This announcement constitutes a solicitation notice for a firm fixed-price construction contract to repair Building 503A located at Fort Shafter, Hawaii. The project scope includes renovating existing barracks modules and common areas, replacing interior finishes, and reconfiguring utilities. The performance period is 780 calendar days with a project magnitude between $25-50 million. The procurement will utilize LPTA procedures and evaluate offerors based on experience, past performance, technical approach, and price. The closing date for proposals is August 28, 2020. The government intends to award to the best valued offeror who must be registered in SAM and comply with small business subcontracting goals.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY20 OMA REPAIR BUILDING 503A
SECTION TABLE OF CONTENTS
DIVISION 14 - CONVEYING EQUIPMENT
ELECTRIC TRACTION PASSENGER ELEVATORS
05/16
PART 1 GENERAL
1.1 REFERENCES
1.2 SUMMARY
1.2.1 Fire Protection System
1.2.2 Miscellaneous Requirements
1.2.3 Provisions for Earthquake Protection
1.3 SUBMITTALS
1.3.1 Shop Drawing Requirements
1.3.2 Product Data Requirements
1.3.3 Design Data
1.3.3.1 Reaction Loads
1.3.3.2 Heat Loads
1.3.3.3 (DELETED)
1.3.4 Detail Drawings
1.3.5 Welders' Requirements
1.3.6 Maintenance Control Program (MCP)
1.4 SCHEDULING
1.5 WARRANTY
1.6 MAINTENANCE AND REPAIR ACTION PLAN
1.7 QUALITY ASSURANCE
1.7.1 Qualification
1.7.1.1 Elevator Specialist
1.7.1.2 Elevator Inspector
1.7.1.3 Elevator Contractor's Elevator Technicians
1.7.2 Manufacturers' Technical Support
1.7.3 Operation and Maintenance Data
1.7.4 Wiring Diagrams
1.7.5 Machine Room Cabinet
1.8 NEW INSTALLATION SERVICE
1.8.1 Periodic Elevator Certification Inspection and Testing
1.9 FIRE PROTECTION SYSTEM
1.9.1 Fire Alarm Initiating Devices
1.9.2 Fire Sprinklers
1.9.3 Shunt Trip Disconnect
PART 2 PRODUCTS
2.1 ELEVATOR DESCRIPTION
2.1.1 Elevator Design Parameters
2.1.1.1 Non-EMSA Elevator
2.1.2 Cab Enclosure and Hoistway Entrance Assemblies
2.2 ELEVATOR OPERATION
2.2.1 Selective Collective Automatic Operation
2.3 SPECIAL OPERATION AND CONTROL
2.3.1 Keys for Elevator Key Switches
2.3.2 Firefighters' Service
2.3.3 Smoke Detectors
SECTION 14 21 23 Page 1 (Am-0003)
2.3.4 Top-of-Car Operating Device
2.3.5 Hoistway Access Switches
2.3.6 In-Car Inspection Operation
2.3.7 Independent Service
2.3.8 Elevator Auxiliary Power Operating System
2.4 ELEVATOR DRIVE MACHINE, HOIST MOTOR, AND DRIVE MOTOR
2.4.1 Manufacturer's Factory Training and Technical Support
2.4.2 Ascending Car Overspeed and Unintended Car Movement Protection
2.5 CONTROL EQUIPMENT
2.5.1 Motor Control Equipment
2.5.1.1 Motor Generator Set
2.5.1.2 SCR Control or VVVF AC Control
2.5.1.3 Electrical Isolation Protection
2.5.2 Logic Control
2.5.2.1 On-Board Diagnostic Panel
2.5.2.2 External Port
2.5.2.3 Repair Requirements
2.5.3 Elevator Microprocessor Controller
2.5.3.1 Elevator Controller Interface Cabinet
2.5.3.1.1 Elevator Microprocessor Human Interface
2.5.3.2 Software and Documentation
2.5.3.3 Elevator Controller Certification
2.6 OPERATING PANELS, SIGNAL FIXTURES, AND COMMUNICATIONS CABINETS
2.6.1 Car and Hall Buttons
2.6.2 Passenger Car-Operating Panel
2.6.2.1 Passenger Controls
2.6.2.2 Service Controls
2.6.2.3 Certificate Window
2.6.2.4 Emergency Signaling Devices
2.6.3 Switches and Devices
2.6.4 In-Car Position and Direction Indicator and Signal
2.6.4.1 In-Car Position Indicator and Signal
2.6.4.2 In-Car Direction Indicator and Signal
2.6.5 Landing Position and Direction Indicator and Signal
2.6.5.1 Landing Position Indicator and Signal
2.6.5.2 Landing Direction Indicator and Signal
2.6.6 Elevator In-Car Position Indicators
2.6.7 Elevator In-Car Direction Indicators
2.6.8 Hall Call Landing Fixtures
2.6.8.1 Designated Landing Hall Call Fixture
2.6.8.1.1 Location of COMMUNICATION MEANS FAILURE (CMF) Visual
Signal
2.6.8.1.2 COMMUNICATION MEANS FAILURE (CMF) Visual and Audible
Signal Operation
2.6.8.1.3 Firefighters' Emergency Operation Phase I Switch and
Visual Signal
2.6.9 Elevator Car Position and Direction Indicators and Car Arrival
Signal
2.6.10 Designated Landing Elevator Identification Fixture
2.6.11 (DELETED)
2.7 CAR DOOR EQUIPMENT
2.7.1 Car Door Operator
2.7.2 Infra-red Curtain Unit
2.8 PASSENGER ELEVATOR GUIDES, PLATFORM, AND ENCLOSURE
2.8.1 Roller Guides
2.8.2 Car Frame and Platform
2.8.3 Car Enclosure Wall Panels, Return Panels, Doors, Entrance
Columns, and Transom
2.8.4 Car Enclosure, Car Door, and Car Illumination
SECTION 14 21 23 Page 2
2.8.5 Car Enclosure Top
2.8.6 Car Door
2.8.7 Car Entrance Sill
2.8.8 Cab Finish Floor
2.8.9 Car Fan
2.8.10 Car Lighting
2.8.11 Car Protection Pads and Hooks
2.9 PASSENGER ELEVATOR HOISTWAY DOORS AND ENTRANCES
2.9.1 Hoistway Entrance Frames
2.9.2 Hoistway Ventilation
2.9.3 Hoistway Entrance Sills
2.9.4 Hoistway Entrance Doors
2.9.5 Hoistway Entrance Door Track Dust Covers
2.10 HOISTWAY AND CAR EQUIPMENT
2.10.1 Car and Counterweight Guide Rails and Fastenings
2.10.2 Car and Counterweight Buffers
2.10.3 Pit Equipment Support Channels
2.10.4 Pit "STOP" Switch
2.10.5 Traveling Cables
2.10.6 Hoistway Pit Ladder
2.10.7 Car and Counterweight Buffers
2.10.8 Lighting of Pits
2.10.9 Terminal Stopping Devices
2.10.10 Wiring and Traveling Cables
2.10.11 Emergency Signaling Devices
2.11 PASSENGER CAR AND HOISTWAY DOOR ACCESSORIES
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Structural Members and Finish Materials
3.1.2 Miscellaneous Requirements
3.1.3 Safety Guards
3.1.4 Firefighters' Service
3.2 FIELD QUALITY CONTROL
3.3 ACCEPTANCE INSPECTION, TESTING AND COMMISSIONING
3.3.1 Acceptance Inspection Support
3.3.2 Testing Materials and Instruments
3.3.3 Field Tests
3.3.3.1 Endurance Tests
3.3.3.2 Speed Tests
3.3.3.3 Insulation Resistance Tests
3.3.3.4 Brake Test
3.3.3.5 Buffer Test
3.3.3.6 Leveling Tests
3.3.3.7 Temperature Rise Tests
3.3.3.8 Balanced Load Test
3.3.3.9 Motor Ampere Tests
3.3.3.10 Elevator Performance and Ride Quality Testing
-- End of Section Table of Contents --
SECTION 14 21 23 Page 3
SECTION 14 21 23
ELECTRIC TRACTION PASSENGER ELEVATORS
05/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2017) Minimum Design Loads for Buildings and Other Structures
AMERICAN WELDING SOCIETY (AWS)
AWS B2.1/B2.1M (2014; Errata 2015) Specification for Welding Procedure and Performance Qualification
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASME INTERNATIONAL (ASME)
ASME A17.1/CSA B44 (2016) Safety Code for Elevators and Escalators
ASME A17.2 (2017) Guide for Inspection of Elevators, Escalators, and Moving Walks Includes Inspection Procedures for Electric Traction and Winding Drum Elevators, Hydraulic Elevators, and Escalators and Moving Walks
ASME A17.3 (2017) Safety Code for Existing Elevators and Escalators
ASME QEI-1 (2018) Standard for the Qualification of Elevator Inspectors
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2018) International Building Code
SECTION 14 21 23 Page 4
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA MG 1 (2018) Motors and Generators
NATIONAL ELEVATOR INDUSTRY, INC. (NEII)
NEII-1 (2000; R thru 2017) Building Transportation Standards and Guidelines, including the Performance Standards Matrix for New Elevator Installation
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2018; TIA 18-1; TIA 18-2; TIA 18-3) Life Safety Code
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
NFPA 70E (2018; TIA 18-1; TIA 81-2) Standard for Electrical Safety in the Workplace
NFPA 72 (2016; Errata 1 2018) National Fire Alarm and Signaling Code
NFPA 252 (2017) Standard Methods of Fire Tests of Door Assemblies
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-560-01 (2017) Operations and Maintenance:
Electrical Safety
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 SUMMARY
Provide a pre-engineered elevator system, by manufacturer regularly engaged in the manufacturer of elevator systems, that complies with ASME A17.1/CSA B44 and ASME A17.2 in their entirety, and additional requirements specified herein.
1.2.1 Fire Protection System
Provide a fire protection system complying with the applicable provisions of NFPA 72, NFPA 101, and ASME A17.1/CSA B44. Additional fire protection requirements are found in the Design Drawings and Section 26 20 00 INTERIOR
DISTRIBUTION SYSTEM.
SECTION 14 21 23 Page 5
1.2.2 Miscellaneous Requirements
Submit one set of wiring diagrams, in plastic or glass cover, framed and mounted in elevator machine room for revised building electrical system, if needed, to make supplied elevator system function as specified. Deliver other sets to Contracting Officer. Coded diagrams are not acceptable unless adequately identified. Submit calculations for the Reaction Loads imposed on the building by the elevator system and Heat Loads generated by the elevator system.
1.2.3 Provisions for Earthquake Protection
This facility is located in seismic zone 3 and shall comply with all ASME A17.1/CSA B44, Part 8, Section 8.4 requirements as applicable by location.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Detail Drawings
Elevator System
Elevator Components
Elevator Machine
Elevator Controller
Wiring Diagrams
SD-03 Product Data
Elevator and Accessories
Elevator Components
Data Sheets
Elevator Microprocessor Controller
SD-05 Design Data
Heat Loads
Reaction Loads
SD-07 Certificates
Elevator Parts and Components Price Lists
Warranty
Welders' Qualifications
SECTION 14 21 23 Page 6
Elevator Controller Certification
SD-10 Operation and Maintenance Data
Elevator, Data Package 4
Maintenance and Repair Action Plan
Maintenance Control Program (MCP)
1.3.1 Shop Drawing Requirements
Provide assembly and arrangement of elevators, accessories, and elevator components. Show location of elevator machine in elevator machine room (MR) or machinery space (MS). Show location of elevator controller in elevator machine room. Provide details for materials and equipment, including but not limited to operating and signal fixtures, doors, door and car frames, car enclosure, controllers, motors, guide rails and brackets, layout of hoistway in plan and elevation, and other layout information and clearance dimensions.
1.3.2 Product Data Requirements
Provide manufacturers' product data for all elevator components, including but not limited to the following: elevator controller, hoist machine and drive motor, design counterbalance, hoist ropes and shackles, overspeed governor, emergency braking system, car and hall fixture buttons and switches, cab, machine room, and machinery space communication devices, door operator, door protection system, and car and counterweight roller guides and buffers. For data sheets, provide document identification number or bulletin number, published or copyrighted prior to the date of contract bid opening. Provide controller manufacturer's published procedures for performance of each and all testing required by
ASME A17.1/CSA B44.
1.3.3 Design Data
1.3.3.1 Reaction Loads
Provide calculations by registered professional engineer for reaction loads imposed on building by elevator system. Calculations must comply with ASCE 7 and ASME A17.1/CSA B44
1.3.3.2 Heat Loads
Provide calculations from elevator manufacturer, or by registered professional engineer, for total anticipated heat loads generated by all of the elevator equipment.
1.3.3.3 (DELETED)
1.3.4 Detail Drawings
a. Submit Detail Drawings, including dimensioned layouts in plan and elevation, showing the arrangement of elevator equipment, accessories, and data sheets showing all:
(1) supporting systems, SECTION 14 21 23 Page 7
(2) Anchorage of equipment,
(3) Clearances for maintenance and operation;
(4) Details on hoistway,
(5) Doors and frames,
(6) Operation and signal stations
(7) Machinery and Controls,
(8) Motors,
(9) Guide rails and brackets,
(10) Points of interface with normal power.
(11) Fire alarm system
(12) HVAC or exhaust systems
b. Include in Drawings complete wiring diagrams showing electrical connections and other details required to demonstrate sequence of operations and functions of system devices, and the appropriate sizing of electrical protective devices which are frequently different from National Electrical Code standard sizes. Drawings shall show any revised building electrical system required to make supplied elevator system function as specified.
1.3.5 Welders' Requirements
Comply with AWS D1.1/D1.1M, Section 4 and AWS B2.1/B2.1M. Provide certified copies of field welders' qualifications and list welders' names with corresponding code marks to identify each welder's welding work
1.3.6 Maintenance Control Program (MCP)
For each elevator, prepare and provide a written Maintenance Control Program (MCP) that complies with ASME A17.1/CSA B44 Section 8.6, including written documentation that details the test procedures for each and every test that is required to be performed by ASME A17.1/CSA B44. Assemble all MCP documentation, and supporting technical attachments, in a single MCP package and provide in both electronic and hard copy. Assemble entire hard copy MCP in 3-ring binders. For each elevator provided, the MCP must include only documentation and instruction that apply to the elevator specified.
For each elevator, provide an additional, separate binder that includes all maintenance, repair, replacement, call back, and other records required by ASME A17.1/CSA B44. The records binder must be kept in the elevator mechanical room, maintained by elevator maintenance and service personnel, and be available at all times to authorized personnel.
Provide detailed information regarding emergency service procedures and elevator installation company personnel contact information. Provide a listing of all tools to be provided to the Contracting Officer as components of the elevator system.
SECTION 14 21 23 Page 8
1.4 SCHEDULING
Every six months, test systems for emergency CAB light and bell battery operation, Earthquake Emergency Operations, and Firefighters' Service.
Schedule to not interfere with building operations. For Firefighter's Service, test monthly in accordance with ASME A17.1/CSA B44, Paragraph
8.6.11.1. Provide written results of each test operation to the Contracting Officer.
1.5 WARRANTY
Provide routine warranty service in accord with the manufacturer's warranty requirements, for a period of 12 months after the date of acceptance by Contracting Officer. Perform work during regular working hours. During the warranty service period, include 24-hour emergency service, with 1 hour response time, without additional cost to the Government. Include adjustments, greasing, oiling, and cleaning. Provide routine inspection and tests of elevators in accordance with ASME A17.1/CSA B44 (Section 8.10) and ASME A17.2. Provide supplies and parts to keep elevator system in operations. Perform service only by factory trained personnel. Maintain a maintenance log of all service orders performed during the warranty period and submit it to the Contracting Officer 21 days prior to the end of the warranty period.
1.6 MAINTENANCE AND REPAIR ACTION PLAN
Provide plan of action by the Elevator Installation Contractor to provide emergency and routine maintenance in accordance with paragraph titled WARRANTY. In addition to Data Package SD-19 "Operation and Maintenance Manuals", provide a list of phone numbers, personnel contacts, and all tools to be provided to the Contracting Officer. Submit elevator manuals in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.
Provide OEM Maintenance Control Program per ASME A17.1/CSA B44.
1.7 QUALITY ASSURANCE
1.7.1 Qualification
Provide a designed and engineered elevator system by an elevator contractor regularly engaged in the installation of elevator systems. Provide elevator components manufactured by companies regularly engaged in the manufacture of elevator components. Utilize only licensed and certified elevator personnel for the installation, adjusting, testing, and servicing of the elevators.
1.7.1.1 Elevator Specialist
Work specified in this section shall be performed in compliance with ASME A17.3 under the direct guidance of the Elevator Specialist who is regularly engaged in the installation and maintenance of the type and complexity of elevator system specified in the contract documents, and who served in a similar capacity for at least three systems that have performed in the manner intended for a period of not less than 24 months. Elevator system manufacturer shall provide a letter of endorsement certifying that the Elevator Specialist is acceptable to manufacturer. The Elevator Specialist shall oversee the acceptance inspections and tests, and sign and certify the successful results, and after completion of the acceptance inspections and tests, certify in writing that the installation is
SECTION 14 21 23 Page 9 accordance with the contract requirements. Bring any discrepancies to the attention of the Contracting Officer in writing, no later than three working days after the discrepancy is discovered.
1.7.1.2 Elevator Inspector
The Elevator Inspector shall be certified in accordance with the requirements of ASME A17.1/CSA B44 and ASME QEI-1 and licensed by the State of Hawaii in elevator inspection. The Certified Elevator Inspector shall inspect the installation of the elevator(s) to ensure that the installation conforms with all contract requirements. The Elevator Inspector shall be directly employed by the Prime Contractor and be independent of the Elevator System Manufacturer and the Elevator Specialist and shall witness the acceptance inspections and tests, approve all results and shall sign and certify the successful results. The Elevator Inspector, after completion of the acceptance inspections and tests, shall certify in writing that the installation is in accordance with the contract requirements. Bring any discrepancy, including any safety related deficiencies, to the attention of the Contracting Officer in writing, no later than three working days after the discrepancy is discovered.
1.7.1.3 Elevator Contractor's Elevator Technicians
For elevator installations in the United States, including United States territories, perform all elevator related work under the direct guidance of a state certified elevator technician with a minimum of three years of experience in the installation of elevator systems of the type and complexity specified in the contract documents. Provide an endorsement letter from the elevator manufacturer, certifying that the elevator specialist is qualified. All elevator technicians must carry a current certification issued by one of the following organizations:
a. National Association of Elevator Contractors (NAEC)
b. National Elevator Industry Education Program (NEIEP)
1.7.2 Manufacturers' Technical Support
Provide elevator components from manufacturers that provide factory training and online and live telephone elevator technical support to any elevator installation, service, and maintenance contractor. Provide elevator components from manufacturers that guarantee accessibility to all replacement and repair parts and components to any elevator installation, service, and maintenance contractor. Use only elevator component manufacturers that provide current published price lists for all elevator parts and components.
1.7.3 Operation and Maintenance Data
Assemble all shop drawing and product data material into O&M Data Packages in accordance with Article SUBMITTALS. Provide two complete O&M Data Packages in hard copy and two complete electronic O&M data packages on separate CDs, in PDF format. Provide all O&M Data Packages to Contracting Officer. Include controller diagnostic documentation and software as required under Article CONTROL EQUIPMENT.
1.7.4 Wiring Diagrams
Provide complete wiring diagrams and sequence of operations, which show
SECTION 14 21 23 Page 10 electrical connections and functions of elevator systems. Provide one set ( 11 inch by 17 inch minimum size) of wiring diagrams, with individual sheets laminated in plastic and assembled in binder, to be stored in the machine room or control room cabinet. Provide one additional hard copy set and two complete electronic sets on separate CDs, in PDF format. Provide all wiring diagram sets to the Contracting Officer. Coded diagrams are not acceptable unless fully identified.
1.7.5 Machine Room Cabinet
For storage of O&M Data Packages and Wiring Diagrams, provide locking metal cabinet with a minimum size of 20 inch W by 12 inch D by 30 inch H.
Cabinet must be sized large enough to accommodate all O&M Data and hardware required in paragraphs OPERATION AND MAINTENANCE DATA and WIRING DIAGRAMS.
Secure cabinet to machine room wall.
1.8 NEW INSTALLATION SERVICE
Provide elevator warranty service in accordance with the manufacturer's maintenance plan, warranty requirements, and applicable safety codes, for a period of 12 months after the date of acceptance by Contracting Officer.
Perform this work during regular working hours. Provide supplies and parts to keep elevator system in operation. Perform service only by factory trained personnel. Provide Bi-weekly services to include repairs, adjustments, greasing, oiling, and cleaning. Provide service log in elevator machine room or control room cabinet and update Bi-weekly, throughout the one-year warranty period.
Provide 24-hour emergency service, with one hour on-site response time, during this period without additional cost to the Government.
1.8.1 Periodic Elevator Certification Inspection and Testing
Provide elevator mechanic to support Army QEI Certified Elevator Inspector in the periodic six-month and the annual Category 1 elevator certification inspection and testing. Perform Category 1 inspection and testing no greater than 30 days prior to the end of the warranty period. Perform all elevator certification testing in the presence of QEI Certified Elevator Inspector.
In conjunction with the testing noted above, test systems for Earthquake Emergency Operation, as applicable. Schedule so that testing does not interfere with building operations.
1.9 FIRE PROTECTION SYSTEM
Coordinate interface between building fire protection system and elevator controls.
Additional fire protection requirements are located in: Section 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION, Section 28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM, and Section 26 20 00 INTERIOR
DISTRIBUTION SYSTEM.
1.9.1 Fire Alarm Initiating Devices
Fire alarm initiating devices are specified in Section 28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM, including conduit and wiring from each detector to fire protection addressable modules in elevator machine
SECTION 14 21 23 Page 11 room or control room.
1.9.2 Fire Sprinklers
Provide fire sprinklers in accordance with all applicable safety codes and with Section 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION.
Provide shutoff valve, check valve, and non-adjustable, zero time-delay flow switch, in each sprinkler line immediately outside of each machine room, control room, and hoistway, as applicable. Provide inspectors' test valve for periodic testing of flow switch and shunt trip disconnect.
Pipe sprinkler piping serving these spaces in a series manner with no laterals. Locate inspectors' test connection at the end of pipe runs such that operation of the test connection will purge air from system piping.
1.9.3 Shunt Trip Disconnect
Provide flow switches specified in paragraph FIRE SPRINKLERS to comply with ASME A17.1/CSA B44 and NFPA 72 for shunt trip of the main line power supply. For each elevator, provide control wiring connecting the flow switch to a shunt trip equipped circuit breaker located in the elevator machine room or control room. Upon flow of water, flow switch will instantaneously cause opening of the shunt-trip circuit breaker and remove power from the elevator. Flow switch must also send a signal to fire alarm control panel to indicate water flow condition.
PART 2 PRODUCTS
2.1 ELEVATOR DESCRIPTION
Provide elevator system that complies with ASME A17.1/CSA B44 in its entirety, ASME A17.2 and ASME A17.3 in its entirety, and additional requirements specified herein. For elevator speeds 350 fpm, up to but not including 500 fpm, comply with the RQPSM "Intermediate Performance" criteria. Submit data package in accordance with section 01 78 23 OPERATION
AND MAINTENANCE DATA.
Provide and install elevators in accordance with 36 CFR 1191 - ABAAS, ICC IBC, IEEE C62.41, NFPA 70 and NFPA 101 requirements.
2.1.1 Elevator Design Parameters
2.1.1.1 Non-EMSA Elevator
a. Type: Gearless
b. Rated load: 3000 lb.
c. Rated Speed: 350 fpm
d. TRAVEL LENGTH: 54ft-5in unless indicated otherwise
e. NUMBER OF STOPS: 7
f. NUMBER OF HOISTWAY OPENINGS: 1 front, 0 rear g.. Car Door Type: Single speed center opening, horizontally sliding.
h. Car Door Opening Width: 3 ft.- 10 in. minimum, 7ft-0in high..
SECTION 14 21 23 Page 12
i. CAR INSIDE DIMENSIONS: 6ft-8in wide and 5ft-5in deep, and 8ft-6in high
j. Voltage: 280 V, 3 pH
2.1.2 Cab Enclosure and Hoistway Entrance Assemblies
Provide finishes as listed below:
a. Floor; Ceramic Tile.
b. Walls; stainless steel. Provide each cab wall with equally spaced and equally sized wall panels. All wall panel fasteners must be concealed.
Wall trim; stainless steel.
Accessories; Provide hand rails on 3 walls of elevator cab.
c. Interior face of door; stainless steel.
d. Ceilings; prefinished steel panels.
Ceiling frame; prefinished steel.
e. Hoistway Door and Frame Finishes; stainless steel.
1. Frame
2. Exterior face of door; stainless steel
2.2 ELEVATOR OPERATION
ASME A17.1/CSA B44, Introduction, Section 3, Definitions.
2.2.1 Selective Collective Automatic Operation
Provide Selective Collective Automatic Operation.
2.3 SPECIAL OPERATION AND CONTROL
Provide the following special operations and control systems.
2.3.1 Keys for Elevator Key Switches
Provide a minimum of twelve keys per unique cylinder used on all key switches for a single elevator. Provide keys with brass or fiberglass tags marked "PROPERTY OF THE U.S. GOVERNMENT" on one side with function of key or approved code number on the other side.
2.3.2 Firefighters' Service
Provide equipment and signaling devices in accordance with ASME A17.1/CSA B44, section 2.27. The designated level for the Firefighters' key operated switch is the ground first floor.
2.3.3 Smoke Detectors
Smoke detectors are specified in Section 28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM, including conduit and wiring from each detector
SECTION 14 21 23 Page 13 to elevator machinery space control panel. Provide connections directly to elevator controls which will, when smoke is detected by any smoke detector, actuate Firefighters' Service and send each elevator to the correct floor as required by ASME A17.1/CSA B44. Provide dual-contact smoke detectors located in the elevator lobbies and the elevator machine room. If sprinkler is provided in the hoistway, provide dual-contact smoke detector at top of hoistway. Include only these smoke detectors in the circuit for elevator controller actuation of Firefighter' Service. In lieu of dual-contract smoke detectors, an addressable fire alarm system with listed smoke detectors are mounted on finished ceiling. Smoke detector system shall comply with ASME A17.1/CSA B44.
2.3.4 Top-of-Car Operating Device
Provide, in accordance with ASME A17.1/CSA B44, Paragraph 2.26.1.4.2 an operating device, mounted on or from the car crosshead, to permit car operation at a speed not exceeding 150 fpm for purposes of adjustment, maintenance, testing, and repair. Include an integral or remote safety device, "UP" and "DOWN" switches or buttons, an emergency stop switch, and inspection switch.
2.3.5 Hoistway Access Switches
Provide key-operated hoistway according to ASME A17.1/CSA B44, Section
3.12. Access switches that permit limited movement of the car at terminal floors for car door opening and car positioning, operative only when the "INSPECTION" switch in car operating panel is in inspection position.
Provide hoistway access operation with switches at top and bottom terminal landings. Locate switch 6 feet above floor level, within 12 inches of elevator hoistway entrance frame or with the ferrule exposed when located in the elevator entrance frame. Provide type 316 stainless steel face plate and NEMA 4X fixture.
2.3.6 In-Car Inspection Operation
Provide In-Car Inspection Operation.
2.3.7 Independent Service
Provide exposed key-operated switch in car operating panel to enable independent service and simultaneously disable in-car signals and landing-call responses. Provide indicator lights that automatically illuminate during independent service. For duplex or group operation, if one car is removed from group another car will respond to its hall calls.
2.3.8 Elevator Auxiliary Power Operating System
Provide elevator auxiliary power operating system.
2.4 ELEVATOR DRIVE MACHINE, HOIST MOTOR, AND DRIVE MOTOR
Provide elevator drive machine, which is gearless traction, direct drive machine according to ASME A17.1/CSA B44, hoist motor, and motor drive system that is designed to be installed in an elevator machine room (MR) or an elevator machinery space. The elevator machine, motor, and drive configuration and installation design must be mechanically and electrically interchangeable with a minimum of two other elevator manufacturer's drive machines that are readily available in the elevator industry. Paint or
SECTION 14 21 23 Page 14 finish ferrous surfaces with a minimum of one coat of manufacturer applied rust- inhibiting paint. Provide hoisting motor with separately excited direct current (DC) generator conforming to NEMA MG 1, part 18. Provide drive motor with class F insulation and rated for continuous duty.
Design the elevator drive system so that the hoist motor amperage does not exceed the motor data tag full load amperage in any operating condition, exclusive of acceleration and deceleration. Provide elevator hoist motor that is designed with Class F insulation and rated for 120 starts/hr.
Design the elevator drive system to limit Total Harmonic Distortion to a maximum of 5 percent. No single harmonic may exceed 3 percent.
Provide an elevator drive machine designed for and provided with stranded steel wire rope for elevator suspension and counterbalance. The minimum acceptable diameter of suspension and counterweight ropes is 3/8 inches.
Aramid fiber ropes, coated steel ropes, and non-circular coated steel belts may not be used for elevator suspension or counterbalance.
The elevator drive machine must be equipped with machine manufacturer's designed and installed standard means for the manual release of the driving-machine brake.
2.4.1 Manufacturer's Factory Training and Technical Support
Provide an elevator drive machine from a manufacturer that provides comprehensive factory training and technical support for installation, adjustment, service, and maintenance of the drive system. The training and support must be identified as available to any licensed elevator contractor. Provide verification of an established and documented training schedule, with pricing, for factory training classes that have been provided for a minimum period of one year prior to contract award date.
The elevator drive system must be identified as available for purchase and installation by any licensed elevator contractor. All drive system related components, parts, diagnostic tools, and software must be available for purchase, installation, and use by any licensed elevator contractor;
"exchange-only" provisions for the purchase of spare parts are not acceptable.
2.4.2 Ascending Car Overspeed and Unintended Car Movement Protection
Provide elevator Ascending Car Overspeed and Unintended Car Movement Protection means that is designed to act directly upon, and apply a retarding force to, the elevator suspension ropes. In addition to the requirements of ASME A17.1/CSA B44, the means must be designed to detect and stop movement of the elevator suspension ropes that occurs as a result of loss of traction between the suspension ropes and the elevator machine drive sheave.
2.5 CONTROL EQUIPMENT
Enclose all elevator control equipment in factory-primed and baked-enamel coated sheet-metal cabinets with ventilation louvers and removable or hinged doors. Mount cabinets at a height of 10 inches above machine room or control room finish floor.
2.5.1 Motor Control Equipment
ASME A17.1/CSA B44, Section 2.26. Provide variable voltage with
SECTION 14 21 23 Page 15 motor-generator set, variable voltage with silicon controlled rectifier (SCR) or Variable-Frequency alternating current (ac) drive control.
Enclose control equipment in factory-primed and baked-enamel coated sheet-metal cabinets with removable or hinged doors with ventilation louvers.
2.5.1.1 Motor Generator Set
NEMA MG 1, Part 18. Provide motor-generator set with Class F insulation, and rated at 120 starts per hour for elevator service. Maximum acceptable generator voltage is 600 volts. Indicate direction of rotation by an arrow painted on the frame. Enclose electric connections at motor generator set in conduit boxes. Provide adjustable timing device which will automatically shut the set off at 20 to 30 seconds predetermined time after the elevator has answered the last registered call.
2.5.1.2 SCR Control or VVVF AC Control
Provide individual isolation transformers and individual choke reactors for each individual hoist motor. Provide filtering to maintain harmonic distortion below IEEE standards as measured at the elevator machine room disconnect.
2.5.1.3 Electrical Isolation Protection
Provide individual isolation transformers and individual choke reactors for each individual hoist motor. Provide filtering to maintain harmonic distortion below IEEE C62.41 standards as measured at the elevator machine room or control room disconnect.
2.5.2 Logic Control
Provide solid-state microprocessor controller to enable programmable control of call allocation, logic functions, door control, speed sensing and car position. Provide a method of reprogramming adjustable parameters of computerized controls. Store all programming in non-volatile memory.
The microprocessor control system is acceptable only if hardware and software, and software documentation required to maintain and utilize microprocessor is provided and training is provided to Government Personnel by the equipment manufacturer and supplier. Provide electromagnetic switch, relay logic control.
2.5.2.1 On-Board Diagnostic Panel
Provide, for each individual elevator microprocessor controller, an on-board diagnostic control and LCD display panel that allows unrestricted access to the comprehensive range of adjustable parameters necessary to perform installation, adjusting, maintenance, and testing of the elevator.
For each elevator group control, provide a separate on-board diagnostic control and LCD display panel that allows unrestricted access to the comprehensive range of options and adjustments necessary to perform installation, adjusting, maintenance, and testing of the elevator group.
Provide LCD displays which also provide the capability to display, monitor, and diagnose any and all fault logs, fault history, trouble calls, and diagnostics. Provide three (3) copies of the complete manufacturer's software program, with complete software documentation, that enables the same level of unrestricted access to all controllers of the same make and model, regardless of the installation date or location. Provide signed certification, from the manufacturer's corporate headquarters, that
SECTION 14 21 23 Page 16 guarantees the microprocessor software and access system will not terminate the unlimited and unrestricted access at any future dates.
2.5.2.2 External Port
For each individual elevator microprocessor controller, and elevator group microprocessor controller, provide a USB port or an RS 232 port that allows connection to an on-site or a remote portable laptop computer. Provide the same level of unrestricted access as the on-board diagnostic panel.
Provide three (3) copies of the complete manufacturer's software program, with complete software documentation, that enables the same level of unrestricted access to all controllers of the same make and model, regardless of the installation date or location. Provide signed certification, from the manufacturer's corporate headquarters, that guarantees the microprocessor software and access system will not terminate the unlimited and unrestricted access at any future date.
2.5.2.3 Repair Requirements
For the repair of microprocessor control system, provide maintenance tools, supporting computer software, and software documentation required for complete maintenance of elevator system including diagnostics and adjustments. Tools may be hand-held or build into control system. Provide tools which do not require recharging to maintain their memory or authorization for use. Do not use software which requires periodic reprogramming, or reauthorization. Store programs in non-volatile memory.
Tools and software may be factory programmed to operate only with this project's identification serial number.
2.5.3 Elevator Microprocessor Controller
For each individual elevator controller, and for each group controller, provide a microprocessor controller that complies with the following paragraphs. Provide controller(s) package that includes all hardware and software required for the installation, maintenance, and service of the elevator, in its' entirety. Provide verification of technical support service that the controller manufacturer provides to any licensed elevator installation, service, and maintenance company.
Provide an elevator controller from a manufacturer that provides comprehensive factory training to include controller installation, adjustment, service, and maintenance. The training must be identified as available to any licensed elevator contractor. Provide verification of an established and documented training schedule, with pricing, for factory training classes that manufacturer has provided for a minimum period of one year prior to contract award date.
The elevator controller must be identified as available for purchase and installation by any licensed elevator contractor. All components, parts, diagnostic tools, and software must be available for purchase and installation and use by any licensed elevator contractor; "exchange-only" provisions for the purchase of spare parts are not acceptable. The elevator controller manufacturer must publish an industry competitive price listing for all controller parts, diagnostic tools, and software.
Provide verification of telephone and internet based technical support service that the elevator controller manufacturer provides to any licensed elevator installation, service, and maintenance company at an industry competitive price. The service must include live telephone based technical
SECTION 14 21 23 Page 17 support for installation, adjustment, maintenance, and troubleshooting of the elevator controller and related elevator components. The service must be available during standard working hours.
Provide an elevator controller that is designed to automatically reestablish normal elevator operation following any temporary loss of power, regardless of duration.
2.5.3.1 Elevator Controller Interface Cabinet
For each individual elevator microprocessor controller, provide a separate elevator control cabinet with an integrated human interface system. For group elevator installations, a single cabinet and interface system with full access to each elevator controller may be utilized. The separate controller interface cabinet must be supplied by the elevator controller manufacturer and include a minimum 12 inch wide keyboard and a minimum 10 inch monitor. The elevator controller interface cabinet must comply with arc-flash protection requirements of NFPA 70E and UFC 3-560-01.
2.5.3.1.1 Elevator Microprocessor Human Interface
The interface system must provide complete elevator controller interface capability and must include the elevator controller manufacturer's comprehensive package of installation and diagnostic software. The microprocessor interface system must provide unrestricted access to all parameters, all levels of adjustment, and all flags necessary for installation, adjustment, maintenance, and troubleshooting of each elevator and for the elevator group. All software programming must be stored in non-volatile memory. The elevator controller fault log must provide non-volatile memory fault log storage of all faults, trouble calls, and fault history for a minimum of one year and the ability to download or print the fault log. The controller interface must also provide the capability to display and diagnose trouble calls, faults, and shutdowns.
Expiring software, degrading operation, and "key" access controls are not acceptable.
2.5.3.2 Software and Documentation
Provide three copies of the manufacturer's maintenance and service diagnostic software, with complete software documentation, that will enable the same level of unrestricted access to all controllers of the same make and model, regardless of the installation date or location. Provide signed certification, from the manufacturer's corporate headquarters, that guarantees that the microprocessor software and access system will not terminate the unlimited and unrestricted access at any future date.
2.5.3.3 Elevator Controller Certification
For elevator installations in the United States, including United States territories, provide an elevator microprocessor controller that has a current certificate of safety code compliance issued by the Technical Standards and Safety Authority (TSSA), Toronto, Canada.
2.6 OPERATING PANELS, SIGNAL FIXTURES, AND COMMUNICATIONS CABINETS
For capacity and data plates, refer to ASME A17.1/CSA B44, Section 2.27.
Attach faceplates with spanner security screws. On car panel, provide stainless steel capacity and data plates, with name of elevator manufacturer.
SECTION 14 21 23 Page 18
For all panels and fixtures, provide identical and uniform fixture design, material, finish, and components for all elevators. For all panels and fixtures, legibly and indelibly identify all buttons and all operating positions for each device. Use engraving and backfilling, or photo etching, for button and switch designations. Do not use attached signs.
Provide elevator manufacturers' standard grade for all key switches unless otherwise specified. All illuminating panels and fixture components must utilize LED lighting for energy efficiency.
2.6.1 Car and Hall Buttons
Provide landing fixture buttons, provide industry-standard, vandal resistant push buttons with positive-stop assembly design. Buttons must be minimum 3/4 inch diameter, satin-finish stainless steel, with illuminating LED halo.
2.6.2 Passenger Car-Operating Panel
Refer to ASME A17.1/CSA B44, Section 211 and 306. Provide each car with one car operating panel that contains operation controls and communication devices. Provide exposed, flush mounted buttons for the controls that shall be passenger accessible. Allow maximum 48 inches between car floor and center line of bottom button. Use engraving and backfilling or photo etching for button and switch designations. Do not use attached signs.
Provide a lockable service cabinet or keyed switches for those controls that should not be passenger accessible and use engraving and backfilling or photo etching for button and switch designations. Do not use attached signs.
2.6.2.1 Passenger Controls
In addition to ASME A17.1/CSA B44 requirements, provide the following operating controls, identified as indicated:
a. Illuminating car-call buttons identified to correspond to landings served by elevator.
b. "DOOR OPEN" and "DOOR CLOSE" buttons.
c. "Help" communication device to include communication between elevator cab and elevator machine room.
d. Keyed "STOP" switch in accordance with ASME A17.1/CSA B44, Section 2.27 (2.27.3.3).
e. "ALARM" button in compliance with UFAS, ADA, and ASME A17.1/CSA B44, Paragraphs 5.1.21.1, 5.7.21, and 2.27.1. Alarm button shall be red with engraved legend "ALARM". Alarm button shall illuminate when pushed. Locate "ALARM" button at panel bottom.
f. "FIRE DEPARTMENT" key switch, with "OFF-HOLD-ON" positions, in that order with key to be removable in all positions. Provide fire sign or jewel and audible signal device, in accordance with ASME A17.1/CSA B44, Figure 2.27.3.1.6(h). Both visual and audible signals are activated when Phase I key switch in hall is activated or when smoke detector activates return of elevator(s) to main fire response floor. Visual and audible signal shall remain activated until car has reached designated or alternate fire response floor. Upon arrival at fire
SECTION 14 21 23 Page 19 response floor visual signal remains illuminated and audible signal becomes silent.
g. Emergency two-way communication. Provide momentary pressure, single illuminating pushbutton operated communication device that compiles with ASME A17.1/CSA B44, UFAS, and the Americans with Disabilities Act.
h. Sound-actuated firefighter phone jack.
2.6.2.2 Service Controls
In addition to ASME A17.1/CSA B44 requirements, provide the following operating controls, identified as indicated:
a. Inspection switch that transfers car control to top-of-car inspection operating controls and prevents car operation from in-car control panel.
b. Independent service switch.
c. Two car light switches, one for light in car and one for lights on top and bottom of car frames.
d. Fan switch, two-speed.
e. Infra-red curtain unit cutout switch. Provide NEMA 4X device.
f. Provide a key-operated, three-position switch for "In car Inspection Operation" and "Hoistway Access". The center switch position will provide normal, automatic operation.
g. "Car Light" switch.
h. "Car Fan" switch with two speed settings identified.
i. 120-volt ac 60 Hz single-phase duplex electrical outlet of ground-fault-circuit-interrupt (GFCI) design.
j. Device for communication between car and elevator machine room.
k. Parking switch.
2.6.2.3 Certificate Window
Provide a minimum 4 inch wide by 6 inch high certificate window for elevator inspection certificate. Locate window in the Service Controls door of the Car Operating Panel.
2.6.2.4 Emergency Signaling Devices
Provide an audible signaling device, operable from the Car Operating Panel button marked "ALARM". The audible signaling device must have a sound pressure rating between 80 and 90 dBA at 10 ft. Provide battery backup power capable of operating the audible signaling device for at least one hour.
2.6.3 Switches and Devices
Provide elevator manufacturer's standard grade for switches and devices on car operating panel. Legibly and indelibly identify each device and its
SECTION 14 21 23 Page 20 operation positions. Locate car dispatching buttons in identical positions in car operating panels for corresponding floors.
2.6.4 In-Car Position and Direction Indicator and Signal
Include in-car direction indicator in the in-car position indicator fixture.
2.6.4.1 In-Car Position Indicator and Signal
Provide horizontal electrical or electronic digital position indicator located minimum of 84 inches above car floor. Arrange indicator to show floor position of car in hoistway and its traveling direction. Indicate position by illumination of numeral or letter corresponding to landing at which car is passing or stopping. Provide audible signal to alert passenger that elevator is passing or stopping at a floor. Provide audible signals exceeding ambient noise level by at least 20 decibels with frequency not higher than 1500 Hz. Provide Type 316 stainless steel faceplate and NEMA 4X fixture and LED Lighting.
2.6.4.2 In-Car Direction Indicator and Signal
Provide visual and audible car direction indicators in car, indicating car traveling direction. For visual directional signal, provide arrow of minimum 2 1/2 inches in size. Use equilateral triangles for arrows, green for upward direction and red for downward direction. Provide audible signal that sounds once for upward direction and twice for downward direction. Provide Type 316 stainless steel faceplate and NEMA 4X fixture and LED lighting.
2.6.5 Landing Position and Direction Indicator and Signal
Provide a single fixture containing the landing position and direction indicators. Provide Type 316 stainless steel faceplate and NEMA 4X fixtures and LED lighting.
2.6.5.1 Landing Position Indicator and Signal
Provide an electrical or electronic digital position indicator similar to the car position indicator. Arrange position indicator in wall horizontally above the door frame or vertically at the side of the door frame. Indicators to show floor position of car in hoistway. Indicate position by illumination of numeral or letter corresponding to landing at which car is passing or stopping. Provide Type 316 stainless steel faceplate and NEMA 4X fixtures and LED lighting.
2.6.5.2 Landing Direction Indicator and Signal
Provide landing direction indicator with visual and audible signal devices. Provide single direction indicator at terminal floors; "UP" and "DOWN" direction indicator at intermediate floors. Provide equilateral triangles not less than 2 1/2 inches in size, green for upward direction and red for downward direction. Provide electronic audible device that sounds once for upward direction and twice for downward direction. Provide audible signals exceeding ambient noise level by at least 20 decibels with frequency not higher than 1500 Hz. Provide Type 316 stainless steel faceplate and NEMA 4X fixtures and LED lighting.
SECTION 14 21 23 Page 21
2.6.6 Elevator In-Car Position Indicators
For all elevators, provide illuminating LED position indicator in the Car Operating Panel.
2.6.7 Elevator In-Car Direction Indicators
For 2-stop elevator installations, provide visual direction indicators and audible car arrival signal in the elevator car door jamb, in accordance with ABA Standards. Visual indicators must be visible from the hall call fixture.
2.6.8 Hall Call Landing Fixtures
Provide a hall call fixture adjacent to each elevator. Provide a single push-button for terminal landings…