This document provides details on a federal contract solicitation to refurbish butterfly valves and associated systems at Fort Peck Dam. The U.S. Army Corps of Engineers, Omaha District is seeking to award a contract to refurbish eighteen foot diameter spiral case inlet butterfly valves and related equipment for two generator units. Work includes refurbishing valve discs and seals, addressing coating deterioration and corrosion through sand blasting and recoating, replacing shaft and thrust bearings, and performing nondestructive testing of discs. The refurbished systems are required to be functional with limited maintenance for fifty years. Optional bid items include exterior penstock paint repairs and valve disc weld repairs. Offerors must provide all necessary personnel, equipment, certifications, and licenses to complete the project. The solicitation number is W9128F23R0009 and bids are due on 27 February 2023. Small businesses must perform fifteen percent of the work cost, excluding materials, with their own employees.

View the file

Other files

File Type Posted
W9128F23R0009 AMD 00003.pdf PDF
W9128F23R0009 Unit 5 pics 2 of 2.zip ZIP file
W9128F23R0009 Unit 5 pics 1 of 2.zip ZIP file
W9128F23R0009 Unit 4 pics 1 of 2.zip ZIP file
W9128F23R0009 Unit 4 pics 2 of 2.zip ZIP file
W9128F23R0009 30MAR2023 Site Visit Roster.pdf PDF
W9128F23R0009 AMD 00002.pdf PDF
Ref File 1-4 5Dec19 NDT Report FP BFV Unit 4.pdf PDF
Ref File PP2 3-4 - 18ft_BFV__Manual_1960.pdf PDF
Ref File 2-4 5May20 NDT Report FP BFV Unit 5.pdf PDF
Ref File PP2 4-4 - 18Ft_BFV_Design-Specs_1959.pdf PDF
W9128F23R0009 - 3_9_2023 Site Visit Sign in.pdf PDF
W9128F23R0009 AM0001.pdf PDF
01 33 00 AM0001.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part5.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part10.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part9.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part2.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part11.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part8.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part7.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part1.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part4.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part6.pdf PDF
FPP_PENSTOCK BUTTERFLY VALVE REHAB VOL2 (PH2)_REFERENCE_BCOES_4-4-22_Part3.pdf PDF
W9128F23R0009 FP BDFV Sol DWGs Complete 3 of 3.pdf PDF
W9128F23R0009 FP Butterfly valve Rehab Specs 2 of 3.pdf PDF
W9128F23R0009 Butterfly Valve Drawings 1_23 3 of 3.pdf PDF
W9128F23R0009 FP Butterfly Valve Advertisement 1 of 3.pdf PDF
W9128F23R0009 FP Butterfly valve Rehab Specs 2 of 3.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WELCOME

FORT PECK DAM

POWERHOUSE #2 BUTTERFLY

VALVE REHABILITATION

INDUSTRY DAY

SOLICITATION: W9128F23R0009

17 NOV 2022 / 11:00 MST

To join the meeting:

https://usace1.webex.com/meet/ronald.s.beyer

Conference line: 1-844-800-2712 (Toll-Free)

1-669-234-1177 (US)

Access Code: 199 032 3791

INTRODUCTIONS

USACE, Omaha District Office Ron Beyer Project Manager Robin Puskar Program Manager Dan Monahan Contracting Officer Lynne Reed Contract Specialist Mo Al Soufi Mechanical Engineer

Fort Peck Dale Pugh Maintenance and Operations Manager Tom Grant Mechanical Engineer Mike Bratz Senior Power Plant Mechanic Irene Whitmer Electrical Engineer

Missouri River Construction Office Tom Westenburg Resident Engineer

Hydroelectric Design Center (HDC), Portland Dan Lundy Mechanical Engineer Kwadwo Amankwa-Poku Electrical Engineer Sean Kim Structural Engineer

AGENDA – NOV 17, 2022

1100 – 1105 Introductions / Project Overview 1105 – 1110 Contracting Briefing / Rules of Engagement 1110 – 1130 Statement of Work / Project Specs 1130 – 1200 Project Site Specifics 1200 – 1230 Q&A

PROJECT OVERVIEW

Objective is to reduce internal bypass leakage on Units 4 and 5 valve discs and address component end of life and system reliability

1) Refurbish the eighteen (18) foot spiral case butterfly valve in Units 4 and 5

2) Manufacture and install new Hydraulic Power Units (HPUs) and related equipment in Units 4 and 5

3) Optional Items

• Ultrasonic testing of Tunnel 2, and the Units 4 and 5 penstock

• Penstock External Paint System Repairs

• Butterfly Valve Weld Repairs as needed

RULES OF ENGAGEMENT

DAN MONAHAN, CONTRACTING OFFICER

• No side bars or independent conversations between contractors and government personnel.

• No discussions relating to other Corps acquisitions.

• No corporate denigration or sabotage will be tolerated.

• Hold all questions until the designated question and answer session.

• The Government will address general questions during this briefing. Specific questions must be entered into ProjNet via the published Bidder Inquiry Key.

• There will be a site visit opportunity once the solicitation is posted.

PROJECTED SCHEDULE

Pre-solicitation Late Dec 2022 Advertise Period Jan-Feb 2023 (30-day advertisement period)

Contractor Site Visit TBD (posted with solicitation)

Award Mar/Apr 2023

Penstock Outage Start 16 September 2024 End 24 January 2025 (130 calendar days)

CONTRACT AND EVALUATION INFORMATION

Contract Information

• Contract Type: Firm Fixed Price Construction

• Solicitation Type: Request for Proposal (RFP)

• Contract Magnitude: $1M-$5M

• Period of Performance: NTP (Est. April 2023) – Jan 2025 (Note: onsite work must be completed by 24Jan2025)

Evaluation Factors

• Factor 1 Past Performance (most important)

• Factor 2 Technical Approach (second most important)

• Factor 3 Personnel Qualifications and Experience (equal to factor 2)

• Factor 4 Small Business Participation (significantly less important than factors 1-3)

• Factor 5 Price (Least important factor. All evaluation factors other than price, when combined, are considered significantly more important than Price.)

PROJNET AND CONTACT INFORMATION

ProjNet

• Used for Contractor(s) to submitted questions

• Website: https://www.projnet.org

• Virtual Industry Day Bidder Inquiry Key: E3BCGG-7ABR3E

• Questions need to be submitted before 4 pm Mountain Standard Time, 20 NOV 2022

Contract Specialist Contact Information

Lynne Reed

• Email: Lynne.D.Reed@usace.army.mil

• Phone: 402-995-2039

9File Name

STATEMENT OF WORK

AND

PROJECT SPECS

HYDROELECTRIC DESIGN CENTER

DAN LUNDY, MECHANICAL ENGINEER

Functional Areas

• Mechanical Scope of Work

• Butterfly Valves

• Hydraulic Power Systems

• Scroll Case and Tunnel Drain Valves

• Other

»Tunnel 2, Unit 4, and Unit 5 Penstock Ultrasonic Testing (optional)

»Penstock Paint Repairs - 10 Locations (optional)

• Electrical Scope of Work

• Electrical Equipment for Hydraulic Power Systems

• Electrical Equipment for Motor Operated Bypass Valves, and Misc.

Mechanical Scope of Work:

(1) Refurbishment of two (2) 216-inch diameter penstock BFVs, performed simultaneously.

• valve disc seal;

• stainless-steel overlay body seat;

• valve internal surfaces (LBP abatement, blast, and recoating);

– Inspect butterfly valve welds;

– Repair butterfly valve welds (OPTION);

Removal and replacement of:

• upper stub shaft (trunnion) bearing and seals;

• lower stub shaft (trunnion) bearing and seals, and thrust bearing assemblies;

– Adjust and align disc leaf seals (contact bluing check);

Mechanical Scope of Work:

(2) Two new complete Penstock BFV grease lubrication systems, including:

Removal and replacement of:

• grease lines;

• grease lubrication components and supporting systems;

Mechanical Scope of Work

(3) Refurbishment of two Penstock BFV bypass systems, including:

Removal and replacement of:

– Limitorque motor operated gate valve with manual handle;

– bypass system piping;

– absolute pressure switch,

– system controls;

Install new manually operated isolation gate valve; and new equalizing line pressure monitoring system;

(4) Refurbishment of two spiral case drain valves:

Removal and replacement of:

• manual gate valve with new manual operated gate valve;

• insulation;

• limit switch;

(5) Refurbishment of tunnel drain valve:

Removal and replacement of:

• one manual gate valve (current location, as shown);

• piping and insulation;

• heating cable and thermostat;

(6) Provide new second manual operated gate valve located as shown;

(7) New maintenance platforms, ladders and guardrails for each BFV;

(8) Modify access hatch for each BFV;

(9) Furnish spare parts, including two sets of bronze metal disc seals.

Hydraulic Scope of Work

• The work specified includes, but is not limited to, all appurtenances required for a complete, fully functional installed hydraulic power system.

• The new BFV operators, HPUs, and associated systems must be identical and interchangeable.

(1) Design and provide two BFV operators (quarter-turn hydraulic cylinder actuators) with integral mechanical locking device:

–Remove existing BFV operator and associated plumbing;

–Install new BFV operator with integral mechanical locking device, and new plumbing;

Hydraulic Scope of Work

(2) Design and provide two BFV HPUs with controls and offline oil filtration system:

• Remove existing BFV HPU and associated plumbing;

• Install new BFV HPU and associated plumbing;

Electrical Scope of Work

Supply and installation of:

(1) New motor actuators for the penstock fill bypass valves and remote operators, remote open/close indicators and control systems, one each for Unit 4 and Unit 5;

(2) Limit switches and wiring for new manually operated spiral case drain valves one each for Unit 4 and Unit 5;

Electrical Scope of Work

(3) Supply and installation of new wall mounted 480VAC panels which contain a disconnect switch, motor starter and control power transformer as follows:

• 2-480VAC panel (BVQ) for the HPU pump motors for each unit:

• BVQ1 - 480VAC panel for HPU pump 1

• BVQ2 - 480VAC panel for HPU pump 2

• Two (2) - oil filtration system 480VAC panels (FSQ), one for each unit's HPU

• Two (2) - 480VAC panel (VP), one for each bypass valve motor actuator

(4) Supply and installation of new heat tape and thermostat for the tunnel drain valve

20File Name

PROJECT SITE

SPECIFICS

FORT PECK PROJECT BRIEF

DAN LUNDY AND TOM GRANT

CONTRACTOR STAGING & WORK AREAS (SHEET G-401 & MD201)

CONTRACTOR STAGING & WORK AREAS (SHEET MD201)

EL 2070.0 SURGE TANK STRUCTURE

EL 2052.0 BFV CORRIDOR

EL 2023.5 BUTTERFLY VALVE ROOM

CONTRACTOR STAGING & WORK AREAS

TUNNEL #2 PENSTOCKS 4 & 5

BIFURCATION

CONTRACTOR STAGING AND WORK AREAS (SH MD101)

SURGE TANK STRUCTURE, EL 2070.00

Office Trailer

10T MONORAIL HOIST

SURGE TANK

STRUCTURE

BFV ACCESS

HATCHES

CONTRACTOR STAGING AND WORK AREAS (SH MD102)

BUTTERFLY VALVE CORRIDOR, EL 2052.00

BFV ACCESS

HATCHES

CONTRACTOR STAGING AND WORK AREAS (SH MD102)

BFV ACCESS

HATCHES

FREIGHT

ELEVATOR

CONTRACTOR STAGING AND WORK AREAS

18 FT (216 INCHES)

BUTTERFLY VALVE

EL 2023.50

EL 2023.50

NORTH EXTERIOR

IMAGES OF

18 FT (216 INCHES)

SOUTH EXTERIOR

18 FT (216 INCHES)

UPSTREAM UNDERSIDE

EXTERIOR IMAGE OF

18 FT (216 INCHES)

DOWNSTREAM

UNDERSIDE EXTERIOR

IMAGES OF

18 FT (216 INCHES)

TOPSIDE EXTERIOR

18 FT (216 INCHES)

INTERIOR IMAGE OF

BUTTERFLY VALVE

INTERNAL LEAKAGE

GOVERNMENT SEAL

ADJUSTMENT U4: 2006

UNIT 4 UNIT 5

CLOSE-UP OF VALVE DISC BRONZE SEAL

CLOSE-UP OF VALVE DISC BRONZE SEAL

STAINLESS STEEL

OVERLAY BODY

SEAT AND

INTERNAL

SURFACES

WISCO DWG H-4070

STAINLESS STEEL

OVERLAY BODY

SEAT AND

INTERNAL

SURFACES

WISCO DWG H-4070

WELDS

WISCO DWG H-4075

(UPSTREAM SIDE)

(DOWNSTREAM

SIDE)

(DOWNSTREAM

SIDE)

UPPER AND LOWER

STUB SHAFT

(TRUNNION)

BEARINGS

UPPER STUB

SHAFT (TRUNNION)

BEARING

LOWER STUB

SHAFT (TRUNNION)

BEARING & THRUST

BEARING

EXISTING GREASE LUBRICATION SYSTEM

(UNIT 4 SHOW, UNIT 5 SIMILAR)

EXISTING GREASE LUBRICATION SYSTEM

(UNIT 4 SHOW, UNIT 5 SIMILAR)

EXISTING BFV BYPASS SYSTEMS

EXISTING BFV BYPASS SYSTEMS

BYPASS VALVE & PIPING, & ABSOLUTE

PRESSURE SWITCH

EXISTING

LIMITORQUE GATE

VALVE – BYPASS

VALVE OPERATOR

BFV POSITION

INDICATOR

BFV ACCESS

HATCH

MAINTENANCE

ACCESS HATCH

EXISTING BFV HPU

BYPASS VALVE

CONTROLS &

INDICATION

BFV CONTROLS &

INDICATION

BYPASS VALVE

CONTROLS BFV CONTROLS

EXISTING SPIRAL CASE DRAIN VALVES

EXISTING TUNNEL DRAIN VALVES

EXISTING MAINTENANCE LADDERS & PLATFORMS

EXISTING BFV MAINTENANCE ACCESS HATCH

HYDRAULIC POWER SYSTEMS

BFV OPERATOR

HYDRAULIC POWER SYSTEMS

BFV HPU

TUNNEL #2, UNIT 4 & 5 PENSTOCK ULTRASONIC TESTING

AND PAINT REPAIR LOCATIONS (S-101)

TUNNEL #2, UNIT 4 & 5 PENSTOCK ULTRASONIC TESTING

AND PAINT REPAIR LOCATIONS (S-101)

UNIT CONTROL SWITCHBOARD &

MCC’S ON TURBINE FLOOR,

EL. 2049.00 (E-101 & E-201)

ELECTRICAL WORK

MCC4 DC

DIST. PANEL

INSTRUMENT CONTROL BOARD,

CONTROL ROOM (E-202)

ELECTRICAL WORK

MOTOR ACTUATORS

FOR BYPASS VALVE

OPERATORS, W/

REMOTE

OPEN/CLOSE

INDICATORS &

CONTROLS

SUPPLY/INSTALL

NEW LIMIT

SWITCHES FOR

SPIRAL CASE DRAIN

(SH M-420)

SUPPLY/INSTALL

NEW LIMIT

SWITCHES FOR BFV

POSITION

INDICATOR

(SH M-420 &

M-601)

WALL MOUNTED

480VAC PANELS

W/ DISCONNECT

SWITCHES, MOTOR

STARTER, &

CONTROL POWER

TRANSFORMER

FOR:

HPU PUMPS 1 & 2

OIL FILT. SYST.

BYPASS VALVE

MOT. ACTUATOR

(SH E-101)

NEW HEAT TAPE

AND THERMOSTAT

FOR TUNNEL DRAIN

VALVE

(SH M-430)

POST-INDUSTRY DAY

Q & A

Welcome��Fort peck Dam�Powerhouse #2 Butterfly Valve rehabilitation��Industry Day�Solicitation: W9128F23R0009��17 Nov 2022 / 11:00 MST���
introductions
Agenda – Nov 17, 2022
Project overview
Rules of engagement�Dan Monahan, contracting officer
Projected schedule
Contract and evaluation information�
Projnet and contact information�
��Statement of work�and�project Specs�
Statement of Work�
Statement of work�
Statement of work�
Statement of work�
Statement of work�
Statement of work�
Statement of work�
Statement of work�
Statement of work�
Statement of work�
��Project SITE�Specifics�
Contractor staging & work areas (sheet g-401 & md201)
Contractor staging & work areas (sheet md201)
Contractor staging & work areas
Contractor staging and work areas (sh md101)�surge tank structure, el 2070.00
Contractor staging and work areas (sh md102) �butterfly valve corridor, el 2052.00
CONTRACTOR STAGING AND WORK AREAS (SH MD102) �BUTTERFLY VALVE CORRIDOR, EL 2052.00
CONTRACTOR STAGING AND WORK AREAS �BUTTERFLY VALVE CORRIDOR, EL 2052.00
18 ft (216 inches) �butterfly valve��EL 2023.50�
18 ft (216 inches) �butterfly valve��EL 2023.50�
North Exterior Images of �18 ft (216 inches) �butterfly valve�
South Exterior Images of �18 ft (216 inches) �butterfly valve�
Upstream Underside Exterior Image of �18 ft (216 inches) �butterfly valve�
downstream Underside Exterior Images of �18 ft (216 inches) �butterfly valve�
Topside exterior Images of �18 ft (216 inches) �butterfly valve�
Interior Image of �18 ft (216 inches) �butterfly valve�
Interior image of �18 ft (216 inches) �butterfly valve�
Interior image of �18 ft (216 inches) �butterfly valve��internal leakage��Government seal adjustment u4: 2006�
close-up of Valve disc bronze seal
close-up of Valve disc bronze seal
Stainless steel overlay body seat and internal surfaces �WISCO dwg H-4070
Stainless steel overlay body seat and internal surfaces �WISCO dwg H-4070
Butterfly valve welds��WISCO DWG H-4075
Butterfly valve welds��(upstream side)
Butterfly valve welds��(upstream side)
Butterfly valve welds��(upstream side)
Butterfly valve welds��(downstream side)
Butterfly valve welds��(downstream side)
Upper and lower stub shaft (trunnion) bearings
Upper stub shaft (trunnion) bearing
Lower stub shaft (trunnion) bearing & thrust bearing
Slide Number 51
Slide Number 52
Existing BFV bypass systems�
Existing BFV bypass systems�bypass valve & piping, & absolute �pressure switch�
Slide Number 55
Slide Number 56
Existing Spiral case drain valves�
Existing tunnel drain valves�
Existing maintenance ladders & platforms�
Existing bfv maintenance access hatch �
Hydraulic power systems
Hydraulic power systems
Tunnel #2, unit 4 & 5 penstock ultrasonic testing�and paint repair locations (S-101)
Tunnel #2, unit 4 & 5 penstock ultrasonic testing�and paint repair locations (S-101)
Unit control switchboard & mcc’s on Turbine floor, �el. 2049.00 (E-101 & e-201)
Instrument control board, �control room (E-202)
Motor actuators for bypass valve operators, w/ �remote open/close indicators & controls
Supply/install new limit switches for spiral case drain��(sh m-420)
Supply/install new limit switches for bfv position indicator��(sh m-420 &�m-601)
Wall mounted �480VAC panels�w/ disconnect switches, motor starter, & control power transformer for:�� hpu pumps 1 & 2�Oil Filt. Syst.�bypass valve mot. actuator��(sh e-101)
New heat tape and thermostat for tunnel drain valve��(sh m-430)
Post-industry day�Q & A