Text version
W68MD952458984
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
W912DW-16-B-0001 FY16 Chief Joseph Dam Intake Gate Repair Pit, Bridgeport, WA
(See continuation page)
1. CONTRACT ID CODE PAGE OF PAGES
1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 29-Jan-2016
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912DW-16-B-0001
X 9B. DATED (SEE ITEM 11)
23-Dec-2015
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
29-Jan-2016
CODE
USA ENGINEER DISTRICT, SEATTLE
ATTN: CECT-NWS
4735 EAST MARGINAL WAY SOUTH, BLDG. 1202
SEATTLE WA 98134-2388
W912DW 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912DW-16-B-0001
Continuation Page
1. This amendment six (0006) provides for the following:
a. Sections 41 22 23.20 JIB CRANE HOISTS and the Submittal Register been revised.
b. The date and time of bid opening has been extended to February 9, 2016 at 1:00:00 p.m. LOCAL TIME.
The SF1442 Solicitation, Offer and Award is revised to reflect the date extension.
2. The attached revised sections are to be replaced in their entirety. Specifications changes are generally identified, for convenience, either by strikeout for deletions, and double underlining of text for additions or a single dark line in the margin. All portions of the revised sections shall apply whether or not changes have been indicated.
3. NOTICE TO OFFERORS: Offerors must acknowledge receipt of this amendment by number and date on offer.
Encl:
SF1442 (revised) 41 22 23.20 (revised) Submittal Register (revised)
SOLICITATION, OFFER,
AND AWARD
(Construction, Alteration, or Repair)
1. SOLICITATION NUMBER 2. TYPE OF SOLICITATION
SEALED BID (IFB)
NEGOTIATED (RFP)
3. DATE ISSUED PAGE OF PAGES
IMPORTANT - The "offer" section on the reverse must be fully completed by the offeror.
4. CONTRACT NUMBER 5. REQUISITION/PURCHASE REQUEST NUMBER 6. PROJECT NUMBER
7. ISSUED BY CODE W912DW
Seattle District, Corps of Engineers
ATTN: CECT-NWS
PO Box 3755 Seattle, WA 98124-3755
8. ADDRESS OFFER TO
Seattle District, Corps of Engineers PO Box 3755 ATTN: CECT-NWS Seattle, WA 98124-3755
HAND CARRY: Federal Center South Building 1202 4735 East Marginal Way South Seattle, WA 98134-2388
9. FOR INFORMATION CALL
A. NAME B. TELEPHONE NUMBER (Include area code) (NO COLLECT CALLS)
SOLICITATION
NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid" and "bidder".
10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS (Title, identifying number, date):
Furnish all labor, materials and equipment and perform all work for
11. The Contractor shall begin performance within calendar days and complete it with calendar days after receiving award, notice to proceed. This performance period is mandatory, negotiable. (See .)
12A. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE PAYMENT BONDS?
(If "YES," indicate within how many calendar days after award in Item 12B.)
12B. CALENDAR DAYS
YES NO
13. ADDITIONAL SOLICITATION REQUIREMENTS:
A. Sealed offers in original and 0 copies to perform the work required are due at the place specified in Item 8 by (hour) local time (date). If this is a sealed bid solicitation, offers will be publicly opened at that time. Sealed envelopes containing offers shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.
B. An offer guarantee is, is not required.
C. All offers are subject to the (1) work requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.
D. Offers providing less than calendar days for Government acceptance after the date offers are due will not be considered and will be rejected.
NSN 7540-01-155-3212
Designed using Perform Pro, WHS/DIOR, Oct 96
1442-103 STANDARD FORM 1442 (REV. 4-85) (EG)
Prescribed by GSA - FAR (48 CFR) 53.236-1(d)
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text in accordance with the attached Contract Clauses, Special Clauses, Technical Specifications and Drawings.
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text 00 11 00 - 1
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
W912DW-16-B-0001
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text Caroline B. Mueller
G3CT9BAW
Typewritten Text 206-764-6741
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
* See Section 00 73 00
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text FY16 Chief Joseph Dam Intake Gate Repair Pit, Bridgeport, WA
G3CT9BAW
Typewritten Text 1:00:00 p.m.
G3CT9BAW
Typewritten Text 23 Dec 2015
G3CT9BAW
Typewritten Text
W68MD952458984
G3CT9BAW
Line
G3CT9BAW
Typewritten Text 9 February 2016
G3CT9BAW
Typewritten Text R0006
G3CT9BAW
Line
OFFER (Must be fully completed by offeror)
STANDARD FORM 1442 BACK (REV. 4-85)
14. NAME AND ADDRESS OF OFFEROR (Include ZIP Code)
Tax ID No: DUNS No:
email: Cage Code:
15. TELEPHONE NUMBER (Include area code) Fax No.:
16. REMITTANCE ADDRESS (Include only if different than Item 14)
CODE FACILITY CODE
17. The offeror agrees to perform the work required at the prices specified below in strict accordance with the terms of this solicitation, if this offer is accepted by the Government in writing within calendar days after the date offers are due. (Insert any number equal or greater than the minimum requirement stated in 13D. Failure to insert any number means the offeror accepts the minimum in Item 13D.)
AMOUNTS See Schedule
18. The offeror agrees to furnish any required performance and payment bonds.
19. ACKNOWLEDGEMENT OF AMENDMENTS
(The offeror acknowledges receipt of amendments to the solicitation - give number and date of each)
AMENDMENT NO.
DATE
20A. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN OFFER (Type or print) 20B. SIGNATURE 20C. OFFER DATE
AWARD (To be completed by Government)
21. ITEMS ACCEPTED
22. AMOUNT 23. ACCOUNTING AND APPROPRIATION DATA
24.SUBMIT INVOICES TO ADDRESS SHOWN IN
(4 copies unless otherwise specified)
ITEM
25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO
10 U.S.C. 2304(c) ( ) 41 U.S.C. 253(c) ( )
26. ADMINISTERED BY
27. PAYMENT WILL BE MADE BY
US Army Corps of Engineers Finance Center
CEFC-AO-P
5722 Integrity Drive Millington, TN 38054-500
CODE
CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE
28. NEGOTIATED AGREEMENT (Contractor is required to sign this document and return copies to the issuing office.) Contractor agrees to furnish and deliver all items or perform all work requirements identified on this form and any continuation sheets for the consideration stated in this contract. The rights and obligations of the parties to this contract shall be governed by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certifications, and specifications incorporated by reference in or attached to this contract.
29. AWARD. (Contractor is not required to sign this document.) Your offer on this solicitation is hereby accepted as to the items listed. This award consummates the contract, which consists of (a) the Government solicitation and your offer, and (b) this contract award. No further contractual document is necessary.
30A. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED TO SIGN
(Type or print)
30B. SIGNATURE 30C. DATE
31A. NAME OF CONTRACTING OFFICER (Type or print)
31B. UNITED STATES OF AMERICA
31C. AWARD DATE
BY
G3CT9BAW
Typewritten Text 00 11 00 - 2
G3CT9BAW
Typewritten Text
SEE ALTERATIONS IN CONTRACT, PAGE 00 11 00 - 3
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text Fairchild Resident Office PO Box 1334 Fairchild AFB, WA 99011-1334
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text
G3CT9BAW
Typewritten Text Bonilie L. Lackey
G3CT9BAW
Typewritten Text R0002
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 1 OF 12 PAGES
CJD Intake Gate Repair Pit
01 14 00 SD-01 Preconstruction Submittals
1.4.1 GBackground Check
1.5.2 CLoading Diagram
1.6.1 GContractor's Work Supervisor(s)
Qualifications 1.6.2.1Contractor Employees 1.6.2Organizational Chart
01 32 01.00 10 SD-01 Preconstruction Submittals
1.3 GProject Scheduler Qualifications
3.4.1 GPreliminary Project Schedule
3.4.2 GInitial Project Schedule
3.6.2 GPeriodic Schedule Update
01 33 00 SD-01 Preconstruction Submittals
1.9 GSubmittal Register
01 35 26 SD-01 Preconstruction Submittals
1.6 GAccident Prevention Plan (APP)
1.7 GActivity Hazard Analysis (AHA)
1.5.1.2 GCrane Operators
SD-06 Test Reports 1.11Notifications and Reports
1.11.2 GAccident Reports
1.11.3Crane Reports
SD-07 Certificates 1.11.4Certificate of Compliance 1.8Hot work permit 1.13License Certificates
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P H
C L A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
(a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) (o) (p) (q) (r)
R0006
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 2 OF 12 PAGES
CJD Intake Gate Repair Pit
01 45 00.00 10 SD-01 Preconstruction Submittals
3.2 GContractor Quality Control (CQC)
Plan 01 50 00 SD-01 Preconstruction Submittals
1.4 GConstruction site plan
3.2.1 GTemporary Utility Connections
Plan
3.6 GDisposal Plan
1.5.2The Original Condition Of Site
Photos 1.5.3Progress Photographs
SD-11 Closeout Submittals 1.5.4Completion Photographs
01 57 20.00 10 SD-01 Preconstruction Submittals
1.7 GEnvironmental Protection Plan
01 62 35 SD-01 Preconstruction Submittals
1.7 GBiobased Products
01 78 00 SD-03 Product Data
1.3.2 GAs-Built Record of Equipment
and Materials
1.7.1 GWarranty Management Plan
1.7.5 GWarranty Tags
1.4 GSpare Parts Data
SD-08 Manufacturer’s Instructions 1.5Preventative Maintenance
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 3 OF 12 PAGES
CJD Intake Gate Repair Pit
01 78 00 1.5Condition Monitoring (Predictive Testing)
1.5Inspection
1.7.1 GInstructions
SD-10 Operation and Maintenance Data
1.9 GOperation and Maintenance
Manuals
SD-11 Closeout Submittals
1.11 GInterim Form DD1354
1.11 GChecklist for Form DD1354
1.3.1 GRecord Drawings
1.6 GCertification of EPA Designated
Items 02 41 00 SD-01 Preconstruction Submittals
1.2.1 GDemolition Plan
1.6Notification of Demolition
05 05 23.16 SD-01 Preconstruction Submittals 3.2Welding Quality Assurance Plan
SD-03 Product Data
1.3 G DOWelding Procedure Qualifications
1.3.5Welder, Welding Operator, and
Tacker Qualification 1.3.6Inspector Qualification 1.3.2Previous Qualifications 1.3.3Pre-qualified Procedures
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 4 OF 12 PAGES
CJD Intake Gate Repair Pit
05 05 23.16 2.2Welding Electrodes and Rods SD-07 Certificates Certified Welding Procedure Specifications (WPS)
Certified Brazing Procedure Specifications (BPS)
Certified Procedure Qualification Records (PQR)
Certified Welder Performance Qualifications (WPQ)
Certified Brazer Performance Qualifications (BPQ)
05 12 00 SD-01 Preconstruction Submittals
1.4.1.1 G DOErection Drawings
SD-02 Shop Drawings
1.4.2 G DOFabrication drawings
SD-03 Product Data 2.5.2Shop primer 2.4.1Welding electrodes and rods 2.3.2.3Direct Tension Indicator Washers 2.4.2Non-Shrink Grout 2.3.3Tension control bolts
SD-06 Test Reports 2.3Bolts, nuts, and washers
SD-07 Certificates
2.2 GSteel
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 5 OF 12 PAGES
CJD Intake Gate Repair Pit
05 12 00 2.3 GBolts, nuts, and washers
2.4.4 GPins and rollers
1.3 GAISC Fabrication Plant Quality
Certification
1.3 GAISC Erector Quality Certification
1.4.3.1 GWelding procedures and
qualifications
2.4.1 GWelding electrodes and rods
05 50 13 SD-02 Shop Drawings
2.5 G DOstructural steel door frames
2.3 G DOFloor gratings
SD-03 Product Data 2.3Floor gratings 2.5Structural steel door frames
05 51 00 SD-02 Shop Drawings
2.1 GIron and Steel Hardware
2.1 GSteel Shapes, Plates, Bars and
Strips
2.7 GMetal Stair System
SD-03 Product Data 2.2Structural Steel Plates, Shapes, and Bars 2.3Structural Steel Tubing 2.5Hot-Rolled Carbon Steel Sheets and Strips Cold Finished Steel Bars
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 6 OF 12 PAGES
CJD Intake Gate Repair Pit
05 51 00 2.4Hot-Rolled Carbon Steel Bars
2.8 GProtective Coating
2.9 G DOSteel Pan Stairs
2.9.7 G DOSteel Stairs
SD-07 Certificates
1.3 GWelding Procedures
1.3 GWelder Qualification
SD-08 Manufacturer’s Instructions 2.2Structural Steel Plates, Shapes, and Bars 2.3Structural Steel Tubing 2.5Hot-Rolled Carbon Steel Sheets and Strips 2.4Hot-Rolled Carbon Steel Bars
2.8 GProtective Coating
05 52 00 SD-02 Shop Drawings
1.2.1 G DOFabrication Drawings
2.1 GIron and Steel Hardware
3.1 GIron and Steel Hardware
2.1 GSteel Shapes, Plates, Bars and
Strips
3.1 GSteel Shapes, Plates, Bars and
Strips SD-03 Product Data
1.2.1 GStructural Steel Plates, Shapes, and Bars
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 7 OF 12 PAGES
CJD Intake Gate Repair Pit
05 52 00 2.3 GStructural Steel Plates, Shapes, and Bars
1.2.1 GStructural Steel Tubing
2.4 GStructural Steel Tubing
1.2.1 GCold-Finished Steel Bars
2.6 GCold-Finished Steel Bars
1.2.1 GHot-Rolled Carbon Steel Bars
2.5 GHot-Rolled Carbon Steel Bars
1.2.1 GCold-Drawn Steel Tubing
1.2.1 G DOProtective Coating
2.9 G DOProtective Coating
1.2.1 G DOSteel Railings and Handrails
2.10 G DOSteel Railings and Handrails
1.2.1 GAnchorage and Fastening
Systems SD-07 Certificates
1.4.1Welding Procedures 1.4.2Welder Qualification
SD-08 Manufacturer’s Instructions
3.1 GInstallation Instructions
07 84 00 SD-02 Shop Drawings
2.1 GFirestopping System
SD-03 Product Data
2.2 GFirestopping Materials
SD-06 Test Reports
3.3 GInspection
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 8 OF 12 PAGES
CJD Intake Gate Repair Pit
07 84 00 SD-07 Certificates 1.5.2Inspector Qualifications 2.2Firestopping Materials
1.5.1 GInstaller Qualifications
09 97 13.00 40 SD-01 Preconstruction Submittals 1.4Material, Equipment, and Fixture
Lists 1.4Safety Plan
SD-03 Product Data 2.1Sealant Compound 2.2.1Inorganic Zinc 2.2.1Inhibitive Polyamide Epoxy 2.2.1Aliphatic Polyurethane
SD-04 Samples 1.4Manufacturer's Standard Color
Charts 3.5Inspection Forms
SD-05 Design Data 1.4Mix Designs 2.2.1Inorganic Zinc 2.2.1Inhibitive Polyamide Epoxy 2.2.1Aliphatic Polyurethane
SD-06 Test Reports 3.5Inspection reports
SD-07 Certificates 2.1Sealant Compound
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 9 OF 12 PAGES
CJD Intake Gate Repair Pit
09 97 13.00 40 3.2.1Inorganic Zinc Coating 2.2.1Inhibitive Polyamide Epoxy 2.2.1Aliphatic Polyurethane
SD-08 Manufacturer’s Instructions 2.2Protective Coatings
14 60 20.10 SD-02 Shop Drawings
2.2.1 GJib Crane system
2.7 GJib Wiring
SD-03 Product Data 1.2.1Bumpers 1.2.1End Stops 2.4.2Manufacturer's Published Tables
SD-05 Design Data
1.2.1 GStructural Design calculations
2.2.2 GStructural and Load Capacity
calculations SD-06 Test Reports
3.3.2125 Percent Rated Load Test
3.3.2No-Load Test 3.3.1Post-Erection Inspection 3.3.2Operational Tests
SD-07 Certificates 3.3.1Compliance with all listed
Standards
2.4 GJib Framework
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 10 OF 12 PAGES
CJD Intake Gate Repair Pit
14 60 20.10 SD-10 Operation and Maintenance Data
1.6 GJib crane
22 00 00 SD-02 Shop Drawings
3.3.1 GPlumbing System
SD-06 Test Reports
3.3Tests and Flushing SD-07 Certificates
2.1.1Bolts 23 00 00 SD-02 Shop Drawings
1.4.4 GDetail Drawings
SD-03 Product Data
2.10.1.1Sidewall Propeller Exhaust Fans 1.4.5Test Procedures
SD-06 Test Reports 3.6Performance Tests
SD-08 Manufacturer’s Instructions 3.2Manufacturer's Installation
Instructions SD-10 Operation and Maintenance Data
3.8.1 GOperation and Maintenance
Manual
2.10.1.1Sidewall Propeller Exhaust Fans 26 20 00.00 27 SD-02 Shop Drawings
3.1.7.1Marking strips
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 11 OF 12 PAGES
CJD Intake Gate Repair Pit
26 20 00.00 27 SD-03 Product Data
2.9 GReceptacles
2.10 GCircuit breakers
2.7Switches
2.11 GEnclosed circuit breakers
GSurge protective devices 2.2.1.1Steel 2.2.3Steel 2.2.4.1Steel
2.2.2PVC
SD-06 Test Reports
3.5.2 G600-volt wiring test
3.5.3Ground-fault receptacle test
SD-07 Certificates 2.8Fuses
SD-10 Operation and Maintenance Data
1.5.1 GElectrical Systems
26 51 00.00 27 SD-03 Product Data
2.1 GLight Emitting Diode (LED)
Lighting Fixtures
SD-04 Samples GLighting fixtures
SD-06 Test Reports 3.3Operating test
41 22 23.20 SD-02 Shop Drawings
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 12 OF 12 PAGES
CJD Intake Gate Repair Pit
41 22 23.20 1.2.1 GComplete schematic wiring diagram with description of operation
SD-03 Product Data
2.3 GElectric Chain Hoist
GTrolley
2.6 GPendant Pushbutton Station
1.2.1 GFestoon System
SD-06 Test Reports
3.3.5125 percent Rated Load test 3.3.4No-Load Test 3.3.1Post-Erection Inspection 3.3.2Operational Tests 3.3.6Rated Load Speed Test
SD-07 Certificates 1.4.1Compliance with all listed
Standards 1.4.1Brake Settings 1.4.1Loss of Power Test
SD-10 Operation and Maintenance Data
1.6 GJib crane with hoist system, all
components, Data Package 3
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
CJD Intake Gate Repair Pit 15007 Chief Joseph Dam, WA W912DW-16-B-0001
SECTION TABLE OF CONTENTS
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
SECTION 41 22 23.20
JIB CRANE HOISTS
04/08
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.2.1 Design Requirements
1.2.1.1 Trade Coordination
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Certificates: Load Chain
1.4.2 Pre-Erection Inspection
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Delivery and Storage
1.5.2 Handling
1.6 MAINTENANCE
PART 2 PRODUCTS
2.1 IDENTIFICATION PLATES
2.2 JIB CRANE HOIST SYSTEM
2.2.1 Capacity and Speed
2.2.2 Material and Design Requirements
2.2.3 Safety
2.3 ELECTRIC CHAIN HOIST
2.4 TROLLEY
2.5 MOTORS
2.5.1 Trolley Motors
2.5.2 Hoist Motors
2.6 CONTROLS
2.7 LIMIT SWITCHES
2.8 BRAKES
2.8.1 Hoist Load Brake
2.8.2 Spring Applied Hoist Brake
2.8.3 Trolley Brake
2.9 LOAD BLOCK AND HOOK
2.10 BEARINGS
2.11 ELECTRIFICATION
2.12 PAINTING SYSTEM
PART 3 EXECUTION
3.1 ERECTION AND INSTALLATION
3.2 ERECTION SERVICES
3.3 FIELD QUALITY CONTROL
3.3.1 Post-Erection Inspection
3.3.2 Operational Tests
3.3.3 Test Data
SECTION 41 22 23.20 Page 1 R0006
3.3.4 No-Load Test
3.3.5 125 percent Rated Load Test
3.3.6 Rated Load Speed Test
3.4 JIB CRANE FIELD TEST PROCEDURES
3.4.1 General Instructions
3.4.2 Equipment Monitoring
3.4.3 Hooks
3.4.4 Preparing For Load Testing
3.4.5 Precautions During Load Testing
3.4.6 Testing
3.4.6.1 No Load Test
3.4.6.2 Hoist Load Testing
3.4.6.3 100 Percent of Rated Capacity (plus 0 percent, minus 5 percent) Load Test
3.4.6.4 125 Percent of Rated Capacity (plus 5 percent, minus 0 percent) Load Test
-- End of Section Table of Contents --
SECTION 41 22 23.20 Page 2 R0006
SECTION 41 22 23.20
JIB CRANE HOISTS
04/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASME INTERNATIONAL (ASME)
ASME B30.11 (2010) Monorails and Underhung Cranes - Safety Standard for Cableways, Cranes, Derricks, Hoists, Hooks, Jacks, and Slings
ASME B30.16 (2012) Overhead Hoists (Underhung)
ASME HST-1 (2012) Performance Standard for Electric Chain Hoists
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ESPG (2009-2010) Electrical Standards and Product Guide (ESPG)
NEMA ICS 8 (2011) Crane and Hoist Controllers
NEMA MG 1 (2014) Motors and Generators
NEMA MG 2 (2014) Safety Standard for Construction and Guide for Selection, Installation and Use of Electric Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2008; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.179 Overhead and Gantry Cranes
1.2 SYSTEM DESCRIPTION
Provide an electric powered hoist and electric powered trolley complete, tested and ready for operation. Hoist shall be part of a complete jib crane system, as indicated on the drawings and in accordance with Section 14 60 20.10 JIB CRANES. Jib crane, hoist, trolley, equipment, materials, installation, examination, inspection, and workmanship shall conform to the applicable requirements of NFPA 70, ASME B30.11, ASME B30.16, and ASME HST-1, MHI MH27.1, as modified and supplemented by this specification. Reference
SECTION 41 22 23.20 Page 3 R0006 in these publications to the "authority having jurisdiction" means the "Contracting Officer."
1.2.1 Design Requirements
Submit shop drawings showing crane capacity, hook envelope, festoon system, and the general arrangement of the jib crane system, including clearances, principal dimensions, details of structural connections, and all component details. Include complete schematic wiring diagram with description of operation. Manufacturer's catalog data will suffice for items of standard manufacturer.
1.2.1.1 Trade Coordination
The Contractor is responsible for the coordination of his work with the work of all trades involved and as it relates to the building structure.
Verify all building dimensions that relate to fabrication of the jib crane system, and notify the Contracting Officer of any discrepancy prior to ordering the jib crane system components.
1.3 SUBMITTALS
Coordinate submittals with those submittals also required under Section
14 60 20.10 JIB CRANES.
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Complete schematic wiring diagram with description of operation; G
SD-03 Product Data
Electric Chain Hoist; G Trolley; G Pendant Pushbutton Station; G Hook Proof Test; G Festoon System; G
Manufacturer's descriptive data and technical literature, performance charts and curves, catalog cuts, and installation instructions, and parts list.
SD-05 Design Data
Structural and Load Capacity calculations; G
SD-06 Test Reports
125 percent Rated Load test No-Load Test Post-Erection Inspection Operational Tests Rated Load Speed Test Load Chain Proof Test
SECTION 41 22 23.20 Page 4 R0006
Hook NDT Report Hook Tram Measurement
Tests and inspections reports. Magnetic particle inspection of hook and hook nut results.
SD-07 Certificates
Compliance with all listed Standards Semi-Annual Overload/Safe for Testing Hazardous Material Brake Settings Loss of Power Test Hook Proof Test
SD-10 Operation and Maintenance Data
Jib crane with hoist system, all components, Data Package 3; G
Submit Data Package 3 as specified in Section 01 78 23 OPERATION
AND MAINTENANCE DATA.
1.4 QUALITY ASSURANCE
1.4.1 Certificates: Load Chain
a. Certification of minimum Load Chain Proof Test, clearly indicating load chain breaking strength for each hoist, and clearly identified for traceability. Submit factory certification of load chain rated capacity.
b. Certification that the hoist, hook, and trolley system contains no hazardous material, asbestos, cadmium, lead, elemental mercury, or PCBs.
c. Semi-Annual Overload/Safe for Testing certification that the hoist, hook, and trolley system is safe to test on a semi-annual overload basis with a test load of 131.25 percent of rated capacity with no detrimental effects.
da. Certification that testing may be performed in which hoist, hook, and trolley system is subjected to a Loss of Power Test during operation with no detrimental effects.
eb. Certification that the hoist, hook, and trolley system design and fabrication is in compliance with all listed standards.
f. Hook Proof Test certification that the hoist hook was subjected to a minimum static load of 200 percent of rated capacity for at least 10 minutes without deformation.
gc. Certification of brake settings, including the allowable range of adjustment for hoist and trolley brakes and the initial setting of each.
1.4.2 Pre-Erection Inspection
Before erection, the Contractor shall inspect the jib crane and hoist systems and components at the job site to determine compliance with specifications and manufacturer's data and shop drawings as approved.
Notify the Contracting Officer 21 days before the inspection.
SECTION 41 22 23.20 Page 5 R0006
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Delivery and Storage
Inspect materials delivered to site for damage; unload and store with minimum handling. Store materials on-site in enclosures or under protective coverings. Protect materials not suitable for outdoor storage to prevent damage or corrosion during periods of inclement weather, including subfreezing temperatures, precipitation, and high winds. Store materials susceptible to deterioration by direct sunlight under cover and avoid damage due to high temperatures. Do not store materials directly on ground. When special precautions are required, prominently and legibly stencil instructions for such precautions on outside of equipment or its crating.
1.5.2 Handling
Handle materials in such a manner as to ensure delivery to final location in undamaged condition. Make repairs to damaged materials at no cost to Government.
1.6 MAINTENANCE
Submit jib crane with hoist system, all components, Data Package 3 for the entire jib crane system in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
PART 2 PRODUCTS
2.1 IDENTIFICATION PLATES
Provide manufacturer installed identification plates of non-corrosive metal showing, in clearly legible permanent lettering, the manufacturer's name, model number, capacity rating in pounds, and other essential information.
2.2 JIB CRANE HOIST SYSTEM
Provide jib crane hoist system for indoor service, with an electrical chain hoist mounted on a motor-driven trolley. The hoist and trolley shall be in accordance with ASME B30.11 and ASME HST-1, Duty Class H3.
2.2.1 Capacity and Speed
Provide hoist with a minimum rated capacity of 1 ton. The hook lift capacity and speed shall be the manufacturer's standard within the limits specified aboveas indicated. The hoist lift height will be sufficient for the hook to reach the finished floor at the bottom of the gate repair pit at Elevation 910 feet.
2.2.2 Material and Design Requirements
Jib crane hoist system shall include the following design requirements:
a. Powered hoists shall include a brake and a controlled braking means, and an overload limiting device.
b. Directional contactors shall include electrical and mechanical interlocks. Design the mainline contactor, along with the
SECTION 41 22 23.20 Page 6 R0006 power-off/power-on circuitry to remove power from the drive motors, brakes and control circuit. The control circuit shall not operate unless a power-on button is depressed.
c. Overcurrent protection for the control circuit and control circuit transformer; fuse or circuit breaker protection for branch circuit short circuit and ground fault protection; and overload protection for each motor, motor controller, and branch circuit conductor shall all conform to the NFPA 70.
d. Provide safety (drop) lugs or a functional equivalent on the trolley frame to prevent derailment in the event of wheel failure.
e. Refer to drawings and electrical specifications for electrical requirements.
f. Provide a non-resettable hour meter, connected across the main line contactor, readable from the exterior of the main control panel, to indicate the elapsed number of hours the crane is energized.
2.2.3 Safety
Comply with the mandatory and advisory safety requirements of ASME B30.11, ASME B30.16, and 29 CFR 1910.179. The Contractor is responsible for checking the proper operation and condition of safety devices, electrical components, mechanical equipment, and structural assemblies prior to installation. Immediately report any observed defective components and replace. Submit structural and load capacity calculations verifying a design safety factor of 5 to 1 to ultimate strength of weakest material (steel) used for any track suspension device or support which is not a standard cataloged product of the system manufacturer.
2.3 ELECTRIC CHAIN HOIST
Electric chain hoist shall conform to ASME HST-1, Class H3 and NEMA ICS 8, NEMA MG 2, and NEMA ESPG except as modified herein. Provide load chain proof test results.
Provide chain hoist with a load chain bucket.
2.4 TROLLEY
Provide an electric motor driven trolley.
2.5 MOTORS
Motors shall conform to NEMA MG 1. All motors shall be minimum 60 minute duty rating. Motor insulation shall be Class H with a Class B temperature rise. Equip all motors with thermal trip type over-temperature protection.
2.5.1 Trolley Motors
Trolley drive motor shall be totally enclosed non-ventilated (TENV), squirrel cage induction type. Provide reduced voltage starting, acceleration and deceleration for the trolley drive.
SECTION 41 22 23.20 Page 7 R0006
2.5.2 Hoist Motors
Provide totally enclosed non-ventilated (TENV), squirrel cage induction type hoist motors.
2.6 CONTROLS
Provide control of electric hoist and trolley from a pendant pushbutton station. Arrange pushbuttons in accordance with ASME B30.11 recommendations. Control pendant shall extend below the underside of the track beam per manufacturer's recommendations.
2.7 LIMIT SWITCHES
Equip hoists with adjustable upper and lower limit switches for wire rope or limit stops for chain to prevent over-travel in both the raising and lowering directions.
2.8 BRAKES
2.8.1 Hoist Load Brake
Provide hoist load brake that is capable of stopping and holding a 131.25 percent test load. If dynamic braking is not included, provide a hoist mechanical load brake that is capable of stopping and holding a 131.25 percent test load. If the hoist has more than one brake, each brake shall independently stop and hold 131.25150 percent of rated capacity.
2.8.2 Spring Applied Hoist Brake
Provide spring applied hoist brake, electrically released, and capable of being adjusted to 50 percent of its full rating. Provide the hoist brake with a manual lever type, self return to ON, release mechanism so that it may be partially released by hand and the lifted load allowed to gradually descend by gravity and brake friction. Screw type, maintained OFF, release mechanisms are not permitted. Mount the brake on the end of the motor opposite the gear case. Design shall permit easy access for inspection and adjustment.
2.8.3 Trolley Brake
Provide trolley with either a non-coasting worm drive or with an electro mechanical brake that is spring applied, electrically released Trolley brake shall have a torque rating equal to or greater than 50 percent of the drive motor rated torque and be adjustable from 85 percent to 100 percent of its torque rating. Equip trolley brake with a manual release. Design to permit easy access for wear, inspection and setting.
2.9 LOAD BLOCK AND HOOK
Provide safety hook fitted with self-closing, spring loaded steel safety latch, and with hook nuts keyed to hook shanks by means of a setscrew installed in a plane parallel to the longitudinal axis of the hook shank, or by any other similar easily removable securing device. Provide unpainted hook and hook nut, permanently marked with an identification number. Clearly mark the hook and hook nut with a unique identification number corresponding to the number used in non-destructive test (NDT) reports.
SECTION 41 22 23.20 Page 8 R0006
2.9.1 Non-Destructive Testing
The following requirements apply:
a. The Hook NDT Report supplier shall provide a letter certifying that the requirements of ASTM E543 are met.
b. The NDT supplier shall develop, and submit for review, procedures, including technique sheets specific to the types, shapes, and sizes of the parts being examined (e.g., shank hook, eye hook, duplex hook, eye bar nut). For the magnetic particle method, the procedures shall adequately describe the orientation of the hook or nut, or pin with the magnetizing equipment.
c. These procedures shall be reviewed by a Level III examiner who is independent of the NDT supplier and is certified in the applicable NDT method.
2.9.2 Hook and Hook Nut Magnetic Particle Inspections
The hook and hook nut shall be magnetic-particle inspected in compliance with ASTM E709 over the entire area in accordance with ASTM A275/A275M, with the following restrictions: Do not use DC yokes (including switchable AC/DC yokes used in the DC mode) and permanent magnet yokes. Do not use automatic powder blowers or any other form of forced air other than from a hand-held bulb for the application or removal of dry magnetic particles.
Remove arc strikes. Equipment ammeters shall have an accuracy of plus or minus 5 percent of full scale (equipment ammeter accuracy other than that stated is acceptable provided the MT procedure states that a magnetic field indicator is used to establish and verify adequate field strength for the aspects of the inspection). The acceptance standard is no linear indications greater than 1/16 inch.
2.10 BEARINGS
All bearings except those subject to a small rocker motion shall be anti-friction type. Provide a means for lubrication for bearings not considered to be lifetime lubricated by the manufacturer.
2.11 ELECTRIFICATION
Provide runway electrification of the flat festooned type. Provide electrical work for the jib crane system in accordance with NFPA 70.
2.12 PAINTING SYSTEM
Provide manufacturer's standard painting of components. Provide a primer and a finish coat. Blast clean all components prior to painting. Primer shall be inorganic zinc type. Paint coats shall be smooth and even, free of runs, sags, orange peel, or other defects.
PART 3 EXECUTION
3.1 ERECTION AND INSTALLATION
Erect and install the jib crane system, complete in accordance with the approved submittals and in condition to perform the operational and acceptance tests.
SECTION 41 22 23.20 Page 9 R0006
3.2 ERECTION SERVICES
Provide supervisory erection services from the jib crane system manufacturer.
3.3 FIELD QUALITY CONTROL
3.3.1 Post-Erection Inspection
After erection, the Contractor, the Contracting Officer, and a representative of the activity maintaining organization, shall jointly inspect the jib crane and hoist systems and components to determine compliance with specifications and approved submittals. Notify the Contracting Officer 30 days before the inspection. A list of deficient items, including a determination of criticality will be provided to the Contractor for corrective action. Outstanding items shall be noted for correction during the inspection. Items considered critical (load bearing, load controlling, or operational safety devices) shall be corrected prior to further testing. Upon correction, provide a report of the inspection indicating the jib crane system is considered ready for operational tests.
3.3.2 Operational Tests
a. After erection and inspection, test the jib crane system, hoist, and trolley as specified herein. Test the systems in service to determine that each component of the system operates as specified, is properly installed and adjusted, and is free from defects in material, manufacturing, installation, and workmanship. Rectify all deficiencies disclosed by testing and retest the system or component to prove the jib crane system is operational.
b. Furnish loads for testing, operating personnel, instruments, and all other necessary apparatus.
3.3.3 Test Data
Record test data on appropriate test record forms suitable for retention for the life of the jib crane system. Record operating and startup current measurements for electrical equipment (motors and coils) using appropriate instrumentation (i.e., clamp-on ammeters). Compare recorded values with design specifications or manufacturer's recommended values. Abnormal differences (i.e., greater than 10 percent from manufacturer's or design values) shall be justified or appropriate adjustments performed. In addition, note any high temperatures or abnormal operation of any equipment or machinery , investigate and correct. Record hoist and trolley speeds during each test cycle.
3.3.4 Hook Tram Measurement
Measure hook for hook throat spread before and after load test. Establish a throat dimension base measurement by installing two tram points and measuring the distance between these tram points (plus or minus 1/64 inch ). Record this base dimension. Measure the distance between tram points before and after load test. An increase in the throat opening from the base measurement is cause for rejection.
SECTION 41 22 23.20 Page 10 R0006
3.3.4 No-Load Test
a. Hoist: Raise the load hook the full operating lift distance and verify satisfactory operation of hoist, upper limit switches, lower limit switch, and the hoisting and lowering speeds.
b. Trolley: Operate trolley assembly the full length of the jib boom in both directions. Verify satisfactory operation and verify trolley speed.
3.3.5 125 percent Rated Load Test
125 Percent (plus 5 percent minus 0) of rated capacity
a. Hoist Static Test: Raise test load approximately one foot above the floor and hold for 10 minutes. Observe load lowering that may occur which indicates malfunction of hoisting component or brake. Lower the test load to the floor until the hoist line is slack.
b. Hoist Dynamic Test: Raise the test load to approximately 5 feet above the floor. Lower the load back to the floor. Stop the test load at least once while lowering and observe proper brake operation. Wait 5 minutes, then repeat the above cycle.
c. Load Brake Test (if equipped): Raise test load approximately 5 feet.
With the hoist controller in the neutral position, release the holding brake. The load brake must hold the test load. Again with the holding brake in the released position, start the test load down and return the controller to off position as the test load lowers. The load brake must stop and hold the test load. If the load brake does not stop the test load, but prevents the test load from accelerating, activities will contact the OEM or activity engineering organization to ensure that the load brake is operating as designed.
d. Loss of Power Test: Raise the test load approximately 3 feet and while lowering test load, cut main power to hoist. The load must stop.
e. Trolley Test: With test load hoisted to a height of one foot above the floor (or at an alternate height that safely allows completion of this test), operate trolley the full distance of the jib boom in both directions. Observe for any malfunctioning of the trolley assembly and jib crane system.
3.3.6 Rated Load Speed Test
With the hoist loaded to rated capacity, raise and lower the load verifying that the hoisting and lowering speeds are provided as specified. With the hoist loaded to rated capacity, operate trolley along the jib boom verifying that the trolley speed is provided as specified. Further, verify that the trolley stops in each direction within a distance (in feet) equal to 10 percent of rated capacity high speed (in feet per minute) when initially traveling at high speed and carrying the rated capacity load.
Record voltage, amperage, hoisting and lowering speeds, trolley travel speed, and motor speed for each motor.
SECTION 41 22 23.20 Page 11 R0006
3.4 JIB CRANE FIELD TEST PROCEDURES
JIB CRANE FIELD TEST PROCEDURES
Supported Command: Date of Inspection:
Contract No.:
Names and Titles of Participating Government, Supported Command, and Contractor Representatives:
3.4.1 General Instructions
The crane and supporting structure shall be tested in accordance with the applicable paragraphs of this guide. Assure that all components and features that affect load bearing, load controlling, or operational safety devices of the cranes are properly tested. Perform all the tests described below along with any other tests required to verify that the crane meets the contract requirements including any contract modifications. The sequence of testing is at the option of the contractor's test director except that the no-load test shall be performed first. Develop data sheets for tests that require data recording. Include in the data sheets the expected results along with the allowable tolerance in accordance with the requirements of the specification. Determine the tools, meters, measuring devices, etc. that are required to perform the test and have them available at the site. When measuring currents less than 5 amps, a 10-amp series type amp meter is recommended instead of an amp probe or use of the drive monitoring display. All equipment shall be calibrated
3.4.2 Equipment Monitoring
During the load test, check for the proper operation and condition of safety devices, electrical components, mechanical equipment, and structural assemblies. Immediately report any observed defects critical to continuing testing to the contractor's test director, who shall suspend the testing until the deficiency is corrected.
SECTION 41 22 23.20 Page 12 R0006
3.4.3 Hooks
Record hook serial number. Measure the hook for hook throat spread before load testing. Install two tram points on hook throat. Measure the distance between these tram points (plus or minus 1/64 inch). Record this base dimension. Check operation of safety latches.
Load Hook Unique Identification Number _________________
Load Hook Nut Unique Identification Number _________________
Load Hook Throat Measurement - Before Load Testing _________________
Load Hook Safety Latches SAT_____ UNSAT_____ NA_____
3.4.4 Preparing For Load Testing
a. Select a safe test area and clear all traffic, unauthorized personnel, and equipment from test area. This test area shall be roped off or otherwise secured to prevent entry of unauthorized personnel and equipment.
b. All rigging used in crane load testing shall conform to applicable OSHA regulations and ASME standards for inspection and testing. Note that test loads INCLUDE the weight of rigging used to connect them to the load block.
3.4.5 Precautions During Load Testing
a. Observe extreme caution at all times.
b. Personnel…
This is the start of the file's text. The full file is on GovTribe.