Building 110 Repairs-Big Gun Shop - Design Build Watervliet Arsensal, New York
Solicitation number
W912DS25RA013
Issued by

About this file

This is a Solicitation Amendment for a Design-Build contract for repairs to Building 110 at Watervliet Arsenal in New York. The amendment modifies the original solicitation by updating Quality Control Manager requirements, confirming that CPARS can be used in place of Past Performance Questionnaires, and clarifying proposal submission details. Key updates include relaxing the QC Manager certification requirements, allowing the qualifications to be met across multiple team members, and confirming that Form A1 will serve as the cover sheet for Tab C of the proposal.

The federal contract opportunity is a firm-fixed-price design-build project for Phase I repairs to a 213,799 square foot industrial building, with work scope including concrete slab repairs, exterior brick and roofing work, interior renovations, and system upgrades for compressed air, water, steam, fire suppression, and electrical systems. The project is an unrestricted full and open competition with a Hubzone price preference, valued between $25M-$100M, with Phase One proposals due by 23 July 2025 at 4 PM EDT. The contract will include a Project Labor Agreement (PLA) and is being issued by the Department of the Army Corps of Engineers Engineering District New York.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER.

If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

16C. DATE SIGNED

Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X) 9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

The purpose of this amendment is to:Block 14 (Description of Amendment/Modification):

1. Post sign-in sheet for site visit

2. Respond to offerors inquiries are provided "for informational purposes only"

REMINDER: ONLY PHASE ONE PROPOSAL IS DUE

NOTE: Offerors must acknowledge receipt of this amendment by date specified in the bid (or as amended) by one of the following methods: In space provided on the SF 1442, by separate letter, or by signing block 15 below . FAILURE TO ACKNOWLEDGE AMENDMENT BY DATE SPECIFIED MY

RESULT IN REJECTION OF YOUR BID IN ACCORDANCE WITH THE LATE BID, LATE

MODIFICATION OF BID, OR LATE WITHDRAWAL OF BID (FAR 14.304).

W912DS25RA0130001

Section 00 22 00 - Supplementary Instructions

BUILDING 110 REPAIRS-BIG GUN SHOP - DESIGN BUILDWATERVLIET ARSENSAL, NEW YORK

Amendment 0001

AMENDMENT 0001 to DRAWINGS and SPECIFICATIONS BUILDING110 REPAIRS-BIG GUN SHOP - DESIGN BUILD WATERVLIET

ARSENSAL, NEW YORK

TO OFFERORS

The following changes shall be made to the drawings and specifications.

DRAWINGS

1. Thefollowing DRAWINGS have been but :REVISED NOT REISSUED

- None

2. The following DRAWINGS have been and :REVISED REISSUED

- - None

3. The following DRAWINGS have been :ADDED

- None

4. The following DRAWINGS have been :DELETED

- None

SPECIFICATIONS

1. The following SPECIFICATION SECTIONS have been and are provided in their entirety herein:ADDED

- None

2. The following SPECIFICATIONS SECTIONS have been in their entirety:DELETED

- None

3. The following SPECIFICATIONS SECTIONS have been and :REVISED REISSUED

- None

W912DS25RA0130001

4. The following SPECIFICATIONS have been but :REVISED NOT REISSUED

- - Section 01 45 00 - paragraph 1.6.2.2 is hereby revised in its entirety as follows: "The QC Manager must possess at least a Bachelor's degree in engineering, architecture, or construction management, and a minimum of 10 years construction experience as a Project Superintendent, QC Manager, Project Manager, Project Engineer or Construction Manager on similar size and type construction Contracts which included the major trades that are part of this Contract. The individual must have at least 4 years experience as a QC Manager. The individual must be familiar with the requirements of EM 385-1-1 and have experience in the areas of hazard identification, safety compliance, and sustainability. The individual must also have a current AMPP Certified Coating Inspector Certification (NACE CIP Level 2 or SSPC PCI Level 2.) Note: AMPP Certified Coating Inspector Certification can be held by another person that is part of the QC team, that person MUST be on site full time when coating work is being performed and must report directly to the QC Manager"

PROPOSER'S QUESTIONSAND GOVERNMENT REPLY

The following questions and answers are provided for information only. Nothing contained below amends or revises any provision of the solicitation.

This is for bidder's reference only, and is not to be considered as a part of the Contract Documents. Contract award will be based on what is contained in the printed Plans and Specifications in a hard copy format or Electronic Bid Set if provided and as posted in SAM.gov.

1. Under TAB 2 Factor 2-Past Performance- Can CPARS be submitted in place of PPQs for the projects listed under Factor 1? Please confirm if this is acceptable.

Response: Yes, CPARS can be use in place of PPQs.

2.

Specification 01 45 00 Quality Control

Section 1.6.2.2 Quality Control (QC) Manager Qualifications

The specifications require the QC Manager to possess the following qualifications:

1. Bachelor's degree in engineering, architecture, or construction management, with a current professional engineer registration in a US State or a current licensed architect in a US State

2. Minimum of 10 years construction experience as a Project Superintendent, QC Manager, Project Manager, Project Engineer or Construction Manager on similar size and type construction Contracts which included the major trades that are part of this Contract

3. Must have at least 4 years experience as a QC Manager

4. Must be familiar with the requirements of EM 385-1-1 and have experience in the areas of hazard identification, safety compliance, and sustainability

5. Must also have a current AMPP Certified Coating Inspector Certification (NACE CIP Level 2 or SSPC PCI Level)

There are relatively few (if any) QC Managers that meet all of the above requirements. In lieu of one QC Manager required to meet all of the requirements, can the above qualifications be satisfied across multiple QC Managers and/or consultants?

Response: Please see revisions to the QCM Requirements as noted in this amendment above.

W912DS25RA0130001

3. Is the Proposal Data Sheet (Form A1) to be used to fulfill the requirement for the Proposal Cover Sheet for Tab C?

Response: Yes. Form A1 is the cover sheet for TAB C. Updated form will be provided with this amendment.

4. The Evaluation and Rating System - Phase One Attachments referenced . However, this formSection F: Form A4 appears to be missing from the provided attachment file. Could you kindly confirm whether Form A4 is required? If so, we would appreciate it if you could provide the form.

Response: Form has been posted in Sam.gov.

W912DS25RA0130001

W912DS25RA0130001

(End of Summary)

IDCode: J
Page: 1
Pages: 2
AmendNo: 0001
EffDate: 17 JUL 2025
ReqNo:
ProjNo: 515598
IssCode: W912DS
AdmCode:
IssuedBy: W2SD ENDIST NEW YORK

KO CONTRACTING DIVISION, 26 FEDERAL PLAZA ROOM 16 300

NEW YORK, NY 10278-0004

UNITED STATES

MOHENDA SURAGE, EMAIL: MOHENDA.R.SURAGE@USACE.ARMY.MIL TELEPHONE: 917-940-8013

AdminBy:

SCD: PAS:

ContractorNameAdd:
Code:
FacCode:
SolChg: 1
SolNo: W912DS25RA013
SolDate: 23 JUN 2025
AwardChg: Off
AwardNo:
AwardDate:
Amended: 1
OffrExt: Off
OffrNoEx: 1
NoCopies: 1
ApprData: SEE SECTION G - CONTRACT ADMINISTRATION DATA
ChgeOrd: Off
ChgeOrder:
Modify: Off
SuppAgre: Off
SuppAuth:
ModOthr: Off
OthrSpec:
NoReq: Off
Require: Off
Copies:
Descript: SEE SCHEDULE
ContNameTitle:
CoNameTitle: NICHOLAS EMANUEL
ContDate:
CODate: 22 JUL 2025