Sheet1
| Capacity | 110 gallons |
| 1st hour delivery @ 135 deg F | 325 gallons |
| Maximum 1st hour rating | 357 gallons at 140 deg F; 507 gallons at 115 deg F. |
| Pressures | Certified at 300 PSI test pressure and 150 PSI working pressure |
| Dimensions | Diameter: 28.5 inches |
| Height: 62.5 inches | |
| Heat Exchanger | Single-wall, glass coated carbon steel coil |
| Performance System | Sediment reducing device |
| Immersed Adjustable Aquastat | Fast-acting, automatic temperature control, adjustable from 80 deg F to 160 deg F. |
| Supply and return connections | 1" NPT for both supply and return |
| Insulation System | 2" non-CFC foam covering the top and sides of the tank. |
| Potable water connections | 3/4" NPT with factory installed true dielectric fittings. |
| Aluminum Anode Rods | Minimum of 3 |
| Tank | Heavy gauge steel; formed, rolled, and welded. |
| Certification | Air-Conditioning, Heating, and Refrigeration Institute certification |