CaptiveAire SHOP DWGS REV1.pdf

PDF 1 MB Posted

Attached to
USACE: Portland District Dredge Vessel MSRA
Solicitation number
W9127N25BA008
Issued by

About this file

This is a master drawing document for a CaptiveAire commercial kitchen ventilation system for the Army Corps of Dredge project (Job #6733486). The system includes two 5' 6" long wall-mount exhaust hoods (Model 5412SND-2), each 54" wide and 12" high, with Captrate Solo filters, a wall-mount utility cabinet, and a comprehensive fire suppression system. The hood configuration features stainless steel construction, insulated backsplash, and end panels, with a 4.0/4.0 tank fire suppression system that includes a gas valve, manual pull station, and interconnected safety components.

The electrical package consists of a smart control system (Model SC-311110MA) with 3-phase power for exhaust and supply fans, thermostatic controls, and building management system integration. The system includes detailed specifications for electrical wiring, fire system connections, low-voltage components, and communication protocols. Key features include cloud-based monitoring, temperature sensors, fan controls, wash functions, and comprehensive fire safety interlocks. The documentation provides extensive installation instructions for electricians, plumbers, and alarm contractors, with specific requirements for wiring, piping, and system configuration.

View the file

Other files

File Type Posted
70.010-5058-918.pdf PDF
681-0879-205 Combined.pdf PDF
Galley Exhaust Fan.pdf PDF
Radar Console 1.jpg JPG image
Radar Console 2.jpg JPG image
70.010-0342-901 Rev B.pdf PDF
Fwd Fire Suction valve.jpg JPG image
parker air actuator 2.jpg JPG image
70.010-4013-902 Hopper Doors Arrangement and Details.pdf PDF
70.010-2775-001 Hopper Overflow Systems General Dimensions.pdf PDF
70.010-4013-903 Hopper Doors.pdf PDF
Evoqua PS Drawing 05071NST and Schematic W3T346111.pdf PDF
70.010-4013-901 General Arrangement of Hopper Door and Actuating Mechanism.pdf PDF
70.010-0342-902.pdf PDF
Fwd Fire Suction valve 2.jpg JPG image
70-010-2339-050 Rev D (1 of 1) Schematic Diagram Flushing System for Sluice Valves.pdf PDF
ESS-25-012 PUMP ROOM HVAC DUCTING S12.pdf PDF
Manual Essayons Smoke Detector 10-22-01 version.docx DOCX document
70.010-0342-901 Rev A.pdf PDF
Parker air actuator.jpg JPG image
Crane hand wheel.jpg JPG image
Smk Det Zones.doc DOC document
Switchboard Circuit Breakers.pdf PDF
681-0853-303 Combined.pdf PDF
E-1720-28 Model General Assembly of Side Dragarm.pdf PDF
681-0853-325 Rev 3 (1 of 1) Hopper Collection Sluice Valve Flushing in Eng Room.pdf PDF
70.010-5069-902 Rev C.pdf PDF
70.010-5058-901.pdf PDF
681-0919-201-3 Rev 2 (1 of 1).pdf PDF
70.010-5069-902.pdf PDF
E-2240-1 PROPELLER SHAFT ROPE GUARD 1.pdf PDF
681-0700-156 Rev 2 (1 of 1).pdf PDF
70.010-5058-902 Rev B.pdf PDF
681-0700-164 Rev 2 (1 of 1).pdf PDF
Deck shack load summary.pdf PDF
70.010-5069-902 Rev B.pdf PDF
681-0919-201-4 Rev 2 (1 of 1).pdf PDF
681-0713-102 Rev 2 (2 of 4).pdf PDF
5058-908 Rev A (1 of 1).pdf PDF
681-0700-138-1 Rev 3 (1 of 1).pdf PDF
70.010-2560-053.pdf PDF
681-0700-157 Rev 1 (1 of 1).pdf PDF
681-0700-137 Rev 2 (1 of 1).pdf PDF
681-0879-203 Combined.pdf PDF
22885-D Tail Shaft ACOE Essayons.pdf PDF
5069-907 Rev A (1 of 1).pdf PDF
390-VGR-02.pdf PDF
681-0713-201 Rev 6 (1 of 3).pdf PDF
RE_ 2417283--Essayons electrical cable upgrade.pdf PDF
Propulsion Exhaust Drawings.pdf PDF
Show 40 more

Latest 50 of 128 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Oregon Office

REGION 90

PHONE: (360) 828 - 5418

EMAIL: reg90@captiveaire.com

FOR QUESTIONS, CALL THE

HOOD INFORMATION - JOB#6733486

SND-2

SND-2

CAPTIVEAIRE

CAPTIVEAIRE

5' 6"

5' 6"

DEG

DEG

I

I

HEAVY

HEAVY

4"

4"

12"

12"

-0.933"

-0.933"

430 SS

100%

430 SS

100%

LEFT

RIGHT

ALONE

ALONE

HOOD

NO

TAG MODEL MANUFACTURER LENGTH

MAX

COOKING

TEMP

TYPE

APPLIANCE

DUTY

DESIGN

CFM/FT

TOTAL

EXH CFM

EXHAUST PLENUM

RISER(S)

WIDTH LENG HEIGHT DIA CFM VEL SP

HOOD

CONSTRUCTION

HOOD CONFIG

END TO

END

ROW

HOOD INFORMATION

CAPTRATE SOLO FILTER

CAPTRATE SOLO FILTER

20"

20"

16"

16"

85% SEE FILTER

SPEC

85% SEE FILTER

SPEC

RECESSED ROUND

RECESSED ROUND

NO

NO

YES

YES

LBS

LBS

HOOD

NO

TAG

FILTER(S)

TYPE QTY HEIGHT LENGTH

EFFICIENCY @ 7

MICRONS

LIGHT(S)

QTY TYPE

WIRE

GUARD

UTILITY CABINET(S)

LOCATION SIZE

FIRE SYSTEM

TYPE SIZE

ELECTRICAL

MODEL #

SWITCHES

QUANTITY

FIRE

SYSTEM

PIPING

HOOD

HANGING

WEIGHT

HOOD OPTIONS

BACKSPLASH 68.00" HIGH X 132.00" LONG X 1.00" WIDE INSULATED 430 SS VERTICAL.

LEFT QUARTER END PANEL 27" TOP WIDTH, 0" BOTTOM WIDTH, 27" HIGH 430 SS.

INSULATION FOR TOP OF HOOD.

W1-SELF CLEANING.

FINISHED BACK - GROUND/POLISH 66.00" LONG.

INSULATION FOR BACK OF HOOD.

RISER SENSOR INSTALL 6IN PLEN.

RIGHT QUARTER END PANEL 27" TOP WIDTH, 0" BOTTOM WIDTH, 27" HIGH 430 SS.

INSULATION FOR TOP OF HOOD.

W1-SELF CLEANING.

FINISHED BACK - GROUND/POLISH 66.00" LONG.

INSULATION FOR BACK OF HOOD.

RISER SENSOR INSTALL 6IN PLEN.

HOOD

NO

TAG OPTION

WALL-MOUNT UTILITY CABINET

1 WALL MNT 12"x84"x24" TANK FS 4.0/4.0 SC-311110MA

1 LIGHT

1 FAN

340.00 LBS

UTILITY CABINET(S)

HOOD

NO

LOCATION SIZE

FIRE SYSTEM

TYPE SIZE

ELECTRICAL

MODEL #

SWITCHES

QUANTITY

WEIGHT

1500500

FLOW RATE (CFM)

0.00

0.50

P R E S S U R E

D R O P i n

H

PRESSURE DROP VS. FLOW RATE

R

R

SPECIFICATION: CAPTRATE GREASE-STOP SOLO FILTER

A UNIQUE S-BAFFLE DESIGN IN CONJUNCTION WITH A SLOTTED REAR BAFFLE DESIGN,

THE CAPTRATE GREASE-STOP SOLO FILTER IS A SINGLE-STAGE FILTER FEATURING

LARGER, WITH A CORRESPONDING PRESSURE DROP NOT TO EXCEED 1.0 INCHES OF WATER GAUGE.

FILTER IS STAINLESS STEEL CONSTRUCTION, AND SIZED TO FIT INTO STANDARD

GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 75% OF GREASE

PARTICLES FIVE MICRONS IN SIZE, AND 85% GREASE PARTICLES SEVEN MICRONS IN SIZE AND

COMPONENTS WHEN ASSEMBLED.

2-INCH DEEP HOOD CHANNEL(S).

TO DELIVER EXCEPTIONAL FILTRATION EFFICIENCY.

UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO

F R A C T I O N A L

E F F I C I E N C Y

0.1

1.0

PARTICLE DIAMETER (UM)

10.0

EFFICIENCY VS. PARTICLE DIAMETER

THE CAPTRATE GREASE-STOP SOLO WAS TESTED TO ASTM STANDARD ASTM F2519-05.

T

E

A

N

S

F

ACCORDANCE

No. 96

NFPA

WITH

BUILT

IN

S

L

I D

T

E

R

O

C

H

B

N

R

A

N

I

O

R

M

Y

R

O

R

L

A

I

G

N

T

S

B

A

T

CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH:.

NFPA #96.

NSF STANDARD #2.

UL STANDARD #1046.

INT. MECH. CODE (IMC).

ULC-S649.

1.00

1.50

2.00

2.50

3.00

3.50

MANUFACTURER APPROVED FOR USE IN SOLID FUEL APPLICATIONS AS A SPARK ARRESTER.

GREASE DUCT & CHIMNEY SPECIFICATIONS:

PROVIDE GREASE DUCT EQUAL TO CAPTIVEAIRE SYSTEMS MODEL "DW"

ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK. MODEL "DW"

IS LISTED TO UL-1978 AND IS INSTALLED USING "V" CLAMP LOCKING

CONNECTIONS SEALED WITH 3M FIRE BARRIER 2000 PLUS. MODEL "DW"

DOES NOT REQUIRE WELDING PROVIDING IT HAS BEEN INSTALLED PER

THE MANUFACTURES INSTALLATION GUIDE.

PROVIDE RATED ACCESS DOORS AT EVERY CHANGE IN DIRECTION AND EVERY 12' ON CENTER.

PER MANUFACTURES LISTING MODEL "DW" HORIZONTAL RUNS LESS THAN 75 FT. CAN BE

SLOPED 1/16" PER 12", HORIZONTAL RUNS MORE THAN 75 FT. CAN BE SLOPED 3/16" PER 12".

DUCT SHOULD BE SLOPED AS MUCH AS POSSIBLE TO REDUCE THE CHANCE OF GREASE

ACCUMULATION IN HORIZONTAL RUNS.

IF THE DUCT OR CHIMNEY IS WITHIN 18 INCHES OF COMBUSTIBLE MATERIAL, PROVIDE

UL-2221 OR UL-103 HT LISTED DOUBLE WALL GREASE DUCT OR DOUBLE WALL CHIMNEY

EQUAL TO CAPTIVEAIRE SYSTEMS MODEL "DW- 2R, 2R TYPE HT, 3R, OR 3Z" ROUND 20 GAUGE

430 STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS OUTER SHELL.

CAPTIVEAIRE SYSTEMS RECOMMENDS THE USE

OF LISTED, PRE-FABRICATED ROUND GREASE

EXHAUST DUCT TO REDUCE STATIC PRESSURE

IN THE SYSTEM, MINIMIZE INSTALLATION AND

INSPECTION TIMES, AND ENSURE DUCT IS

LIQUID TIGHT

CUSTOMER APPROVAL TO MANUFACTURE:

APPROVED AS NOTED

APPROVED WITH NO EXCEPTION TAKEN

REVISE AND RESUBMIT

SIGNATURE

YOUR TITLE DATE

HEIGHT REQUIRED TO VERIFY THAT HOOD FITS SPACE AND TO SIZE THE ENCLOSURE PANELS

VERIFY CEILING HEIGHT

HVAC DISTRIBUTION NOTE

HIGH VELOCITY DIFFUSERS OR HVAC RETURNS

SHOULD NOT BE PLACED WITHIN TEN (10) FEET

OF THE EXHAUST HOOD. PERFORATED

DIFFUSERS ARE RECOMMENDED.

PATENT NUMBERS

EXHAUST HOODS ND-2/BD-2/SND-2 (CANADA) - CA PATENT 2520435 C.

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

.c om

DATE:

A C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

R

C

U S

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

5' 6"NOM./5' 6.00"OD.

54"

1" LAYER OF INSULATION FACTORY

INSTALLED IN INTERNAL BACK STANDOFF.

MEETS 0 INCH REQUIREMENTS FOR

CLEARANCE TO COMBUSTIBLE SURFACES.

3"

7"

4"

7"

4"

15"

3 1/2"

15"

3 1/2"

33" 33"

10"

∅12"

U.L. LISTED RECESSED ROUND LED

FIXTURE AND LED LIGHT.

WATER LINE FOR SELF

CLEANING SYSTEM

45.00-70 PSI OPERATING PRESSURE

125 PSI MAXIMUM STATIC PRESSURE

140 - 170 DEG F

7.7 GPM MINIMUM

K FACTOR 1.4

1.0000" WATER CONNECTION.

5' 6"NOM./5' 6.00"OD.

54"

1" LAYER OF INSULATION FACTORY

INSTALLED IN INTERNAL BACK STANDOFF.

MEETS 0 INCH REQUIREMENTS FOR

CLEARANCE TO COMBUSTIBLE SURFACES.

3"

7"

4"

7"

4"

15"

3 1/2"

15"

3 1/2"

7"

4"

7"

4"

1.5" I.P.S. DRAIN DROP

ENGINEER IS RESPONSIBLE FOR DRAIN LINE DESIGN BEYOND THE HOOD.

DRAIN LINE MUST BE INSTALLED PER LOCAL CODES, DRAIN LINE MUST

BE SLOPED (MINIMUM ¼ INCH PER FOOT), AVOID ANY UNNECESSARY 90

DEGREE TURNS, IF COMBINED WITH OTHER DRAIN LINES, THEN PIPE SIZE

SHOULD BE INCREASED ACCORDINGLY. P-TRAPS SHOULD NOT BE USED IN

THE GREASE DRAIN LINE AND HEAT TAPE MUST BE USED WHERE DRAIN

LINE IS RUN IN ENVIRONMENTS THAT WOULD SOLIDIFY GREASE.

SIZE BUILDING GREASE INTERCEPTOR ACCORDINGLY.

BOTH ENDS

15"

3 1/2"

15"

3 1/2"

3/4" I.P.S. (N.P.T.) HOT WATER

CONNECTION STUBS ARE PREFIT

BY FACTORY.

BOTH ENDS

33" 33"

10"

∅12"

U.L. LISTED RECESSED ROUND LED

FIXTURE AND LED LIGHT.

11'-0.00" OVERALL LENGTH

PLAN VIEW - HOOD #1

5' 6.00" LONG 5412SND-2

PLAN VIEW - HOOD #2

5' 6.00" LONG 5412SND-2

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUT.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUTS.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL ALL-THREAD.

HOOD CORNER

HANGING ANGLE

(WEIGHT BEARING

ANCHOR POINT

FOR HOOD).

HOOD CORNER

HANGING ANGLE

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUTS.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

ASSEMBLY INSTRUCTIONS

HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI

GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING

ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5

(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI

GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE

DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING

ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4" OF

EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE

ALL HEX NUTS TO 57 FT-LBS.

(HARDWARE BY INSTALLER)

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUT.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

FULL LENGTH

HANGING ANGLE

(WEIGHT BEARING

ANCHOR POINT

FOR HOOD).

FULL LENGTH

HANGING ANGLE

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL ALL-THREAD.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUTS.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUT.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

ASSEMBLY INSTRUCTIONS

HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI

GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING

ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5

(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI

GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE

DOUBLED HEX NUT CONFIGURATION ABOVE CEILING

ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS

ACCEPTABLE FOR FULL LENGTH HANGING ANGLES.

MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM

HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS.

(HARDWARE BY INSTALLER)

WALL-MOUNT UTILITY CABINET

ASSEMBLY INSTRUCTIONS

CABINET TO BE HUNG BY OTHERS. SEE UTILITY CABINET

SCHEDULE FOR CABINET SIZE.

HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI

GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING

ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5

(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI

GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE

DOUBLED HEX NUT CONFIGURATION BENEATH UTILITY

CABINET HANGING ANGLES AND ABOVE CEILING ANCHORS.

MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM

HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUT.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUTS.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL ALL-THREAD.

HOOD CORNER

HANGING ANGLE

(WEIGHT BEARING

ANCHOR POINT

FOR HOOD).

UTILITY CABINET

HANGING ANGLE

1/2" - 13 TPI

GRADE 5 (MINIMUM)

STEEL HEX NUTS.

1/2" GRADE 5

(MINIMUM) STEEL

FLAT WASHER.

(HARDWARE BY INSTALLER)

CLEARANCE TO COMBUSTIBLES

HOODS # SURFACE *CLEARANCE

1,2

TOP 0"

FRONT 0"

BACK 0"

LEFT 18"

RIGHT 18"

- *0" CLEARANCE TO COMBUSTIBLES CONFORMS TO UL710

STANDARD.

1" LAYER OF INSULATION FACTORY

INSTALLED IN 3" INTERNAL STANDOFF.

MEETS 0 INCH REQUIREMENTS FOR

CLEARANCE TO COMBUSTIBLE SURFACES.

1.5" I.P.S. FINAL DRAIN DROP LOCATION

ALL NECESSARY FITTINGS FROM THE VENTILATOR

TO THE BUILDING WASTE LINE(S), I.E. FLOOR

SINKS, AIR GAPS, OR OTHER DEVICES REQUIRED

BY THE GOVERNING CODES, BY OTHERS.

ENGINEER IS RESPONSIBLE FOR DRAIN LINE DESIGN BEYOND THE HOOD.

DRAIN LINE MUST BE INSTALLED PER LOCAL CODES, DRAIN LINE MUST

BE SLOPED (MINIMUM ¼ INCH PER FOOT), AVOID ANY UNNECESSARY 90

DEGREE TURNS, IF COMBINED WITH OTHER DRAIN LINES, THEN PIPE SIZE

SHOULD BE INCREASED ACCORDINGLY. P-TRAPS SHOULD NOT BE USED IN

THE GREASE DRAIN LINE AND HEAT TAPE MUST BE USED WHERE DRAIN LINE

IS RUN IN ENVIRONMENTS THAT WOULD SOLIDIFY GREASE.

SEE HOOD TABLE.

EXHAUST RISER.

HANGING ANGLE.

RECESSED ROUND LED FIXTURE AND LED LIGHT,

3500 K WARM OUTPUT.

1.00" WIDE INSULATED

BACKSPLASH 68.00" HIGH

X 132.00" LONG.

1" LAYER OF INSULATION FACTORY INSTALLED

ON TOP OF HOOD. MEETS 0 INCH

REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE

SURFACES.

27"

27"

LEFT QUARTER END PANEL.

EQUIPMENT

BY OTHERS.

27" MIN.

48.0" MAX.

68"

80"

12" NOM.

54"

SECTION VIEW - MODEL 5412SND-2

HOOD - #1

IT IS THE RESPONSIBILITY

OF THE ARCHITECT/OWNER TO

ENSURE THAT THE HOOD CLEARANCE

FROM LIMITED-COMBUSTIBLE

AND COMBUSTIBLE MATERIALS

IS IN COMPLIANCE WITH

LOCAL CODE REQUIREMENTS.

20" CAPTRATE SOLO

FILTER WITH HOOK.

ADJUST DUCT NOZZLE 5° -10°

FROM VERTICAL TO POINT SLIGHTLY

TOWARDS BACK OF RISER.

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

1" LAYER OF INSULATION FACTORY

INSTALLED IN 3" INTERNAL STANDOFF.

MEETS 0 INCH REQUIREMENTS FOR

CLEARANCE TO COMBUSTIBLE SURFACES.

1.5" I.P.S. FINAL DRAIN DROP LOCATION

ALL NECESSARY FITTINGS FROM THE VENTILATOR

TO THE BUILDING WASTE LINE(S), I.E. FLOOR

SINKS, AIR GAPS, OR OTHER DEVICES REQUIRED

BY THE GOVERNING CODES, BY OTHERS.

ENGINEER IS RESPONSIBLE FOR DRAIN LINE DESIGN BEYOND THE HOOD.

DRAIN LINE MUST BE INSTALLED PER LOCAL CODES, DRAIN LINE MUST

BE SLOPED (MINIMUM ¼ INCH PER FOOT), AVOID ANY UNNECESSARY 90

DEGREE TURNS, IF COMBINED WITH OTHER DRAIN LINES, THEN PIPE SIZE

SHOULD BE INCREASED ACCORDINGLY. P-TRAPS SHOULD NOT BE USED IN

THE GREASE DRAIN LINE AND HEAT TAPE MUST BE USED WHERE DRAIN LINE

IS RUN IN ENVIRONMENTS THAT WOULD SOLIDIFY GREASE.

SEE HOOD TABLE.

EXHAUST RISER.

HANGING ANGLE.

RECESSED ROUND LED FIXTURE AND LED LIGHT,

3500 K WARM OUTPUT.

1" LAYER OF INSULATION FACTORY INSTALLED

ON TOP OF HOOD. MEETS 0 INCH

REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE

SURFACES.

27"

27"

RIGHT QUARTER END PANEL.

EQUIPMENT

BY OTHERS.

27" MIN.

48.0" MAX.

68"

80"

12" NOM.

54"

SECTION VIEW - MODEL 5412SND-2

HOOD - #2

IT IS THE RESPONSIBILITY

OF THE ARCHITECT/OWNER TO

ENSURE THAT THE HOOD CLEARANCE

FROM LIMITED-COMBUSTIBLE

AND COMBUSTIBLE MATERIALS

IS IN COMPLIANCE WITH

LOCAL CODE REQUIREMENTS.

20" CAPTRATE SOLO

FILTER WITH HOOK.

ADJUST DUCT NOZZLE 5° -10°

FROM VERTICAL TO POINT SLIGHTLY

TOWARDS BACK OF RISER.

1"

INSULATED BACKSPLASH

COMBUSTIBLE WALL

LENGTH

- STAINLESS STEEL BACKSPLASH INSULATED WITH

1" THICK DUCTBOARD WITH FOIL BACKING.

- INSULATED BACKSPLASH REQUIRES APPLIANCES

WITH CLEARANCE TO COMBUSTIBLES REQUIREMENTS

TO BE MOUNTED A MINIMUM OF 6" OFF OF THE

COMBUSTIBLE WALL.

-HOOD REAR INSULATION MUST BE UTILIZED WITH

INSULATED.

BACKSPLASH, UNLESS INSULATED BACKSPLASH

EXTENDS TO TOP OF HOOD.

SLIDE TOP FLANGE BEHIND

LOWER REAR EDGE OF HOOD

UNLESS LOCAL JURISDICTION

REQUIRES EXTENDED

BACKSPLASH

FLANGES LOCATED

AT TOP AND

BOTTOM

HEIGHT

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

FIRE SYSTEM INFORMATION - JOB#6733486

1 TANK FS 4.0/4.0 40 36 WALL UTILITY CABINET LEFT N/A

FIRE

SYSTEM

NO

TAG TYPE SIZE MAX FP

DESIGN

FP

INSTALLATION

SYSTEM LOCATION ON HOOD

GAS VALVE(S)

1 SC ELECTRICAL 1.250 CAPTIVEAIRE SYSTEMS

FIRE

SYSTEM

NO

TAG TYPE SIZE SUPPLIED BY

FIRE SYSTEM PARTS LIST KEY

0 - 0 - TANK FIRE SUPPRESSION POST-DISCHARGE PROCEDURE UTILITY CABINET LABEL SHEET.

0 - 0 - TANK FIRE SUPPRESSION MAINTENANCE GUIDE UTILITY CABINET LABEL SHEET.

0 - 0 - 12-F28021-32144-OT-360 DUCT FIRE THERMOSTAT WITH 12 FOOT WIRE LEADS. NO,

CLOSE ON TEMP RISE AT 360°F. (A0034310).

0 - 0 - 32-00002 QUIK SEAL - 1/2" (UL).

0 - 0 - 361091 3/8" BRASS PLUG.

0 - 0 - 4429K153 1/2" MALE NPT TO 1/2" FEMALE NPT ELBOW, BRASS.

0 - 0 - 4429K422 1/2" X 1/4" BRASS REDUCING BUSHING.

0 - 0 - 79425 3/8" NPT FEMALE TO 1/2" MALE PROPRESS ADAPTER.

0 - 0 - 79525 1/2" 90 PRO-PRESS ELBOW WITH 1/2” NPT FEMALE CONNECTION, VIEGA.

0 - 0 - 79580 1/2" X 1/2" PRO-PRESS TEE X 1/2” NPT FEMALE CONNECTION, VIEGA.

0 - 0 - 87-120042-001 SECONDARY ACTUATOR VALVE (SVA) - SINGLE ACTUATOR, REQUIRES

PRIMARY RELEASE ACTUATOR, TANK FIRE SUPPRESSION.

0 - 0 - 87-120045-001 HOSE, SECONDARY ACTUATOR HOSE, 7.5" BRAIDED STAINLESS STEEL, TANK FIRE SUPPRESSION.

0 - 0 - 87-300001-001 TANK - PRESSURIZED TANK USED FOR TANK FIRE SUPPRESSION.

0 - 0 - 87-300030-001 PRIMARY ACTUATOR KIT (PAK) - ACTUATOR AND RELEASE SOLENOID

ASSEMBLY, ONE NEEDED PER FIRE SYSTEM, SUPERVISED, TANK FIRE SUPPRESSION.

0 - 0 - 87-300152-001 HARDWARE, SVA BOLTS, TANK FIRE SUPPRESSION.

0 - 0 - 9055455PC PRO PRESS 1/2 PRESS X PRESS 90 ELBOW LD.

0 - 0 - 9097200PC PRO PRESS PC611 1/2 PRESS TEE LD.

0 - 0 - 98694A115 HARDWARE, DATANKLOCK LOCKING BRACKET SQUARE NUTS 5/16" ZINC, TANK

FIRE SUPPRESSION.

0 - 0 - A0034332 JUNCTION BOX FOR MANUAL PULL STATION. 1.5" DEEP BACK BOX, RED COLOR.

0 - 0 - A31484 1/4" NPT SCHRADER VALVE AND CAP, JB INDUSTRIES. 1/4" FLARE X 1/4"

MPT HALF UNION. USED ON TANK SERVICE PORT.

0 - 0 - BI145 3/8" BLACK IRON 90 ELL.

0 - 0 - DATANKLOCK DISCHARGE ADAPTER TANK LOCKING PLATE FOR FIRE SYSTEM TANK INSTALLATION

IN UTILITY CABINETS, TANK FIRE SUPPRESSION.

0 - 0 - SLPCON-05FT SUPERVISED LOOP CONNECTION KIT. CONTAINS THE PARTS NEEDED TO

CONNECT THE SUPERVISED LOOP BETWEEN END TO END HOODS WITH LESS THAN A 4' GAP. KIT

CONTAINS 7 FEET OF BLACK MG WIRE, 7 FEET OF TAN MG WIRE, 5 FEET OF FLEXIBLE CONDUIT, AND TWO 7/8" CONNECTORS.

0 - 0 - SLPCON-20FT SUPERVISED LOOP CONNECTION KIT. CONTAINS THE PARTS NEEDED TO

CONNECT THE SUPERVISED LOOP BETWEEN HOODS WITH UPTO 19' GAP. KIT CONTAINS 22 FEET

OF BLACK MG WIRE, 22 FEET OF TAN MG WIRE, 20 FEET OF FLEXIBLE CONDUIT, AND TWO 7/8"

CONNECTORS.

0 - 0 - TANK STRAP TANK STRAP - USED FOR TANK FIRE SUPPRESSION.

0 - 0 - TFS-UCTANKBRACKET TANK BRACKET FOR FIRE SYSTEM TANK INSTALLATION IN UTILITY

CABINETS, TANK FIRE SUPPRESSION.

0 - 0 - WK-283952-000 DISCHARGE ADAPTER, TANK FIRE SUPPRESSION.

16 - 16 - 79210 1/2" X 3/8" NPT MALE ADAPTER, VIEGA.

16 - 16 - OL-F NOZZLE - TANK PROTECTION APPLIANCE COVERAGE NOZZLE (INCLUDES METAL

BLOW OFF CAP, LANYARD, USED WITH CHROME-PLATED PIPE).

26 - 26 - QSA-3/8 QUIK SEAL - 3/8" (UL).

34 - 34 - A0034331 24VDC SINGLE ACTION MANUAL ACTUATION DEVICE (PUSH/PULL STATION)

WITH PROTECTIVE COVER, ONE (1) NORMALLY OPEN CONTACT. RED COLOR.

FIRE

SYSTEM

NO

TAG KEY NUMBER - PART DESCRIPTION

QTY BY

FACTORY

QTY BY

DIST

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

FACTORY PIPING EXTENDS A MAXIMUM

OF 6" ABOVE THE TOP OF THE HOOD.

10"

∅12"

HOOD FRONT

HOOD BACK

HOOD # 1 JOB # 6733486 FS # 1

MODEL: SND-2 SIZE: 54"x12" LENGTH: 5' 6"

T A N K

O V E R L A P P I N G

P R O T E C T I O N

S H E L F

H I G H

P R O X I M I T Y

L

X

D

DUCT

S

OL-F

OL-F

25.00" 25.00"

13.50"

OL-F

S H I P

L O O S E

13.50"

OL-F

S H I P

L O O S E

13.50"

OL-F

S H I P

L O O S E

13.50"

OL-F

NOZZLE HEIGHT

35-50" FROM

COOKING SURFACE.

(41.25")

S H I P

L O O S E

18.00" 32.00" 16.00" 16.00" 32.00" 18.00"

SLPCON-05FT

KIT

SLPCON-20FT

KIT

7"

4"

7.00"

4"

1.5" I.P.S. DRAIN DROP

BOTH ENDS.

10"

∅12"

HOOD FRONT

HOOD BACK

HOOD # 2 JOB # 6733486 FS # 1

MODEL: SND-2 SIZE: 54"x12" LENGTH: 5'

6"

DUCT

S

OL-F

OL-F

SLPCON-20FT

KIT

7"

4"

7.00"

4"

1.5" I.P.S. DRAIN DROP

BOTH ENDS.

84.00"

12.00"

84.00"

24.00"

WALL UC BACK

WALL UC FRONTHood#1

HANGING ANGLES

IN EACH CORNER.

2 5

WATER LINE FOR SELF

CLEANING SYSTEM

45-70 PSI OPERATING PRESSURE

125 PSI MAXIMUM STATIC PRESSUR.E

140 - 170 DEG F.

7.7 GPM MINIMUM.

K FACTOR 1.4.

1.0000" WATER CONNECTION. TO HOOD PLENUM

- SYSTEM REQUIRES A MINIMUM OF 7 FT OF

EQUIVALENT PIPE LENGTH BETWEEN TANK AND

NEAREST APPLIANCE NOZZLE FOR MOST APPLIANCES.

EACH 90 DEGREE ELBOW ADDS 1.3 FT OF

EQUIVALENT LENGTH. SEE MANUAL FOR DETAILS

TO HOOD# 1 WALL-UC

ALTERNATE FIELD-CONNECTION POINT

P L E N U M

P L E N U M

NOTES

- FIELD PIPE DROPS AS SHOWN

PIPING, ELBOWS, TEES, AND NOZZLES SUPPLIED BY CAS.

- FIELD INSTALLED DROP: FACTORY WILL PROVIDE QTY 2 60IN LONG PIECES OF CHROME

PLATED PIPING SHIPPED LOOSE TO BE FIELD-INSTALLED.

- SHIP LOOSE DROP: FACTORY WILL PROVIDE THE EXACT CHROME PIPE LENGTH NEEDED

SHIPPED LOOSE TO BE FIELD-INSTALLED.

- RELOCATE NOZZLES IF FLOW PATTERN IS BLOCKED BY SHELVING,

SALAMANDERS, ETC.

- OVERLAPPING COVERAGE SHALL NOT BE USED ON ANY APPLIANCE WITH AN OBSTRUCTION.

- IF APPLICABLE, EXTENDED PRE-PIPED DROPS ARE SHIPPED LOOSE.

- FACTORY PIPING EXTENDS A MAXIMUM OF 6" ABOVE THE TOP OF THE HOOD.

- APPLIANCE DIMENSIONS LISTED REPRESENT THE COOKING SURFACE

SIZE, NOT THE OVERALL APPLIANCE SIZE.

- THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS.

- OL-F NOZZLE PART NUMBER REPLACES 3070-3/8H-10-SS

JOB #: 6733486.

JOB NAME: ARMY CORP DREDGE.

SYSTEM SIZE: TANK-SP-2-WC DESIGN FP: 36. MAXIMUM FP: 40.

HOOD # 1 5' 6.00" LONG x 54" WIDE x 12" HIGH.

RISER # 1 SIZE: 12" DIA.

HOOD # 1 METAL BLOW-OFF CAPS INCLUDED.

HOOD # 2 5' 6.00" LONG x 54" WIDE x 12" HIGH.

RISER # 1 SIZE: 12" DIA.

HOOD # 2 METAL BLOW-OFF CAPS INCLUDED.

- HEAVY-DUTY APPLIANCES (RATED 600°F) WILL REQUIRE AN ADDITIONAL

DOWNSTREAM FIRESTAT IN THE EVENT THAT THE DUCTWORK CONTAINS ANY

HORIZONTAL RUNS OVER 25 FT IN LENGTH.

- MEDIUM TO LIGHT-DUTY APPLIANCES (RATED 450°F) WILL NOT REQUIRE

ANY ADDITIONAL DOWNSTREAM DETECTION.

AGENT DISTRIBUTION PIPING LIMITATIONS

PIPE SECTION MAX PIPE LENGTH (FT)

MAX SUPPLY LINE TO FIRST OVERLAPPING NOZZLE 42

OVERLAPPING NOZZLE APPLIANCE BRANCH 10

DEDICATED NOZZLE APPLIANCE BRANCH 10

PRESSURE SUPERVISION SWITCH.

PRIMARY ACTUATOR RELEASE.

4 GALLON TANK.

LEGEND - FIRE CABINET TANK SYSTEM

PRIMARY HOSE ASSEMBLY.

SECONDARY ACTUATOR RELEASE.3

SECONDARY HOSE ASSEMBLY.

REMOTE MANUAL ACTUATION DEVICE.

INCLUDES: FIELD INSTALLATION AND HOOKUP DURING NORMAL BUSINESS HOURS

BY CERTIFIED INSTALLERS ONLY IN THE LOCATION NOTED ABOVE, TWO SITE

VISITS ONLY (ONE VISIT TO SET PULL STATION & SYSTEM HOOKUP AND ONE

VISIT FOR ONE TEST; ADDITIONAL VISITS WILL RESULT IN ADDITIONAL

CHARGES), ONE MECHANICAL OR ELECTRICAL GAS VALVE PER SYSTEM AT A

MAXIMUM SIZE OF 2", PERMIT, AND SYSTEM TEST.

EXCLUDES: UNION LABOR & PREVAILING WAGE (LABOR & WAGES WILL BE

ADDED IF APPLICABLE), GAS VALVE INSTALLATION, ELECTRICAL HOOKUP AND

CONNECTIONS, HANGING OF FIRE CABINET, SHUNT TRIP, HANDHELD

EXTINGUISHER(S), ON-SITE RE-PIPING DUE TO EQUIPMENT LAYOUT CHANGES.

VOLTAGESIZE

TYPE

GAS VALVE SIZING GAS VALVE DIMENSIONS

DIM "A" DIM "B" DIM "C" DIM "D" DIM "F" DIM "G"

PART NUMBERS

GAS VALVES AND STRAINERS

INSTALLATION

MIN. INLET

PRESSURE

MAX. INLET

PRESSURE

FLOW AT 1 IN.W.C.

DROP NATURAL GAS

FLOW AT 1 IN.W.C.

DROP PROPANE

MOUNTING

ORIENTATION

GAS VALVE

PART NUMBER

STRAINER PART

NUMBER

GAS

VALVE/STRAINER KIT

ELECTRICAL

1-1/4"

120 VAC

4417K668214265

7-5/8"

6-3/8"

5-1/8" 5-15/16" 13-1/2" 12-1/16" (SC)EGVA1-1/4

GAS VALVE FOR FS#1

0 PSI

(0 IN.W.C.)

5 PSI

(138 IN.W.C.)

1,925,000 BTU/HR

1,249,105 BTU/HR

HORIZONTAL

FLOW.

ELECTRIC GAS VALVE.

STRAINER.

4" MIN.

DIM "G"

DIM "D"

DIM "A"

DIM "F"

DIM "C"

DIM "B"

ELECTRIC GAS VALVES ONLY:

3/4"-2" 120VAC GAS VALVES CAN BE MOUNTED WITH THE SOLENOID IN ANY POSITION ABOVE HORIZONTAL.

2 1/2"-3" 120VAC GAS VALVES MUST BE MOUNTED WITH THE SOLENOID VERTICAL AND UPRIGHT.

24VDC GAS VALVES MUST BE MOUNTED WITH THE SOLENOID VERTICAL AND UPRIGHT.

ALL GAS VALVES/STRAINERS

TO CALCULATE GAS FLOW FOR OTHER THAN 1 IN.W.C. PRESSURE DROP

NEW BTU/HR = (BTU/HR AT 1 IN.W.C. PRESSURE DROP) X NEW PRESSURE DROP

0.5

TO CALCULATE GAS FLOW FOR OTHER THAN 0.64 SPECIFIC GRAVITY

NEW BTU/HR = (BTU/HR AT 0.64) X (0.64 / NEW SPECIFIC GRAVITY)

0.5

CALCULATIONS

PROPER CLEARANCE MUST BE PROVIDED IN ORDER TO SERVICE THE

STRAINERS A MINIMUM OF 4" CLEARANCE DISTANCE MUST BE

PROVIDED AT THE BASE OF THE STRAINER CUSTOMER MUST VERIFY

BTU CONSUMPTION AS WELL AS PRESSURE RATING SPECIFIC GRAVITY

OF NATURAL GAS = 0.64, SPECIFIC GRAVITY OF LP = 1.52.

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

1/2" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

ELECTRICAL PACKAGE - JOB#6733486

1 SC-311110MA WALL UTILITY CABINET LEFT

SHIP LOOSE W/

PREWIRE

1 LIGHT

1 FAN

SMART CONTROLS THERMOSTATIC CONTROL

W/ RELAY ON/OFF WITH SUPPLY

EXHAUST

SUPPLY

3.000

5.000

4.6

7.0

NO TAG PACKAGE # LOCATION

SWITCHES

LOCATION QUANTITY

OPTION

FANS CONTROLLED

TYPE

ɸ

HP VOLT FLA

CASlink Monitor and Control

- Hood control panel to support communications to cloud-based Building

Management System.

- Hood Control Panel to allow cloud-based Building Management System to monitor real time parameters outlined as MONITOR in the points list.

- Hood Control Panel to allow cloud-based Building Management System to control parameters outlined as CONTROL in the points list.

- Hood Control Panel to allow cloud-based Building Management System to implement SYSTEM ECONOMIZER control strategies for fully integrated Building

Management.

MONITORING AND CONTROL POINTS LIST

SC Packages

DCV Packages

Function

Room Temperature(s)

MONITOR

Duct Temperature(s)

MONITOR

MUA DIscharge Temperature

MONITOR

Kitchen RTU Discharge Temperature

MONITOR

Controller Faults MONITOR

Fan Faults MONITOR

Fan Status MONITOR

PCU Faults MONITOR

PCU Filter Clog Percentages

MONITOR

Fire Condition MONITOR

CORE Fire System

MONITOR

Building Pressures

MONITOR

Fans Button(s)

MONITOR & CONTROL

Lights Button(s)

MONITOR & CONTROL

Wash Button MONITOR & CONTROL

Function

Room Temperature

MONITOR

Duct Temperature(s)

MONITOR

MUA Discharge Temperature

MONITOR

Kitchen RTU Discharge Temperature

MONITOR

Fan Speed

MONITOR

Fan Amperage

MONITOR

Fan Power MONITOR

VFD Faults MONITOR

Controller Faults MONITOR

Fan Faults MONITOR

Fan Status MONITOR

PCU Faults MONITOR

PCU Filter Clog Percentages

MONITOR

Fire Condition MONITOR

CORE Fire System

MONITOR

Building Pressures

MONITOR

Prep Time Button

MONITOR & CONTROL

Fans Button MONITOR & CONTROL

Lights Button

MONITOR & CONTROL

Wash Button MONITOR & CONTROL

Field Connection Antennas

Wired OR Paddle

Field Connection to Router

OR Ethernet switch

Connection for Modbus

Factory wired OR Field Wired

Terminal Blocks for wired connection

Cellular Module

Compute module

DESCRIPTION OF OPERATION:

JOB NO

JOB NAME

MODEL NUMBER

DATE

DRAWN BY

DWG NO

SCHEMATIC TYPE

6733486

ARMY CORP DREDGE

SC-311110MA

12/2/2024

INSTALL

ECP #1-1

3 Phase w/ control for 1 Exhaust Fan, 1 Supply Fan, Exhaust on in Fire, Lights out in Fire, Relay On/Off with Supply

Fan, Fan(s) On/Off Thermostatically Controlled. Room temperature sensor shipped loose for field installation.

INVERTER DUTY 3 PHASE MOTOR REQUIRED FOR USE WITH VFD.

BREAKER PANEL TO PRIMARY CONTROL PANEL

Responsibility: Electrician

BREAKER PANEL PRIMARY CONTROL PANEL

BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED

BREAKER 1PH

CONTROL POWER. DO NOT WIRE

TO GFCI OR SHUNT TRIP

BREAKER.

Hot

Neutral

H1

N1

120 V

15 A

Ground

GND

1ST HOOD LIGHT BREAKER SHARED W/

CONTROL POWER. SWITCH #1

BREAKER PANEL TO ADDITIONAL CONTROL PANEL

Responsibility: Electrician

BREAKER PANEL ADDT'L PANEL

BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED

WIRE TO VFD QUICK CONNECTOR

BREAKER 3PH

MCA:

MOCP:

LINE

LINE

Ground

EF-13 SM-1

GND

L1

L2

LINE

L3

460 V

5.8 A

15 A

BREAKER 3PH

WIRE TO VFD QUICK CONNECTOR

MCA:

MOCP:

LINE

LINE

460 V

Ground

T/A S3 SM-2

GND

L4

L5

LINE

L6

8.8 A

15 A

CONTROL PANEL TO FANS

Responsibility: Electrician

PRIMARY PANEL FANS

MAKE UP AIR

PROVING

INTERLOCK

DAMPER

LOW VOLTAGE CONNECTION FOR

DAMPER INTERLOCK. WIRE

MULTIPLE SUPPLY ON THE SAME

ZONE IN SERIES. SHOULD

MUA ZONE 1

TERMINAL NAMES

DO NOT APPLY

IF MUA BY OTHERS

ON PCB

REMOVE JUMPER

HAVE CONTINUITY WHEN DAMPER

IS PROVEN OPEN.

NOT REQUIRED FOR ALL UNITS.

SEE MAKE-UP AIR SCHEMATIC.

IL1A

IL1B

D3

D7

CONTROL PANEL TO FANS

Responsibility: Electrician

ADDT'L PANEL FANS

Load Wiring

WIRE TO

VFD QUICK

WIRE TO

DISCONNECT

CONNECTOR

MUST HAVE ITS OWN CONDUIT

DO NOT SHARE CONDUIT!

FLA:

HP:

VOLT:

EF-1301

LOAD LEG 1

LOAD LEG 2

GND

GROUND

FAN:

SM-1

LOAD LEG 3

U1

V1

W1

4.6

3.000

460 V

Load Wiring

BLACK

BLACK

BLACK

GREEN

WIRE TO

VFD QUICK

CONNECTOR

WHITE

RED

FLA:

HP:

VOLT:

MUST HAVE ITS OWN CONDUIT

DO NOT SHARE CONDUIT!

IF VFD MOUNTED

IN 2ND PANEL,

WIRE SF SIGNAL

FROM PANEL WITH

ECPM03.

U2

V2

W2

LOAD LEG 1

LOAD LEG 2

LOAD LEG 3

GND

GROUND

T/A S3

02FAN:

SM-2

N1

120V NEUTRAL

120V HOT

N1

7.0

5.000

460 V

H1

CONTROL PANEL TO ACCESSORY ITEMS

Responsibility: Electrician

CONTROL PANEL COMPONENT

WIRE DIRECTLY TO CONTROL BOARD

CAT-5 CONNECTION

CONTROL PANEL

REMOTE

TO

MOUNTED

SWITCHES

PLACE END OF LINE PLUG

EOL120A

IN EMPTY JACK. PN: EOL120A

HMI

J4 1

CONTROL PANEL

HOOD LIGHTS

TO

1400 W MAX

WIRE TO J-BOX ON TOP OF HOOD

B1

W1

GND

BLACK

WHITE

GREEN

HOOD LIGHTS 1

WIRE DIRECTLY TO COMMUNICATION

ROUTER

COMM

MODULE. NET REQUIRES 1) DHCP 2)

UDP PORT 1444 & 1445 OPEN FOR

CAT-5 ETHERNET CONNECTION

CONTROL PANEL

WORLD WIDE

TO

WEB

OUTBOUND TRAFFIC ONLY.

WIRE TO CONTROL BOARD. INSTALL

SENSOR IN ROOM AWAY FROM HEAT

SOURCES. DO NOT INSTALL SENSOR

CONTROL PANEL

ROOM TEMP

TO

SENSOR

ON THE CEILING GRID, SEE MANUAL.

GROUPS:

T1A

T1B

ROOM TEMP

WIRE TO CONTROL BOARD.

SENSOR MOUNTED IN HOOD CAPTURE

CONTROL PANEL

CAPTURE VOLUME

TO

SENSOR

VOLUME.

T2A

T2B

HOOD 1

CAPTURE 1

WIRE TO CONTROL BOARD.

SENSOR MOUNTED IN HOOD CAPTURE

CONTROL PANEL

CAPTURE VOLUME

TO

SENSOR

VOLUME.

T3A

T3B

HOOD 2

CAPTURE 1

FACTORY WIRED TEMPERATURE

SENSOR MOUNTED IN SELF CLEANING

CONTROL PANEL

WATER WASH

TO

WATER TEMPERATURE.

T4A

T4B

HOOD 1

WATER TEMP

CONTROL PANEL

GAS VALVE

TO

120V ONLY

ONLY ENERGIZED THROUGH LCD

HMI WHEN FIRE SYSTEM ARMED.

GAS

N1

HOT TO GAS VALVE

NEUTRAL

GAS SOLENOID

THE FOLLOWING CONNECTIONS

MAY OR MAY NOT BE

REQUIRED BASED ON JOBSITE

SPECIFICATIONS

CONTROL PANEL

EXTERNAL

SIGNAL FOR

SHUNT TRIP

ST TERMINAL IS ENERGIZED

IN FIRE CONDITION.

CONTROL PANEL

EXTERNAL

SIGNAL FOR

CONTACTOR COIL

KS TERMINAL IS DE-ENERGIZED

IN FIRE CONDITION.

ST

N1

NEUTRAL FROM SHUNT COIL

HOT TO SHUNT COIL

SHUNT COIL

KS

N1

NEUTRAL_TO_CONTACTOR_COIL

HOT_TO_CONTACTOR_COIL

CONTACTOR_COIL

SPARE CONTACTS WILL MAKE

CONTROL PANEL

ON/OFF WITH

DRY CONTACT

SUPPLY FAN

COMMON TO NORMALLY OPEN

WHEN SUPPLY FAN IS ON.

GROUP 1

SFC1

SFO1

COMMON

NORMALLY OPEN

SFC2

SFO2

COMMON

NORMALLY OPEN

CONTROL PANEL

EXTERNAL

TO

SWITCH

SIGNAL SWITCH THROUGH BMS

WILL ACTIVATE ZONE1 FANS AND

LIGHTS

H1

IO1

BMS SWITCH

C NO

CONTROL PANEL

GAS VALVE

TO

24V DC ONLY

ONLY ENERGIZED THROUGH LCD

HMI WHEN FIRE SYSTEM ARMED.

(NOT NEEDED IF USING 120V

GAS VALVE).

LGV

N1D

POSITIVE TO GAS VALVE

NEGATIVE

GAS SOLENOID

CONTROL PANEL TO FIRE SYSTEM

Responsibility: ALARM CONTRACTOR

CONTROL PANEL COMPONENT

CONTROL PANEL

BUILDING

SIGNAL FOR

FIRE ALARM

PANEL

AL1

AL2

J9

BUILDING

ALARM PANEL

FIRE INPUT

WIRE DIRECTLY TO CORE CIRCUIT

BOARD. AL1 WILL MAKE AL2 IN FIRE

CONDITION.

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

DESCRIPTION OF OPERATION:

JOB NO

JOB NAME

MODEL NUMBER

DATE

DRAWN BY

DWG NO

SCHEMATIC TYPE

6733486

ARMY CORP DREDGE

SC-311110MA

12/2/2024

INSTALL

ECP #1-2

3 Phase w/ control for 1 Exhaust Fan, 1 Supply Fan, Exhaust on in Fire, Lights out in Fire, Relay On/Off with Supply

Fan, Fan(s) On/Off Thermostatically Controlled. Room temperature sensor shipped loose for field installation.

INVERTER DUTY 3 PHASE MOTOR REQUIRED FOR USE WITH VFD.

CONTROL PANEL

BUILDING

SIGNAL FOR

TROUBLE

TROUBLE RELAY CONTACTS WILL

MAKE TBC TO TBL IN TROUBLE

CONDITION.

BUILDING

ALARM PANEL

ALARM

TBC

TBL

COMMON

NORMALLY CLOSED

CONTROL PANEL TO FIRE SYSTEM

Responsibility: CERTIFIED INSTALLER

CONTROL PANEL COMPONENT

FIRE STAT SUPERVISED LOOP

May be mixed factory and field wiring. See Installation Schematic.

Multiple fire sensors possible.

HIGH TEMP WIRE (842 F), PN:

SLPCON-xFT required for all

Supervised Loop wiring in contact with a hood. All other wiring shall be PN: 6320UL, Belden or similar.

FS-01

BK WH

Fire Stat

FS-02

BK WH

Fire Stat

CONTROL PANEL

MOUNTED FIRE

TO DUCT

DETECTION

STAT(S)

FIRE STATS

CONTROL PANEL

SYSTEM PULL

TO FIRE

STATION

MANUAL ACTUATION LOOP / REMOTE FIRE

SYSTEM LOOP.

Multiple manual actuation possible.

Multiple manual actuation possible.

A Plug jumper with wires from pin1 to pin4 and from pin2 to pin3 is mounted on

J10, remove the jumpers and wire in the supervised actuation loop.

Microswitch MS-01 is optional for fire system interlock.

Auxiliary Interlock (AUX-01):

Wire AU1 / AU2 of adjacent Master FS panel(s) in each manual activation loop for simultaneous activation. See Fire system drawings for more information.

AUX-01

AU1 AU2

PULL STATION

MS-01

C NO

Micro SW

MAD-01

C NO

Manual

Actuation

Device

Adjacent

FS

Panel

CAT-5 CONNECTION

CONTROL PANEL

MASTER FS

TO

BOARD.

PLACE END OF LINE PLUG

EOL120A

IN EMPTY JACK. PN: EOL120A

CORE PCB

ADDITIONAL DEVICES MAY BE INLINE.

ECPM03

UNLESS VFD, PCU,

OR OTHER COMPONENT IN SERIES.

J3 J5

J6

CONTROL PANEL

MASTER FS

TO

PANEL

WIRE TO LIKE TERMINALS IN ALL

CORE PANELS THAT MUST ACTIVATE

TOGETHER. SET MASTER & SLAVE

DIP SWITCHES PER FIRE SYSTEM

SHIELDED TWISTED PAIR

INTERLOCK NETWORK MASTER CORE

MANUAL.

CA

CB

CC

BLACK

RED

SHIELD

CA

CB

CC

WALL MOUNT UTILITY CABINET TANK PROTECTION

ELECTRICAL DETAIL

10/01/2023 Rev. 03

ELECTRICIAN:

1. WIRE MAIN CONTROL PANEL PER INCLUDED SCHEMATIC

2. WIRE ALL FANS PER INCLUDED SCHEMATIC

3. WIRE SHUNT TRIP BREAKER (OPTIONAL)

4. WIRE UDS APPLIANCE KILL SWITCH, IF EQUIPPED (OPTIONAL)

5. WIRE GAS VALVE

NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS

36 INCHES CLEARANCE REQUIRED IN FRONT

OF ALL UTILITY CABINET DOORS

THE PANEL SHALL ALSO BE LOCATED IN AN

ACCESSIBLE AREA WHERE THE AUDIBLE AND

VISUAL ALARMS CAN BE HEARD AND SEEN

GAS

ELECTRIC

ELECTRICAL CONTRACTOR REQUIREMENT

ITEM CONNECTION IN PANEL CONNECTION IN DEVICE VOLTAGE AMPERAGE COMMENTS

SHUNT TRIP BREAKER (OPTIONAL) ST & N1

BREAKER COIL

(A1 & A2)

120 VAC < 4 AMPS ST TO A1 ON SHUNT BREAKER COIL, AND NEUTRAL TO A2 ON SHUNT TRIP BREAKER COIL

CONTROL PANEL POWER H1 & N1 + GROUND CIRCUIT BREAKER 120 VAC 15 AMPS CONTROL PANEL POWER MUST NOT BE RUN THROUGH SHUNT TRIP BREAKER

UDS APPLIANCE KILL SWITCH (OPTIONAL) KTS & N1 KTS & N1 120 VAC < 4 AMPS KILL SWITCH TERMINALS MUST BE IN SERIES WITH OTHER KILL SWITCHES

REMOTE 120VAC ANSUL AUTOMAN (OPTIONAL) AU1, AU2 SOLENOID 120 VAC < 6 AMPS 120V TO AU1, AU2 TO ANSUL ELECTRIC AUTOMAN, ANSUL SOLENOID TO NEUTRAL

GAS VALVE

LGV & N1D (IF 24 VDC)

GAS & N1 (IF 120 VAC)

RED/RED/GREEN

24 VDC

OR 120 VAC

< 1.0 AMPS

IF 24 VDC - 2 WIRES & GROUND, N1D TO RED, LGV TO RED, AND GREEN TO GROUND

IF 120 VAC - 2 WIRES & GROUND GAS TO RED, N1 TO RED, AND GREEN TO GROUND

SHUNT TRIP BREAKER (OPTIONAL)

-2 WIRES, 120VAC

-ST TO A1 ON SHUNT BREAKER

-NEUTRAL TO A2 ON SHUNT TRIP

BREAKER

POWER TO ELECTRIC

APPLIANCE

CONTROL PANEL POWER

-2 WIRES & GROUND

-120 VAC, 15 AMP SERVICE

-WIRE TO H1 AND N1, GROUND

-POWER MUST NOT ORIGINATE

FROM SHUNT TRIP BREAKER

GAS VALVE POWER

-2 WIRES & GROUND

-24 VDC WIRE TO LGV & N1D

-120 VAC WIRE TO GAS & N1

GAS VALVE

-STRAINER MUST BE

INSTALLED UPSTREAM

OF VALVE

COOKING

APPLIANCE(S)

DESCRIPTION OF OPERATION:

EXHAUST HOOD

JOB NO

JOB NAME

MODEL NUMBER

DATE

DRAWN BY

DWG NO

SCHEMATIC TYPE

6733486

ARMY CORP DREDGE

SC-311110MA

12/2/2024

INSTALL

ECP #1-3

Fire System #1 TANK FS - 4.0/4.0.

FS-1: MASTER

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

ALARM CONTRACTOR:

1. WIRE MANUAL ACTUATION DEVICE(S), REMOTE FIRESTAT(S), CORE INTERLOCK(S), FIRE SENSOR(S) AND FIRE ALARM CONTACTS

2. COMPLETE FINAL HOOKUP OF SYSTEM

3. VERIFY FINAL FIRE SYSTEM TEST

ATTENTION: LOW-VOLTAGE DC OR SIGNALING WIRE SHOULD

BE ROUTED IN SEPARATE CONDUIT FROM ALL AC SOURCES

36 INCHES CLEARANCE REQUIRED IN

FRONT OF ALL UTILITY CABINET DOORS

THE PANEL SHALL ALSO BE LOCATED IN

AN ACCESSIBLE AREA WHERE THE

AUDIBLE AND VISUAL ALARMS CAN BE

HEARD AND SEEN

ELECTRIC GAS

NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS

ALARM CONTRACTOR REQUIREMENT

ITEM CONNECTION IN PANEL CONNECTION ON DEVICE VOLTAGE AMPERAGE COMMENTS

MANUAL ACTUATION DEVICE(S)

101 AND 104

102 AND 103

1 & 2 24 VDC < 1.0 AMPS

WIRE MANUAL ACTUATION DEVICE TERMINAL 1 BETWEEN CORE PANEL TERMINALS 102 AND 103

WIRE MANUAL ACTUATION DEVICE TERMINAL 2 BETWEEN CORE PANEL TERMINALS 101 AND 104

JUMPER 101 TO 104 AND 102 TO 103 IF NO MANUAL ACTUATION DEVICE IS INSTALLED

MANUAL ACTUATION DEVICE COVER N/A N/A N/A N/A

MANUAL ACTUATION DEVICE COVER MUST BE INSTALLED

IF SURFACE MOUNTED, USE COVER EXTENSION STI-6531B

REMOTE FIRESTAT SENSOR(S)

21 AND 24

22 AND 23

BLACK AND WHITE 24 VDC < 1.0 AMPS

WIRE FIRE SENSOR WHITE WIRES BETWEEN HOOD CORE PANEL TERMINALS 22 AND 23

WIRE FIRE SENSOR BLACK WIRE BETWEEN HOOD CORE PANEL TERMINALS 21 AND 24

OF HOOD; OTHERWISE BELDEN #6320UL OR SIMILAR PLENUM RATED WIRE; SEE FIGURE 1

FIRE ALARM CONTACT AL1, AL2 VARIES

50V MAX

(AC/DC)

UP TO 1 AMP

FIRE ALARM RELAY CONTACTS FOR BUILDING FIRE ALARM LOCATED IN THE

CORE ELECTRICAL CONTROL PANEL

CORE INTERLOCK(S)

RS-485 COMMUNICATIONS

SIGNAL

TROUBLE CONTACT

TBC, TBL, TOK

VARIES MAX 120 VAC

UP TO 6

AMPS

WIRE TO TBL & TBC NORMALLY OPEN CONTACT, CLOSES IN TROUBLE CONDITION

CORE COMMUNICATIONS CABLE RJ-45 Jack INTERNET CONNECTION SIGNAL <1.0 AMPS

TYPICAL CONNECTION CAT5 CABLE TO LOCAL AREA NETWORK VIA ETHERNET SWITCH OR

WIRELESS ROUTER WITH VALID INTERNET CONNECTION

42 TO 48 INCHES

ABOVE FLOOR

LEVEL TO

CENTER OF PUSH

STATION

MANUAL

ACTUATION

DEVICE

10 TO 20

FEET FROM

HOOD LOCATED

NEAR POINT

OF EGRESS

FROM HOOD

MANUAL ACTUATION DEVICE WIRES

-4 WIRES, 24VDC WIRE (TERMINAL 1)

BETWEEN 102 AND 103

-WIRE (TERMINAL 2) BETWEEN 101 AND 104

-ADDITIONAL PULL STATIONS WIRED IN

SUPERVISED LOOP

-USE BELDEN #6320UL OR SIMILAR WIRE

MANUAL ACTUATION DEVICE

PROTECTIVE COVER MUST BE INSTALLED

SUPERVISED LOOP

-4 WIRES, 24VDC CONNECT BLACK

WIRES BETWEEN 21 AND 24 IN PANEL,

CONNECT WHITE (OR RED) WIRES

BETWEEN 22 AND 23 IN PANEL

-ADDITIONAL FIRESTATS, WIRED IN

SUPERVISED LOOP

-USE HIGH TEMP (842°F)

RAN OVER TOP OF HOOD;

OTHERWISE BELDEN #6320UL OR

SIMILAR PLENUM RATED WIRE

-SEE FIGURE 1

CORE COMMUNICATIONS CABLE

-CAT5 CABLE

MUST BE INSTALLED TO A LOCAL AREA

NETWORK WITH VALID INTERNET ACCESS

VIA ETHERNET SWITCH OR WIRELESS

ROUTER

CORE INTERLOCK

-2 WIRES + SHIELD

-USE BELDEN#88760 OR SIMILAR WIRE

-SEE FIGURE 3

FIRE ALARM PANEL

FIRE ALARM CONTACT

-2 WIRES WIRED TO NORMALLY OPEN CONTACTS

(CLOSES IN FIRE CONDITION)

-CORE CONTROL PANEL AL1 AND AL2

-SEE FIGURE 2

TROUBLE CONTACT

-2 WIRES TO NORMALLY OPEN

CONTACTS (CLOSE IN TROUBLE

CONDITION)

-CORE PANEL TERMINALS TBL AND TBC

-SEE FIGURE 4

COOKING

APPLIANCE(S)

DESCRIPTION OF OPERATION:

WALL MOUNT UTILITY CABINET TANK PROTECTION LOW-

VOLTAGE DETAIL

10/01/2023 Rev. 3

EXHAUST HOOD

HIGH TEMP (842°F) #441601C6.FE9 (WHT) & #441601C6.FE0 (BLK)WIRE OR SIMILAR ONLY IF RAN

CA, CB, CC CA, CB, CC

CORE SYSTEM (1) CA, TO CORE SYSTEM (2) CA. CORE SYSTEM (1) CB, TO CORE SYSTEM (2) CB.

CORE SYSTEM (1) CC, TO CORE SYSTEM (2) CC. USE BELDEN# 88760 OR SIMILAR WIRE

-SEE FIGURE 1A

PART #SS2031ZA-EN

#441601C6.FE9 (WHT) &

#441601C6.FE0 (BLK)WIRE ONLY IF

JOB NO

JOB NAME

MODEL NUMBER

DATE

DRAWN BY

DWG NO

SCHEMATIC TYPE

6733486

ARMY CORP DREDGE

SC-311110MA

12/2/2024

INSTALL

ECP #1-4

Fire System #1 TANK FS - 4.0/4.0.

FS-1: MASTER

10/01/2023 Rev. 17

AL1

AL2 END

OF

LINE

DEVICE

WIRING CONNECTIONS FOR FIRE

ALARM CONTACT

FIGURE 2

CORE

CONTROL

PANEL

FIRE

ALARM

CONTACT

ALARM

INPUT

BUILDING

FIRE ALARM

SHIELDED TWISTED PAIR

CA

CC

CB

CA

BK

CB

RD

BK

RD

WIRING CONNECTIONS

FOR CORE INTERLOCK

FIGURE 3

CC

ATTENTION: LOW-VOLTAGE DC OR SIGNALING WIRE SHOULD

BE ROUTED IN SEPARATE CONDUIT FROM ALL AC SOURCES

SUPERVISION

SWITCH

1 2

C

BUILDING

FIRE ALARM

TROUBLE

INPUT

CORE

CONTROL

PANEL

TROUBLE CONTACT

NO

C

NC

C

SUPERVISION

SWITCH

SUPERVISION

SWITCH

END

OF

LINE

DEVICE

TBC

TBLTOK

WIRING CONNECTIONS FOR

TROUBLE CONTACT

FIGURE 4

BK-C

BK-C

J2-1

J2-2

J2-4

J2-3

BK-C

J10-1

J10-2

J10-4

J10-3

BK-C

WIRING CONNECTIONS

FOR FIRESTAT LOOP

FIGURE 1

WIRING CONNECTIONS

FOR MANUAL ACTUATION LOOP

FIGURE 1A

BREAK WIRE

BEFORE

INSERTING

INTO

TERMINALS

FIRE

STAT-2

FIRE

STAT-1

NO-WH

(OR RD)

NO-WH

(OR RD)

BREAK WIRE

BEFORE

INSERTING

INTO

TERMINALS

NO-WH

(OR RD)

MANUAL

ACTUATION

DEVICE

NO-WH

(OR RD)

MANUAL

ACTUATION

DEVICE

MICROSWITCH/

NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS

USE BELDEN #6320UL

OR SIMILAR WIRE

DESCRIPTION OF OPERATION:

TOTAL PROTECTION LOW-VOLTAGE FIGURES

FS-1: MASTER

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

DESCRIPTION OF OPERATION:

0.6

1.3

1.9

2.5

3.1

3.8

4.3

4.8

5.3

5.4

5.9

6.3

10/01/2023 Rev. 01

PLUMBER:

1. CONNECT HOT WATER LINE; **PVC, COPPER STAINLESS STEEL PIPE, OR LISTED BRAIDED HOSE ONLY

2. CONNECT HOOD DRAIN(S) STAINLESS STEEL, COPPER, OR STEEL PIPE ONLY

3. CONNECT ALL END-TO-END AND BACK-TO-BACK HOOD WATER LINE CONNECTIONS (PLUMBING IS FIELD SUPPLIED FOR THIS). FIELD PLUMBING MUST NOT EXCEED HEIGHT OF VACUUM BREAKER IN MAIN UTILTY CABINET.

REMOVE PLUG FROM MAIN HOOD SPRAY BAR AND CONNECT TO NEXT HOOD STAINLESS STEEL, COPPER, OR STEEL PIPE ONLY

4. PLUMB GAS VALVE, STRAINER MUST BE INSTALLED UPSTREAM OF VALVE

5. INSTALL FLOOR DRAIN

6. INSTALL BACKFLOW PREVENTER IF CODE REQUIRES

EXHAUST HOOD

36 INCHES CLEARANCE REQUIRED IN FRONT

OF ALL UTILITY CABINET DOORS

THE PANEL SHALL ALSO BE LOCATED IN AN

ACCESSIBLE AREA WHERE THE AUDIBLE AND

VISUAL ALARMS CAN BE HEARD AND SEEN

ELECTRIC GAS

NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS

**PVC PIPING CANNOT BE WITHIN 10 FT OF HOOD, CONNECTIONS TO THE MANIFOLD MUST BE HARD PIPED WITH COPPER, OR STAINLESS STEEL.

WALL MOUNT UTILITY CABINET TANK PROTECTION WITH SELF

CLEANING PLUMBING DETAIL

PLUMBING CONTRACTOR REQUIREMENT

ITEM CONNECTION TEMPERATURE PRESSURE FLOW RATE COMMENTS

HOT WATER LINE 1 INCH NPT 140 to 170°F 45.00 PSI TO 70 PSI

7.7 GPM (0.7 GPM PER FOOT

OF HOOD)

INSULATE HOT WATER PIPE, MINIMUM PRESSURE DEPENDENT ON LENGTH AND CONFIGURATION OF HOOD

SYSTEM

HOOD DRAIN(S) 1-1/2 INCH NPT N/A GRAVITY DRAIN SEE ABOVE 2 DRAINS ON 24 INCH TALL HOODS WITH 20 INCH TALL FILTERS AND HOODS 10 FEET AND LONGER

END-TO-END CORE CONNECTION VARIES N/A N/A N/A CONNECT WITH NPT PIPE, SEAL ALL THREADS, HOOD CONNECTION PROVIDED

BACK-TO-BACK CORE CONNECTION VARIES N/A N/A N/A CONNECT WITH NPT PIPE, SEAL ALL THREADS, HOOD CONNECTION PROVIDED

GAS VALVE VARIES N/A SEE TABLE N/A UP TO 2 INCHES NPT WITH 24V CONTROLS, 2-1/2 AND 3 INCH USE 120V CONTROL

FLOOR DRAIN(S) 1-1/2 INCH N/A GRAVITY DRAIN N/A USED TO HELP CLEAN UP FIRE SYSTEM DISCHARGE, GREASE INTERCEPTOR MAY BE REQUIRED

BACKFLOW PREVENTER DRAIN LINE

(OPTIONAL)

INLET/OUTLET

DRAIN

N/A VARIES N/A

INSTALLED WHEN PACKAGE HAS A BACKFLOW PREVENTER VALVE, SEE BACKFLOW PREVENTER VALVE

MANUAL FOR DETAILS

REQUIREMENTS

LENGTH OF

HOOD (FT)

MINIMUM INLET

WATER PRESSURE

FOR HOT WATER (PSI)

DISCHARGE

COEFFICIENTS

(K-FACTOR)

GAS VALVE

-THREADED NPT CONNECTION

-SEE TABLE BELOW FOR MAX PRESSURE

-STRAINER INSTALLED UPSTREAM OF VALVE

END-TO-END OR BACK-TO-BACK

CONNECTION

-INSTALLED AND PROVIDED BY

PLUMBER

STAINLESS STEEL, COPPER, STEEL PIPE,

OR LISTED BRAIDED HOSE ONLY

HOOD DRAIN(S)

-1-1/2 INCH NPT CONNECTED TO

BUILDING GREASE TRAP

-2 DRAINS ON 24 INCH TALL HOODS

WITH 20 INCH FILTERS

-2 DRAINS ON HOODS 10 FEET AND

LONGER

-STAINLESS STEEL, COPPER OR STEEL

PIPE ONLY

-SLOPED MINIMUM 1/4" PER FOOT,

AVOID ANY UNNECESSARY 90°

TURNS

-PIPE SIZE SHOULD BE INCREASED

WHEN COMBINED WITH OTHER

DRAINS

-P-TRAPS SHOULD NOT BE USED IN

THE GREASE DRAIN LINE AND HEAT

TAPE MUST BE USED WHERE DRAIN

LINE IS RUN IN ENVIRONMENTS THAT

WOULD SOLIDIFY GREASE

FLOOR DRAIN

-1-1/2 DRAIN INSTALLED

IN FLOOR, NEAR

APPLIANCES

-FLOOR DRAINS MAY BE

USED TO DRAIN HOOD

-GREASE INTERCEPTOR

MAY BE REQUIRED COOKING

APPLIANCE(S)

HOT WATER LINE

-**PVC, COPPER, STAINLESS STEEL

PIPE, OR LISTED BRAIDED HOSE ONLY

-140-170°F OPERATING

TEMPERATURE

-45.00 PSI TO 70 PSI OPERATING PRESSURE

-125 PSI MAX STATIC PRESSURE

-7.7 GPM(0.7 GPM PER FOOT OF HOOD)

-1 INCH NPT NPT FITTING, INSULATED

PRESSURE REGULATOR VALVE

PRV INCLUDED, UNLESS OUTSIDE DESIGN PRESSURE.

PART NUMBERS: LFN55BM1-U(3/4"), LFN55BM1-U(1"), OR LFN55BU(1-1/2")

CONSULT FACTORY FOR SIZING

1" HOT WATER LINE MINIMUM OPERATING PRESSURE

JOB NO

JOB NAME

MODEL NUMBER

DATE

DRAWN BY

DWG NO

SCHEMATIC TYPE

6733486

ARMY CORP DREDGE

SC-311110MA

12/2/2024

INSTALL

ECP #1-6

Fire System #1 TANK FS - 4.0/4.0.

FS-1: MASTER

WH

BK

A B C D E F G H I

FACTORY WIRING

SCHEMATIC

CIRCUIT BOARDS

MOTOR POWER CIRCUIT

PANEL LID

COMPONENT LIST

LABEL DESCRIPTION

ST-X

varies

Starter

OL-X

varies

Overload

C-X varies

Contactor

120 VAC

RELAY

NO

COM

COIL

NC

6 5

RA-x

24 VDC

RELAY

RD-x

NO

COM

COIL

NC

6 5

PS-1

MDP18-24A-1C

Power Sup. 24VDC

BK

RA-x

34.110.0184.0

120V Relay DPDT

WH

RA-x

34.110.0184.0

120V Relay DPDT

GR

UNLESS SPECIFIED OTHERWISE, ALL FACTORY AC WIRING 16 AWG. ALL FACTORY DC WIRING 18 AWG.

N1

H1

D C

G N D

D C

H1

PCU

ST

KS

KTS

GAS

AR1

N1

120VJ9

OV1

SF1

EF1

B1

IO1

120VJ7

AR1

H1

2x

N1

2x

B1

EF1

SF1

BK

IO1

BK

BK

BK

JUMPER

W1

BK 14AWG

BK

RD-1

BL PR

DC+ RO1

RD-x

34.110.0188.0

24VDC Light Relay

BK

WH

SF1 7 8

RA-2

8 7

RD-1

24V

1 2 3 4 5 6 7

8 9 10 11 121314

J6

N1

ON/OFF

WITH

SUP

N1

R O

NH

FAN

PANEL COOLING

DRY CONTACTS (SHOWN DE-ENERGIZED)

HOOD LIGHTS

J3

ECPM03/DAISY CHAIN

AR1 H1

JUMPER FIRE SYSTEM

BK

BK

BK

GAS

KS

ST

NOTE: Configure ECPM03 for CORE

SM-1 SM-2

ECPM03

J10

I L A

I L B

JUMPER

MAKE UP AIR INTERLOCK.

JUMPER

JUMPER

NOTE: All items on ECPM03 J3 line to be daisy chained from one component to the next, with EOL120A at end of line. Place PN: EOL120A in empty RJ45 port.

J3

ECPM03 or Previous EOL

J5

MASTER CORE

C

RA-2-1

NO

SFC1

SFO1

14 AWG

YW

C

RA-2-2

NO

SFC2

SFO2

14 AWG

YW

SC-24 x 18 x 8.625 BOX ADDITIONAL / SC-12 x 18 x 8.625 BOX ADDITIONAL

CONTROL INPUT 120V

H1=LINE, N1=NEUTRAL,

15A BREAKER. DO NOT

CONNECT TO SHUNT TRIP

BREAKER. SEE

INSTALLATION SCHEMATIC

FOR ADDITIONAL REQ.

LR-X

varies

Line/Load Reactor

LEGEND

FIELD WIRING

FACTORY WIRING

BK- BLACK

BL- BLUE

BR- BROWN

OR- ORANGE

WH- WHITE

OR/BL- OR/BL STRIPE

BL/RD- BL/RD STRIPE

RD/GN- RD/GN STRIPE

WH/BL- WH/BL STRIPE

YW- YELLOW

GY- GREY

PR- PURPLE

RD- RED

GR- GREEN

W H B L

B L

H

N

D C

D C

LN

PS-01

AC

24V

G N D

DC

KSKS

BK

KS

BK

BK

GAS

ST

BK

EF1

P R

WH

G R Y W

W H B L

B L

J4 J5

NH

FAN

SECONDARY PANEL COOLING IF NECESSARY

EF1

WH

BK

J1

ECPM03

SCADA

WIRED

BK

RD

DEST

DEST

ILB

ILC

ILA

DEST

DEST

TO ETH

CAT-5

SCADA

SCADA Module

SHD

ANT

Wired to

Master CORE

(if applicable)

Use shielded wire

BK

RD

SD

JUMPER

ECPM03

J10

I L A

I L B

TERMINAL GAS USED FOR

120V POWERED GAS

VALVES ONLY

DWG NO

JOB NO

DATE

DRAWN BY

JOB NAME

DESCRIPTION OF OPERATION

TYPE

DRAWING TITLE

6733486

ARMY CORP DREDGE

FACTORY

SC-311110MA

12/2/2024

ECP #1-7

3 Phase w/ control for

1 Exhaust Fan, 1 Supply

Fan, Exhaust on in Fire, Lights out in Fire, Relay

On/Off with Supply Fan, Fan(s) On/Off

Thermostatically

Controlled. Room temperature sensor shipped loose for field installation. INVERTER

DUTY 3 PHASE MOTOR

REQUIRED FOR USE WITH

VFD.

BK

BK

BK

BK

BK

BK

BK

BK

BK

U/T1

V/T2

W/T3

L1

L2

L3/N

GR

GND

VFD:

A2

B2

C2

A1

B1

C1

GR

BK

BK

BK

HP:

MTR:

FLA:

P107:

P108:

P410:

P150:

P100:

P194:

P101:

P131:

P167:

P103:

P102:

L1

L2

L3

14 AWG

3 PH

15 A

460 V

SM-1

ESV222N04TXB571

W1

V1

U1

KDRMA8L1

LR-01

4.6

3.000

EF-13

N/A

N/A

60.0

80.0

0.0

GND

BK

BK

BK

BK

BK

BK

BK

BK

BK

U/T1

V/T2

W/T3

L1

L2

L3/N

GR

GND

VFD:

A2

B2

C2

A1

B1

C1

GR

BK

BK

BK

HP:

MTR:

FLA:

P107:

P108:

P410:

P150:

P100:

P194:

P101:

P131:

P167:

P103:

P102:

L4

L5

L6

14 AWG

3 PH

15 A

460 V

SM-2

ESV402N04TXB571

W2

V2

U2

KDRAA3L2

LR-01

7.0

5.000

T/A S3

N/A

N/A

60.0

80.0

0.0

GND

SHEET NO.

SCALE:

DWG.#:

DRAWN

DATE:

BY:

REVISIONS

DESCRIPTION

w w w .c ap tiv ea ire

C C O R D A N C E

N o

B U I L T

N F P A

W I T H

I N

S

L

I D

T E

6733486

MASTER DRAWING

kcurtis

12/2/2024

A R M Y

C O R P

D R E D G E

3/4" = 1'-0"

P O R T L A N D

O R

O re go n

O ff ic e

N E

4t h Av e, S ui te

, V an co uv er

, W A, P

H O

N E:

(3

) 8

F

AX

: 9

EM

AI

L:

re g9

0@ ca pt iv ea ire

A B C D E F G H I

FACTORY WIRING

SCHEMATIC

CORE FIRE

PROTECTION

COMPONENT LIST

LABEL DESCRIPTION

120 VAC

RELAY

NO

COM

COIL

NC

6 5

RA-x

24 VDC

RELAY

RD-x

NO

COM

COIL

NC

6 5

24 VOLT BATTERY PACK

5 AMP FUSE

RD

BK 16AWG

OR

SHIELDED TWISTED PAIR

PCB-2

J3-2

RD

WH

J4-1

J3-11

J4-3

J4-2

J4-8

J4-9

J4-12

J3-14

J4-5

J3-13

J3-4

J4-6

J3-10

J2-1

J2-2

J2-3

J2-4

J7-2

J7-3

J7-1

J3-1 J3-3

RD

RD BR

RD

ALL 18AWG

RD BK

ORRD

PKRD

BRRD

RD OR/BL

BK 18AWG

BK

BK

J3-5

J1-1

J1-2

PK

RD

BK

BK

RD

FIRE STAT SUPERVISED LOOP

May be mixed factory and field wiring. See Installation Schematic.

Multiple fire sensors possible.

RD

BK

BK

RD

Shield

BK

RD

RS-485 CORE INTERLOCK

NETWORK. Connection to other CORE Panels or

Communication Module. See

Installation Schematic for

Connection.

N1D

3x

H1D

3x

DISCONNECT J1

16AWG

WH

N1

H1

PN: 1606-XLP-60EQ

Adjust power supply to 27.5

Volts with an accurate

Digital Volt Meter or with an

HMI plugged into the CORE board.

NL

PS-02 60W

GR

BK

GND

PCB-2

PCBCORE-APP

CORE PCB

PS-02

1606-XLP-60E

CORE POWER SUPPLY

WS-x varies

Water Solenoid

LT-06

WL-1090D1-28V

24V Red Ind. Light

LL-01

AQ5510

Surf. Level Sensor

AA-01

SCE120LA3FP1B

Audible Alarm

PB-XX

ZB4BA2/ZB4BZ1015

Prime/Reset Switch

SW-04

BZ-2RQ1-A2

Tamper Switch

SP-1

50000-805

Surfactant Pump

H1 N1

LGV

WS3

NOC

RD-16

PB-01

Prime / Reset

WS-3

Hot Water Wash Solenoid

A2A1

RD-20

Trouble Relay

A2A1

RD-17

Fire Relay

DRY CONTACTS (SHOWN DE-ENGERGIZED)

AA-01

Audible Alarm

SW-04

Door Tamper Switch

C NO

PUT END OF LINE PLUG IN EMPTY RJ45

J3

ECPM03

FS-01

BK WH

Fire Stat

FS-02

BK WH

Fire Stat

HIGH TEMP WIRE (842 F),

PN: SLPCON-xFT required for all Supervised Loop wiring in contact with a hood. All other wiring shall be PN: 6320UL, Belden or similar. Factory mounted hood sensors will be terminated at junction box on top of hood.

GV-1

24V DC Gas Valve

GV-1

varies

24v DC Gas Valve

RD RD

INTERLOCK FOR AUTOMAN ACTIVATION.

Used for activating 120V automan or adjacent Master CORE panels during active Fire Condition.

RD-18-1

YW

J3-16

J3-8

LT-6

R

FIRE INDICATOR

DIP Switch

ATTENTION: LOW-VOLTAGE DC OR SIGNALING WIRE SHOULD

BE ROUTED IN SEPARATE CONDUIT FROM ALL AC SOURCES.

RD/GNRD

A2A1

RD-19

Equipment Relay

UNLESS VFD, PCU, OR OTHER COMPONENT IN SERIES.

COOKING EQUIPMENT DISABLE RELAY.

For UDS Kill Switch, wire EKC and

EKS terminals to like terminals in

UDS panel.

RD-19-1

EKC

EST

EKS

YW

INTERLOCK FOR AUTOMAN ACTIVATION.

Used for activating 120V automan or adjacent Master CORE panels during active Fire Condition.

RD-18-1

YW

RD OR/BL

A2A1

RD-18

Auxiliary Interlock Relay

CAT-5 WIRING (MASTER ONLY)

FS-XX

12-F28021-000360

Duct Fire Sensor

LT-05

WL-1090D3-28V

24V YLW Ind. Light

PS-01

Station STI-SS2431

Remote Puill/Push

FIELD WIRED IF REMOTE PREWIRE

GY WH

LT-4

G

WASH INDICATOR

GY WH

LT-4

G

WASH INDICATOR

GY WH

LT-4

G

WASH INDICATOR

FOR SHIPMENT

J10-1

J10-2

J10-3

J10-4

RD

BK

BK

RD

MANUAL ACTUATION LOOP / REMOTE FIRE

SYSTEM LOOP.

Multiple manual actuation possible.

A Plug jumper with wires from pin1 to pin4 and from pin2 to pin3 should be mounted on J10 if there is no manual actuation device and no microswitch.

MAD-01

C NO

Manual

Actuation

Device

MS-01

C NO

Micro SW

1 2 3 4 5 6 7 8

S W

ON

RD-XX

PLC-RPT-24DC/21

24VDC Phoenix Relay

AUX-01

AU1 AU2

Auxiliary Interlock (AUX-01):

Wire AU1 / AU2 of adjacent Master CORE panel(s) in each manual activation loop for simultaneous activation.

AU1/AU2 will have continuity for 10 seconds if adjacent panel goes into fire condition, activating this CORE Panel but allowing for a reset after 10 seconds.

NOTE: AU1/AU2 terminals of CORE Panel should not be wired into its own manual activation loop.

Adjacent

CORE

Panel

Master CORE set DIP SW 8 to CLOSED position. Slave

CORE with address 1 set

DIP SW 8 to

CLOSED

position. All other CORES set DIP SW 8

OPEN.

18AWG

LEGEND

FIELD WIRING

FACTORY WIRING

BK- BLACK

BL- BLUE

BR- BROWN

OR- ORANGE

WH- WHITE

OR/BL- OR/BL STRIPE

BL/RD- BL/RD STRIPE

RD/GN- RD/GN STRIPE

WH/BL- WH/BL STRIPE

YW- YELLOW

GY- GREY

PR- PURPLE

RD- RED

GR- GREEN

FIRE INDICATOR FAULT CONDITION FLASH CODES

2 Release Solenoid

3 Pressure Switch

4 Auxiliary Fault

5 Microcontroller Fault

6 N/A

7 Supervised Loop

8 Ground Fault

9 Surfactant Low

10 Battery Voltage Low

11 AC Power Failure

12 Door Tamper Switch

13 Test Mode

14 CORE Interlock Network

15 Fault on Hood in Interlock Network

16 Fault on PCU in Interlock Network

FIRE ALARM SYSTEM DRY CONTACTS.

Termials AL1 & AL2 make in FIRE.

To Building Fire

Alarm Panel

J9

AL1

AL2

J3-7

FIRE SYSTEM DRY CONTACTS.

Dry contacts will make C2 to AR2 when system is armed.

RD-17-1

C2

AR2

14 AWG

YW

TROUBLE RELAY. Contact terminals

TBC & TBL make if there is trouble.

Contact terminals TBC & TOK make if the system is ok.

RD-20-1

TBC

TBL

TOK

YW

BK

J4-4

YW

LT-05

A

SURFACTANT LOW

RD

J3-6

RD

SP

SP-1

Surfactant Pump

RD WH

J4-7

BK BK

LL-1

Liquid Level Sensor

J3-14

RD BL/RD

A2A1

RD-16

Hot Water Relay

TROUBLE RELAY. Contact terminals

TBC & TBL make if there is trouble.

Contact terminals TBC & TOK make if the system is ok.

RD-20-1

TBC

TBL

TOK

YW

FIRE SYSTEM DRY CONTACTS.

Dry contacts will make C2 to AR2 when system is armed.

RD-17-1

C2

AR2

14 AWG

YW

AL2

AL1

J9

To Building Fire

Alarm Panel

FIRE ALARM SYSTEM DRY CONTACTS.

Termials AL1 & AL2 make in FIRE.

FIRE INDICATOR FAULT CONDITION FLASH CODES

2 Release Solenoid

3 Pressure Switch

4 Auxiliary Fault

5 Microcontroller Fault

6 N/A

7 Supervised Loop

8 Ground Fault

9 Surfactant Low

10 Battery Voltage Low

11 AC Power Failure

12 Door Tamper Switch

13 Test Mode

14 CORE Interlock Network

15 Fault on Hood in…