TE 4.2 UPS Inventory List 1JUN2026.xlsx
XLSX spreadsheet 20 KB Posted
- Solicitation number
- W912CM26QA007
About this file
This is a UPS Inventory List documenting uninterruptible power supply systems at USAG Wiesbaden as of June 1, 2026. The inventory catalog comprises 20 UPS units distributed across multiple buildings at Clay Kaserne, including transformer stations, access control points, and infrastructure buildings. The systems vary significantly in capacity, ranging from 10 KVA to 125 KVA, with voltage levels at either 110V or 230/400/50V. Battery configurations differ by unit, utilizing manufacturers including EATON, Akkutronik, Woehrle, Riello, Legrand, and Westhaus, with battery capacities ranging from 7Ah to 200Ah and manufacture dates spanning 2009 to 2025. Each unit includes specifications such as serial number, year of construction, battery type, and maintenance requirements, with most systems requiring annual system maintenance and either annual or five-year battery replacement intervals.
This inventory list directly supports the solicitation W912CM26QA007 for Maintenance and Repair of Emergency Power and Power Generation Systems at USAG Wiesbaden, with a performance start date of approximately July 29, 2026. The contractor will be responsible for maintaining and repairing these UPS systems throughout the base period (12 months) and four optional 12-month renewal periods. The inventory provides essential technical specifications enabling contractors to assess maintenance and repair requirements, parts availability, manufacturer support needs, and labor planning for the hybrid fixed-price and time-and-materials contract. Performance will take place in Wiesbaden, Germany, and contractors must comply with all applicable German laws and regulations.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPS Inventory
| Inventory_List_UPS Systems_ USAG WIESBADEN | ||||||||||||||||
| Invent.-No. | Code | Area | Bldg-No. | Building supplied | Capacity | Battery Manufacturer | Battery capacity | Battery Type | Manufacture date of battery | Quantity of batteries | Manufacturer UPS | Type | Ser.No | Date of construction | Voltage level | Maintenance |
| BLDG | Building supplied | KVA | VOLTS,HZ | Maintenance | ||||||||||||
| UPS 001 | Clay | 1038 | DPW UEMCS | 15 | SP | 7Ah | SP12-7 | 2022 | 32 | EATON | 9155 | 23400016 | 2012 | 230/400/50 | Luefter und Batterien+ 1 Systemwartung/Jahr | |
| UPS 002 | Clay | 1086 | Transformerstation 20kV UPS (lights and network) | 20 | CTM | 26Ah | CTL150-12 | 2022 | 32 | Akkutronik | X-Plus MOD HP2 | W475P20001 | 2023 | 230/400/50 | Luefter und Batterien+ 1 Systemwartung/Jahr | |
| UPS 003 | Clay | 1090 | Access Control Point UPS (barriers, lights and network) | 40 | CTM | 12Ah | CT12-12L | 2025 | 40 | Akkutronik | X-Plus TE | TD8165DAN0004 | 2024 | 230/400/50 | Luefter und Batterien+ 1 Systemwartung/Jahr | |
| UPS 004 | Clay | 1217 | AFN | 60 | CTM | 33Ah | CTL33-12 | 2023 | 40 | Akkutronik | X-Plus MST | MA27UT552250003 | 2012 | 230/400/50 | Luefter und Batterien+ 1 Systemwartung/Jahr | |
| UPS 005 | Clay | 1761 | Transformerstation 20kV UPS (lights and network) | 20 | Sonnenschein | 50Ah | A412/50A | 24 | Woehrle | USV-WP-R50 | 4201H0001 | 2022 | 230/400/50 | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 006 | Clay | 1569 | TACAN | 10 | GP | GP1272 F2 | 2024 | 40 | Riello | Sentryum S3T 10-11 CPT | AR50UT288420008 | 2024 | 230/400/50 | Luefter und Batterien+ 1 Systemwartung/Jahr | ||
| UPS 007 | Clay | 1625 | Transformerstation 20kV UPS (lights and network) | 20 | Rpower-Battery | 134 Ah | OGiV 121340LP | 2025 | 20 | Legrand | TRIMOD LG-310432 | W465P20011 | 230/400/50 | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 008 | Clay | 1647 | Transformerstation 20kV UPS (lights and network) | 20 | Rpower-Battery | 134 Ah | OGiV 121340LP | 2025 | 20 | Legrand | TRIMOD LG-310432 | W065P20001 | 230/400/50 | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 009 | Clay | 3372 | Transformerstation 20kV UPS (protection device) | Hoppecke | 100Ah | grid power V L 6-200 | 2025 | 9 | Westhaus | E230 G110/30BWrug-SF | 13100056 | 2013 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 010 | Clay | 3547 | Transformerstation 20kV UPS (protection device) | Classic | 200 Ah | 6V OPzS 200 LA | 2025 | 18 | Westhaus | D400 G108/20 BWrg-s | 118200187/3 | 2018 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 011 | Clay | 1086 | Transformerstation 20kV UPS (protection device) | Classic | 200 Ah | 6V OPzS 200 LA | 2021 | 18 | Westhaus | D400 G108/20 BWrg-s | 118200187/1 | 2018 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 012 | Clay | 1761 | Transformerstation 20kV UPS (protection device) | Bayern Batterie | 200 Ah | 6V 4 0PzS 200 | 2020 | 18 | Westhaus | D400 G108/30 BWrg-s | 20200294 | 2020 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 013 | Clay | 1647 | Transformerstation 20kV UPS (protection device) | Hoppecke | 200 Ah | grid power V L 6-200 | 2025 | 18 | Westhaus | E230 G110/30BWrug-SF | 11100125/1 | 2011 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 014 | Clay | 1712 | Transformerstation 20kV UPS (protection device) | Hoppecke | 200Ah | 4 OPzS 200 | 2013 | 18 | Westhaus | E230 G110/30BWrug-SF | 13100149/3 | 2013 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 015 | Clay | 1625 | Transformerstation 20kV UPS (protection device) | Hoppecke | 200Ah | 4 OPzS 200 | 2011 | 18 | Westhaus | E230 G110/30BWrug-SF | 11100125/2.1 | 2011 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 016 | Clay | 1642 | Transformerstation 20kV UPS (protection device) | Hoppecke | 200Ah | 4 OPzS 200 | 2011 | 18 | Westhaus | E230 G110/30BWrug-SF | 11100125/2.2 | 2011 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | ||
| UPS 017 | Clay | 1062 | Transformerstation 20kV UPS (protection device) | Westhaus | D400 G108/20 BWrg-s | 118200187/2 | 2018 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | |||||||
| UPS 018 | Clay | 1059 | Infrastructure Bldg. #01059 | 30 | Vision | 50Ah | V-LFP51.2V50AH | 13.09.2024 | 10 | Socomec | Mosterys GP4 | P395844001 | 13.09.2024 | 230/400/50 | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr | |
| UPS 019 | Clay | 3340 | Infrastructure Bldg. #03340 | 125 | SPGN | 135Ah | SPGN12-135 | 2022 | 40 | Benkert/Socomec | Multi Sentry MST125 | 2022 | 230/400/50 | Luefter und Batterien+ 1 Systemwartung/Jahr | ||
| UPS 020 | Clay | 1507 | Transformerstation 20kV UPS (protection device) | Classic | 85Ah | 8/9/26 | 9 | Unbekannt/ | D400 G 108 /30 | AE905506 | 2009 | 110V | Batterien alle 5 Jahre+ 1 Systemwartung/Jahr |