Amendment 8.pdf
PDF 7 MB Posted
- Attached to
- Air Traffic Control Tower Kelly Field
- Solicitation number
- W9126G22R0002
About this file
This federal solicitation is for the construction of an Air Traffic Control Tower at Kelly Field in San Antonio, Texas. The project magnitude is between $10 million and $25 million. Offerors must enter a National Institute of Standards and Technology score in the Supplier Performance Risk System before an award can be made. The soliciting agency is the Department of the Army Corps of Engineers Engineering District Fort Worth. The point of contact is Alfredo Avila of the Corps of Engineers. The response due date is not provided in this document.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04 EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The Solicitation for Air Traffic Control Tower Kelly Field; Lackland Air Force Base, Texas is amended as follows.
See SF30 Continuation Sheet(s)
NOTE: Proposal Receipt date is 24 February 2022 at 2:00p.m., CT, as previously announced.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA 15C. DATE SIGNED 15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer) (Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
W9126G22R0002
X 9B. DATED (SEE ITEM 11)
17-Dec-2021
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour specified for receipt of Offer is extended, x is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
18 -Feb- 2022
CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A19
P.O. BOX 17300
FORT WORTH TX 76102-0300
W9126G 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODE CODE
EMAIL: TEL:
W9126G22R0002
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
CHANGES TO SOLICITATION W9126G22R0002
CHANGES TO THE SPECIFICATIONS
1. New Sections - Add the following accompanying new section, each bearing the notation W9126G22R0002-0008.
07 14 00 FLUID-APPLIED WATERPROOFING
2. Replacement Sections - Replace the following section with the accompanying new section of the same number and title, bearing the notation W9126G22R0002-0008.
05 12 00 STRUCTURAL STEEL
07 81 00 SPRAY-APPLIED FIREPROOFING
08 39 54 BLAST RESISTANT DOORS
10 28 13 TOILET ACCESSORIES
14 21 13 ELECTRIC TRACTION FREIGHT ELEVATORS
CHANGES TO THE DRAWINGS
3. Replacement Drawings.- Replace the drawings listed below with the attached new drawings(s) of the same number, bearing the notation W9126G22R0002-0008.
GC100 EROSION CONTROL PLAN
GI010 CODE COMPLIANCE PLAN
CD101 DEMOLITION PLAN
CS101 SITE PLAN
CG101 GRADING PLAN
CG110 DRAINAGE PLAN
CU100 UTILITY PLAN
L-100 LANDSCAPING PLAN
GC101 EROSION CONTROL PLAN
CD102 DEMOLITION PLAN
CS102 SITE PLAN
CG 102 GRADING PLAN
L-101 LANDSCAPING PLAN
End of Summary of Changes
Air Traffic Control Tower AM#8 TO W9126G22R0002 JBSA-Lackland, Kelly Field Annex, TX 16 February 2022
SECTION 07 14 00
FLUID-APPLIED WATERPROOFING
02/12, CHG 2: 02/18
AMENDMENT NO. 0008 - ADDED SECTION
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C33/C33M (2018) Standard Specification for Concrete Aggregates
ASTM C836/C836M (2015) High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane for Use With Separate Wearing Course
ASTM C1522 (2013) Standard Test Method for Extensibility After Heat Aging of Cold Liquid-Applied Elastomeric Waterproofing Membranes
ASTM D412 (2016) Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers - Tension
ASTM D2240 (2015; E 2017) Standard Test Method for Rubber Property - Durometer Hardness
ASTM D2369 (2010; R 2015; E 2015) Volatile Content of Coatings
ASTM E96/E96M (2016) Standard Test Methods for Water Vapor Transmission of Materials
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Fluid-Applied Membrane
Membrane Primer
Solvent
Drainage Panel
Jacobs WFXO2003 SECTION 07 14 00 Page 1
W9126G22R0002-0008
SD-11 Closeout Submittals
Warranty
1.3 PREWATERPROOFING CONFERENCE
Prior to starting application of waterproofing system, arrange and attend a prewaterproofing conference to ensure a clear understanding of drawings and specifications. Give the Contracting Officer 7 days advance written notice of the time and place of meeting. Ensure that the mechanical and electrical subcontractor, flashing and sheetmetal subcontractor, and other trades that may perform other types of work on or over the membrane after installation, attend this conference.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver waterproofing materials in manufacturer's original, unopened containers, with labels intact and legible. Containers of materials covered by a referenced specification number shall bear the specification number, type, and class of the contents. Deliver materials in sufficient quantity to continue work without interruption. Store and protect materials in accordance with manufacturer's instructions, and use within their indicated shelf life. When hazardous materials are involved, adhere to special precautions of the manufacturer, unless precautions conflict with local, state, and federal regulations. Promptly remove from the site materials or incomplete work adversely affected by exposure to moisture or freezing. Store materials on pallets and cover from top to bottom with canvas tarpaulins.
1.5 ENVIRONMENTAL CONDITIONS
Apply materials when ambient temperature is 40 degrees F or above for a period of 24 hours prior to the application and when there is no ice, frost, surface moisture, or visible dampness on the substrate surface.
Apply materials when air temperature is expected to remain above 40 degrees F during the cure period recommended by the manufacturer.
Moisture test for substrate is specified under paragraph entitled "Moisture Test." Work may be performed within heated enclosures, provided the surface temperature of the substrate is maintained at a minimum of 40 degrees F for 24 hours prior to the application of the waterproofing, and remains above that temperature during the cure period recommended by the manufacturer.
1.6 WARRANTY
Provide manufacturer's standard warranty from the date of supply covering material.
PART 2 PRODUCTS
2.1 FLUID-APPLIED MEMBRANE
Water activated, cold-applied, solvent-free, non-shrink, liquid waterproofing membrane in accordance with ASTM C836/C836M.
Jacobs WFXO2003 SECTION 07 14 00 Page 2
2.1.1 Physical Properties
PROPERTY TYPICAL TEST VALUE TEST METHOD
Solids Content By Weight 98 percent ASTM C1522
Tensile Strength 100 psi ASTM D412
Elongation at Break 425 percent ASTM D412
Permeability 0.1 perm in. ASTM E96/E96M BW
Shore 00 Hardness 57 ASTM D2240
Service Temperature 40 to 200 degrees F
Minimum Application Temperature Above 30 degrees F (-1) and rising
VOC Content 36 g/L ASTM D2369
2.2 MEMBRANE PRIMER
As recommended by the fluid-applied membrane manufacturer unless specifically prohibited by the manufacturer of the fluid-applied membrane.
2.3 SEALANT
As specified in Section 07 92 00 JOINT SEALANTS.
2.4 SEALANT PRIMER
As specified in Section 07 92 00 JOINT SEALANTS.
2.5 BACKING MATERIAL
Premolded, closed-cell, polyethylene, or polyurethane foam rod having a diameter 25 percent larger than joint width before being compressed into joint. Provide bond breaker of polyethylene film or other suitable material between backing material and sealant.
2.6 JOINT FILLER
As specified in Section 03 30 00 CAST-IN-PLACE CONCRETE,.
2.7 ELASTOMERIC SHEET ADHESIVE
As recommended by the elastomeric sheet manufacturer.
2.8 DRAINAGE PANEL
Geocomposite Drainage Board shall consist of a high strength dimple raised moulded polystyrene core with a high strength, monofilament geotextile fabric bonded to the dimples of the core.
2.9 DRAINAGE COURSE AGGREGATE
ASTM C33/C33M, size No. 8 or as recommened by the membrane manufacturer's
Jacobs WFXO2003 SECTION 07 14 00 Page 3 printed instructions.
PART 3 EXECUTION
3.1 PREPARATION
Coordinate work with that of other trades to ensure that components to be incorporated into the waterproofing system are available when needed.
Inspect and approve surfaces immediately before application of waterproofing materials. Remove laitance, loose aggregate, sharp projections, grease, oil, dirt, curing compounds, and other contaminants which could adversely affect the complete bonding of the fluid-applied membrane to the concrete surface.
3.1.1 Flashings
Make penetrations through sleeves in concrete slab watertight before application of waterproofing. After flashing is completed, cover elastomeric sheet with fluid-applied waterproofing during waterproofing application.
3.1.1.1 Penetrations and Projections
Flash penetrations and projections through structural slab with an elastomeric sheet adhered to the concrete slab and the penetration. Leave elastomeric sheet unadhered for one inch over joint between penetration and concrete slab. Adhere elastomeric sheet a minimum of 4 inches onto horizontal deck.
3.1.1.2 Walls and Vertical Surfaces
Flash wall intersections which are not of monolithic pour or constructed with reinforced concrete joints with an elastomeric sheet adhered to both vertical wall surfaces and concrete slab. Flash intersections which are monolithically poured or constructed with reinforced concrete joints with either an elastomeric sheet or a vertical grade of fluid-applied waterproofing adhered to vertical wall surfaces and concrete slab. Leave sheet unadhered for a distance of one inch from the corner on both vertical and horizontal surfaces.
3.1.2 Cracks and Joints
Prepare visible cracks and joints in substrate to receive fluid-applied waterproofing membrane as required by membrane the manufacturer's printed instructions.
3.1.3 Priming
Prime surfaces to receive fluid-applied waterproofing membrane. Apply primer as required by membrane manufacturer's printed instructions.
3.2 SPECIAL PRECAUTIONS
Protect waterproofing materials during transport and application. Do not dilute primers and other materials, unless specifically recommended by materials manufacturer. Keep containers closed except when removing contents. Do not mix remains of unlike materials. Thoroughly remove residual materials before using application equipment for mixing and transporting materials. Do not permit equipment on the project site that
Jacobs WFXO2003 SECTION 07 14 00 Page 4 has residue of materials used on previous projects. Use cleaners only for cleaning, not for thinning primers or membrane materials.
3.3 APPLICATION
Over primed surfaces, provide a uniform, wet, monolithic coating of fluid-applied membrane, 60 mils thick, plus or minus 5 mils by following manufacturer's printed instructions. Apply material by trowel, squeegee, roller, brush, spray apparatus, or other method recommended by membrane manufacturer. Check wet film thickness as specified in paragraph entitled "Film Thickness" and adjust application rate as necessary to provide a uniform coating of the thickness specified. Where possible, mark off surface to be coated in equal units to facilitate proper coverage. At expansion joints, control joints, prepared cracks, flashing, and terminations, carry membrane over preformed elastomeric sheet in a uniform 60 mil thick, plus or minus 5 mils , wet thickness to provide a monolithic coating. If membrane cures before next application, wipe previously applied membrane with a solvent to remove dirt and dust that could inhibit adhesion of overlapping membrane coat. Use solvent recommended by the membrane manufacturer, as approved.
3.3.1 Drainage Panel
Install drainage board as recommended by manufacturer's printed instructions. Protect fluid-applied membrane by placing drainage board over membrane at a time recommended by the membrane manufacturer. Protect membrane application when drainage board is not placed immediately. Butt drainage boards together and do not overlap.
3.3.2 Drainage Course
Place drainage course as indicated on the drawings.
3.4 FIELD QUALITY CONTROL
3.4.1 Film Thickness
Measure wet film thickness every 100 square feet during application by placing flat metal plates on the substrate or using a mil-thickness gage especially manufactured for the purpose.
3.5 CLEANING AND PROTECTION
Remove any masking materials after installation. Clean any stains on materials which would be exposed in the completed work.
Protect completed membrane waterproofing from subsequent construction activities as recommended by manufacturer.
-- End of Section --
Jacobs WFXO2003 SECTION 07 14 00 Page 5
THIS PAGE INTENTIONALLY LEFT BLANK
Jacobs WFXO2003 SECTION 07 14 00 Page 6
SECTION 05 12 00
STRUCTURAL STEEL
05/14
AMENDMENT NO. 0008
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO HB-17 (2002; Errata 2003; Errata 2005, 17th Edition) Standard Specifications for Highway Bridges
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 303 (2016) Code of Standard Practice for Steel Buildings and Bridges
AISC 325 (2017) Steel Construction Manual
AISC 326 (2009) Detailing for Steel Construction
AISC 341 (2016) Seismic Provisions for Structural Steel Buildings
AISC 360 (2016) Specification for Structural Steel Buildings
AISC DESIGN GUIDE 10 (1997) Erection Bracing of Low-Rise Structural Steel Buildings
AMERICAN WELDING SOCIETY (AWS)
AWS A2.4 (2012) Standard Symbols for Welding, Brazing and Nondestructive Examination
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASME INTERNATIONAL (ASME)
ASME B46.1 (2009) Surface Texture, Surface Roughness, Waviness and Lay
ASTM INTERNATIONAL (ASTM)
ASTM A108 (2013) Standard Specification for Steel Bar, Carbon and Alloy, Cold-Finished
ASTM A123/A123M (2017) Standard Specification for Zinc
Jacobs WFXO2003 SECTION 05 12 00 Page 1
(Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A29/A29M (2016) Standard Specification for General Requirements for Steel Bars, Carbon and Alloy, Hot-Wrought
ASTM A307 (2014; E 2017) Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM A325 (2014) Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A490 (2014a) Standard Specification for Structural Bolts, Alloy Steel, Heat Treated, 150 ksi Minimum Tensile Strength
ASTM A500/A500M (2013) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A563 (2015) Standard Specification for Carbon and Alloy Steel Nuts
ASTM A6/A6M (2017) Standard Specification for General Requirements for Rolled Structural Steel Bars, Plates, Shapes, and Sheet Piling
ASTM A668/A668M (2017) Standard Specification for Steel Forgings, Carbon and Alloy, for General Industrial Use
ASTM A992/A992M (2011) Standard Specification for Structural Steel Shapes
ASTM C1107/C1107M (2017) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM C827/C827M (2016) Standard Test Method for Change in Height at Early Ages of Cylindrical Specimens of Cementitious Mixtures
ASTM F1554 (2015; E 2016; E 2017) Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength
ASTM F2329 (2013) Zinc Coating, Hot-Dip, Requirements for Application to Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special
Jacobs WFXO2003 SECTION 05 12 00 Page 2
Threaded Fasteners
ASTM F3125/F3125M (2015a) Standard Specification for High Strength Structural Bolts, Steel and Alloy Steel, Heat Treated, 120 ksi (830 MPa) and 150 ksi (1040 MPa) Minimum Tensile Strength, Inch and Metric Dimensions
ASTM F436 (2011) Hardened Steel Washers
ASTM F844 (2007a; R 2013) Washers, Steel, Plain (Flat), Unhardened for General Use
ASTM F959/F959M (2017) Standard Specification for Compressible-Washer-Type Direct Tension Indicators for Use with Structural Fasteners, Inch and Metric Series
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-301-01 (2013; with Change 1) Structural Engineering
UFC 3-310-04 (2016) Seismic Design for Buildings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Erection Drawings ; G
SD-02 Shop Drawings
Fabrication Drawings Including Description of Connections; G
SD-03 Product Data
Shop Primer
Welding Electrodes and Rods
Direct Tension Indicator Washers
Non-Shrink Grout
Tension Control Bolts
SD-06 Test Reports
Class B Coating
Bolts, Nuts, and Washers
Jacobs WFXO2003 SECTION 05 12 00 Page 3
Weld Inspection Reports
Direct Tension Indicator Washer Inspection Reports
SD-07 Certificates
Steel
Bolts, Nuts, and Washers
Galvanizing
Pins and Rollers
AISC Fabrication Plant Quality Certification
AISC Erector Quality Certification
Welding Procedures and Qualifications
Welding Electrodes and Rods
1.3 AISC QUALITY CERTIFICATION
Work must be fabricated in an AISC Certified Fabrication Plant, Category Std. Submit AISC fabrication plant quality certification .
Work must be erected by an AISC Certified Erector, Category CSE. Submit AISC erector quality certification .
1.4 QUALITY ASSURANCE
1.4.1 Preconstruction Submittals
1.4.1.1 Erection Drawings
Submit for record purposes. Indicate the sequence of erection, temporary shoring and bracing. The erection drawings must conform to AISC 303 .
Erection drawings must be reviewed, stamped and sealed by a registered professional engineer.
1.4.2 Fabrication Drawing Requirements
Submit fabrication drawings for approval prior to fabrication. Prepare in accordance with AISC 326 and AISC 325 . Fabrication drawings must not be reproductions of contract drawings. Sign and seal fabrication drawings by a registered professional engineer. Include complete information for the fabrication and erection of the structure's components, including the location, type, and size of bolts, welds, member sizes and lengths, connection details, blocks, copes, and cuts. Use AWS A2.4 standard welding symbols. Shoring and temporary bracing must be designed and sealed by a registered professional engineer and submitted for record purposes, with calculations, as part of the drawings. Any deviations from the details shown on the contract drawings must be clearly highlighted on the fabrication drawings. Explain the reasons for any deviations from the contract drawings.
Jacobs WFXO2003 SECTION 05 12 00 Page 4
1.4.3 Certifications
1.4.3.1 Welding Procedures and Qualifications
Prior to welding, submit certification for each welder stating the type of welding and positions qualified for, the code and procedure qualified under, date qualified, and the firm and individual certifying the qualification tests. If the qualification date of the welding operator is more than one-year old, the welding operator's qualification certificate must be accompanied by a current certificate by the welder attesting to the fact that he has been engaged in welding since the date of certification, with no break in welding service greater than 6 months.
Conform to all requirements specified in AWS D1.1/D1.1M .
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide the structural steel system, including shop primer, complete and ready for use. Structural steel systems including design, materials, installation, workmanship, fabrication, assembly, erection, inspection, quality control, and testing must be provided in accordance with AISC 360 , AISC 341 , UFC 3-301-01 and UFC 3-310-04 except as modified in this contract.
2.2 STEEL
2.2.1 Structural Steel
Wide flange and WT shapes, ASTM A992/A992M . Angles, Channels and Plates, ASTM A36/A36M.
2.2.2 Structural Steel Tubing
ASTM A500/A500M , Grade C.
2.2.3 Steel Pipe
ASTM A53/A53M, Type E or S, Grade B.
2.3 BOLTS, NUTS, AND WASHERS
Submit the certified manufacturer's mill reports which clearly show the applicable ASTM mechanical and chemical requirements together with the actual test results for the supplied fasteners.
2.3.1 Common Grade Bolts
2.3.1.1 Bolts
ASTM A307, Grade A. The bolt heads and the nuts of the supplied fasteners must be marked with the manufacturer's identification mark, the strength grade and type specified by ASTM specifications.
2.3.1.2 Nuts
ASTM A563, Grade A, heavy hex style.
Jacobs WFXO2003 SECTION 05 12 00 Page 5
2.3.1.3 Self-Locking Nuts
Provide nuts with a locking pin set in the nut. The locking pin must slide along the bolt threads, and by reversing the direction of the locking pin, the nut must be removed without damaging the nut or bolt.
Provide stainless steel locking pins.
2.3.1.4 Washers
ASTM F844.
2.3.2 High-Strength Bolts
2.3.2.1 Bolts
ASTM F3125/F3125M Grade A325, or A490
2.3.2.2 Nuts
ASTM A563, Grade and Style as specified in the applicable ASTM bolt standard.
2.3.2.3 Direct Tension Indicator Washers
ASTM F959/F959M .
2.3.2.4 Washers
ASTM F436, plain carbon steel.
2.3.3 Tension Control Bolts
ASTM F3125 (heavy hex) or Grade F1852 or F2280 (twist-off/TC), Type 1, consisting of steel structural bolts with splined ends, heavy-hex carbon steel nuts, and hardened carbon steel washers. Assembly finish must be plain.
2.3.4 Foundation Anchorage
2.3.4.1 Anchor Rods
ASTM F1554 Gr 36 55 or 105 as indicated on Drawings, Class 1A 2A.
2.3.4.2 Anchor Nuts
ASTM A563, Grade A, hex style.
2.3.4.3 Anchor Washers
ASTM F844.
2.3.4.4 Anchor Plate Washers
ASTM A36/A36M
Jacobs WFXO2003 SECTION 05 12 00 Page 6
2.4 STRUCTURAL STEEL ACCESSORIES
2.4.1 Welding Electrodes and Rods
AWS D1.1/D1.1M .
2.4.2 Non-Shrink Grout
ASTM C1107/C1107M , with no ASTM C827/C827M shrinkage. Grout must be nonmetallic.
2.4.3 Welded Shear Stud Connectors
ASTM A29/A29M, Type B. AWS D1.1/D1.1M .
2.4.4 Pins and Rollers
ASTM A668/A668M , Class C, D, F, or G; ASTM A108, Grades 1016 to 1030.
Provide as specified in AASHTO HB-17, Division II, Sections 10.26 and 10.27, except provide pins in lengths to extend a minimum of 0.25 inch beyond the outside faces of the connected parts.
2.5 GALVANIZING
ASTM F2329 for threaded parts or ASTM A123/A123M for structural steel members, as applicable, unless specified otherwise galvanize after fabrication where practicable.
2.6 FABRICATION
Fabrication must be in accordance with the applicable provisions of AISC 325 . Fabrication and assembly must be done in the shop to the greatest extent possible. Punch, subpunch and ream, or drill bolt holes perpendicular to the surface of the member.
Compression joints depending on contact bearing must have a surface roughness not in excess of 500 micro inch as determined by ASME B46.1 , and ends must be square within the tolerances for milled ends specified in
ASTM A6/A6M.
Shop splices of members between field splices will be permitted only where indicated on the Contract Drawings. Splices not indicated require the approval of the Contracting Officer.
2.6.1 Markings
Prior to erection, members must be identified by a painted erection mark.
Connecting parts assembled in the shop for reaming holes in field connections must be match marked with scratch and notch marks. Do not locate erection markings on areas to be welded. Do not locate match markings in areas that will decrease member strength or cause stress concentrations.
2.6.2 Shop Primer
<AM#8>SSPC Paint 20 or SSPC Paint 29 , (zinc rich primer). Provide fabricator's lead- and chromate-free, nonasphaltic, rust-inhibiting primer.
Shop prime structural steel, except as modified herein , in accordance with SSPC PA 1 . </AM#8> Do not prime steel surfaces embedded in concrete, Jacobs WFXO2003 SECTION 05 12 00 Page 7 galvanized surfaces, surfaces to receive sprayed-on fireproofing, or surfaces within 0.5 inch of the toe of the welds prior to welding (except surfaces on which metal decking is to be welded). If flash rusting occurs, re-clean the surface prior to application of primer. Apply primer to a minimum dry film thickness of 2.0 mil .
Slip critical surfaces must be primed with a Class B coating in accordance with AISC 325 . Submit test report for Class B coating.
Prior to assembly, prime surfaces which will be concealed or inaccessible after assembly. Do not apply primer in foggy or rainy weather; when the ambient temperature is below 45 degrees F or over 95 degrees F ; or when the primer may be exposed to temperatures below 40 degrees F within 48 hours after application, unless approved otherwise by the Contracting Officer. Repair damaged primed surfaces with an additional coat of primer.
2.6.2.1 Cleaning
<AM#8> SSPC SP 3. </AM#8> SSPC SP 6/NACE No.3 , except steel exposed in spaces above ceilings, attic spaces, furred spaces, and chases that will be hidden to view in finished construction may be cleaned to SSPC SP 3 when recommended by the shop primer manufacturer. Maintain steel surfaces free from rust, dirt, oil, grease, and other contaminants through final assembly.
2.6.3 Fireproofing Coated Surfaces
Surfaces to receive sprayed-on fireproofing coatings must be cleaned and prepared in accordance with the manufacturer's recommendations, and as specified in Section 07 81 00 SPRAY-APPLIED FIREPROOFING.
2.7 DRAINAGE HOLES
Adequate drainage holes must be drilled to eliminate water traps. Hole diameter must be 1/2 inch and location must be indicated on the detail drawings. Hole size and location must not affect the structural integrity.
PART 3 EXECUTION
3.1 ERECTION
a. Erection of structural steel, except as indicated in item b. below, must be in accordance with the applicable provisions of AISC 325 .
b. For low-rise structural steel buildings ( 60 feet tall or less and a maximum of 2 stories), the structure must be erected in accordance with AISC DESIGN GUIDE 10 .
After final positioning of steel members, provide full bearing under base plates and bearing plates using nonshrink grout. Place nonshrink grout in accordance with the manufacturer's instructions.
3.1.1 STORAGE
Material must be stored out of contact with the ground in such manner and location as will minimize deterioration.
Jacobs WFXO2003 SECTION 05 12 00 Page 8
3.2 CONNECTIONS
Except as modified in this section, connections not detailed must be designed in accordance with AISC 360 . Build connections into existing work. Do not tighten anchor bolts set in concrete with impact torque wrenches. Holes must not be cut or enlarged by burning. Bolts, nuts, and washers must be clean of dirt and rust, and lubricated immediately prior to installation.
3.2.1 Common Grade Bolts
ASTM A307 bolts must be tightened to a "snug tight" fit. "Snug tight" is the tightness that exists when plies in a joint are in firm contact. If firm contact of joint plies cannot be obtained with a few impacts of an impact wrench, or the full effort of a man using a spud wrench, contact the Contracting Officer for further instructions.
3.2.2 High-Strength Bolts
Provide direct tension indicator washers in all ASTM A325 and ASTM A490 bolted connections where slip-critical connections are indicated. Bolts must be installed in connection holes and initially brought to a snug tight fit. After the initial tightening procedure, bolts must then be fully tensioned, progressing from the most rigid part of a connection to the free edges. In connections not indicated to be slip critical tighten bolts to a snug tight fit.
3.2.2.1 Installation of Direct Tension Indicator Washers (DTIW)
Where possible, the DTIW must be installed under the bolt head and the nut must be tightened. If the DTIW is installed adjacent to the turned element, provide a flat washer between the DTIW and nut when the nut is turned for tightening, and between the DTIW and bolt head when the bolt head is turned for tightening. In addition to the LIW, provide flat washers under both the bolt head and nut when ASTM A490 bolts are used.
3.2.3 Tension Control Bolts
Bolts must be installed in connection holes and initially brought to a snug tight fit. After the initial tightening procedure, bolts must then be fully tensioned, progressing from the most rigid part of a connection to the free edges.
3.3 GAS CUTTING
Use of gas-cutting torch in the field for correcting fabrication errors will not be permitted on any major member in the structural framing. Use of a gas cutting torch will be permitted on minor members not under stress only after approval has been obtained from the Contracting Officer.
3.4 WELDING
Welding must be in accordance with AWS D1.1/D1.1M . Grind exposed welds smooth as indicated. Provide AWS D1.1/D1.1M qualified welders, welding operators, and tackers.
Develop and submit the Welding Procedure Specifications (WPS) for all welding, including welding done using prequalified procedures.
Prequalified procedures may be submitted for information only; however, Jacobs WFXO2003 SECTION 05 12 00 Page 9 procedures that are not prequalified must be submitted for approval.
3.4.1 Removal of Temporary Welds, Run-Off Plates, and Backing Strips
Remove backing strips from bottom flange of moment connections, backgouge the root pass to sound weld metal and reinforce with a 5/16 inch fillet weld minimum.
3.5 SHOP PRIMER REPAIR
Repair shop primer in accordance with the paint manufacturer's recommendation for surfaces damaged by handling, transporting, cutting, welding, or bolting.
3.5.1 Field Priming
Steel exposed to the weather, or located in building areas without HVAC for control of relative humidity must be field primed. After erection, the field bolt heads and nuts, field welds, and any abrasions in the shop coat must be cleaned and primed with paint of the same quality as that used for the shop coat.
3.6 FIELD QUALITY CONTROL
Perform field tests, and provide labor, equipment, and incidentals required for testing. The Contracting Officer must be notified in writing of defective welds, bolts, nuts, and washers within 7 working days of the date of the inspection.
3.6.1 Welds
3.6.1.1 Visual Inspection
AWS D1.1/D1.1M . Furnish the services of AWS-certified welding inspectors for fabrication and erection inspection and testing and verification inspections.
Inspect proper preparation, size, gaging location, and acceptability of welds; identification marking; operation and current characteristics of welding sets in use.
3.6.1.2 Nondestructive Testing
Nondestructive testing must be in accordance with AWS D1.1/D1.1M . Test locations must be selected by the Contracting Officer. If more than 20 percent of welds made by a welder contain defects identified by testing, then all welds made by that welder must be tested by ultrasonic testing, as approved by the Contracting Officer. When all welds made by an individual welder are required to be tested, magnetic particle testing must be used only in areas inaccessible to ultrasonic testing. Retest defective areas after repair. Submit weld inspection reports .
Testing frequency: Provide the following types and number of tests:
3.6.2 Direct Tension Indicator Washers
3.6.2.1 Direct Tension Indicator Washer Compression
Direct tension indicator washers must be tested in place to verify that
Jacobs WFXO2003 SECTION 05 12 00 Page 10 they have been compressed sufficiently to provide the 0.015 inch gap when the direct tension indicator washer is placed under the bolt head and the nut is tightened, and to provide the 0.005 inch gap when the direct tension indicator washer is placed under the turned element, as required by ASTM F959/F959M . Submit direct tension indicator washer inspection reports .
3.6.3 High-Strength Bolts
3.6.3.1 Inspection
Inspection procedures must be in accordance with AISC 360 . Confirm and report to the Contracting Officer that the materials meet the project specification and that they are properly stored. Confirm that the faying surfaces have been properly prepared before the connections are assembled. Observe the specified job site testing and calibration, and confirm that the procedure to be used provides the required tension.
Monitor the work to ensure the testing procedures are routinely followed on joints that are specified to be fully tensioned.
Inspect calibration of torque wrenches for high-strength bolts.
3.6.3.2 Testing
The Government has the option to perform nondestructive tests on 5 percent of the installed bolts to verify compliance with pre-load bolt tension requirements. Provide the required access for the Government to perform the tests. The nondestructive testing will be done in-place using an ultrasonic measuring device or any other device capable of determining in-place pre-load bolt tension. The test locations must be selected by the Contracting Officer. If more than 10 percent of the bolts tested contain defects identified by testing, then all bolts used from the batch from which the tested bolts were taken, must be tested at the Contractor's expense. Retest new bolts after installation at the Contractor's expense.
-- End of Section --
Jacobs WFXO2003 SECTION 05 12 00 Page 11
THIS PAGE INTENTIONALLY LEFT BLANK
Jacobs WFXO2003 SECTION 05 12 00 Page 12
SECTION 07 81 00
SPRAY-APPLIED FIREPROOFING
02/11
AMENDMENT NO. 0008
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASSOCIATION OF THE WALL AND CEILING INDUSTRY (AWCI)
AWCI TM 12-A (1997; 3rd Ed) Standard Practice for the Testing and Inspection of Field Applied Sprayed Fire-Resistive Materials; An Annotated Guide
ASTM INTERNATIONAL (ASTM)
ASTM E1042 (2002; R 2014) Acoustically Absorptive Materials Applied by Trowel or Spray
ASTM E119 (2016a) Standard Test Methods for Fire Tests of Building Construction and Materials
ASTM E605/E605M (1993; R 2015; E 2015) Standard Test Methods for Thickness and Density of Sprayed Fire-Resistive Material (SFRM) Applied to Structural Members
ASTM E736 (2000; R 2011) Cohesion/Adhesion of Sprayed Fire-Resistive Materials Applied to Structural Members
ASTM E759/E759M (1992; R 2015; E 2015) Standard Test Method for Effect of Deflection on Sprayed Fire-Resistive Material Applied to Structural Members
ASTM E760/E760M (1992; R 2015; E 2015) Standard Test Method for Effect of Impact on Bonding of Sprayed Fire-Resistive Material Applied to Structural Members
ASTM E761/E761M (1992; R 2015; E 2015) Standard Test Method for Compressive Strength of Sprayed Fire-Resistive Material Applied to Structural Members
ASTM E84 (2017) Standard Test Method for Surface Burning Characteristics of Building Materials
Jacobs WFXO2003 SECTION 07 81 00 Page 1
ASTM E859/E859M (1993; R 2015; E 2015) Standard Test Method for Air Erosion of Sprayed Fire-Resistive Materials (SFRMs) Applied to Structural Members
ASTM E937/E937M (1993; R 2015; E 2015) Standard Test Method for Corrosion of Steel by Sprayed Fire-Resistive Material (SFRM) Applied to Structural Members
ASTM G21 (2015) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
ICC EVALUATION SERVICE, INC. (ICC-ES)
ICC-ES AC23 (2004; R 2008; R 2011) Acceptance Criteria for Spray-Applied and Intumescent Mastic Coating Fire-Protection Materials
UNDERWRITERS LABORATORIES (UL)
UL 263 (2011; Reprint Jun 2015) Fire Tests of Building Construction and Materials
UL Fire Resistance (2014) Fire Resistance Directory
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
Protect all structural steel, undersides of steel floors (if required) and steel roof decks (if required) with spray-applied fireproofing to a fire resistance hour-rating as indicated below, unless otherwise indicated.
1.2.2 Fire Resistance Rating
Fire resistance ratings shall be in accordance with the fire rated assemblies listed in UL Fire Resistance . Proposed materials not listed in UL Fire Resistance shall have fire resistance ratings at least equal to the UL Fire Resistance ratings as determined by an approved independent testing laboratory, based on tests specified in UL 263 or ASTM E119.
Submit reports and test records, attesting that the fireproofing material conforms to the specified requirements. Each test report shall conform to the report requirements specified by the test method. For the underside of the decking use metal lath installed prior to the fireproofing material or Rigid Board Fireproofing Material as outlined in the UL Fire Resistance Directory Volume 1. Apply fireproofing to structural steel members, with the following hourly fire resistance rating and in accordance with the following UL design or approved equivalent. Use unrestrained fire resistance ratings, unless the architect/engineer has specified that the degree of thermal restraint of the construction meets or exceeds the degree of thermal restraint of the tested assembly. Performance tests shall be in accordance with ASTM E119.
Jacobs WFXO2003 SECTION 07 81 00 Page 2
Fire Rating Schedule
Element Hourly Rating
Columns supporting one floor 2 Hours
Columns supporting more than one floor 2 Hours
Columns supporting roof 2 Hours
Floor decks 2 Hours
Floor supports 2 Hours
Roof decks <AM#8> 1 Hour </AM#8> 2 Hours
Roof supports <AM#8> 1 Hour </AM#8> 2 Hours
1.2.3 Evaluation Reports - ICC-ES Reports
Materials shall be evaluated in accordance with ICC-ES AC23 . ICC-ES Reports shall be included as part of the Submittals below. The reports will identify the product as code compliant and having met the physical performance requirements outlined in paragraphs "Dry Density and Cohesion/Adhesion" through "Air Erosion".
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Fireproofing Material ; G
SD-04 Samples
Spray-Applied Fireproofing ; G
SD-06 Test Reports
Fire Resistance Rating ; G Field Tests ; G Evaluation Reports ; G
SD-07 Certificates
Installer Qualifications ; G Surface Preparation Report ; G Manufacturer's Inspection Report ; G
Jacobs WFXO2003 SECTION 07 81 00 Page 3
1.4 QUALITY ASSURANCE
1.4.1 Installer Qualifications
Engage an experienced installer that is certified, licensed, or otherwise qualified by the spray-on fireproofing manufacturer as having the necessary experience, staff, and training to install the manufacturer's products in accordance with specified requirements. Submit manufacturer's certification that each listed installer is qualified and trained to install the specified fireproofing. Show evidence that each fireproofing installer has had a minimum of 3 years experience in installing the specified type of fireproofing. Each installer of fireproofing material shall be trained, have a minimum of 3 years experience and a minimum of three installations using fireproofing of the type specified. A manufacturer's willingness to sell its products to the Contractor or installer does not infer qualification of the buyer.
1.4.2 Pre-Installation Meeting
Hold a meeting with the installer, field testing agency, the manufacturer, subcontractors (whose employees come into contact with the fireproofing), and the Contracting Officer prior to the installation of any fireproofing material to review the substrates for acceptability, method of application, applied thickness, patching, repair, inspection and testing procedures.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver packaged material in the original unopened containers, marked to show the brand name, the manufacturer, and the UL markings. Keep fireproofing material dry until ready to be used, and store off the ground, under cover and away from damp surfaces. Damaged or opened containers will be rejected. Apply material with shelf-life prior to expiration of the shelf-life.
1.6 PROJECT/SITE CONDITIONS
1.6.1 Temperature
Maintain substrate and ambient air temperatures above 40 degrees F during application and for 24 hours before and after application. Maintain relative humidity within the limits recommended by the fireproofing manufacturer.
1.6.2 Ventilation
Provide adequate ventilation to properly dry the fireproofing after application. In enclosed areas, provide a minimum of 4 air exchanges per hour by forced air circulation.
PART 2 PRODUCTS
2.1 SPRAY-APPLIED FIREPROOFING
Provide spray-applied fireproofing material, including sealer, conforming to ASTM E1042, Class (a), Category A, either Type I or Type II, except that the dust removed shall not exceed 0.0025 gram per square foot of fireproofing material applied as specified in the project. Only products that have been evaluated at UL and bear and "investigated for exterior
Jacobs WFXO2003 SECTION 07 81 00 Page 4 use" approval are allowed in waterfront areas where the fireproofing may be directly exposed to a natural body of water. Material shall be asbestos free, and shall resist fungus for a period of 28 days when tested in accordance with ASTM G21. Material shall have a flame spread of 25 or less and a smoke developed rating of 50 or less when tested in accordance with ASTM E84. Submit one sample panel, 18 inches square, for each specified type of fireproofing. Also, a designated sample area of not less than 100 square feet shall be prepared. Sample area shall be representative of typical installation of fireproofing including metal decks, beams, columns and attachments. Equipment, materials and procedures used in the sample area shall be the same as, or representative of, that to be used in the work. The sample area shall be approved prior to proceeding with fireproofing work in any other area. The approved sample area shall be used as a reference standard for applied fireproofing material. Sample area shall remain in place and open to observation until all spray-applied fireproofing is completed and accepted, at which time it may become part of the work.
2.1.1 Dry Density and Cohesion/Adhesion
Fireproofing shall have a minimum ASTM E605/E605M dry density and ASTM E736 cohesion/adhesion properties as follows:
2.1.1.1 Concealed Structural Components
Fireproofing for structural components concealed above the ceiling, or within a wall, chase, or furred space, shall have a minimum applied dry density of 15 pounds per cubic foot and a cohesion/adhesion strength of 200 psf .
2.1.1.2 Exposed Structural Components
Fireproofing for exposed structural components, except where otherwise specified or indicated, shall have a minimum applied dry density of 22 pounds per cubic foot and a cohesion/adhesion strength of 434 psf .
2.1.1.3 Mechanical Rooms and Storage Areas
Fireproofing for structural components located in mechanical rooms and storage areas shall have a minimum applied dry density of 40 pcf and a cohesion/adhesion strength of 1,000 psf .
2.1.2 Deflection
Spray-applied fireproofing shall not crack, spall, or delaminate when backing to which it is applied is subject to downward deflection 1/120 of 10 foot clear span, when tested in accordance with ASTM E759/E759M .
2.1.3 Bond-Impact
Spray-applied fireproofing material shall not crack, spall or delaminate when tested in accordance with ASTM E760/E760M .
2.1.4 Compressive Strength
The minimum compressive strength shall be 1000 psf when tested in accordance with ASTM E761/E761M .
Jacobs WFXO2003 SECTION 07 81 00 Page 5
2.1.5 Corrosion
Spray-applied fireproofing material shall not contribute to corrosion of test panels when tested as specified in ASTM E937/E937M .
2.1.6 Air Erosion
Dust removal shall not exceed 0.025 gram per square foot when tested in accordance with ASTM E859/E859M .
2.2 SEALER
Sealer shall be the type approved by the manufacturer of the fireproofing material, shall be fungus resistant, shall have a flame spread of 25 or less and a smoke developed rating of 50 or less when tested in accordance with ASTM E84, and shall be white color.
2.3 WATER
Water used for material mixing and surface preparation shall be potable.
2.4 SPRAY-APPLIED INTUMESCENT EPOXY COATING SYSTEM
Provide a two-component epoxy based intumescent fire protective coating that meets the following requirements.
a. On curing it forms a flexible and tough epoxy barrier which transforms into a ceramic-like, insulating char to provide thermal protection of the substrate in the event of a fire.
b. The coating system includes the manufacturer's required surface preparation, primer, and fire protective layer, and topcoat.
c. The coating system protects the substrate from corrosion and retain its fire protection properties under aggressive chemical environments.
d. Resistant to solvents, acids, alkalis, salts and abrasion while retaining its fire protective properties.
Provide a system that exhibits the following properties:
2.4.1 Percent Solids by Weight
100 percent
2.4.2 In Service Temperature Restrictions
Up to 150 degrees F
2.4.3 Application Method
Air spray or specialized plural component airless equipment approved by the manufacture. Troweling can be used for small areas or touch-up work.
2.4.4 Drying Time
Approximately 24 hours to achieve a Shore D hardness of 25.
Jacobs WFXO2003 SECTION 07 81 00 Page 6
2.4.5 Shelf Life
Minimum shelf life under proper storage condition is 1 Year from date of manufacture.
2.4.6 Pot Life
Approximately 40 minutes at 77 degrees F and 50 percent relative humidity.
Pot life is not a factor when using specialized plural component airless spray equipment.
2.4.7 Flash Point
Greater than 212 degrees F Pensky-Martens for each component.
PART 3 EXECUTION
3.1 SURFACE PREPARATION
Thoroughly clean surfaces to be fireproofed of dirt, grease, oil, paint, primers, loose rust, rolling lubricant, mill scale or other contaminants that will interfere with the proper bonding of the sprayed fireproofing to the substrate. Test painted/primed steel substrates in accordance with ASTM E736, with specified sprayed fireproofing material, to provide the required fire-resistance rating; painted or primed steel surfaces may require a fireproofing bond test to determine if the paint formulation will impair proper adhesion. Certify the acceptability of surfaces to receive sprayed-applied fireproofing by inspection and submit a Surface Preparation Report accordingly. The statement shall list the structural members and the areas that have been inspected and certified. Overhead areas to be fireproofed shall be cleared of all obstructions interfering with the uniform application of the spray-applied fireproofing. Hardware such as support sleeves, inserts, clips, hanger attachment devices and the like shall be installed prior to the application of the fireproofing.
Condition of the surfaces shall be acceptable to the manufacturer prior to application of spray-applied fireproofing. Applications listed for use on primed surfaces shall be in accordance with the manufacturer's recommendations and standards, and detailed in submittal item SD-03 Product Data.
3.2 PROTECTION
Cover surfaces not to receive spray-applied fireproofing to prevent contamination by splatter, rebound and overspray. Cover exterior openings in areas to receive spray-applied fireproofing prior to and during application of fireproofing with tarpaulins or other approved material.
Clean surfaces not to receive fireproofing of fireproofing and sealer.
3.3 FIREPROOFING MATERIAL
Mix fireproofing material in accordance with the manufacturer's recommendations. Submit data identifying performance characteristics of fireproofing material. Data includes recommended application requirements and indicate thickness of fireproofing to be applied to achieve each required fire rating.
Jacobs WFXO2003 SECTION 07 81 00 Page 7
3.4 APPLICATION
3.4.1 Sequence
Prior to application of fireproofing on each floor, the manufacturer shall inspect and approve application equipment, water supply and…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .