B08 Appendix A - 1160 HAZMAT Surveys.pdf

PDF 2 MB Posted

Attached to
Air Traffic Control Tower Kelly Field
Solicitation number
W9126G22R0002
Issued by

About this file

This hazardous materials survey report documents regulated building materials identified at Joint Base San Antonio Building 1160, a nine-story air traffic control tower. The survey identified asbestos-containing floor tiles, duct mastic, and window glazing. Lead-based paint was also detected on metal stairs and stair landings. Fluorescent and high intensity discharge light bulbs containing mercury were inventoried. The HVAC unit was found to contain 38 pounds of R-22 refrigerant. A 100KVA backup generator and 30-gallon day tank holding diesel fuel were also identified. The report provides testing methodology details and includes recommendations for abatement and disposal of all regulated materials in accordance with federal and state regulations should renovation or demolition occur. Sampling was limited due to inaccessibility of some areas. The appendices include analytical laboratory reports and certifications.

View the file

Other files

File Type Posted
Amendment 11.pdf PDF
Amendment 10.pdf PDF
Amendment 9.pdf PDF
Amendment 8.pdf PDF
Amendment 07.pdf PDF
Amendment 06.pdf PDF
Kelly ATCT SIte Visit Sign In Sheet 01FEB22.pdf PDF
Amendment 05.pdf PDF
Attachment 2 Past performance Assesment Worksheet As 20220131.pdf PDF
Amendment 04.pdf PDF
Site Visit 1 Kelly ATCT SIte Visit Sign In Sheet.pdf PDF
Amendment 03.pdf PDF
Monaco JA.pdf PDF
Best Locks Name Brand JA.pdf PDF
Amendment 02.pdf PDF
UAR Form jbsanantonio7.pdf PDF
Amendment 01.pdf PDF
MPLS_MBPB01160_10790_D685_005.pdf PDF
MPLS_MBPB01160_10807_KC01_015.pdf PDF
MPLS_MBPB01160_10790_D685_002.pdf PDF
76-0048.pdf PDF
MPLS_MBPB01160_10807_KC01_019.pdf PDF
MPLS_MBPB01160_10807_KC01_018.pdf PDF
MPLS_MBPB01160_10790_D685_006.pdf PDF
MPLS_MBPB01160_10807_KC01_010.pdf PDF
82-0027.pdf PDF
MPLS_MBPB01160_10807_KC01_011.pdf PDF
MPLS_MBPB01160_10790_D685_001.pdf PDF
g22r0002_Drawings.pdf PDF
MPLS_MBPB01160_10807_KC01_016.pdf PDF
71-4.pdf PDF
MPLS_MBPB01160_10807_KC01_002.pdf PDF
MPLS_MBPB01160_10807_KC01_017.pdf PDF
W9126G22R0002.pdf PDF
MPLS_MBPB01160_10807_KC01_022.pdf PDF
DACA63-68-B-0130.pdf PDF
MPLS_MBPB01160_10807_KC01_008.pdf PDF
MPLS_MBPB01160_10807_KC01_001.pdf PDF
MPLS_MBPB01160_10807_KC01_006.pdf PDF
MPLS_MBPB01160_10807_KC01_007.pdf PDF
MPLS_MBPB01160_10807_KC01_004.pdf PDF
MPLS_MBPB01160_10807_KC01_003.pdf PDF
MPLS_MBPB01160_10790_D685_003.pdf PDF
g22r0002_Demo Drawings.pdf PDF
MPLS_MBPB01160_10807_KC01_020.pdf PDF
MPLS_MBPB01160_10807_KC01_014.pdf PDF
MPLS_MBPB01160_10790_D685_004.pdf PDF
MPLS_MBPB01160_10807_KC01_005.pdf PDF
MPLS_MBPB01160_10807_KC01_012.pdf PDF
MPLS_MBPB01160_10807_KC01_023.pdf PDF
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8626 Tesoro Dr., Suite 810 ● San Antonio, TX 78217 ● (210) 930 2834 ● www.atei97.com

Hazardous Materials Survey Report

Building 1160

Air Traffic Control Tower

Kelly Field Annex

Joint Base San Antonio, Texas

Prepared for:

Jacobs Engineering Group

777 Main Street

Fort Worth, Texas 76102

February 16, 2018

JACOBS~

Hazardous Materials Survey JBSA Building 1160 JACOBS Alpha Terra Engineering Inc. February 16, 2018

Contents

0 EXECUTIVE SUMMARY

1 INTRODUCTION

2 PROPERTY DESCRIPTION

3 HAZARDOUS MATERIALS SURVEY

3.1 ASBESTOS-CONTAINING MATERIAL

3.1.1 Procedures and Methodology

3.1.1 Results

3.2 LEAD

3.2.1 Procedures and Methodology

3.2.2 Results

3.3 POLYCHLORINATED BIPHENYLS

3.3.1 Procedures and Methodology

3.3.2 Results

3.4 MERCURY

3.5 CHLOROFLUOROCARBONS

3.6 GENERATOR AND ABOVEGROUND DIESEL FUEL TANK (AST)

4 RECOMMENDATIONS

4.1 ASBESTOS

4.2 LEAD

4.3 POLYCHLORINATED BIPHENYLS

4.4 MERCURY

4.5 CHLOROFLUOROCARBONS

4.6 GENERATOR AND ABOVEGROUND STORAGE TANK (AST)

5 LIMITATIONS

Appendix A1 - Photos of Asbestos Containing Building Material

Appendix A2 - Photos of Lead (Pb) Containing Building Components

Appendix A3 - Photos of Mercury (Hg) Containing Bulb Fixtures

Appendix A4 - Photos of Chlorofluorocarbon Containing Equipment

Appendix A5 - Photos of Generator, and 30 Gallon Fuel Tank

Appendix A6 - Photos of Underground Storage Tank

Appendix B1 – Asbestos Certifications

Appendix B2 – Lead Certification

Appendix C1 – Laboratory Analytical Reports

Appendix C2 – Lead Laboratory Reports

TABLES OF TABLES

Table 1 – Regulated Materials Identified

Table 2 - Positive Asbestos Containing Material (Interior and Exterior)

Table 3 - Positive Lead Based Paint Components

Table 4 - Mercury Containing Components

Table 5 - Asbestos-Containing Materials Sample Inventory Table 6 - Lead Based Paint Sample Inventory

TABLES OF FIGURES

Figure 1 - Property Location Map

Figure 2 - Interior and Exterior / Asbestos and Lead Sample Locations

0 EXECUTIVE SUMMARY

Jacobs Engineering Group commissioned Alpha Terra Engineering Inc. to complete a hazardous materials survey for Building 1160 located at Kelly Field Annex on Kelly Airfield Joint Base

San Antonio (JBSA) Texas. The purpose of this hazardous material survey was to identify, to the extent feasible, regulated building materials such as mercury bulbs, lead based paint, asbestos, and HVAC refrigerant that may require abatement before demolition activities. This survey included the inspection of the property, a nine story air traffic control tower built in 1970. The surveys performed comply with all applicable local state and federal regulations. The asbestos inspection, bulk sampling, and analytical procedures were performed in general accordance with the Environmental Protection Agency’s (EPA) interpretations, and guidelines of the Asbestos

Hazard Emergency Response Act (AHERA). The lead (Pb) inspection was performed in general accordance with the Housing and Urban Development (HUD) and the Occupational Safety &

Health Administration’s (OSHA’s) Lead in Construction. This document is not meant to be used as a hazardous materials specification for abatement. Any reliance on this report by a third party is at such party’s sole risk.

The following regulated building materials were identified during the course of the survey.

Table 1 – Regulated Materials Identified

Regulated Material Material Description Quantity Asbestos White 12x12 Floor Tile 145 Sq/ft

Green 12x12 Floor Tile & 145 Sq/ft Black Mastic Under Green Floor Tile 145 Sq/ft Gray Duct Mastic 25 Sq/ft Window Glazing on Six Windows 30 LF

Lead (Pb) Red/Brown Metal Stairs 876 Sq/ft Red/Brown Stair Landings 8 Landings

Polychlorinated Biphenyls None N/A Mercury Mercury Containing Fluorescent Light Tubes 58 Tubes High Intensity Discharge Bulbs 8 Bulbs Chlorofluorocarbons R-22 Refrigerant 38 lbs.

Diesel Fuel Generator 30 Gallons Underground Storage Tank 500 Gallons

Access was not provided to the boiler room. The room no longer contained boilers, but was used as storage. Access was not provided to the elevator equipment room or upper roof of the

Property building. Non-destructive sampling was performed. Hidden suspect asbestos containing materials such as vermiculite may be present in the cement masonry walls, along with pipe insulation inside the interior walls. This executive summary is presented solely for introductory purposes, and the information contained in this section should be used only in conjunction with the full text of this report.

1 INTRODUCTION

Alpha Terra Engineering Inc. (ATEI) has prepared this report at the request of Jacobs

Engineering Group (JACOBS) to present the results of the hazardous materials survey conducted at Joint Based San Antonio (JBSA), Lackland Building 1160, in San Antonio, Texas (the

Property). The Property location is shown on Figure 1. This HAZMAT survey included an inspection of the Property. The hazardous materials survey of the Property included the sampling and analysis of suspect asbestos-containing material (ACM), lead-containing components, PCB-containing light ballasts, mercury-containing light tubes, fuel, and cooling systems that may contain chlorofluorocarbons (CFCs). The purpose of the hazardous materials survey was to locate and identify building materials and components at the Property that may require special handling and/or disposal during any future demolition or construction activities. The hazardous materials survey was conducted by Mr. Dan Turek who lead the team and performed the

Mercury and PCB analysis, Mr. Alexander Jackson, Asbestos Hazard Emergency Response Act

(AHERA) Building Inspector, and Ms. Trina Mullen, a Texas Lead certified Lead-Based Paint

Inspector, as defined in Texas Occupations Code, Chapter 1955 and Title 25 of the Texas

Administrative Code Chapter 295. Copies of the AHERA and Texas relevant certifications are provided in Appendix B. This report includes inspection findings and presents the laboratory analytical results from samples collected from the building.

2 PROPERTY DESCRIPTION

The referenced building is a nine (9) story steel beam and CMU brick constructed air traffic control tower with a metal exterior sleeve built in 1970. The interior is finished out in plaster/lathe, CMU, and sheetrock/joint compound. Flooring consists of carpet, metal, and several vinyl tile finishes. This building shares the property with building 1161, the Airfield

Operations Flight Complex. There is an elevator, generator, and HVAC system located on property.

3 HAZARDOUS MATERIALS SURVEY

The hazardous materials survey was performed on January 3, 2018. The scope of work was conducted to meet the objectives of the hazardous materials survey and included the following:

Visual inspection of the interior and exterior of the Property for the presence of suspect

ACM, lead-containing paint; PCB-containing light ballasts; cathode ray tubes (CRTs), mercury-containing light tubes and thermostats; generator fuel; and CFC-containing refrigerant units.

Collection and analysis of bulk samples to confirm whether the suspect building material was asbestos-containing.

Collection and analysis of suspect lead-containing paint samples to confirm whether the associated paint contained lead.

Documentation of the number of PCB-containing light ballasts; mercury-containing fluorescent and high-intensity discharge (HID) light bulbs and thermostats; potential and

CFC containing components at the Property.

Preparation of this report.

3.1 ASBESTOS-CONTAINING MATERIAL

ATEI conducted a survey for suspect ACM on the Property, which included locating and collecting samples of suspected asbestos containing building materials (ACBMs), submitting the samples for laboratory analysis, and provide a written report of findings and recommendations in accordance with AHERA sampling protocol (U.S. Environmental Protection Agency [EPA]

1987). A building material is considered asbestos containing if it contains more than 1% of asbestos.

3.1.1 Procedures and Methodology

Sample locations of identified suspect ACM were chosen by the inspectors in accessible locations. The following sampling procedures were followed:

Personal Protective Equipment for this assessment consisted of:

Eye protection, either personal glasses or safety glasses

Respiratory protection

Disposable gloves: donned prior to sample collection and changed between samples locations to avoid cross-contamination.

Sample containers were labeled with identification numbers.

Sample locations and material type were documented on a sampling data form.

Samples were extracted using a decontaminated knife or chisel to cut out or scrape off approximately 1 tablespoon of the material. When layers were present in the building material, all layers were penetrated and incorporated into each specific sample.

Each sample was placed in a re sealable plastic bag, which was then sealed.

Sampling tools were decontaminated with wet wipes, and material generated during sampling was wet-wiped to remove debris.

Protective clothing, wet wipes, rags, and drop cloths were placed in a labeled plastic waste bag for disposal.

Sample bags were then placed in a large, labeled, resealable plastic bag for transport to Crisp

Analytical, L.L.C., located in Carrollton, Texas, a National Voluntary Laboratory

Accreditation Program (NVLAP) certified laboratory (NVLAP code # 200349-0), using chain-of-custody protocols for Bulk Asbestos Analysis by Polarized Light Microscopy, EPA

Method 600/R-93/116

3.1.1 Results

ATEI collected a total of 35 samples of suspect ACM from the interior and exterior of building

1160. Sample locations are presented on Figure 2, and an inventory of the positive asbestos samples is provided in Table 1. Laboratory analytical reports are provided in Appendix C.

Building materials identified as asbestos-containing include the following:

Table 2 - Positive Asbestos Containing Material (Interior and Exterior)

Interior Material Amount Location Sample # 12x12 White Floor Tile and Black Mastic 145 Sq/ft Room at 10ft. Level 232-034 to 036 12x12 Green Floor Tile and Black Mastic 145 Sq/ft Room at 40ft. Level 232-058 to 060 Gray Duct Mastic/Sealant 25 Sq/ft Room at 40ft. Level 232-043 to 045

Exterior Material Amount Location Sample #

Window Glazing 85 l/ft 2 at 10ft. Level 2 at 40ft. Level 1 at 50ft. Level at Stairs 1 at 60ft. Level at Stairs 3 at 70ft. Level

232-040 to 042

Photos of Positive Asbestos Containing Materials Located in Appendix A

3.2 LEAD

ATEI conducted a survey for interior and exterior paint coatings on the Property building, which included collecting representative measurements utilizing the Niton 300 XLp Series XRF from each color and/or layer identified. Lead based paint report located in Appendix C.

3.2.1 Procedures and Methodology

Sample locations of identified painted surfaces were chosen by the inspector in accessible locations. The following sampling procedures were followed:

Personal protective equipment, including gloves, was donned prior to sample collections.

XRF calibrations were performed prior to and after testing in accordance with Performance

Characteristics Sheets (PCS).

Sample locations were documented on a sampling data form.

Test results from the XRF Analyzer are tracked in the field by the lead inspector and later tabulated in table format for inclusion in this report.

Protective clothing, wet wipes, rags, and drop cloths were placed in a labeled plastic waste bag for disposal.

The inspection was performed in general accordance with the Housing and Urban

Development (HUD) and the Occupational Safety & Health Administration’s (OSHA’s)

Lead in Construction. The XRF is a direct read instrument and does not require laboratory analysis.

3.2.2 Results

A total of eighty (80) measurements were taken utilizing the Niton 300 XLp Series XRF and were collected from representative interior and exterior painted surfaces on the Property building. An inventory of positive samples is provided in Table 3; sample locations are presented on Figure 2. Laboratory analytical reports are provided in Appendix C. The following samples were identified as lead-containing:

Table 3 - Positive Lead Based Paint Components

Material Description Location Sample # Metal Stairs brown/red paint at 9.8% Stairs on all levels 11 Metal Floor Landings brown/red paint at 20.2% & 9.7% Stairs on all levels 28 & 42

Photos of Positive Lead (Pb) Paint Components Located in Appendix A

3.3 POLYCHLORINATED BIPHENYLS

Suspect PCB electrical devices and PCB-containing light ballasts were inspected from the interior of the Property building.

3.3.1 Procedures and Methodology

The following is a listing of procedures and methodologies used in this project.

Representative fluorescent light fixtures were observed for suspect PCB-containing ballasts. The following inspection procedures were followed.

Personal protective equipment, including gloves, was donned prior to ballast inspection.

Electrical power was disconnected at the light fixtures prior to inspecting the ballasts.

Fluorescent light tubes were removed from the fixtures after which the light fixture covers were removed.

Representative fluorescent light ballasts were inspected for “No PCBs” labeling.

Light fixture covers and tubes were reconnected to the fluorescent light fixtures after inspection.

3.3.2 Results

All representative fluorescent light ballasts inspected for PCB labeling in the Property building were branded with “No PCBs” labeling.

3.4 MERCURY

Fluorescent and HID light tubes, which may contain mercury, were inventoried during the survey. ATEI personnel counted 68 fluorescent and three HID light tubes at the Property. No mercury-containing thermostats were observed at the Property during the survey; however, the elevator equipment room, and adjacent room were not accessed and may contain mercury-containing thermostats. The specific number and locations of the fluorescent and HID light tubes are provided in table 4:

Table 4 – Mercury Containing Components

Location Items Quantity

Ground Floor Fluorescent Light Tubes Four Ten Foot Level Fluorescent Light Tubes Ten Twenty Foot Level Fluorescent Light Tubes Four Thirty Foot Level Fluorescent Light Tubes Four Forty Foot Level Fluorescent Light Tubes

High Intensity Discharge Lights Eight One

Fifty Foot Level Fluorescent Light Tubes High Intensity Discharge Lights

Four One

Sixty Foot Level Fluorescent Light Tubes Ten Seventy Foot Level Fluorescent Light Tubes

High Intensity Discharge Lights Six One

Control Room Level Fluorescent Light Tubes Eight Exterior Door to Elevator Equip. High Intensity Discharge Lights One Main Exterior Door High Intensity Discharge Lights One

3.5 CHLOROFLUOROCARBONS

One HVAC unit was observed at the Property during the survey that serves Bldg 1160 (tower).

The HVAC unit sits adjacent to the Tower in a fenced in area. The HVAC unit contains 38 lbs of R-22 refrigerant. This refrigerant must be recovered from the HVAC unit during its decommissioning phase. See Appendix A for corresponding photo.

3.6 GENERATOR AND ABOVEGROUND DIESEL FUEL TANK (AST)

The Tower building contains a 100 KVA back-up generator on the ground level. See Appendix

A for corresponding photo. This generator is relatively unused, as it only has 420 hours of run time per the recorder device. This diesel generator contains diesel fuel, engine oil and antifreeze coolant that must all be recovered or contained during the removal process. The generator room contains a diesel fuel tank (day tank) of approximately 63 gallons that must be drained and removed before building demolition. See accompanying photo. As an observation and outside of

ATEI scope of work, located approximately fifty (50) feet from the Tower building, an aboveground Storage Tank (AST) located in a vault exists that has a capacity of 1000 gallons of diesel fuel. The age of the fuel tank is unknown. The tank must be excavated and removed according to DoD and State of Texas environmental standards. A one inch (1”) fuel pipeline is in place approximately 30 inches deep from the UST to the building inlet where a pump is located to deliver the diesel fuel from the AST to the day tank. This 1” diesel fuel pipeline must also be excavated and removed during the demolition phase.

4 RECOMMENDATIONS

Based on the information gathered during the hazardous materials survey, ATEI makes the following recommendations.

4.1 ASBESTOS

Planning and coordination of ACM removal should begin prior to renovation and/or demolition activities. The ACM identified in this report should be removed by certified, trained, and protected personnel using appropriate work practices and engineering controls prior to disturbance by renovation or demolition, as outlined in the Unified Facilities Guide

Specifications in conjunction with the Texas Asbestos Health Protection Rules. Areas that were inaccessible to our Inspectors such as the elevator equipment room, and the storage room previously used for boilers should have any additional, previously unsampled, suspect materials encountered during renovation and/or demolition activities should be sampled by a certified

AHERA Building Inspector and analyzed by a NVLAP-accredited laboratory to evaluate asbestos content prior to disturbing the material.

4.2 LEAD

A representative sample of the demolition waste associated with samples 11, 28, and 42, each of which contained elevated concentrations of lead, should be collected and analyzed using a toxicity characteristic leaching procedure (TCLP) to characterize the waste for disposal.

Demolition waste streams with leachable lead concentrations exceeding 5.0 milligrams per liter when prepared for analysis using the TCLP method are considered hazardous and require special handling according to federal and state regulations, including 40 CFR 247.

If work is to be performed on the components with lead based paint, then OSHA requires the contractor to inform its employees of potential lead hazards, based upon the work being performed. The purpose of OSHA’s lead construction standard is to reduce the exposure to lead for all construction workers. ATEI recommends contractors to be informed of the presence of

LCP within the facility prior to disturbance. OSHA’s standard includes an 8-hour time weighted average (TWA) of 50 micrograms of lead per cubic meter of air (mg/m3) and an action level

(regardless of respirator use) of 30 mg/m3. Although the standard emphasizes exposure assessment for individual job tasks, varying levels of worker protection are required of the contractor for certain tasks or activities involving lead based and lead-containing paint. Two locations were inaccessible to our Inspectors (Elevator Equipment Room and Storage Room) and should additional, previously unsampled, painted surfaces be revealed through renovation and/or demolition activities, ATEI recommends the coatings be sampled by a TDSHS-certified inspector and analyzed to evaluate lead content prior to destruction, removal, or personnel exposure.

4.3 POLYCHLORINATED BIPHENYLS

During demolition activities, any light ballast without “No PCBs” labeling should be handled and disposed of according to state and federal regulations (i.e., workers should employ proper personal protective equipment when handling the ballasts and properly store the ballasts in sealed plastic bags or buckets to minimize potential contact with any exposed or leaking PCB-containing oil). All PCB waste must be labeled, manifested, transported, and disposed of according to federal and state regulations, including 40 CFR 761.

4.4 MERCURY

Fluorescent and HID light tubes may contain mercury vapors. These tubes and mercury containing heat thermostats should be removed without breakage and disposed of property in accordance with TCEQ Texas Administrative Code (TAC) Chapter 335, Subchapter H, Waste

Minimization and Recycling in accordance with 40 CFR Part 273. No Mercury containing thermostats were located on property.

4.5 CHLOROFLUOROCARBONS

During demolition activities, HVAC systems should be evacuated of refrigerant by a Texas registered and licensed HVAC firm prior to being impacted by demolition activities. Any discharge of spent CFCs to the environment constitutes disposal and is subject to full regulation under 40 CFR 82.156. The federal rules for the management of chlorofluorocarbon (CFC), https://enviro.blr.com/trial_v2/signup.aspx?layoutid=72 hydrochlorofluorocarbons, and other ozone-depleting substances are in effect in Texas, although the state has not incorporated the rules into its own regulations. There are no state regulations pertaining to the management of ozone-depleting substances. However, the Texas regulations governing municipal solid waste specifically state that refrigerators, freezers, air conditioners, and any other items containing the CFCs must be handled in accordance with 30 Texas

Administrative Code 330.15(e)(5) and 30 TAC 330.147(C). All refrigerant must be properly transported, recycled, and reclaimed in accordance with all applicable federal, state, and local regulations by an authorized hazardous waste handler.

4.6 GENERATOR AND ABOVEGROUND STORAGE TANK (AST)

The rules for used oil recycling are found in 30 Texas Administrative Code (TAC) Chapter 324 in conjunction with 40 CFR Part 279. Identified material should be separated from the general demolition waste stream, transported by an authorized hazardous materials transporter, and disposed of at an authorized waste facility. This applies to the 63 gallon diesel fuel generator day tank, and not the 1,000 gallon underground storage tank observed but not in the scope of work. Based on review of Texas Commission for Environmental Quality (TCEQ) records, no detrimental information was found on the AST.

During the demolition, the demolition contractor must notify Environmental (502 CES/CEIEC) of the 63 gallon diesel fuel generator day tank when it is removed. Removal of any USTs or

ASTs, must comply with the following technical requirements:

Texas Administrative Code, Title 30 Environmental Quality Part 1, Texas Commission

On Environmental Quality, Chapter 334 Underground And Aboveground Storage Tanks

Air Force Instruction 32-7044 "Storage Tank Environmental Compliance"

Air Force Instruction 23-204 "Organizational Fuel Tanks"

5 LIMITATIONS

The services described in this report were performed consistent with generally accepted professional consulting principles and practices. No other warranty, expressed or implied, is made. These services were performed consistent with our current consulting agreement with the client. This report is solely for the use and information of our client unless otherwise noted. Any reliance on this report by a third party is at such party’s sole risk. ATEI was not provided access to the elevator equipment room, the adjacent storage room, or the upper roof. ATEI was subsequently unable to sample these areas. Additionally, because the tower is currently in use, ATEI was unable to safely access the roof. ATEI performed non-destructive sampling of suspect materials, therefore ATEI was unable to access inside the wall cavities inspecting for suspect

ACM. Hidden suspect ACM such as vermiculite may be present in the cement masonry walls, along with insulation piping inside the interior walls. Table 5 are the asbestos samples taken, and table 6 is for the locations and components of what was sampled. Opinions and recommendations contained in this report apply to conditions existing when services were performed and are intended only for the client, purposes, locations, time frames, and project parameters indicated. ATEI is not responsible for the impacts of any changes in environmental standards, practices, or regulations subsequent to performance of services.

Table 5 - Asbestos-Containing Materials Sample Inventory

Sample Number Material Location Asbestos Type & Percent

232-028 Sheetrock/Joint Compound Room 40 ft. Level None Detected 232-029 Sheetrock/Joint Compound Break Room None Detected 232-030 Sheetrock/Joint Compound Generator Room None Detected 232-031 Tank TSI Ground Floor None Detected 232-032 Tank TSI Ground Floor None Detected 232-033 Tank TSI Ground Floor None Detected 232-034 White Floor Tile/Black Mastic Room 10 ft Level 3% Chrysotile 232-035 White Floor Tile/Black Mastic Room 10 ft Level 3% Chrysotile 232-036 White Floor Tile/Black Mastic Room 10 ft Level 3% Chrysotile 232-037 Ceiling Tile w/ Small Holes Room 10 ft Level None Detected 232-038 Ceiling Tile w/ Small Holes Room 10 ft Level None Detected 232-039 Ceiling Tile w/ Small Holes Room 40 ft. Level None Detected 232-040 Window Glazing Window 10 ft. Level 4% Chrysotile 232-041 Window Glazing Window 40 ft. Level 4% Chrysotile 232-042 Window Glazing Window 70 ft. Level 4% Chrysotile

Sample Number Material Location Asbestos Type & Percent

232-043 Gray HVAC Caulk Room 40 ft. Level 8% Chrysotile 232-044 Gray HVAC Caulk Room 40 ft. Level 8% Chrysotile 232-045 Gray HVAC Caulk Room 40 ft. Level 8% Chrysotile 232-046 Ceiling Tile w/ Large Holes Room 10 ft Level None Detected 232-047 Ceiling Tile w/ Large Holes Room 40 ft. Level None Detected 232-048 Ceiling Tile w/ Large Holes Break Room None Detected 232-049 Pipe TSI Generator Room None Detected 232-050 Pipe TSI Room 10 ft Level None Detected 232-051 Pipe TSI Room 50 ft. Level None Detected 232-052 Cove Base Mastic Break Room 60ft. None Detected 232-053 Cove Base Mastic Restroom at 60ft None Detected 232-054 Cove Base Mastic Control Room None Detected 232-055 Plaster 40 ft. Cable Ducts None Detected 232-056 Plaster Break Room None Detected 232-057 Plaster Mechanical None Detected 232-058 Green Floor Tile/Black Mastic 40 ft. Level Back 3-4% Chrysotile 232-059 Green Floor Tile/Black Mastic 40 ft. Level Middle 3-4% Chrysotile 232-060 Green Floor Tile/Black Mastic 40 ft. Level by Door 3-4% Chrysotile 232-061 Roofing Material Roof at 10 ft. Level None Detected 232-062 Roofing Material Roof Above Elevator None Detected 232-063 Roofing Material Roof at Catwalk None Detected

Table 6 - Lead Based Paint Sample Inventory

Sample Location Component Substrate Color Lead (Pb) % 01 Generator Room Wall C CMU White 0.0 02 Generator Room Door Metal Red 0.0 03 Generator Room Door Jam Metal White 0.13 04 Generator Room Floor Concrete Gray 0.02 05 Generator Room Generator Pedestal Concrete Black 0.04 06 Generator Room Generator Metal Green 0.0 07 Generator Room Cabinets Metal White 0.01 08 Generator Room Diesel Tank Metal White 0.0 09 Ground Floor Wall C CMU White 0.01 10 Ground Floor Wall D CMU White 0.01 11 Ground Floor Stairs Metal Brown/Red 9.8 12 Ground Floor Floor Concrete Gray 0.01 13 Ground Floor Door Frame Metal Brown 0.06 14 Ground Floor Door Metal Brown 0.0 15 Ground Floor Rail Metal Brown 0.07 16 Ground Floor Structural Steel Metal Brown 0.08 17 10 Ft. Radio Rm. Wall A CMU Tan 0.0 18 10 Ft. Radio Rm. Wall B Drywall Tan 0.0 19 10 Ft. Radio Rm. Wall C Drywall Tan 0.0 20 10 Ft. Radio Rm. Wall D Drywall Tan 0.0 21 10 Ft. Radio Rm. Window Sill Drywall Tan 0.0 22 10 Ft. Radio Rm. Door Frame Metal Brown 0.16 23 10 Ft. Radio Rm. Door Jamb Metal Brown 0.18

Sample Location Component Substrate Color Lead (Pb) % 24 10 Ft. Radio Rm. Door Metal Brown 0.05 25 10 Ft. Vestibule Wall D CMU Off-White 0.01 26 10 Ft. Vestibule Door Frame Metal Brown 0.04 27 10 Ft. Vestibule Door Metal Brown 0.01 28 10 Ft. Vestibule Stair Landing Metal Brown/Red 20.2 29 Elevator Shaft Rm. Structural Steel Metal Yellow 0.03 30 Elevator Shaft Rm. Structural Steel Metal Brown 0.03 31 40 Ft. Brite Radar Wall A CMU Beige 0.01 32 40 Ft. Brite Radar Wall B Drywall Beige 0.0 33 40 Ft. Brite Radar Wall C Drywall Beige 0.01 34 40 Ft. Brite Radar Wall D Drywall Beige 0.0 35 40 Ft. Brite Radar Door Metal Brown 0.02 36 40 Ft. Brite Radar Door Frame Metal Brown 0.02 37 40 Ft. Level Elevator Door Frame Metal Brown 0.21 38 40 Ft. Level Elevator Door Metal Brown 0.16 39 50 Ft. Level Walls CMU Beige 0.0 40 50 Ft. Level Door Frame Metal Brown 0.02 41 50 Ft. Level Stair Rail Metal Brown 0.06 42 50 Ft. Level Stair Landing Metal Brown/Red 9.7 43 60 Ft. Break Room Wall A Drywall White 0.0 44 60 Ft. Break Room Wall B Drywall White 0.0 45 60 Ft. Break Room Wall C Drywall White 0.0 46 60 Ft. Break Room Wall D Drywall White 0.0 47 60 Ft. Break Room Elevator Door Frame Metal Brown 0.25 48 60 Ft. Break Room Elevator Door Metal Brown 0.20 49 60 Ft. Break Room Door Frame Metal Brown 0.09 50 60 Ft. Break Room Door Metal Brown 0.02 51 70 Ft. Level Wall A CMU Peach 0.0 52 70 Ft. Level Wall B Drywall Peach 0.0 53 70 Ft. Level Wall C Drywall Peach 0.0 54 70 Ft. Level Wall D Plaster Peach 0.0 55 70 Ft. Level Door Frame Metal Brown 0.01 56 70 Ft. Level Door Metal Brown 0.24 57 70 Ft. Restroom Wall A Wood White 0.01 58 70 Ft. Restroom Wall B CMU White 0.03 59 70 Ft. Restroom Wall C CMU White 0.30 60 70 Ft. Restroom Wall D CMU White 0.0 61 70 Ft. Restroom Door Metal Brown 0.07 62 70 Ft. Restroom Door Frame Metal Brown 0.0 63 70 Ft. Level Landing Floor Concrete Brown 0.0 64 70 Ft. Level Landing Ladder Metal White 0.04 65 70 Ft. Level Landing Wall CMU White 0.0 66 70 Ft. Level Landing Ceiling Plaster White 0.0 67 Control Room Stair Rail Metal Black 0.03 68 Control Room Door Metal Black 0.0 69 CR Exterior Deck Metal Siding Metal Beige/Teal 0.04 70 CR Exterior Deck Railing Metal Brown 0.11 71 CR Exterior Deck Siding Concrete Gray 0.18

Sample Location Component Substrate Color Lead (Pb) % 72 CR Exterior Deck Floor Metal Brown 0.02 73 Exterior Siding Siding Metal Tan 0.0 74 Exterior Siding Trim Metal Brown 0.0 75 Gen. Room Exterior Stairs Metal Tan/Brown 0.4 76 Exterior Gutters Metal Tan 0.0 77 Boiler Rm. Exterior Door Metal Brown 0.07 78 Calibration N/A N/A N/A 0.9 79 Calibration N/A N/A N/A 1.1 80 Calibration N/A N/A N/A 1.0

Figure 1 - Property Location Map

Design: AJ Sheet:

Dwg: AJ Dwg#:

Ck: RM Date:

Appr: RM

Company: Facility: Project #

Facility Layout Diagram

Alpha Terra Engineering, Inc.

KELL123018

Scale

NTS

2-21-2018

A

Building 1160 JBSA

Site Location Details

Figure 2 - Interior and Exterior / Asbestos and Lead Sample Locations

Ck: RM Date:

Appr: RM

Company: Facility: Project #

Facility Layout Diagram

Alpha Terra Engineering, Inc.

KELL123018

Scale

NTS

02-21-18

Asbestos Inspection Sample Locations

0 1 vtn. 029 ass fDRil fl L£'.VtL

EICTY EI, LEYE;L

Ck: RM Date:

Appr: RM

Company: Facility: Project #

Facility Layout Diagram

Alpha Terra Engineering, Inc.

KELL123018

Scale

NTS

B

Asbestos Inspection Sample Locations

029 056

S:IX!Y FT. LCVE;L

Ck: RM Date:

Appr: RM

Company: Facility: Project #

Facility Layout Diagram

Alpha Terra Engineering, Inc.

KELL123018

Scale

NTS

Lead (Pb) Inspection Sample Locations

GROUND EL 008

ItN fT. LCYEL

& 33 fDR!Y EL L tyn

E'IOX ft, LtyE'.L

Ck: RM Date:

Appr: RM

Company: Facility: Project #

Facility Layout Diagram

Alpha Terra Engineering, Inc.

KELL123018

Scale

NTS

B

Lead (Pb) Inspection Sample Locations

SIXTY EL L£ytL

SE:V£NTY EL LE:YEL

Appendix A1 - Photos of Asbestos Containing Building Material

Picture 1 - White 12x12 Floor Tile Picture 2 - Green 12x12 Floor Tile & Black Mastic

Picture 3 - Gray Duct Caulk/Mastic Picture 4 - Window Glazing

Appendix A2 - Photos of Lead (Pb) Containing Building Components

Appendix A3 - Photos of Mercury (Hg) Containing Bulb Fixtures

Picture 5 - Brown/Red Metal Stairs Picture 6 - Brown/Red Metal Stair Landings

Picture 7 - Compact Fluorescent Light bulbs Picture 8 - Fluorescent Light Tubes

Appendix A4 - Photos of Chlorofluorocarbon Containing Equipment

Appendix A5 - Photos of Generator, and 30 Gallon Fuel Tank

Picture 9 - HVAC System to Bldg. 1160 Picture 10 - HVAC System Spec. Plate

Picture 11 - 100 KVA Generator Bldg. 1160 Picture 12 - 30 Gallon Diesel Day Tank

THE. tRANt COMPANY ADIVISM:>NOfM1ERIC,\N$TAM>AROINC

~ I ® MGLIU■MIII CGAFc.t0fAHA10000F0000N0000000D UITEO a l'IM. IWMIUI COSG015Ul5 "'t,°'!.1for:f~1~ Ullf

M.1l010L,AII n1 unuu,no• WOLU,cn. MIIU liONIMA&. fflTUI VC,.H.HI

MZ IO l'HASE to1 - lSI

Mt~■IJ• ct~l ,..,AtrtY PlltoM•flDto OUM. lUNtNl PUlt l!AXJIIUM O'fUCUWlll 1'1'01fC1IOII DRICf

CITY ,o.n "' C""IU:AOfl M.)TOI A ' .. •

COIVMIICWI.OTIIAI .. •

CIINPIIHICMIMOTCNIC ' - .

COMflMNOft NOTOII 0 ' - • ffl ,an ..

todtlftll FM 901111 . - .

l 'l,tNIMTOR l'M MJOI -•- IIDWIITPAl_,TOI -•- .. --· _,_ ll.lffllCtUIIIClt

CIIIClJII - \ ,.

I -

ClflCUn - z llllQlll•:t .. ,. ,.,. .. , IU ... ... "" ., '" ., .., ...... Nl'(A

Appendix A6 - Photos of Underground Storage Tank

Picture 13 - 500 Gallon Underground Storage Tank

Appendix B1 – Asbestos Certifications

TEXAS DEPARTMENT OF TATE HEALTH SERVICES

LPILA TERRA E C l EERl C L C u w11fo.f '" pr,f11rw J.S 41 be to Coowltaot Agent)' in 11' St,11,• 11/Tr;w, ,.,,hin thl' pur-.ic.,. of T, ,.,, On-u,,.111on1 Cr>d,• 1 lwpltr 1'154. 11 fong u.11h1.1 /uc,me u no, usp,·nded or TL'\'0/tru and u rrnri--.·J accordinr: 10 1hr rula udopu-,I bl' the TrWJ B0urJ of I lrnlth

JOI!' IIF.I I IRSllDT, MD

C-OMMLSSK>,tR Of llt.ALTH l icenx umber ~ hpirauon OJI.: 8 23 2019

Coo1rol Num~'t 970:?'i (\'ouJ After hp1rat1on Dale)

VOID If M.TE_llf.O NO .... TRANSFEAA81.E

Health Services

Asbestos Individual Consultant

EARL C MCINTOSH

License No. 105518 Control No. 97108 Expiration Date: 11/8/2018

Health Services

Asbestos Inspector

ALEXANDER JACKSON

L1cenff No. 602759 Control No. ga,21 exp rat on Date: 10/16/2018

Appendix B2 – Lead Certification

TE DEPARTME or TAT HE LTH ERVlCE

Bt• it Ano"'" 1ha1

TRI .\ L \ll: LU:"1

1 ccrt11icd to pcrto,m iu •

Lnid Ruk sussor

,n the I.SIC of I CJtlll, and is bc:n:by go, cmcd b} the ri ht pm ii 111..S resp,, u, bil11i w t forth in T" Ocxupauons Code, Chapter 1955 and Title 25, Tc'l A1h111ni 1n1u,c Code, Chapter ~5 rclaun 10 Te, Ennronmca~ Lead Rcducnon, iu loog a.~ thi. h.:cn; 1 no1 uspeodcd or n!\.11 cJ.

VOID IF Al1£~0

John Hcllcrstcdt. !-1.D.

Comm, ,,one, ofHa'th

\'oiJ a- b pm1tJOC1 Date eo,,,...., Nambor '392

Appendix C1 – Laboratory Analytical Reports

Customer Project:

Reference #: Date: 1/15/2018

Analysis and Method

Discussion

Qualifications

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

Materials Characterization - Bulk Asbestos Analysis Laboratory Analysis Report - Polarized Light

Alpha Terra Engineering Inc

8626 Tesoro Dr, Suite 810

San Antonio, TX 78217 S171019-232, Building 1160 Kelly/Lackland Field

CAL1801134AG

Summary of polarized light microscopy (PLM / Stereomicroscopy bulk asbestos analysis) using the methods described in 40CFR Part 763

Appendix E to Subpart E (Interim and EPA 600 / R-93 / 116 (Improved). The sample is first viewed with the aid of a stereomicroscope. Numerous liquid slide preparations are created for analysis under the polarized microscope where identifications and quantifications are preformed. Calibrated liquid refractive oils are used as liquid mouting medium. These oils are used for identification (dispersion staining). A calibrated visual estimation is reported, should any asbestiform mineral be present. Other techniques such as acid washing are used in conjugation with refractive oils for detection of smaller quantities of asbestos. All asbestos percentages are based on calibrated visual estimation traceable to NIST standards for regulated asbestos. Traceability to measurement and calibration is achieved by using known amounts and types of asbestos from standards where analyst and laboratory accuracy are measured. As little as 0.001% asbestos can be detected in favorable samples, while detection in unfavorable samples may approach the detection limit of 0.50% (well above the laboratory definition of trace).

Vermiculite containing samples may contain trace amounts of actinolite/tremolite. When not detected by PLM, these samples should be analyzed using TEM methods and / or water separation techniques. Suspected actinolite/vermiculite presence will be indicated through the sample comment section of this report.

Fibrous talc containing samples may contain a regulated asbestos fiber known as anthophyllite. Under certain conditions the same fiber may actually contain both talc and anthophyllite (a phenomenon called intergrowth). Again, TEM detection methods are recommended. CA Labs PLM report comments will denote suspected amounts of asbestiform anthophyllite with talc, where further analysis is recommended.

Some samples (floor tiles, surfacings, etc.) may contain fibers too small to be delectable by PLM analysis and should be analyzed by TEM bulk protocols.

AIHA LAP, LLC Laboratory #102929

A "trace asbestos" will be reported if the analyst observes far less than 1% asbestos. CA Labs defines "trace asbestos" as a few fibers detected by the analyst in several preparations and will indicate as such under these circumstances.

Since allowable variation in quantification of samples close to 1% is high, <1% may be reported. Such results are ideal for point counting, and the technique is mandatory for friable samples (NESHAP, Nov. 1990 and clarification letter 8 May 1991) under 1% percent asbestos or "trace asbestos".

In order to make all initial PLM reports issued from CA Labs NESHAP compliant, all <1% asbestos results (except floor tiles) will be point counted at no additional charge.

CA Labs is accredited by the National Voluntary Accreditation Program (NVLAP) for selected test methods for airborne fiber analysis (TEM), and for bulk asbestos fiber analysis (PLM). CA Labs is also accredited by AIHA LAP, LLC. in the PLM asbestos field of testing for Industrial Hygiene. All analysts have completed college courses or hold a degree in a natural science (geology, biology, or environmental science). Recognition by a state professional board in one these disciplines is preferred, but not required. Extensive in-house training programs are used to augment the educational background of the analyst. The Laboratory Director and Quality Manager have received supplemental McCrone Research training for asbestos identification. Analysis performed at Crisp Analytical Labs, LLC 1929 Old Denton Road Carrollton, TX 75006

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

Labs

A

C

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 1 of 11

Overview of Project Sample Material Containing Asbestos

Customer Project: S171019-232, Building 1160 Kelly/Lackland Field CA Labs Project #: CAL1801134AG white floor tile white caulking gray sealant green floor tile black mastic

Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

Sample # Layer

Analysts Physical Description of

Subsample

Asbestos type / calibrated visual estimate percent

List of Affected Building

Material Types

White 12x12 Floor Tile and

Mastic/ white floor tile

232-034 34-1

White 12x12 Floor Tile and

Mastic/ white floor tile 3% Chrysotile

Window Glazing/ white caulking

3% Chrysotile

232-036 36-1

White 12x12 Floor Tile and

Mastic/ white floor tile 3% Chrysotile

232-035 35-1

Window Glazing/ white caulking

4% Chrysotile

232-041 41-1

Window Glazing/ white caulking 4% Chrysotile

232-040 40-1

HVAC Caulk/ gray sealant

4% Chrysotile

232-043 43-1 HVAC Caulk/ gray sealant 8% Chrysotile

232-042 42-1

8% Chrysotile

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)

232-044 44-1

This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 2 of 11

Overview of Project Sample Material Containing Asbestos

Customer Project: S171019-232, Building 1160 Kelly/Lackland Field CA Labs Project #: CAL1801134AG

Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

Sample # Layer

Analysts Physical Description of

Subsample

HVAC Caulk/ gray sealant

Asbestos type / calibrated visual estimate percent

List of Affected Building

Material Types black mastic

8% Chrysotile

232-058 58-1

12x12 Green Tile and Mastic/ green floor tile 4% Chrysotile

232-045 45-1 black mastic

3% Chrysotile

232-059 59-1

12x12 Green Tile and Mastic/ green floor tile 4% Chrysotile

58-2 black mastic

3% Chrysotile

232-060 60-1

12x12 Green Tile and Mastic/ green floor tile 4% Chrysotile

59-2

3% Chrysotile

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)

60-2

This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 3 of 11

Polarized Light Asbestiform Materials Characterization

Customer Info: Attn: Customer Project:

1/15/2018

1/9/18 11:00AM

Phone # 1/3/2018

Fax #

Tanner Rasmussen Senior Analyst

Analyst Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Alpha Terra Engineering Inc

S171019-232, Building 1160

Kelly/Lackland Field

CAL1801134AG

8626 Tesoro Dr, Suite 810

San Antonio, TX 78217 Date:

Turnaround Time: Samples Received:

210-325-3641 5 days Date Of Sampling:

210-654-3802 Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

232-028 28-1

Sheetrock, Joint Compound/ off-white surfaced white compound n None Detected 100% mi,bi,ca

28-2 white drywall with brown paper n None Detected 22% ce 78% qu,gy

232-029 29-1

Sheetrock, Joint Compound/ off-white surfaced white compound n None Detected 100% mi,bi,ca

29-2 white drywall with brown paper n None Detected 24% ce 76% qu,gy

232-030 30-1

Sheetrock, Joint Compound/ off-white surfaced white compound n None Detected 100% mi,bi,ca

30-2 white drywall with brown paper n None Detected 23% ce 77% qu,gy

232-031 31-1

Tank TSI/ off-white sealant with foil and paper n None Detected

14% fg

14% ce 72% qu,bi,ot

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Robert Olivarez Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

10. TEM analysis suggested

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 4 of 11

1/15/2018

1/9/18 11:00AM

Phone # 1/3/2018

Fax #

Tanner Rasmussen Senior Analyst

Analyst Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Alpha Terra Engineering Inc

S171019-232, Building 1160

Kelly/Lackland Field

CAL1801134AG

8626 Tesoro Dr, Suite 810

San Antonio, TX 78217 Date:

Turnaround Time: Samples Received:

210-325-3641 5 days Date Of Sampling:

210-654-3802 Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

232-032 32-1

Tank TSI/ off-white sealant with foil and paper n None Detected

13% fg

11% ce 76% qu,bi,ot

232-033 33-1

Tank TSI/ off-white sealant with foil and paper n None Detected

14% ce

15% fg 71% qu,bi,ot

232-034 34-1

White 12x12 Floor Tile and

Mastic/ white floor tile y 3% Chrysotile 97% qu,ca

34-2 black mastic y None Detected 100% gy,bi

232-035 35-1

White 12x12 Floor Tile and

Mastic/ white floor tile y 3% Chrysotile 97% qu,ca

35-2 black mastic y None Detected 100% gy,bi

232-036 36-1

White 12x12 Floor Tile and

Mastic/ white floor tile y 3% Chrysotile 97% qu,ca

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Robert Olivarez Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 5 of 11

1/15/2018

1/9/18 11:00AM

Phone # 1/3/2018

Fax #

Tanner Rasmussen Senior Analyst

Analyst Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Alpha Terra Engineering Inc

S171019-232, Building 1160

Kelly/Lackland Field

CAL1801134AG

8626 Tesoro Dr, Suite 810

San Antonio, TX 78217 Date:

Turnaround Time: Samples Received:

210-325-3641 5 days Date Of Sampling:

210-654-3802 Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

36-2 black mastic y None Detected 100% gy,bi

232-037 37-1

Ceiling Tile Small Hole/ tan ceiling tile y None Detected

38% ce

37% fg 25% qu,pe,ot

232-038 38-1 Ceiling Tile/ white surfacing y None Detected 100% qu,bi

38-2 tan ceiling tile y None Detected

38% ce

38% fg 24% qu,pe,ot

232-039 39-1 Ceiling Tile/ white surfacing y None Detected 100% qu,bi

39-2 tan ceiling tile y None Detected

37% ce

36% fg 27% qu,pe,ot

232-040 40-1

Window Glazing/ white caulking y 4% Chrysotile 96% qu,bi,ca

Dallas NVLAP Lab Code 200349-0…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .