About this file

Amendment 0003 Plans

View the file

Other files

File Type Posted
Bid_Results_14-B-0002_Greenbrook.pdf PDF
Amendment_0007.pdf PDF
Amendment_6_specs.pdf PDF
Amendment_0006.pdf PDF
Amendment_6_Plans_01-29-14.pdf PDF
Amendment_0005.pdf PDF
Amendment_0004.pdf PDF
Amend_3-_specs.pdf PDF
Amendment_0003.pdf PDF
Amendment_0002.pdf PDF
Amend_1_Plans-_File_1.pdf PDF
Amend_1_Specs.pdf PDF
Amend_1_Plans_-File_2.pdf PDF
Amendment_0001.pdf PDF
Plans_GB_SEG_R2_T_8_Nov_2013_File_2.pdf PDF
Plans_GB_SEG_R2_T_8_Nov_2013_File_3.pdf PDF
Plans_GB_SEG_R2_T_8_Nov_2013_File_4.pdf PDF
Plans_GB_SEG_R2_T_8_Nov_2013_File_5.pdf PDF
Plans_GB_SEG_R2_T_8_Nov_2013_File_1.pdf PDF
Specs_SEGR2T_-_East_Main.pdf PDF
Solicitation.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S O

L

IC

IT

A

T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

US Army Corps of Engineers

D A

T E

S

IZ

E

S U

B M

IT

T

E D

B Y

P L

O T

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T

N O

A N

S I

D

:4

:0

P M

P L

O T

T E

D B

Y s il a s c u n n in g h a m

New York District

U

S

A R

M Y

E N

G

IN

E E

R D

IS

T

R

IC

T

N E

W Y

O R

K h tt p

/w w w .n a n .u s a c e .a rm y .m il

SHEET

REFERENCE

NUMBER

M A

Y

N

Y D

B O

R D

E R

WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE

INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED

IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE

EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.

ALL DIMENSIONS/EXISTING CONDITIONS SHOWN SHALL BE CHECKED AND VERIFIED

BY THE CONTRACTOR AT THE SITE, ANY DISCREPANCIES SHALL BE IMMEDIATELY

REPORTED TO THE GOVERNMENT FOR CLARIFICATIONS. DRAWING SHALL NOT BE

SCALED TO OBTAIN DIMENSIONS OR DISTANCES.

C o n s u lt in g E n g in e e rs

C o rp o ra ti o n

S -4

.d g n

Submitted by:

DATETHOMAS C. MacALLEN

N.J. PROFESSIONAL ENGINEER

Lic. No. 24GE02594500

B ro a d

S tr e e t, C li ft o n

N J

T E

L

-8

-8

G R

E E

N B

R O

O K

F L

O O

D R

IS

K

M A

N A

G E

M E

N T

P R

O J E

C T

S

E G

M E

N T

R -2

E X

T E

N S

IO

N

A N

D S

E G

M E

N T

T R

A

IS

IN

G

B O

R O

U G

H O

F B

O U

N D

B R

O O

K N

J

F

IL

E N

A M

E s il a s c u n n in g h a m

S u b m it te d b y

/1

/2

P lo t D a te

N

P r o je c ts

\G r e e n B r o o k \1

S e g m e n t

C lo s u r e \C

A D

\C u r r e n t

D r a w in g s \S

.d g n

:4

:0

P

M

E .E

.W

A .P

.O

T O

M M a c A

L L

E N

O C

T O

B E

R

L I C

I T

A T

I O

N

N

O

F I L

E

N

A M

E

D W

N

B

Y

C K

D

B

Y

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

US Army Corps of Engineers

D A

T E

S I Z

E

S U

B M

I T

T E

D

B

Y

P L

T

D

A T

E

D A

T E

M A

R K

D E

S C

R I P

T I O

N A

P P

R

D A

T E

C O

N T

R A

C

N

X-XXX

XXX

A N

S I

D

P L

O T

T E

D

B

Y

New York

District

U

S

A

R M

Y

E

N G

I N

E E

R

D

I S

T R

I C

T

N E

W

Y

O R

K h t t p w w w n a n u s a c e a r m y m i l

SHEET

REFERENCE

NUMBER

S H

E E

T

I N

F O

R M

A T

I O

N

L I N

E

S H

E E

T

I N

F O

R M

A T

I O

N

L I N

E

S H

E E

T

I N

F O

R M

A T

I O

N

L I N

E

DATE

A M

E N

D M

E N

T

XX

G R

E E

N

B

R O

K

F

L O

R

I S

K

M

A N

A G

E M

E N

T

P R

O J E

C T

S

E G

M E

E

X T

E N

S I O

N

A N

D

S

E G

M E

I S

I N

G

B O

R O

U G

H

O

F

B

O U

B

O

O K

N

J

SHEET OF 124

WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE

INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED

IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE

EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.

ALL DIMENSIONS/EXISTING CONDITIONS SHOWN SHALL BE CHECKED AND VERIFIED

BY THE CONTRACTOR AT THE SITE, ANY DISCREPANCIES SHALL BE IMMEDIATELY

REPORTED TO THE GOVERNMENT FOR CLARIFICATIONS. DRAWING SHALL NOT BE

SCALED TO OBTAIN DIMENSIONS OR DISTANCES.

PROFESSIONAL

STAMP AND SEAL

NOT FOR CONSTRUCTION

ISSUED FOR REVEW

ONLY

THIS BAR IS 20 mm ON

ORIGINAL DRAWING

IF NOT 20 mm ON THIS

SHEET, ADJUST SCALES

ACCORDINGLY

TOMMY HUANG

C o n s u l t i n g

E n g i n e e r i n g

P

C

B r o a d w a y

S u i t e

N e w

Y o r k

N

Y

T E

L

F

X

G

B S

E G

R

T

S d g n d w g

WATERSTOP DETAIL

SCALE: 1" = 1'-0" 0 6" 1' 2'

CORNER DETAIL

SCALE: 1" = 1'-0" 0 6" 1' 2'

S-505

S E

G M

E N

T

R

D R

A I N

A G

E

S

T R

U C

T U

R E

P L A

N

A

E T

A I L S

S-301

S-505

B

DRAINAGE STRUCTURE PARTIAL PLAN

SCALE: 1/2" = 1'-0" 0 1' 2' 4'

A

B

B

S-401

S-505

A M

E N

D M

E N

T

M

O D

I F

I E

D

W

A T

E R

S T

P

T

A I L

E-502

.C

M .F

M .F

A .K

GROUND TESTING WELL (NTS)

103 103

(SEE SHEET C-105 FOR LOCATION)

CONTROL BUILDING

NEW ROOFTOP EXHAUST FAN SCHEMATIC

(SEE SHEETS C-105 & C-507 FOR LOCATION)

E L E

C T

R

IC

A L D

E T

A

IL

S

S E

G M

E N

T T

WALL SECTION

NOT TO SCALE

/0

/2

A N

D R

E V

IS

E N

O T

E

A M

E N

D M

E N

T

A D

D W

A L L S

E C

T

IO

N D

E T

A

IL

/1

/2

T E

S T

IN

G W

E L L

A M

E N

D M

E N

T

A D

D D

IM

E N

S

IO

N T

O N

E W

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R of Engineers

US Army Corps

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

A N

S I

D :5

:3

P

M

P L

O T

T E

D B

Y

O n s y

M o a w a d

New York District h tt p /w w w .n a n .u s a c e .a rm y .m il

N E

W Y

O R

K

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IC

T

NUMBER

REFERENCE

SHEET

M A

Y

Y

B

R D

E R

RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.

EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE

INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED

WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE

SCALED TO OBTAIN DIMENSIONS OR DISTANCES.

REPORTED TO THE GOVERNMENT FOR CLARIFICATIONS. DRAWING SHALL NOT BE

BY THE CONTRACTOR AT THE SITE, ANY DISCREPANCIES SHALL BE IMMEDIATELY

ALL DIMENSIONS/EXISTING CONDITIONS SHOWN SHALL BE CHECKED AND VERIFIED

C o n s u lt in g E n g in e e rs

C o rp o ra ti o n

G B S

E G

R

T E -5

-2 .d g n

DATETHOMAS C. MacALLEN

B ro a d S tr e e t, C li ft o n

N J

T E

L -8

-8

B O

R O

U G

H O

F B

O U

N D B

R O

O K

N J

A N

D S

E G

M E

N T T R

A

IS

IN

G

P R

O J E

C T S

E G

M E

N T R -2 E

X T E

N S

IO

N

G R

E E

N B

R O

O K F

L O

O D R

IS

K M

A N

A G

E M

E N

T

F

IL

M E

O n s y

M o a w a d

S u b m it t e d b y

P lo t

D a t e

K

C A

D D

G

B

P L

A N

S

A M

E N

D M

E N

T

G B

S E

G

R

T

E .d g n

:5

:3

P M

SHEET OF 124

O C

T O

B E

R

Submitted by:

Lic. No. 24GE02594500

N.J. PROFESSIONAL ENGINEER

1.

NOTES:

SEE NOTE 1

EXISTING EXHAUST FAN

EXISTING THERMOSTAT

EXISTING JUNCTION BOX

SOURCE

TO POWER

EXISTING GRADE EL. 37.30

EXISTING GRAVEL

EXOTHERMIC CONNECTION

2.

3.

4’-0"

ENCLOSURE

EXISTING

ENCLOSURE

EXISTING TOP OF GRAVEL INSIDE EXISTING

BACKFILL WITH GRAVEL TO MATCH

PROPOSED GRAVEL

EXISTING GROUND CONDUCTOR

EXISTING 3/4" X 10’ GROUND ROD TO REMAIN

TO REMAIN

WIRES

GROUNDING

EXISTING

SYSTEM

EXISTING ELECTRICAL GROUNDING

ENCLOSURE WITHOUT DISTURBING

REMOVE EXISTING UNDERGROUND

FINAL GRADE EL. 39.50

48"X48" MINIMUM INSIDE DIMENSIONS

APPROVED EQUAL) AND LADDER RUNGS

EXTERIOR DOOR WITH H20 LOADING OR

WITH ACCESS HATCH (BILCO TYPE JD-AL

UNDERGROUND ENCLOSURE COMPLETE

INSTALL NEW PRECAST CONCRETE

C-509)

(SEE DETAIL ON SHEET

LADDER RUNGS

SWITCH AT FAN

PROVIDE DISCONNECT

RECOMMENDATION AND

MANUFACTURER’S

WITH #12 AWG WIRE PER

WIRE TO NEW 1/4 HP FAN

TO EXISTING JUNCTION BOX

CONNECT NEW �" CONDUIT

AND PLUG JUNCTION BOX

EXISTING JUNCTION BOX

DISCONNECT 1/2 HP FAN FROM

CONTROL TO REMAIN

EXISTING THERMOSTAT

1’-7"

3"

430-IX. DISCONNECT SWITCH SHALL BE IN A NEMA 3R ENCLOSURE.

A DISCONNECT SWITCH FOR THE EXHAUST FAN SHALL BE PROVIDED IN ACCORDANCE WITH NEC ARTICLE

ELIMINATE CONDUIT PENETRATION OF ROOFING.

JUNCTION BOX FOR CONNECTION TO FAN. CONTRACTOR SHALL STUB-UP THROUGH RACEWAY IN CURB TO

UPON INSTALLATION OF NEW ROOFTOP EXHAUST FAN EXTEND WIRING AND CONDUIT AS REQUIRED FROM

WIRING AND CONDUIT BACK TO JUNCTION BOX AND SAFE-OFF WIRING FOR REUSE.

DISCONNECT, REMOVE AND DISPOSE EXISTING EXHAUST FAN AS INDICATED. DISCONNECT AND REMOVE EXISTING

POWER SOURCE

TO EXISTING

EXISTING TO REMAIN