND JAMB.
A CONTINOUS BEAD OF SEALANT PER SILL PAN MFR GUIDLINES AND
AIR BARRIER REQUIREMENTS
SEAL AROUND THE WINDOW OPENING AT
THE INTERIOR, USING APPROVED SEALANT
AND BACKER ROD AS NECESSARY.
CUT TWO PIECES OF SELF ADHERED
SHEET MEMBRANE FOR JAMB FLASHING,
EXTENDING 1" ABOVE THE WINDOW HEAD
FLANGE AND BELOW THE BOTTOM EDGE
OF SILL FLASHING. REMOVE RELEASE
PAPER AND PRESS TIGHTLY ALONG THE
SIDES OF THE WINDOW FRAME.
INSTALL WINDOW, SQUARE WINDOW AND CENTER
IN THE WINDOW OPENING PER WINDOW MFR.
CUT A PIECE OF SELF ADHERED SHEET MEMBRANE FOR HEAD
FLASHING, WHICH EXTENDS BEYOND THE OUTER EDGES OF JAMB
FLASHINGS. REMOVE RELEASE PAPER AND INSTALL
COMPLETELY,ADHERING TO THE EXPOSED SHEATHING OR
FRAMING MEMBERS.
APPLY CONTINUOUS 5/8" THICK BEAD OF APPROVED
ADHESIVE/SEALANT SELF AHDERED SHEET
MEMBRANE BELOW BOTTOM PLATE AND 6" ON THE
SIDES, APPROX 1/2" AWAY FROM THE ROUGH
OPENING.
SEAL VERTICAL LIP OF SILL
PAN TO THE SELF
ADHERED SHEET
MEMBRANE.
6"
EXTERIOR
TAPE ALONG ALL CUTS IN THE
VAPOR-BARRIER AND TAPE ACROSS
THE HEAD OF THE WINDOW WITH
SELF ADHERED SHEET MEMBRANE.
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:5
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-009
H
AL
E
AI
R B
AR
R
IE
R
O
PE
N
IN
G D
ET
AI
L S
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
A-201
A-201
A-201
A-201
APPARATUS BAY
EQUIPMENT
WASH/
DISINFECT
EQUIPMENT
MAINTENANCE
WORKROOM
PROTECTIVE CLOTHING
LAUNDRY ROOM
SCBA
COMPRESSOR
ROOM
SCBA
MAINTENANCE
SOUTH CORR
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM
ROOM
DORM
ROOM
DORM
ROOM
RECYCLING
ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DAY/TRAINING
ROOM
RECREATION ROOM
134WOMENS
RESTROOM
FITNESS ROOM
ELECTRICAL ROOM
MECHANICAL ROOM
HAZMAT/SAFETY
OFFICE
NORTH CORR
DEPARTMENT TRAINING
ROOM
TRAINING
OFFICER
TRAINING
STORAGE
116COMPUTER
TRAINING
ROOM
CHIEF'S DORM
CHIEF'S
BATH
DEP. CHIEFS
OFFICE
CHIEF'S OFFICE
MENS
RESTROOM
CONFERENCE
ROOM
ASSISTANT
CHIEF OF FP
EMS OFFICE
FIRE INSPECTORS
OFFICE
123CAPTAINS
DORM ROOM
BATHROOM
ASSISTANT CHIEF
DORM ROOM
ASSISTANT
CHIEF
STATION
CAPTAIN
HAZMAT
EQUIPMENT/CBRNE
STORAGE
147B
LAUNDRY
ROOM
JANITORS
CLOSET
WOMENS ABA
RESTROOM
MENS ABA
RESTROOM
DISPATCH
ROOM
103AUPS ROOM
LOGISTICS
OFFICE
147A
EMT
STORAGE
147C
KITCHENETTE
103B
KITCHEN/DINING
ROOM
LOBBY
A-301
A-301
JANITORS
CLOSET
CLEAN UP ROOM
SPARE PPE STORAGE
PPE GEAR
STORAGE
C
H
MATCHLINE - ZONE B
MATCHLINE - ZONE C
M
AT
C H
LI
N
E
- Z
O N
E C
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E B
A-404
TELECOMM
ROOM
CATV ROOM
VESTIBULE
VESTIBULE
PANTRY
A-302
E
A
B
D
F
G
I
J
119 12 13
141 2 3 4 5 6
CLEAN UP
ROOM BATH
DISPATCH
BATHROOM
103C
MAINTENANCE/AGENT
STORAGE
GEN ADMIN
UNISEX BATH
UNISEX BATH
CENTRAL
CORR
A-301
A-203 A-204
A-204
A-205
A-205
A-205
VESTIBULE
VESTIBULE
12" CARPETED
PLATFORM (SEE 3/A-509)
6" CARPETED PLATFORM
(SEE 3/A-509)
VESTIBULE
CANOPY ABOVE
WEST
CORR.
STORAGE
SOUTH
CORR
SOUTH
CORR
121' - 10" 24' - 8" 117' - 4"
0'
8"
8'
0"
13' - 4" 36' - 0" 28' - 8" 36' - 0" 28' - 0"
1' - 7" 23' - 9" 17' - 3" 18' - 0" 18' - 0" 17' - 3" 23' - 9"
2'
2"
2'
2"
23' - 9" 17' - 3" 18' - 0" 18' - 0" 17' - 3" 23' - 9"
FOM
FO
M
1' - 7"
FOM
FO
M
GENERAL NOTES
1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.
2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS
TYPES ARE INDICATED ON ENLARGED PLANS.
3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.
4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.
5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,
AND EXTERIOR FINISH SCHEDULE.
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:5
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-101
H
AL
E O
VE
R
A L L
FI
R
ST
F
LO
O
R P
LA
N
3/32" = 1'-0"A-101
1 OVERALL FIRST FLOOR PLAN
PLAN NORTH
KEY PLAN
A B
C
SCALE:
3/32" = 1' - 0"
8' 8' 16' 24'
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
SCBA
COMPRESSOR
ROOM
ASSISTANT
CHIEF
STATION
CAPTAIN
UPS ROOM
KITCHENETTE
103B
7 8
C
H
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E B
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E C
A-310
A-310
E
B
D
F
G
I
J
1 2 3 4 5 6
3B
JANITORS
CLOSET
MAINTENANCE/AGENT
STORAGE
PPE GEAR
STORAGE
146A
155A
3A
A-310
177A
1B
1C
W5
W4
W8B
W8B
4'
A-310
A-510
A-510
A-510
A-311
155B
DIMS TO FACE
OF CMU
6"
121' - 10"
A-501
A-510
A-501
9'
8" 4'
0" 1'
8"
4'
8"
1'
6'
8"
3'
4"
2'
0"
3'
4" 2'
8"
3'
0"
2'
8"
3'
0"
2'
8"
3'
4"
2'
8"
4'
8" 2'
0"
3'
4"
4'
0"
2'
0"
121' - 4"
APPARATUS BAY
101L 101M 101N 101P 101Q 101R
1D
176A
101K 101J 101H 101G 101F 101E 10 1A
3' - 7" 3' - 4" 1' - 8"
14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 2' - 0"3' - 4" 3' - 5"
1' - 7" 23' - 9" 17' - 3" 18' - 0" 18' - 0" 17' - 3" 23' - 9" 2' - 3"
2'
2"
2'
2"
3'
7'
0"
6" 3' - 0" 6"
6" 3' - 0" 6"
4' - 1" 3' - 4"
1' - 2"
14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 2' - 0"3' - 4" 3' - 5"
6"
A-511
A-510
GENERAL NOTES
1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.
2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS
TYPES ARE INDICATED ON ENLARGED PLANS.
3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.
4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.
5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,
AND EXTERIOR FINISH SCHEDULE.
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:0
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-102
H
AL
E
PA
R T I
AL
F
IR
ST
F
LO
O R
P
LA
N
ZO
N
E A
1/8" = 1'-0"1 PARTIAL FIRST FLOOR PLAN - ZONE A
PLAN NORTH
SHEET KEYNOTES
KEY NOTE
1 BOLLARD, 12" DIA. STEEL PIPE, CONC. FILLED, SEE STRUCTURAL
2 DOWNSPOUT
3 TRENCH DRAIN
4 RECESSED FLOOR GRATE (4/A-510)
5 PPE GEAR STORAGE LOCKER, 3-PACK (LK-1)
KEY PLAN
A B
C
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
5'
0"
EQUIPMENT
WASH/
DISINFECT
EQUIPMENT
MAINTENANCE
WORKROOM
PROTECTIVE CLOTHING
LAUNDRY ROOM
SOUTH CORR
DAY/TRAINING
ROOM
RECREATION ROOM
WOMENS
RESTROOM
FITNESS ROOM
ELECTRICAL ROOM
MECHANICAL ROOM
HAZMAT/SAFETY
OFFICE
NORTH CORR
DEPARTMENT TRAINING
ROOM
TRAINING
OFFICER
TRAINING
STORAGE
COMPUTER
TRAINING
ROOM
CHIEF'S DORM
CHIEF'S
BATH
DEP. CHIEFS
OFFICE
CHIEF'S OFFICE
MENS
RESTROOM
CONFERENCE
ROOM
126ASSISTANT
CHIEF OF FP
EMS OFFICE
FIRE INSPECTORS
OFFICE
CAPTAINS
DORM ROOM
BATHROOM
ASSISTANT CHIEF
DORM ROOM
ASSISTANT
CHIEF
STATION
CAPTAIN
HAZMAT
EQUIPMENT/CBRNE
STORAGE
147B
LAUNDRY
ROOM
JANITORS
CLOSET
WOMENS ABA
RESTROOM
MENS ABA
RESTROOM
DISPATCH
ROOM
103A
UPS ROOM
LOGISTICS
OFFICE
147A
EMT
STORAGE
147C
KITCHENETTE
103B
LOBBY
7 8
H
MATCHLINE - ZONE B
MATCHLINE - ZONE C
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E B
M
AT
C H
LI
N
E
- Z
O N
E A
M
AT
C H
LI
N
E
- Z
O N
E B
M
AT
C H
LI
N
E
- Z
O N
E C
CLEAN UP ROOM
A-310
A-311
A-401
A-402
A-403
A-401
18' - 8" 23' - 8" 11' - 8" 6' - 6 1/2" 25' - 6 3/8" 13' - 0" 17' - 9 1/2" 24' - 6"
6'
1/
2"
5'
3/ 4"
/8
/2
E
D
F
G
I
J
119 12 13
PPE GEAR
STORAGE
DISPATCH
BATHROOM
103C
4' - 4 1/8"
2'
6"
GEN ADMIN
TELECOMM
ROOM
CATV ROOM
22' - 0" 33' - 3 1/2"
5' - 5 1/2" 25' - 0 1/2" 12' - 0" 13' - 0" 5' - 8 7/8"
31' - 4 3/8"
13' - 0" 9' - 0" 8' - 9 1/2" 24' - 6"
JANITORS
CLOSET
5 5
7B
5B
175B 175A
3B
3A
177A 177B
147B
146B
146A
VESTIBULE
VESTIBULE
CENTRAL
CORR
VESTIBULE
CLEAN UP
ROOM BATH
1A
5' - 4" 19' - 0"
5' - 4" 20' - 0"
18' - 1 7/8"
14' - 4" 4' - 0"
6' - 3" 20' - 9" 6' - 3" 20' - 8"
/2
1/ 2"
/2 " 29
18B 18D 18C
18C
18C18B
14B 14B
18C 18C
18C
18C
18A 3B
13A
18E
18E18A
18E18E
18C
18A
18A
13A
13A
18D
18D 13A
13A
18A
18E
13A13A 13A
18A
18C18C18A 13A18A18A18B 18A
14A18A
18A
18A
A-405
8'
0"
W3W6W4W3W6W4
W1
W5
W2
M.O.
6' - 8" 1' - 4"
M.O.
4' - 0"
1' - 4"
M.O.
6' - 8" 10' - 4"
M.O.
6' - 8" 1' - 4"
M.O.
4' - 0"
1' - 4"
M.O.
6' - 8" 2' - 0"
6'
1/
2"
CANOPY ABOVE
11 6
W10
W10
W10
W10
A-508
A-508
3'
3/
4"
A-501
A-501
5'
5'
" 132A
12" CARPETED
PLATFORM (SEE
3/A-509)
6" CARPETED
PLATFORM (SEE
3/A-509)
176A 176B
80' - 8"
3B
W8A
W9A
A-515
A-515
5' - 0"
STORAGE
WEST
CORR.
W5
2'
0" M
.O
6'
8"
1'
4" M
.O
4'
0"
1'
4" M
.O
6'
8"
1'
4"
5'
4" 7'
8"
6'
8"
3'
4"
7'
8"
/4
5A
F. O. CMU
24' - 8" 117' - 4"
A-512
10' - 0" 8' - 0" 8' - 6" A-510
A-510
A-510
W9A
1B
137B 137A
GENERAL NOTES
1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.
2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS
TYPES ARE INDICATED ON ENLARGED PLANS.
3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.
4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.
5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,
AND EXTERIOR FINISH SCHEDULE.
SHEET
IDENTIFICATION
D W
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
D
AT
E:
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
SE
AT
TL
E
D
IS
TR
IC
T
E
AS
T
M
AR
G
IN
AL
W
AY
S
O U
TH
SE
AT
TL
E, W
AS
H
IN
G
TO
N
C
KD
B
Y:
US Army Corps of Engineers
AN
S I
D
FI
LE
N U
M
BE
R
PL
O
T D
AT
E
/ T
IM
E:
1 2 3 4 5
D
C
B
A FY
P N
YT
FS
M
O D
IF
IE
D H
EA
D
Q U
AR
TE
R S
FI
R
E
ST
AT
IO
N
YA
KI
M
A
TR
AI
N
IN
G
C
EN
TE
R
, W
AS
H
IN
G
TO
N
SEATTLE DISTRICT
s/
0-
-0
J
U N
E
1 8
SC
O
TT
W
. L O
N G
RTA DESIGN SUBMITTAL
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
DESIGN FILE:
W
2D W
R
6/ 1/
1:
:0
AM
C:\Users\G3ENEBS9\Documents\FY18_PN55199_YTFS_Architectural_CENTRAL_G3ENEBS9.rvt
BR
ES
H
EA
R S
BR
ES
H
EA
R S
A-103
H
AL
E
PA
R T I
AL
F
IR
ST
F
LO
O R
P
LA
N
ZO
N
E B
1/8" = 1'-0"1 PARTIAL FIRST FLOOR PLAN - ZONE B
SHEET KEYNOTES
KEY NOTE
1 PPE GEAR STORAGE LOCKER, 3-PACK (LK-1)
2 STACK WASHER/DRYER (GFGI)
3 RECESSED FLOOR GRATE (4/A-510)
4 FOLDING PANEL PARTITION, MANUAL, SINGLE
5 DOWNSPOUT
6 FLOOR MOUNTED BENCH
7 LADDER SEE 3/A-506
8 SHOWER BASE AND WALLS
9 PPE WASHER EXTRACTOR
10 PPE DRYING CABINET
11 PRE-FABRICATED SHOWER STALL (SEE INTERIORS)
12 RECESSED CEILING MOUNTED PROJECTOR SCREEN (CFCI)
PLAN NORTH KEY PLAN
A B
C
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
1. SEE SHEET A-001 FOR DIMENSIONAL NOTES.
2. SEE A-601 AND A-602 FOR WALL TYPE SCHEDULES. SOME WALLS
TYPES ARE INDICATED ON ENLARGED PLANS.
3. SEE STRUCTURAL DRAWINGS FOR MASONRY DETAILS.
4. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATIONS.
5. SEE A-603 FOR DOOR SCHEDULE AND A-604 FOR WINDOW, LOUVER,
AND EXTERIOR FINISH SCHEDULE.
7 8
C
A-311
SCBA
COMPRESSOR
ROOM
SCBA
MAINTENANCE
SOUTH CORR
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM
ROOM
DORM
ROOM
DORM
ROOM
RECYCLING
ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
DORM ROOM
KITCHEN/DINING
ROOM
MATCHLINE - ZONE B
MATCHLINE - ZONE CZO
N
E
A ZO
N E
B
ZO
N E
C M
AT
C
H
LI
N E
- Z O
N E
C
M
AT
C H
LI
N
E
- Z
O N
E A
5' - 4" 20' - 0" 2' - 6 1/8" 20' - 2 7/8" 10' - 0 5/8" 10' - 0 5/8" 10' - 0 5/8" 11 7/8" 10' - 8" 2' - 11" 5' - 4 7/8" 6' - 0" 12' - 7 3/4"
VESTIBULE
VESTIBULE
A
B
D
119 12 13
UNISEX BATH
UNISEX BATH
7'
3/
4" 9'
/8
9'
/8
/4
3'
5/ 8"
5'
1/
2"
SPARE PPE STORAGE
MAINTENANCE/AGENT
STORAGE
5'
1/
2" 6'
/8
8'
3/ 4"
7'
1/
4" 9'
/8
9'
/8
/2
5'
0"
10' - 6" 17' - 7 3/4" 5' - 4 7/8" 2' - 0" 8' - 1 5/8" 4' - 4 3/4" 10' - 0 5/8" 10' - 0 5/8" 10' - 8 1/4" 11' - 0 1/4" 8' - 3 7/8" 10' - 1 3/8" 25' - 3 1/4" 7' - 9 1/8"
PANTRY
2'
8"
5'
4" 4'
8"
5'
4" 4'
8"
5'
4"
9'
4" 5'
4"
4'
8" 5'
4"
4'
8" 5'
4"
3'
4"
2' - 0" 5' - 4" 4' - 8" 5' - 4" 10' - 0" 1' - 4"
146A 146B 14
142 14
168B168A164A164B 172
5C
3B
3A
3A
/1 6"
9'
/8
9'
/8
7'
5/
7/ 8"
5'
1/
2"
2' - 8" 6' - 8" 4' - 0"
18A18A
18A
18A 18A
18B
18A
18A
13A
18A 18A11
18A
18A
18A
18A
18A 18A
18A
18A
18A
18A
18A
13A
18B
18A
18A
18C
18C
13A
18A
14A14A
13A
18C 18C
18C
18C13A 18A18A18A
18A
18B
18A
13A14A 14A
13A
14A
17 12 19 15
14A 14A 14A
13A
2'
8" 5'
4"
4'
8" 5'
4"
4'
8" 5'
4"
9'
4" 5'
4"
4'
8" 5'
4"
4'
8" 5'
4"
3'
4"
132B
A-405
W7W7W7
W7
W7
W7
W7
W7
W7
W7
W7
W7
W7
W7 W7
W7
W7
W7
A-501
A-508
A-511
A-501
A-501
A-501
142' - 0"
4' - 0" 4' - 8" 4' - 0" 16' - 0" 2' - 0" 5' - 4" 2' - 0" 5' - 4" 4' - 8"
19 19
VESTIBULE
SOUTH
CORR
SOUTH
CORR
13' - 4" 36' - 0" 28' - 8" 36' - 0" 28' - 0"
15' - 1 3/4" 5' - 4 7/8" 11' - 5 3/8" 4' - 0" 4' - 0" 11' - 5 3/8" 5' - 4 7/8" 15' - 1 3/4"
4'
0"
3' - 4" 5' - 4"…