About this file
This document is a Drager PSS5000 Self-Contained Breathing Apparatus (SCBA) test results report from Alexander Gow Fire Equipment dated February 16, 2023. The test results cover a complete SCBA functional and visual inspection for a specific unit with serial number BRCE-1638 11 and Posi3 USB serial number U07336. The test report includes detailed measurements and assessments across multiple performance categories, including exhalation pressure, facepiece leakage, static facepiece pressure, breath activation, high-pressure leakage, bypass flow, alarm activation pressure, and gauge accuracy. All tested parameters passed the inspection, with specific measurements recorded for each test point, such as exhalation pressure at 5.7" H2O, facepiece leakage at 0.4" H2O, and alarm activation at 1104 PSI. The report was completed by Jeramy Griffith at the company's Seattle, Washington location.
View the file
Other files
Show 40 more
Latest 50 of 59 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Posi3 USB Test Results 2/16/2023 8:07:45 AM
Complete SCBA Test
Drager
PSS5000
S/N: BRCE-1638 11
Dredge Yaquina
Posi3 USB serial # U07336 - Calibration was up to date when the test was performed
Tested by : Jeramy Griffith
Alexander Gow Fire Equipment EP
1436 NW 53rd St Seattle, WA 98107 Page 1 Version 4.1.1.109
Functional Tests
Exhalation Pressure 5.7 " H 2 O
Facepiece Leakage Pass 0.4 " H 2 O
Static Facepiece Pressure Pass 0.8 " H 2 O
1st Breath Activation -2.6 " H 2 O
High Pressure Leakage Pass 20 P S I
Bypass Flow 50 L / m i n
Alarm Activation Pressure
4500 PSI Whistle Pass 1104 P S I
Gauge Accuracy
4500 PSI Digital Pass
630 PSI ±225 PSI 1850 PSI ±225 PSI 3090 PSI ±225 PSI
Pass 543 Pass 1838 Pass 3068
Auxiliary IDs
Facepiece
Second Stage BRDE00378P
First Stage/Reducer
Low Pressure Alarm
Cyl Connector
Airline Attachment
Harness BRCE-1638 11
Visual Inspection
Facepiece Pass
Backframe/Harness Pass
Cylinder Not Perform
Low Pressure Warning Pass
Hoses Pass
Manifold Volume: 0.062
Minimum Maximum Breathing Results Minimum Maximum
0.3 " H 2 O 2.3 " H 2 O Pass Facepiece Pressure 0.5 " H 2 O 2.7 " H 2 O Pass