UNCLASSIFIED\\FOR OFFICIAL USE ONLY

Bid Inquiry Contractor Report All Inquiries

Project: Reservoir Replacement, DLA, New Cumberland, PA Review: W912DR-17-R-0010 (00001) (sorted by CommentID ) Displaying 58 inquiries.

Id Discipline Sheet Detail Spec

6790010 Other 16 C05_W912DR-17-R- 0010_Reservoir_Replacement_Solicitation_

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Per page 16 of the RFP, Section 2.4. Factor 4 – Past Performance Questionnaires for Experience in Relevant Projects: The RFP requests that proposing firms submit USACE Past Performance Questionnaire for Relevant Experience (Form PPQ-0) for each project submitted under Factor 1. The RFP further states that "Contractor Assessment Reporting System (CPARS) ratings will not be accepted in lieu of PPQ-0s."

We have a USACE Baltimore Contracting Officer client that states they can only release formal CPARS evaluations for references, they are not to submit PPQs or similar.

Since the RFP won't allow CPARS, and our USACE Baltimore client will not submit a PPQ, we would like to request that the RFP language be amended to allow CPARS to be utilized to demonstrate Past Performance.

On: Jan 11 2017.

Government Response. . The RFP language was amended to allow CPARS to be utilized to demonstrate Past Performance per Amendment 0001. On: Jan 19 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797930 Project Management 0105500 1.12

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Specification 010500 1.12 specifies work hours are 7-3:30. Will extended work hours be allowed? Critical schedule tasks like tank erection and painting work is typically done 7 days per week as weather conditions permit. Please confirm this will be acceptable.

On: Jan 18 2017.

Government Response. . Hours beyond 7-3:30 can typically be discussed and agreed upon at the pre-construction meeting. Hours earlier than 6 am OR later than 6pm may require increased coordination.

Weekend work should be discussed at project meetings and 7 day work could be coordinated with minimal exceptions. On: Jan 20 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797931 Materials 331615 2.5 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

The reservoir mixing system is specified in 331615 2.5. Can you provide a manufacturer or model number for the solar powered reservoir mixing system that is the basis of the design?

On: Jan 18 2017.

Government Response. . Potential manufacturers with solar powered mixing systems include PAX and Solar Bee, this list is not intended to be inclusive or imply a particular requirement. System must meet the performance requirements specified in the solicitation. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797932 Engineering Management Asbuilt request

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Are there any Asbuilts or details on the construction of the existing reservoir to be demolished?

Page 1 of 13ProjNet: Logged In User

1/25/2017https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicPublicReportAl...

On: Jan 18 2017.

Government Response. . See provided drawing set (10 sheets) from recent repairs showing reservoir dimensions and details. On: Jan 20 2017 Government Response. . The text below appends or clarifies ALL previous replies.

Can you please tell me what drawing numbers are being referenced?

3240.1 through 3240.10 are attached to the original response. On: Jan 23 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797933 Site Site Visit Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Will we be able to conduct a site visit for the reservoir to determine the complete scope of work since we were unable to at the initial site visit?

On: Jan 18 2017.

Government Response. . An additional site visit will not be conducted. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797934 Survey Hazardous Survey Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Has a hazardous survey been performed on the existing reservoir for hazardous materials such as lead paint, asbestos, etc?

On: Jan 18 2017.

Government Response. . No, however the demolition site has been identified as Category I - No reason to suspect contamination will be encountered during construction. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797936 Electrical 331615 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Specification 331615 describes the electrical work for the tank, but the lighting is specified as illumination requirements, i.e. meet 20 ft candles at 2' 6" above finish floor. With the irregular shape of the tank, it is difficult to predict lighting levels and perform this design at the bid stage of the project. Thus can you provide a quantity of lighting fixtures to include as a basis of bid so we can avoid building unnecessary contingencies into our bid?

On: Jan 18 2017.

Government Response. . The contractor will be responsible for performing and submitting lighting calculations for determination of the number of lighting fixtures. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797939 General 00010 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Can the Government extend the RFI deadline to 1/23/17?

On: Jan 18 2017.

Government Response. . The Government cannot extend the RFI deadline to 1/23/2017 On: Jan 25 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797940 Equipment Dwg G2 and Dwg

C-2 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Page 2 of 13ProjNet: Logged In User

There are conflicting comments about the diameter of the tank's base. Dwg G2 Note 9 mentions a 42' column diameter. Dwg C-2 says 32'. Then the spec offers a 35' +/- dia dimension. Please confirm there is no minimum or maximum diameter for the tank's base and that it is up to the tank designer to determine this dimension.

On: Jan 18 2017.

Government Response. . Project permits a fluted column or spheroid style elevated tank. The column base diameter of each style is different and can vary by manufacture. The diameters shown are common in the industry for this size elevated tank. For the site plan the larger fluted column diameter was used since the larger diameter governs for site layout while the smaller spheroid diameter was used for the floor plan layout on C-2 such that if it fits in the smaller area we know it will fit in the larger area. There are no minimum or maximum diameters specified. It is up to the tank manufacturer to size the column diameter based on their standard design practice and that which will work adequately with foundation requirements.

Since sizes common in the industry for this size tank were used the final approved sizes should be reasonably close. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797941 Equipment Dwg C-2 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Dwg C-2 detail 2 shows there being a ladder on the exterior of the Access Tube, as does page 13 of the tank spec.

However, the main tank sketch (detail) 1 does not highlight one. Please confirm this ladder is required.

On: Jan 18 2017.

Government Response. . This ladder was inadvertently left off the main sketch Section 1 but is in the specifications and shown on the more detailed section so it is a part of the contract and should be provided. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797942 General Waterspheroid standard design

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Current industry standard designs for the Waterspheroid style of tank mandate a pressed "knuckle" at the tank's main bell-to-shaft joint, but one is not spec'd or depicted. Please confirm one is desired.

On: Jan 18 2017.

Government Response. . Not sure what the ' current industry standard design is referring to. If it is AWWA D100 then the specifications do indicate the tank should comply to this standard. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797943 Environmental 015720.0010 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Does the NPDES permit cover both the new water tank site and the existing tank site?

On: Jan 18 2017.

Government Response. . Yes On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797944 Geotechnical Geotech Report Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Please provide a complete copy of the Geotechnical Report, vs just the Boring Logs.

On: Jan 18 2017.

Government Response. . The Geotechnical Report will be added in an amendment however the document is for reference only. DO NOT USE this document as the basis for your bid. On: Jan 25 2017 Current Request Status: Request Closed

Page 3 of 13ProjNet: Logged In User

Information for this report is procurement sensitive.

6797946 Environmental 015720.0010 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Will the successful contractor be required to become a co-permitte on the permit? If so who will handle this process (Contractor or Government)?

On: Jan 18 2017.

Government Response. . Yes, the successful Contractor will be required to become a co-permitte and will be added by the Government. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797947 Electrical Lighting Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Please provide a copy of the latest FAA Determination Letter confirming that there is no special lighting or special markings req'd.

On: Jan 18 2017.

Government Response. . The FAA Determination Letter will be included in an amendment. On: Jan 25 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797950 General Tank spec item 2.1.4.3 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Page 7 of the tank spec item 2.1.4.3 says "all joints inside the tank must be flanged". Furthermore, page 13 mentions that the overflow pipe is "steel or ductile iron" (and coated inside). The dwgs, however, reference that this pipe (as well as the inlet / outlet lines) is to be welded (not flanged) stainless steel. Which governs, and what thickness do you want (we typically use sch 10 when installing expensive SS).

On: Jan 18 2017.

Government Response. . This will be addressed in Amendment 0002 On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797951 General Tank Roof seal welding

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Seal Welding of the tank roof plate's underside, normally un-welded, joint/seams should be considered so as to maximize the life of the tank's roof.

On: Jan 18 2017.

Government Response. . Bid as shown in the solicitation. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797952 Environmental Engineering C-7, C-9 9, 4

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Drawing C-7 notes 9 and C-9 note 4 call for construction oversite by a licensed professional engineer or designee.

Will this be by the Governments EOR or the Contractor?

On: Jan 18 2017.

Government Response. . Construction oversite is provided by the Government; however, Government oversite does not preclude the Quality Control (QC) requirements as stated in the solicitation. On: Jan 25 Current Request Status: Request Closed

Page 4 of 13ProjNet: Logged In User

Information for this report is procurement sensitive.

6797953 General National guideline for tank tank weld surface inspection

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Furthermore, consideration of the use of a national guideline for inspection of the tank's weld surfaces / smoothness should be added to assist your inspections. For example "NACE level C for welds in the tank's interior wet welds and NACE D for the remaining areas" would be a good suggestion.

On: Jan 18 2017.

Government Response. . Bid per specification Division 5 On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797954 Environmental Engineering C-9 5

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Drawing C-9 note 5 calls for the PCSM as-builts to be provided within six months flowing completion and for them to be signed and sealed by a licensed professional engineer. Is the requirement for the Contractor to provide as-built redline hard copies to the Government EOR and then the Government will have their EOR formalize and sign and seal them or will the Contractor be required to do all this? If this is the Contractors responsibility then please provide the submission format and quantity.

On: Jan 18 2017.

Government Response. . This is the Contractor's responsibility. CAD and PDF format is required for electronic submission. Refer to Section 01 78 00, paragraph 3.3.1 for quantities and format. On: Jan 25 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797956 General Reference to outdated code versions

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

In multiple places there are references to versions of codes that have been updated since. For example AWWA's 2005 version, when there is a 2011 edition now. Please confirm that we should design to the latest edition of all codes.

On: Jan 18 2017.

Government Response. . Yes - the reference/code/standard in effect at the time of proposal submittal should be utilized. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797957 Engineering Support C-7 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Drawing C-7, Item 9 for Sequence of Construction (both sites) – what is the frequency of construction oversite by Licensed Professional or Designee?

On: Jan 18 2017.

Government Response. . Frequency of construction oversite shall be daily, or as required. On: Jan 25 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797958 Environmental Engineering C-9 6

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Page 5 of 13ProjNet: Logged In User

Drawing C-9 note 6: Who is responsible for preparing and submitting the notice of termination?

On: Jan 18 2017.

Government Response. . The Corps/DLA is the permittee and would be responsible for terminating the permit unless stated otherwise in the contract documents. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797959 General Water heating requirements

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Please confirm that the tank does not require water heating systems nor complete certification/compliance with

NFPA.

On: Jan 18 2017.

Government Response. . The tank does not require water heating systems. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797960 Engineering Support C-9 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Drawing C-9, Items 4 & 5 of PCSM Plan Notes refers to "Permittee or Designee shall provide construction oversite" Who is this?

On: Jan 18 2017.

Government Response. . Oversite may be implemented by any and all permittees, to include Contractor, Quality Control, and Federal and State Government personnel. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797961 Electrical 331615-3 item 1.2.3.2 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Spec 331615-3 item 1.2.3.2 requires Lightning Strike calculations which are not common for tanks as they are grounded per AWWA requirements already. Please delete the need for calcs.

On: Jan 18 2017.

Government Response. . The spec wording is "Tank manufacturer to submit sufficient evidence, in the form of calculations OR other justification of how this requirement will be met." If 'or other justification' is available in the form of stating how the tank meets the NFPA 780 Chpt 3 and 4 requirements for receiving a stroke of lightning without damage, then calculations are not required. The spec wording is adequate as stated. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797962 Environmental 015720.0010 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Is a PADEP Water Supply Permit required for this project? If so then has it been obtained? (Please provide if so). If not then who is responsible for obtaining it?

On: Jan 18 2017.

Government Response. . It is not required. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797964 Engineering Support C-9 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Page 6 of 13ProjNet: Logged In User

Drawing C-9, Items 6 of PCSM Plan Notes refers to "Notice of Termination (NOT) after submission of As-Built PCSM Plans" Who is this?

On: Jan 18 2017.

Government Response. . The Corps/DLA is the permittee and would be responsible for terminating the permit unless stated otherwise in the contract documents. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797965 General 331615-13 item 2.2.1.1 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Spec 331615-13 item 2.2.1.1 references the need for two 36" manholes in the tank shaft. Please confirm that these are not required on the Waterspheroid version, as this style typically only includes a single 24" hatch at the upper painters rail.

On: Jan 18 2017.

Government Response. . The two 36" manholes are in addition to painter's hatch. These manholes are for future use by the Corps/DLA. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797966 Engineering Support C-5 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Has an approved Erosion & Sedimentation Control Plan been approved for both sites (existing reservoir and new tank sites)?

On: Jan 18 2017.

Government Response. . Yes On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797967 Structural Roof Posts Loads Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Please advise what loads the roof posts (six 2" dia x 5' tall) must support/resist, and whether gussets or kickers are required, etc.

On: Jan 18 2017.

Government Response. . The roof mounting posts are to be constructed as detailed on sheet C2, section

7. The detail shows the height as the handrail and requires gussets. At this time the Corps/DLA plans to mount cameras and/or lights to these posts. Actual loading is not available at this time. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797969 Engineering Support C-5 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Has the PADEP Water Supply Permit Modification for 'construction' of the water storage tank been obtained?

If so, who is responsible to submit for the PADEP 'operation' permit after construction of the tank has been completed?

On: Jan 18 2017.

Government Response. . PADEP Water Supply Permit is not required for this project. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797970 General 010500 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Page 7 of 13ProjNet: Logged In User

Does the tank itself require an FAA permit? If so has the Government obtained this (Please provide if so). If not who is responsible for obtaining this permit?

On: Jan 18 2017.

Government Response. . See response to Question 67979747. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797971 Engineering Support

G-1 thru FA-501 All

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Have all FAA Permits been obtained?

If so, does the FAA permit require transfer or addition of co-permittee?

Does FAA permit require submission of supplemental information for crane erection of tank during construction?

Is there an FAA permit requirement for tank top warning strobe?

On: Jan 18 2017.

Government Response. . FAA Determination Letter has been obtained and will be included in Amendment 0002. Procedueres for FAA Notification and obstruction lighting of cranes can be found in Sec 01 05 00, paragraph 1.18. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797972 Engineering Support

G-1 thru

FA-501 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Is a signed/sealed land survey required – OR – is construction layout survey only for horizontal and vertical control per plans?

On: Jan 18 2017.

Government Response. . No signed or sealed land survey is required. The contractor is required to perform the construction stakeout per the horizontal and vertical coordinates depicted in the plans. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797973 Civil C-2 331615 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Does the water tank require any aircraft warning lights? If so please advise where these can be found in the design?

On: Jan 18 2017.

Government Response. . See response to question 6797947. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797974 Engineering Support C-1 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

On Drawing C-1, Note 13 specifies the "RENTAL DIESEL HIGH CAPACITY PUMP" discharge shall be connected to the existing Pump Station (2065).

Is an engineering design required for the 'Rental diesel high capacity pump'?

Will this pump be connected to the existing test manifold on outside of PS building 2065? (FD connection does not appear to tie into system piping) What size (GPM) will the rental pump be (match existing pump capacity)?

Will a duplex pump be required while both existing electric and emergency diesel pumps are replaced?

Is frost protection (heat trace) required for temporary above-grade piping to/from high capacity pump if working in freezing conditions?

On: Jan 18 2017.

Page 8 of 13ProjNet: Logged In User

Government Response. . The existing test manifold is the "Fire Test Station" referred to on drawing C-1.

Rental fire pump requirements are stated in Article 2.18 of specification section 21 30 00.

Please refer to Article 1.6 – Construction Sequence Plan in specification section 01 11 00. At least one permanent fire pump (existing or new) will be in service at all times under this sequence. Duplex temporary pumps are not required.

Contractor is responsible for providing any necessary materials and equipment to insure the temporary pump is always available and operational. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797976 Engineering Support C-2 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Has a geotechnical investigation been completed in the area of the new water tower?

If so, can a copy of the geotechnical report be obtained?

On: Jan 18 2017.

Government Response. . Please see response to question 6797944. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797977 Mechanical C-9, DP-1, S-1

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Please provide complete mechanical as-builts for the pump and piping system at building 2065.

On: Jan 18 2017.

Government Response. . Complete mechanical as-builts cannot be provided at this time. The successful offeror can coordinate specific as-builts upon award. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797983 Mechanical 011100 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Are there specifications for the rental diesel high capacity pump and temp piping? (e.g. Pump performance criteria, service records, tie in connection points, pipe material, heat trace, controls, etc.)

On: Jan 18 2017.

Government Response. . Requirements for temporary rental pump are described in Article 2.18 of specification section 21 30 00. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6797987 Electrical 011100, 261219.10 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Are there any requirements for temp monitoring, comms, control, or power of building 2065 during the transformer change out?

On: Jan 18 2017.

Government Response. . Building power will be provided by new 100 KW generator while transformer change out is taking place. Refer to Article 1.6 e. of specification section 01 11 00 and drawing E-8. On:

Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

Page 9 of 13ProjNet: Logged In User

6797998 Civil C-5 31 23 00.00 20 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Does the Government have a borrow site that can be used to fill the existing reservoir after demolition? If so please provide location and requirements.

On: Jan 18 2017.

Government Response. . No borrow site is available. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798001 Civil 33 16 15 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Are there any chlorine monitoring requirements for the new tank?

On: Jan 18 2017.

Government Response. . Permanent chlorine monitoring is not a design requirement of the new tank.

On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798006 Civil G-2 33 40 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Do any of the valves on the 20" line downstream of the existing reservoir need to be closed in order to isolate the existing tank? If so please identify the valves(s), provide location(s), provide valve installation date(s), and date last exercised.

On: Jan 18 2017.

Government Response. . Valve 327 will isolate the existing tank. Functionality was confirmed in September 2017. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798012 Civil C-5 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Does the existing 20" line from the existing water tank to the isolation point downstream need to be filled with material or will it simply be abandoned in place?

On: Jan 18 2017.

Government Response. . Line shall be capped and abandoned in place. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798014 Electrical E-1 7 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Sheet E-1 note 7 calls for a two year warranty on the electrical scope. Please confirm this is accurate.

On: Jan 18 2017.

Government Response. . This is accurate. Bid as shown. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798019 Electrical E-1 20 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Sheet E-1 note 20. Please confirm all salvage items are as noted on the drawings and no further review is required.

On: Jan 18 2017.

Page 10 of 13ProjNet: Logged In User

Government Response. . Items shall be removed as indicated on the drawings. A list of electrical equipment to be removed shall be provided to DLA Installation Support for confirmation of salvage or removal. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798023 Civil 31 23 00.00 20 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Can the demolished concrete from the basin be used for backfilling the existing reservoir or will it need hauled off site. Also, if it can be used as backfill, what will it's maximum allowable diameter be?

On: Jan 18 2017.

Government Response. . Spec section 02 41 00 Demolition, para 3.1.1.a indicates to remove existing structures indicated to be removed in their entirety. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798079 Construction Management C-1 02000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Will DLA provide size, type, depth, quantity of existing utilities/facilities surrounding the site that may be encountered while performing underground work?

On: Jan 18 2017.

Government Response. . Utilities, other than overhead lighting, are shown on the contract drawings.

Utilities will be field marked per contract and depths can be coordinated during progress meetings. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798080 Construction Management C-1 02000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

11. Is there an approved waste site allocated for tank excavation spoils?

On: Jan 18 2017.

Government Response. . There is no approved waste site. Material must be disposed of offsite, by the Contractor, in an approved manner. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798081 Site C-5 02000 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Is there an approved borrow site for filling in of the existing reservoir site?

On: Jan 18 2017.

Government Response. . No borrow site is available. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798082 Site C-5 02 41 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Dwg C-5 refers to Specification Section 02 41 00 – Demolition: Is a Demolition Plan required?

If so, does it have to be prepared by a Professional/Engineer?

What are the limits of demolition for the existing reservoir?

Demolition of roof and infill void space to grade – or – full removal of ALL structures?

On: Jan 18 2017.

Page 11 of 13ProjNet: Logged In User

Government Response. . Para 1.2.1 requires a demolition plan to be submitted.

If so, does it have to be prepared by a Professional/Engineer? As indicated in para 1.2.1

What are the limits of demolition for the existing reservoir? As shown on sheet C5 and indicated in contract specifications On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798083 Civil C-2 33 00 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Is the new water tower going to provide both emergency fire protection, and potable water?

On: Jan 18 2017.

Government Response. . Yes. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798084 Engineering Support C-2 01000

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

What is the anticipated turnover rate for the new water tower (GPD)?

On: Jan 18 2017.

Government Response. . Per specifications:

One draw/fill cycle is approximately 16 to 28 hours and tank level drops 7 to 10 feet. The average draw rate is 160 gpm AND THE AVERAGE FILL RATE IS 2,000 GPM. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798085 Engineering Support C-2 33 00 00

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Is there any chlorine (PPM) monitoring required at the inlet/outlet of the tank?

On: Jan 18 2017.

Government Response. . Permanent chlorine monitoring is not a design requirement of the new tank.

On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798088 Engineering Support C-5 33 16 15

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Is a tank stirring / water circulating device to be provided under this contract?

On: Jan 18 2017.

Government Response. . Yes, as described in specifications. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798089 Fire

Protection/Life Safety

E-5 28 31 76

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

On drawings E-5, keyed note #6 and FA101, drawing note #1 they reference phase 2. Please describe phase 2?

On: Jan 18 2017.

Page 12 of 13ProjNet: Logged In User

Government Response. . See Project Notes on drawing FA001 for description of Phase 1 and Phase 2 of Fire Alarm/Mass Notification System installation. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

6798137 Civil C-1 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

The drawings do not show vertical profiles for the 6" DIP tank drain, 12" HDPE tank overflow pipe, 14" DIP and the 8" DIP. Can the DOR provide this information?

On: Jan 18 2017.

Government Response. . Profiles are not part of the contract drawings. On: Jan 25 2017 Current Request Status: Request Closed

Information for this report is procurement sensitive.

Report Complete