Switchboard Circuit Breakers.pdf

PDF 89 KB Posted

Attached to
USACE: Portland District Dredge Vessel MSRA
Solicitation number
W9127N25BA008
Issued by

About this file

This document is an inventory list of circuit breakers and cradles from manufacturers Square D and G.E., used in various electrical system locations such as Bow Thruster, Port and Starboard OSDP, IBDP, Generator, Bus Tie, and Jetting Pump positions. The circuit breakers are predominantly Square D models with ANSI 37 / UL 1066 ratings, featuring different interrupt and sensor ratings ranging from 1600A to 5000A, with Micrologic settings of 5.0. The list includes detailed specifications like frame size (NW 16 to NW 50), long time pickup values, and unique serial numbers and manufacturing dates for each component. Two G.E. circuit breakers (Power Break II) are also included in the inventory, with ratings of 1600A and 800A respectively. The document provides a comprehensive technical overview of electrical switching equipment, likely for a marine or industrial installation.

View the file

Other files

File Type Posted
70.010-5058-918.pdf PDF
681-0879-205 Combined.pdf PDF
CaptiveAire SHOP DWGS REV1.pdf PDF
Galley Exhaust Fan.pdf PDF
Radar Console 1.jpg JPG image
Radar Console 2.jpg JPG image
70.010-0342-901 Rev B.pdf PDF
Fwd Fire Suction valve.jpg JPG image
parker air actuator 2.jpg JPG image
70.010-4013-902 Hopper Doors Arrangement and Details.pdf PDF
70.010-2775-001 Hopper Overflow Systems General Dimensions.pdf PDF
70.010-4013-903 Hopper Doors.pdf PDF
Evoqua PS Drawing 05071NST and Schematic W3T346111.pdf PDF
70.010-4013-901 General Arrangement of Hopper Door and Actuating Mechanism.pdf PDF
70.010-0342-902.pdf PDF
Fwd Fire Suction valve 2.jpg JPG image
70-010-2339-050 Rev D (1 of 1) Schematic Diagram Flushing System for Sluice Valves.pdf PDF
ESS-25-012 PUMP ROOM HVAC DUCTING S12.pdf PDF
Manual Essayons Smoke Detector 10-22-01 version.docx DOCX document
70.010-0342-901 Rev A.pdf PDF
Parker air actuator.jpg JPG image
Crane hand wheel.jpg JPG image
Smk Det Zones.doc DOC document
681-0853-303 Combined.pdf PDF
E-1720-28 Model General Assembly of Side Dragarm.pdf PDF
681-0853-325 Rev 3 (1 of 1) Hopper Collection Sluice Valve Flushing in Eng Room.pdf PDF
70.010-5069-902 Rev C.pdf PDF
70.010-5058-901.pdf PDF
681-0919-201-3 Rev 2 (1 of 1).pdf PDF
70.010-5069-902.pdf PDF
E-2240-1 PROPELLER SHAFT ROPE GUARD 1.pdf PDF
681-0700-156 Rev 2 (1 of 1).pdf PDF
70.010-5058-902 Rev B.pdf PDF
681-0700-164 Rev 2 (1 of 1).pdf PDF
Deck shack load summary.pdf PDF
70.010-5069-902 Rev B.pdf PDF
681-0919-201-4 Rev 2 (1 of 1).pdf PDF
681-0713-102 Rev 2 (2 of 4).pdf PDF
5058-908 Rev A (1 of 1).pdf PDF
681-0700-138-1 Rev 3 (1 of 1).pdf PDF
70.010-2560-053.pdf PDF
681-0700-157 Rev 1 (1 of 1).pdf PDF
681-0700-137 Rev 2 (1 of 1).pdf PDF
681-0879-203 Combined.pdf PDF
22885-D Tail Shaft ACOE Essayons.pdf PDF
5069-907 Rev A (1 of 1).pdf PDF
390-VGR-02.pdf PDF
681-0713-201 Rev 6 (1 of 3).pdf PDF
RE_ 2417283--Essayons electrical cable upgrade.pdf PDF
Propulsion Exhaust Drawings.pdf PDF
Show 40 more

Latest 50 of 128 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Item MFR Location ANSI Rating Type Interrupt Rating Frame

Sensor Rating

(ln) long time pickup Trip Set Cat # S/N MFR Date Micrologic

Circuit Breaker Square D Bow Thruster ANSI 37 / UL 1066 NW 16 H2 85-85-85 1600 A 1200A WA5ECR43A9CFFFXHDA 085090817901 07381 5.0 A

Circuit Breaker Square D Port OSDP ANSI 37 / UL 1066 NW 20 H2 85-85-85 2000 A 2000 A 0.8 1600 A WA5FFR43A9CFFFXCFA 085121831101 09072 5.0 A

Circuit Breaker Square D Stbd OSDP ANSI 37 / UL 1066 NW 20 H2 85-85-85 2000 A 2000 A 0.8 1600 A WA5FFR43A9CFFFXCFA 085121831102 09072 5.0 A

Circuit Breaker Square D Port IBDP ANSI 37 / UL 1066 NW 32 H2 85-85-85 3200 A 3200 A 1.0 3200 A WA5JJR43A9CFFFXHDA 085090812901 07381 5.0 A

Circuit Breaker Square D Stbd IBDP ANSI 37 / UL 1066 NW 32 H2 85-85-85 3200 A 3200 A 1.0 3200 A WA5JJR43A9CFFFXHDA 085090812902 07381 5.0 A

Circuit Breaker Square D Port 600v Gen ANSI 37 / UL 1066 NW 50 H2 85-85-85 5000 A 5000 A 1.0 5000 A YA5LLR43A9DFFFXHDA 085090813001 07312 5.0 A

Circuit Breaker Square D Stbd 600v Gen ANSI 37 / UL 1066 NW 50 H2 85-85-85 5000 A 5000 A 1.0 5000 A YA5LLR43A9DFFFXHDA 085090813002 07381 5.0 A

Circuit Breaker Square D 600V Bus Tie ANSI 37 / UL 1066 NW 32 H2 85-85-85 3200 A 2500 A 0.8 2000 A WA5JGR43A9CFFFXDHA 085090812701 07381 5.0 A

Circuit Breaker Square D Dredge Tie ANSI 37 / UL 1066 NW 32 H3 100-100-85 3200 A 3200 A 1.0 3200 A WA6JJR33A9CFFFXHXA 085090042201 07374 5.0

Circuit Breaker Square D Stbd SS Gen ANSI 37 / UL 1066 NW 20 H3 100-100-85 2000 A 2000 A 0.9 1800 A WA6FFR33A9CFFFXHXA 085090042302 07374 5.0

Circuit Breaker Square D Bus Tie ANSI 37 / UL 1066 NW 32 H3 100-100-85 3200 A 3200 A 1.0 3200 A WA6JJR33A9SFFFXHXA 085090042501 07374 5.0

Circuit Breaker Square D Center SS Gen ANSI 37 / UL 1066 NW 20 H3 100-100-85 2000 A 2000 A 0.9 1800 A WA6FFR33A9CFFFXHXA 085090042301 07374 5.0

Circuit Breaker Square D Port SS Gen ANSI 37 / UL 1066 NW 20 H3 100-100-85 2000 A 2000 A 0.9 1800 A WA6FFR33A9CFFFXHXA 085090042303 07374 5.0

Circuit Breaker Square D Emer Tie ANSI 37 / UL 1066 NW 16 H3 100-100-85 1600 A 1000 A 0.7 700 A WA6EBR33A9SFFFXHXA 085090042101 07374 5.0

Circuit Breaker Square D Spare OSDP ANSI 37 / UL 1066 NW 20 H2 85-85-85 2000 A 2000 A WA5FER43A9CFFFXHDA 085090812801

Circuit Breaker Square D Spare OSDP ANSI 37 / UL 1066 NW 20 H2 85-85-85 2000 A 2000 A WA5FER43A9CFFFXHDA 085090812802

Circuit Breaker G.E. E Bus Tie Power Break II 1600 A 1600 A SSD16V216 175445740400201

Circuit Breaker G.E. E Gen Breaker Power Break II 800 A 700 A SHD08B208H 175445740300101

Cradle Square D Bow Thruster NW 16 CWAGYBPALBXBXXEFXH 085088494701 07345

Cradle Square D Port OSDP NW 20 CWAJYV9AMBXBXXEFXH 085086220601 07312

Cradle Square D Stbd OSDP NW 20 CWAJYV9AMBXBXXEFXH 085086220602 07312

Cradle Square D Port IBDP NW 32 CWARRF9ARBXBXXEFXH 085086220801 07312

Cradle Square D Stbd IBDP NW 32 CWARRF9ARBXBXXEFXH 085087018601 07322

Cradle Square D Port 600v Gen NW 50 CYAVWN9ATBXBXXEFXJ 085086220901 07312

Cradle Square D Stbd 600v Gen NW 50 CYAVWN9ATBXBXXEFXJ 085086220902 07385

Cradle Square D 600V Bus Tie NW 32 CWARRF9ARBXBXXEFXH 085086220802 07312

Cradle Square D Dredge Tie NW 32 CWARRF9ARBXBXXEFXX 085087463301 07334

Item MFR Location ANSI Rating Type Interrupt Rating Frame

Sensor Rating

(ln) long time pickup Trip Set Cat # S/N MFR Date Micrologic

Cradle Square D Stbd SS Gen CWAJYV9AMBXBXXEFXH 085086487402 07322

Cradle Square D Bus Tie

Cradle Square D Center SS Gen CWAJYV9AMBXBXXEFXH 085087463402 07325

Cradle Square D Port SS Gen CWAJYV9AMBXBXXEFXH 085087463403 07325

Cradle Square D Emer Tie

Cradle Square D Port Jetting Pump NW 16 CWAGYV9ALBXBXXEFXX 085088494801 07345

Cradle Square D Stbd Jetting Pump NW 16 CWAGYV9ALBXBXXEFXX 085088494802 07345

Sheet1

File details come from the government source that posted it. Updated .