W9126G21R0037-Drawings_Part5.pdf
PDF 7 MB Posted
- Attached to
- Fort Hood Fuel Facility Replacement
- Solicitation number
- W9126G21R0037
About this file
This solicitation is for a firm-fixed price construction contract to build a new Type III Hydrant System at Fort Hood, Texas. Work includes constructing new above ground fuel storage tanks, a pump shelter with control room, a product recovery tank, truck loading points with a combined hydrant hose truck checkout stand, truck unloading points, spill containment, and supporting facilities. A new aircraft direct fuel system will supply a new parking apron at Robert Gray Army Airfield. Construction value ranges from $25-100 million. Responses are due September 10, 2021 unless extended. The contract will be awarded September 30, 2021.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMPRESSION RING (NOTE 7)
TENSION RING AT
TOP OF TANK
TANK SHELL
SHELL STIFFENER PLATE (AS
REQUIRED TO RESIST BUCKLING
OF SHELL PLATE DUE TO VERTICAL
LOADS AND THERMAL MOVEMENT
OF ROOF PLATE)
" ROOF PLATE
(NOTE 4)
ROOF GUARDRAIL (NOTE 2)
W x
R
A
F
T
E
R
E
Q
U
A
L
L
Y
S
P
A
C
E
D
(NOTE 3)
T
Y
P
BOTTOM
PLATFORM
CIRCUMFERENTIAL STAIR
℄ INTERMEDIATE
PLATFORM
STAIRWAY SUPPORT
1'-9" 1'-9"
RAFTER (TYP) (NOTE 6)
NOTE: STAIRCASE LAYOUT IS FOR REFERENCE
ONLY. SEE MT401 FOR EXACT PLATFORM
LOCATION AND DETAILS
0°
90°
180°
270°
RAFTER (TYP)
COMPRESSION
RING
TANK SHELL
STEEL PLATE TANK
BOTTOM t=0.3125"
SEE NOTE 5
44'-0" I.D.
TENSION RING
6'-0"
S H
E L L
T
H I C
K N
E S
S t t t t
FLOATING PAN
1/4" ROOF PLATE
(NOTE 4)
RAFTER (TYP)
SHELL STIFFENER
CONTAINMENT
BASIN
SEE CIVIL
ROOF PLATE
RIM ANGLE
TANK SHELL
6'-0" ±
℄ TANK ROOF
HSS OR W SHAPE RAFTER (HS SHOWN)
RAFTER-COMPRESSION
RING CONNECTION
RAFTER-SHELL
CONNECTION
COMPRESSION RING
HSS RAFTER
OR W SHAPE
ROOF PLATE
PROVIDE WELDED MOMENT
CONNECTION AT
COMPRESSION RING (TYP)
VENT HOLE
RIM ANGLE
DO NOT STIFFEN
SHELL WITHIN 6"
OF TOP OF ANGLE
CONTINUOUS ANGLE TENSION RING, MIN 10'-0"
SECTIONS, WELD SIMILAR TO SHELL PLATES
ROOF PLATE SITS DIRECTLY ON RAFTERS.
ALL RAFTER BRACING SHALL BE LOCATED
BELOW ROOF PLATE AND TOP OF RAFTER
HSS OR W SHAPE RAFTER
(BRACE AS REQUIRED)
SEAL END OF HSS RAFTER
WITH WELDED END PLATE
PROVIDE SHEAR PLATE EACH SIDE OF
HSS RAFTER (WELDED CONNECTION)
OR PROVIDE BOLTED CONNECTION AS
DESIGNED BY TANK MANUFACTURER
RAFTER SEAT, SHIM TO PROVIDE FULL
BEARING BENEATH RAFTER (PROVIDE
AS REQUIRED)
TANK SHELL
SHELL STIFFENER PLATE AS REQUIRED
TO RESIST BUCKLING OF SHELL PLATE
DUE TO VERTICAL DEAD AND LIVE LOADS
SEE NOTE
TYP
B3
CROSS SECTION
SCALE: 1/4" = 1'-0"
B1
6K BBL TANK ROOF PLAN
SCALE: 1/4" = 1'-0"
NOTES:
1. SEE MECHANICAL DRAWINGS FOR SIZE, ELEVATION AND ORIENTATION OF
NOZZLES AND APPURTENANCES.
2. PROVIDE GUARDRAIL ALL AROUND PERIMETER OF ROOF EXCEPT AT
STAIRWAY TOP PLATFORM.
3. PROVIDE 6"x18" OPENING IN INTERMEDIATE LANDING FOR PIPING AND
CONDUIT.
4. LAP ROOF PLATE SEAMS TO SHED WATER (INNER PLATES ON TOP).
5. PROVIDE A ROOF WITH SLOPE 1 1/2:12.
6. COORDINATE ROOF OPENING LOCATIONS WITH ROOF RAFTERS TO AVOID
INTERFERENCE. RAFTER SIZE SHOWN IS FOR BIDDING PURPOSE.
7. MITER AND PROVIDE FULL PENETRATION WELDED MOMENT CONNECTION
AT COMPRESSION RING.
SCALE: 1/4" = 1'-0"
4 0 4 8
S
T
B
F I
E
N
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
U M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
C
O
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
F
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODESENG I NEER
REGISTERED
No. SE000413
ST102
O P
E R
A T
I N
G
T
A N
K
R
O O
F
P
L A
N
A
N D
E L
E V
A T
I O
N
K R
K R
H D
R A
C
F H
S
T D
W G
A1
SECTION 1
SCALE: 3/4" = 1'-0"
B5
RAFTER COMPRESSION RING CONNECTION
SCALE: 1" = 1'-0"
A3
RAFTER-SHELL CONNECTION
SCALE: 3/4" = 1'-0"
℄ SUMP
SLOPE 1:50
TANK BOTTOM (NOTE 1)
FML SUMP LEAK
DETECTION
K
B
B
N
K
TOP OF RINGWALL
SAND
SLOPE 1:50
FML
4" FRP LEAK DETECTION
TELL-TALE PIPE
2" PVC CP/TRACER PIPE
TOP OF RINGWALL
TANK BOTTOM
SLOPE 1:50
1'-0"
MONITORING WELL RISER,
4" SCH 80 PVC PIPE
CONTAINMENT BASIN
SEE CIVIL
FML OVER TOP OF
GEOTEXTILE FABRIC
RINGWALL
RINGWALL
ST302
A3
ST301
B1
SELF-ANCHORED (UNANCHORED TANK)
1/2" BUNA-N TANK BOTTOM
TO FOUNDATION GASKET
(PER SPEC)
POLYSULFIDE MASTIC
SEALANT CAULK. DO NOT
CAULK END OF CHIME
TOP OF CONCRETE
RINGWALL FOUNDATION
TANK SHELL
TANK BOTTOM
SLOPE DOWN 5%
SET HIGH POINT OF RINGWALL AT CENTER OF
RINGWALL. SET SHELL DIRECTLY ON HIGH POINT OF
RINGWALL
ANNULAR RING PLATE
(NOTE 2)
PAINT PER
SPECIFICATION
POLYSULFIDE MASTIC SEALANT
CAULK. DO NOT CAULK END OF
CHIME.
SLOPE DOWN 5%
2" CHIME WIDTH
CONCRETE TANK APRON
SET TOP OF CONCRETE
TANK APRON 1'-0" BELOW
TOP OF RINGWALL
REINFORCE AS REQUIRED
TANK SHELL
SET HIGH POINT OF RINGWALL AT
CENTER OF RINGWALL.
SET SHELL DIRECTLY ON HIGH POINT OF
RINGWALL
TANK BOTTOM
C1
TANK FOUNDATION CROSS SECTION
SCALE: 1/4"=1'-0"
SCALE: 1 1/2" = 1'-0"
01 1
SCALE: 1/4" = 1'-0"
4 0 4 8
NOTES:
1. ON SIDE FURTHER MOST FROM SUMP, SLOPE TANK BOTTOM FROM SHELL TO
OFF-CENTER SUMP AT A SLOPE OF NOT LESS THAN 1:20. SEE TANK ELEVATION FOR
TOP OF SUMP ELEVATION.
2. ANNULAR RING PLATES SHALL BE MINIMUM 30" WIDE, PLATES SHALL BE BUTT
WELDED PER API 650
3. FOR FOUNDATION CONSTRUCTION, THE USAGE OF FAT CLAYS IS RESTRICTED FOR
BACKFILL PURPOSE.
B1
SELF ANCHORED TANK BOTTOM-TO-FOUNDATION GROUTING
SCALE: 1 1/2"=1'-0"
A1
RINGWALL
SCALE: N.T.S.
A3
DETAIL
SCALE: NTS
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODESENG I NEER
REGISTERED
No. SE000413
ST301
T A
U
N D
A T
I O
N
S
E C
T I O
D
D E
T A
I L
S
K R
K R
H D
R A
C
F H
S
T D
W G
GRAPHIC SCALES
TANK BOTTOM
℄ SUMP
FML LINER ABOVE
GEOTEXTILE FABRIC
SUMP AND PIPING
C1
MT503
1'-3"
V A
R I E
S
2'-0"
3'-4"
℄ TANK
4'-0"
GEOTEXTILE
FABRIC
FRP COUPLING FRP CAP
FML
PENETRATION
4" FRP WELL SCREEN WRAPPED WITH
FILTER FABRIC WRAP AND (2) NYLON TIE
STRAPS AT EACH END
ST302
A1
30" EXTRA STRONG
WELD CAP
CONTINUOUS BEAD OF ADHESIVE SEALANT, 360° AROUND
INTERIOR OF CONCRETE RINGWALL AND AROUND COLUMN
SUPPORT FOUNDATIONS
GEOTEXTILE FABRIC
1/4" THICK x 2" WIDE ALUMINUM MOUNTING STRIP, 360°, WITH HOLES @ 1'-0" OC
3/8" Ø GALVANIZED ANCHOR BOLTS W/NUTS @ 1'-0" OC
GALVANIZED WASHER
1/8"x2-40 DUROMETER BUNA-N GASKET
FML
3/8" MIN
PROVIDE 3" OF SLACK IN FML AT RINGWALL BELOW
PENETRATIONS
4" THREADED SS
COUPLING (TYP)
RINGWALL FOUNDATION
CONTAINMENT DIKE BASIN
SEE CIVIL
4" SS LEAK DETECTION
TELL-TALE PIPE
HINGED, LOCKABLE COVER
8" SS CASING PIPE. EMBED 16"
MINIMUM INTO FOUNDATION AND
FILL VOID WITH GROUT
LEAK DETECTION WELL 4" SCH 40
304 SS PIPE AND FITTINGS
4" FRP LEAK DETECTION
TELL-TALE PIPE
RINGWALL
FML
GEOTEXTILE FABRIC
TANK BOTTOM
TANK SHELL
FILTER FABRIC WRAP
RINGWALL PENETRATION
1'-6"
WELLSCREEN
SOLID PVC
6"
2" PVC CP/TRACER PIPE PER
SPEC 33.56.13.15
NYLON ZIP TIE
2'-0"
FML PENETRATION
SELF ANCHORED
TANK BOTTOM FOUNDATION
ST301
B1
ST302
A1
ST-302
C2
RINGWALL REINF
(3) #4 VERTICAL BARS(3) #4 VERTICAL BARS
#4 HAIRPIN BARS SPACE
TO MATCH RINGWALL
HORIZONTAL BARS EXTEND TO
INSIDE FACE OF RINGWALL
4" SS PIPE SLEEVE
2" NPT GALV
PIPE CAP
2"x4" LINK SEAL
2" SS PIPE LONG
THREAD BOTH ENDS
2" PVC NPT CPLG
TANK SHELL
FML
2" PVC COMBINATION CP
REFERENCE SLIDER
TUBE AND TRACER GAS
LEAK DETECTION PIPE
TANK BOTTOM
LINER ANCHOR
TO CONCRETE
FML PENETRATION
(2) SS BAND CLAMPS
SAND
ST302
C4
ST302
A1
(2) SS CLAMPS
CATHODIC PROTECTION SYSTEM CONDUIT
1/8"x2"-40 DUROMETER BUNA-N GASKET
FML
GEOTEXTILE FABRIC
FUEL RESISTANT SEALANT
FML PENETRATION BOOT
SAND
NOTE:
FML PENETRATION SHOWN IS FOR THE CATHODIC PROTECTION SYSTEM CONDUIT. THE FML
PENETRATIONS FOR THE CP REFERENCE SLIDER TUBES, THE TRACER GAS LEAK DETECTION PIPES, AND
THE LEAK DETECTION TELL-TALE PIPE ARE SIMILAR.
PROVIDE 3" OF SLACK IN FML AT
RINGWALL BELOW PENETRATIONS
2" SCH 40 SOLID PVC PIPE
RINGWALL
PENETRATION
FML
GEOTEXTILE FABRIC
10'-0"±
NYLON TIE STRAP
FILTER FABRIC WRAP
2" PVC COUPLING
(LEAVE END OPEN)
ST302
C2
C1
FML SUMP LEAK DETECTION
SCALE: 1/2"=1'-0"
C2
RINGWALL PENETRATION
SCALE: 1 1/2"=1'-0"
C4
LINER ANCHOR TO CONCRETE
SCALE: N.T.S.
A2
LEAK DETECTION
SCALE: 1"=1'-0"
A1
FML PENETRATION
SCALE: N.T.S.
SCALE: 1 1/2" = 1'-0"
01 1
SCALE: 1" = 1'-0"
1 0 1 2
SCALE: 1/2" = 1'-0"
2 0 2 4
A4
LEAK SIMULATION PROBE
SCALE: 1 1/2"=1'-0"
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODESENG I NEER
REGISTERED
No. SE000413
ST302
T A
U
N D
A T
I O
N
S
E C
T I O
D
D E
T A
I L
S
K R
K R
H D
R A
C
F H
S
T D
W
SEE DETAIL A2 ON THIS
DWG. FOR LINER
ANCHORAGE DETAIL TO
CONCRETE
CONTAINMENT
LINER
APPLY LINER SEALANT
TO ENSURE PROPER
SEAL
CONCRETE
WALL OR RING
WALL
CONTAINMENT
LINER
1/4" THICK x 2" WIDE
ALUMINUM MOUNTING STRIP,
360°, WITH HOLES @ 1'-0" OC
3/8"Ø GALVANIZED ANCHOR
BOLTS W/NUTS @ 1'-0" OC
GALVANIZED WASHER
1/8"x2-40 DUROMETER BUNA-N
GASKET
NOTES:
1. INSTALL PER MANUFACTURER'S
SPECIFICATIONS
APPLY LINER SEALANT
TO ENSURE PROPER
SEAL
FLEXIBLE
MEMBRANE LINER
TOP OF CONCRETE
O.C. ALTERNATE
AT 180°
BOTT. HOOK
#4 AT 1'-0"
SEE CIVIL DWG.
LINER AND SAND BEDDING
3-#4
NOTE:
CONTINUOUS
#4 AT 6" O.C.
1. SEE CIVIL DWG FOR LOCATION OF DIKE WALLS.
LINER ANCHORAGE
M I N
3. SEE A1/ST501 FOR REQUIREMENT OF CONTROL/CONSTRUCTION
JOINTS OF DIKE WALLS.
2. SEE ST101 FOR ADDITIONAL NOTES.
8"
2'-4"
#5 @ 12" EA. FACE
CL. BM.
I S
S U
E
L
I N
E
F
I L
L
L
I N
E
SEE CIVIL DWG.
ST501
A3
TOP OF PIER
(9) #6
(STANDARD HOOK AT BOTH ENDS
& EXTEND MIN 1'-3" INTO RING WALL)
PIPE SUPPORT
PIER, SEE B1/ST-501
FOR REINFORCEMENT
OH
RING WALL
EXTENSION
BOT OF TANK SHELL
ST501
B2
PIPE ANCHOR
BASE PLATE
ALTERNATE HORIZ. BARS
DISCONTINUOUS
2"x4" KEY & 6" JET FUEL RESISTANT
ELASTOMERIC WATERSTOP
6" JET FUEL RESISTANT
ELASTOMERIC WATERSTOP
1/2" x 3/4" CONTINUOUS
RUSTICATION FILL
WITH FUEL RESISTANT
SEALANT EA. SIDE
CONTROL JOINT - 30' MAX SPACING
1/2" x 3/4" CONTINUOUS
RUSTICATION FILL
WITH FUEL RESISTANT
SEALANT EA. SIDE
CONSTRUCTION JOINT (OPTIONAL)
LAP
NOTE: SECURE WATERSTOP TO REBARS USING
WIRE TIES AND HOG RINGS
#3 TIES @ 1.5" O.C. AT TOP 3
@ 8" OC, TYP
1'-6"
(9) #5
(STANDARD HOOK AT TOP
& EXTEND MIN 12" INTO CAP
PLUS HOOK)
PIPE SUPPORT
ANCHOR BOLTS
ANCHOR DETAIL
14"x14"x1/2"
BASE PLATE,
GALVANIZED
1"x1 3/8" SLOT
TYP.
7/8"Ø ANCHOR BOLTS, 18" MIN
EMBEDMENT WITH WASHER,
GALVANIZED
TYPICAL
ST504
C3
GSE POLYLOCK OR
APPROVED EQUAL
(SET IN CONCRETE)
CONCRETE
EXTRUSION WELD
MEMBRANE LINER
SEE CIVIL
1'-3"
TYP. RINGWALL
(STANDARD HOOK AT BOTH ENDS
EXTEND MIN 1'-3" INTO RING WALL)
S E
E
S C
H E
D U
L E
S
H E
M
PROVIDE SHORT SLOTTED
BOLT HOLES ALONG PIPE AXIS
SEE MECH.
#5 @ 12" EA. FACE
(8) #6
(STANDARD HOOK
AT BOTH ENDS
EXTEND MIN 1'-3"
INTO RING WALL)
TYP. RINGWALL
PIPE SUPPORT
ANCHOR BOLTS
#3 TIES @ 2" O.C. AT TOP 3
@ 8" OC, TYP
(7) #5
(STANDARD HOOK AT
TOP & EXTEND MIN 12"
INTO CAP PLUS HOOK)
SEE PLAN
3" CL.
Scale: Scale:
Scale:Scale:
Scale:
SCALE: 1/2" = 1'-0"
2 0 2 4
Scale:
SCALE: 3/4" = 1'-0"
1 0 31 2
Scale:
Scale:
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODESENG I NEER
REGISTERED
No. SE000413
ST501
T A
N
T A
I N
M E
E
A
T
Y P
D E
T A
I L
S
K R
K R
H D
R A
C
F H
S
T D
W G
Scale:
Scale:
ST501
B3
TANK SHELL
TANK ROOF (4 SIDES)
WELD WATER CURB TO
1'-6" HOLE6"
SIDE COVER FOR
AIRSCOOP, 18 GA SS
HANDLE, 10"x1"x18 GA SS, WELDED IN PLACE
TOP COVER FOR
AIR SCOOP, 18 GA SS
CORROSION-RESISTANT SCREEN,
3/4" FLATTENED EXPANDED METAL
(ASTM F1267)
TANK SHELL
TANK ROOF
PERIMETER ROOF
GUARDRAIL
TANK ROOF
GUARDRAIL POST
PIANO HINGE,
1"x1" (2" OPEN WIDTH) x 24"x16 GA SS
1'-6" HOLE
WELDED
IN PLACE
ROOF PERIMETER GUARDRAIL
(BEYOND)
6"
PROVIDE 3/16" GALV CHAIN BETWEEN POSTS AT
VENT AS A REMOVEABLE, INTERMEDIATE RAIL WITH
ONE END WELDED TO POST AND ONE END HOOKED
TO THE OTHER POST
AIRSCOOP FRAME, L 1 1/2"x1 1/2"x3/16" SS WATER
CURB
KEEPER PLATE, SS, (2) REQUIRED
LINK LOCK, SS, (2) REQUIRED
NOTE: AIR SCOOP NOT SHOWN FOR CLARITY.
3'-0"
REINFORCING PLATE
REINFORCING PLATE
L 1 1/2"x1 1/2"x3/16" WATER CURB
3/16
1/4
TYP
ST503
A5
ST503
A5
2 1/2"x1/2" FLAT BAR
TANK ROOF
5'-0" x 6'-0" REINFORCING PLATE
1/2" U-BOLT FOR 5" PIPE (OVERSIZED).
TIGHTEN NUTS TO ANGLE. DO NOT TIGHTEN
U-BOLTS TO LADDER RAILS, TYP
5/8"Ø BAR, BENT FOR
HAND GRIP (TYP OF 2)
1/2"x3 1/2" LONG EYEBOLT
(SHOWN IN UNLATCHED POSITION)
5/8" WING NUT W/WASHER
1'-5"
3/4" BOLT
2"x3/8" FLAT BAR
(2 REQD)
1/2" BOLT
KEEPER BAR
NUT (TYP)
L 2"x2"x1/4"
3'-0"
I N
S I D
E
11 1/4" 11 1/4"
SAFETY RAIL
3 1/16"
3 1/16"
PLAN
SECTION A-A
4"
1'-6"
3/4"
SAFETY RAIL
3"
(TYP)
RIM ANGLE
2"
(TYP)
PERIMETER OF
ROOF PLATE
AA
2"x3/8" ⅊ (2
REQD)
BONDING
STRAP
1/4" THICK PLATE
1 1/4" x 1/4" FLAT BAR (2) REQD
(KEEPER BAR)
L 2"x2"x1/4"
REINFORCING PLATE
5'-0"
ROOF PERIMETER GUARDRAIL
3'-6"x4'-6" GA COVER
PLATE
1/4
1/4
1/4
1 1/2"
1 1/4 WIDE x 2'-2" LONG, TINNED COPPER BRAID. BRAZE
TO MANHOLE COVER AND LUG
ST503
A5
ACCESS LADDER
3/4" EYE BOLT W/NUT & WASHER
(GALVANIZED)
5/16" PLATE
2'-1"
1/4" PLATE
5/8" HANDLE
(TYP)
SHELL MANHOLE DAVIT
MACHINE FINISH
UP STAIRS
DOWN STAIRS
2" XXS PIPE DAVIT
GREASE FITTING
REINFORCING PLATE
TANK SHELL
MANHOLE PLATE IS SHOWN CUT FOR
CLARITY. MANHOLE PLATE SHALL NOT BE
WELDED TO THE DAVIT HINGE
⅊ 1/2"x2"x18"
2 1/2" STD WT PIPE (TYP)
TYP
SHELL MANHOLE
COVER
34"Ø, 3/16" THICK PLATE DISC,
ROLL TO MATCH SHELL CURVATURE
12"x4" OPENING, TOP AND
BOTTOM
G A
P
24"Ø CYLINDER, 3/16"
THICK
36" MANHOLE
NOTE:
PROVIDE FILLER DRUM ON SHELL MANHOLES OF
TANKS WITH FLOATING PANS.
TYP
2-12
GRIND OFF INTERIOR CORNERS TO
" RADIUS
ALL AROUND
DAVIT
C1
CIRCULATION VENT/INSPECTION HATCH
SCALE: 1"=1'-0"
C4
SHELL MANHOLE DAVIT
SCALE: 3/4"=1'-0"
A1
ROOF MANHOLE/LADDER HATCH
SCALE: 1"=1'-0"
A4
FILLER DRUM
SCALE: 3/4"=1'-0"
SCALE: 1" = 1'-0"
1 0 1 2
SCALE: 3/4" = 1'-0"
1 0 31 2
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODESENG I NEER
REGISTERED
No. SE000413
ST502
T A
P
U R
T E
N A
N C
E
D
E T
A I L
S
K R
K R
H D
R A
C
F H
S
T D
W
STEEL ANGLE
STEEL CHANNEL
5/8" BOLTS (TYP)
3/8" PLATE (TYP)
GRATING
GUARDRAIL 1 1/2" SCH 40 PIPE
TANK ROOF
TANK SHELL
MOUNTING PLATE
TYP
TANK SHELL
TANK ROOF
4"x5/16" FLAT
BAR TOE BOARD
6"
6"x6"x5/16" PLATE
1 1/2" PIPE (TYP)
LEAVE OUT INTERMEDIATE
RAIL AT ROOF CIRCULATION
VENT INSPECTION HATCH
TANK SHELL
NOTE:
PROVIDE STAIRWAY SUPPORTS AS REQUIRED. SUPPORT
STAIRWAY ENTIRELY ON SHELL.
STEEL ANGLE
(TYP)
(2) 5/8" BOLTS
STEEL
ANGLE
STEEL PLATE
(TYP)
5/8" DIA BOLT
WITH NUT
(TYP)
(TYP)
LOCATE SUPPORTS NO MORE
THAN 8'-0" APART
6"x6"x1/4" PLATE (TYP)
TANK SHELL
(TYP)
(TYP)
8 1/2"
TANK
APRON
1 1/2" SCH 40 PIPE (TYP)
TANK MOUNTED
CIRCUMFERENTIAL
STAIRWAY
HANDRAIL
GUARDRAIL
SIDE ELEVATION
3"x3"x1/4" GROUNDING
LUG
#4 BARE COOPER WIRE TO TANK
GROUNDING SYSTEM
EXOTHERMIC WELD
GROUND CABLE TO
GROUNDING LUG
2"
CONCRETE APPROACH STAIRS
2"
COPPER GROUNDING BAR,
1/8"x1 1/4"x12" BRAZED TO
GUARDRAIL ALL AROUND.
CLEAN TO BARE COPPER
AFTER GALVANIZING
(2) 5/8" DIA BOLTS
TOP OF TANK
FOUNDATION
#4 @ 12" OC
TYP
(10) #4
1 1/2" SCH 40 PIPE
HANDRAIL
TANK FOUNDATION
TANK SHELL
GUARDRAIL
SUPPORT HANDRAIL AT EVERY POST
(MAXIMUM OF 8'-0" APART)
TANK MOUNTED
CIRCUMFERENTIAL
STAIRWAY
NOTE:
SUPPORT STAIRWAY ENTIRELY ON SHELL. (SUPPORTS NOT SHOWN ON DETAIL)
3"
2'-10
8"
END ELEVATION
HANDRAIL
POST
GUARDRAIL
SECTION A-A
1/4" STEEL PLATE
STRINGER (TYP)
4"
REPLACEABLE GALVANIZED BOLT-
ON STEP TREAD METAL BAR GRATING
WITH NON-SLIP NOSING (TYP)
TANK
APRON
CONCRETE APPROACH STAIRS
INSIDE PLATE
STRINGER
A A
GROUND WIRE
C1
PLATFORM SUPPORT
SCALE: 3/4"=1'-0"
C2
STAIRWAY SUPPORT
SCALE: 3/4"=1'-0"
C4
STAIRWAY SECTION
SCALE: 3/4"=1'-0"
A1
SECTION - CIRCUMFERENTIAL STAIR
SCALE: 3/4"=1'-0"
A5
ROOF PERIMETER GUARDRAIL
SCALE: 1"=1'-0"
ST-503
C4
SCALE: 1" = 1'-0"
1 0 1 2
SCALE: 3/4" = 1'-0"
1 0 31 2
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODESENG I NEER
REGISTERED
No. SE000413
ST503
T A
A
I R
W A
Y
A
D
A
R D
R A
I L
D E
T A
I L
S
K R
K R
H D
R A
C
F H
S
T D
W
BASE PLATE
1" GROUT
TEFLON SECURED TO
SADDLE SUPPORT
(TYP.)
PIPE
S E
E
C
I V
I
D
A
W I N
G S
ADJUSTABLE PIPE SADDLE SUPPORT
1'-8"
SEE A1/ST501
#3 TIES @ 12" O.C.
(6)- #7
EL. VARIES
SEE CIVIL
(4) 1/2"Ø EXPANSION ANCHOR
WITH 5" MIN EMBEDMENT
#3 TIES IN TOP 5" (TOTAL OF 3)
8x8x1/2"
BASE PLATE
EXPANSION ANCHOR
T
Y P
1 1/4" TYP
Ø
(6) VERTICAL
BARS
TIE
BASE PLATE
1" GROUT
TANK APRON, SEE CIVIL
(4) 1/2"Ø EXPANSION ANCHOR
WITH 3 1/2" MIN EMBEDMENT
4" PIPE
NOTES:
1. SEE GENERAL NOTES ON DWG. ST101.
2. FOR LOCATION OF PIPE SUPPORTS SEE MECHANICAL DWG MTXXX MTXXX, &
MTXXX.
3. ALL ADJUSTABLE PIPE SADDLE SUPPORTS SHALL BE COATED PER PIPE
SPEC, AND SHALL BE SELECTED AND INSTALLED PER MANUFACTURER'S
RECOMMENDATIONS.
4. ALL BASE PLATE SHALL BE ASTM A36. ALL BASE PLATES SHALL BE COATED
PER PIPE SPEC. ANCHOR BOLTS & NUTS SHALL BE GALVANIZED.
ST504
A3
ST504
A1
SCALE: 3/4" = 1'-0"
1 0 31 2
ST504
A1
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D
2 3
C
4 5
A
B
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L O
T
S
C A
L E
P
L O
T
D
A T
E
S M
B L
D E
S C
R I P
T I O
N
C O
N T
R A
SHEET
IDENTIFICATION
D A
T E
A P
P R
US Army Corps of Engineers
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
O M
A H
A
N
E B
R A
S K
A
A N
S I
D
OMAHA DISTRICT
S E
A L
F U
E L
S
F
A C
I L
I T
Y
R
E P
L A
C E
M E
N
R
T
H
O O
D
K
I L
L E
E N
T
E X
A S
R
READY TO ADVERTISE
S O
L I C
I T
A T
I O
N
N
O
D A
T E
W
G
R
J U
STRUCTURAL
G EORG I A
PH
I L I P D . RHODES
ENG I NEER
REGISTERED
No. SE000413
ST504
P I P
E
S
U P
P O
R T
S
I
N
K
C O
N T
A I N
M E
E
A
K R
K R
H D
R A
C
F H
S
T D
W
GRAPHIC SCALE
HYDRANT PIT #2
HYDRANT PIT #3 HYDRANT PIT #4
HYDRANT PIT #5
HYDRANT PIT #6
10" SS HYDRANT
LOOP FUEL LINES
M
FS
FS
PS
PS
F S
F S
F S
S
F
PS
M-404
TRUCK FILLSTAND
POSITION #2
TRUCK FILLSTAND
POSITION #1
HYDRANT
PIT #1
10" SS HYDRANT
LOOP FUEL LINES
4,000 GALLON ABOVEGROUND
PRODUCT RECOVERY TANK
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
2 3
C
4 5
A
B
FI
LE
N U
M
BE
R
SI
ZE
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
SM
BL
D
ES
C
R
IP
TI
O
N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
O M
AH
A
D
IS
TR
IC
T O
M
AH
A, N
EB
R
AS
KA
AN
SI
D
OMAHA DISTRICT
SE
AL
FY
D
ES
C
R
EP
LA
C
E R
EF
U
EL
IN
G F
AC
IL
IT
IE
S/ R
EQ
U
IR
EM
EN
TS
D O
C U
M
EN
T
FO
R T
H O
O D
, T
EX
AS
R
READY TO ADVERTISE
SO
LI
C
IT
AT
IO
N N
O
D
AT
E:
W
-G
-2 1-
R -0
JU
LY
EC-101
O
VE
R
AL
L C
AT
H
O D
IC
P
R O
TE
C
TI
O
N
PL
AN
N .W
IL
LI
AM
S
N .W
IL
LI
AM
S
J.
M
AG
G
AR
T
SU
BM
IT
TE
D B
Y:
C
. L
AY
SO
N
FH
_E C
-1
.D W
G
GRAPHIC SCALE
2 OVERALL CATHODIC PROTECTION PLAN
1" = 60'-0"
1 OVERALL CATHODIC PROTECTION PLAN
1" = 60'-0"
FO
R
CO
NT
IN
UA
TI
ON
S
EE
M
AT
CH
LI
NE
FO
R
CO
NT
IN
UA
TI
ON
S
EE
M
AT
CH
LI
NE
60'
1" = 60'- 0"
120'60'030'
SEE SHEET EC-103
FOR TANK 2 CATHODIC
PROTECTION .
SEE SHEET EC-103
FOR TANK 1 CATHODIC
PROTECTION
NOTES:
1. INSTALL MONITORING TEST STATIONS EVERY 200 FEET ALONG PIPE AS SHOWN THIS SHEET.
2. INSTALL FLANGE ISOLATION KITS WHERE SHOWN IN MECHANICAL DRAWING & AT ANY OTHER LOCATIONS
DEEMED NECESSARY BY THE PROJECT CATHODIC PROTECTION SPECIALIST.
3. FLANGE ISOLATION KITS ARE REQUIRED ANYWHERE UNDERGROUND FUEL PIPES CONNECT TO ABOVE GROUND
PIPE OR GROUNDED EQUIPMENT IN VAULTS.
4. FUEL PIPE MUST PASS THROUGH CONCRETE VAULT WALLS AND SLABS IN METALLIC SLEEVES WITH INSULATING
LINK SEALS TO INSULATE THE FUEL PIPE FROM REBAR & STRUCTURAL METAL.
5. INSULATE STEEL FUEL PIPE FROM METAL PIPE STANDS USING PHENOLIC AND NEOPRENE PADS AS NECESSARY.
6. ALL PIPE MUST BE INSTALLED IN SUCH A MANNER THAT IT DOES NOT CONTACT OTHER METALLIC
STRUCTURES SUCH AS ELECTRICAL GROUNDS, STRUCTURAL STEEL,.
7. INSTALL RECTIFIERS, ANODE TERMINAL BOXES AND NEGATIVE BOND BOXES WHERE SHOWN.
8. PULL 115/230 VAC FROM PUMP HOUSE TO RECTIFIERS.
9. INSTALL ANODES IN APPROXIMATE LOCATION SHOWN.
10. MINIMUM HORIZONTAL SEPARATION DISTANCE BETWEEN THE ANODES AND CLOSEST FUEL PIPE IS 50 FEET.
11. MINIMUM HORIZONTAL SEPARATION DISTANCE BETWEEN ANODES AND EXISTING UNDERGROUND METALLIC
PIPE IS 40 FEET.
12. RUN A SEPARATE #8 HMWPE NEGATIVE WIRE FROM EACH PIPE TO NEGATIVE BOND BOX, DIRECT BURY.
13. ANODE LEAD WIRES AND NEGATIVE WIRES TO PIPE ARE DIRECT BURY. MAKE SURE WIRE TRENCH IS FREE FROM
SHARP OBJECTS, LARGE ROCKS AND DEBRIS.
14. EXERCISE CAUTION NOT TO DAMAGE HMWPE INSULATION DURING INSTALLATION AND BACKFILL.
15. UNDERGROUND SPLICES IN ANODE LEAD WIRES ARE NOT PERMITTED.
16. ANODE LEAD WIRES MUST BE ROUTED INTO ANODE TERMINAL BOX WITHOUT SPLICES.
17. WIRE BETWEEN RECTIFIERS AND TERMINAL BOXES MUST BE IN CONDUIT.
18. FIELD ROUTE 2-INCH CONDUITS BETWEEN NEMA 4X TERMINAL BOXES ADJACENT TO TANK RECTIFIERS &
EXPLOSION PROOF TERMINAL BOXES AT TANK RING WALLS.
19. FOLLOW NEC AND UFGS GUIDELINES FOR CONDUIT AND WIRES IN CONDUIT.
SEE SHEET EC-102 FOR
ENLARGED PUMP HOUSE AREA
VIEW.
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
2-INCH CONDUIT BETWEEN EXPLOSION
PROOF TERMINAL BOX AT TANK & NEMA 4X
TERMINAL BOX AT RECTIFIER .
TANK 2 RECTIFIER & NEMA 4X TERMINAL BOX
SEE DETAILS #3 & #5 SHEET EC-502.
2-INCH CONDUIT BETWEEN EXPLOSION PROOF TERMINAL
BOX AT TANK & NEMA 4X TERMINAL BOX AT RECTIFIER .
EXPLOSION PROOF TERMINAL BOXES DETAILS
SEE DETAILS #2 & #4 SHEET EC-502.
EXPLOSION PROOF TERMINAL BOXES DETAILS
SEE DETAILS #2 & #4 SHEET EC-502.
TANK 1 RECTIFIER & NEMA 4X TERMINAL BOX
SEE DETAILS #3 & #5 SHEET EC-502.
ANODE GROUNDBED
APPROXIMATELY 85'
WEST OF PUMP HOUSE
IN NON-PAVED AREA,
FIELD LOCATE. SEE NOTE 10
THIS SHEET & DETAIL #1 ON
SHEET EC-501
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
M
FS
FS
PS
PS
F S
F S
F S
S F
PS
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
2 3
C
4 5
A
B
FI
LE
N U
M
BE
R
SI
ZE
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
SM
BL
D
ES
C
R
IP
TI
O
N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
O M
AH
A
D
IS
TR
IC
T O
M
AH
A, N
EB
R
AS
KA
AN
SI
D
OMAHA DISTRICT
SE
AL
FY
D
ES
C
R
EP
LA
C
E R
EF
U
EL
IN
G F
AC
IL
IT
IE
S/ R
EQ
U
IR
EM
EN
TS
D O
C U
M
EN
T
FO
R T
H O
O D
, T
EX
AS
R
READY TO ADVERTISE
SO
LI
C
IT
AT
IO
N N
O
D
AT
E:
W
-G
-2 1-
R -0
JU
LY
EC-102
EN
LA
R G
ED
P
U M
P H
O U
SE
C
AT
H
O D
IC
P
R O
TE
C
TI
O
N P
LA
N
N .W
IL
LI
AM
S
N .W
IL
LI
AM
S
J.
M
AG
G
AR
T
SU
BM
IT
TE
D B
Y:
. L
AY
SO
N
FH
_E C
-1
.D W
G
GRAPHIC SCALE
1 ENLARGED PUMP HOUSE CATHODIC PROTECTION PLAN
NTS
FO
R
CO
NT
IN
UA
TI
ON
S
EE
M
AT
CH
LI
NE
60'
1" = 60'- 0"
120'60'030'
NOTES:
1. INSTALL MONITORING TEST STATIONS EVERY 200 FEET AND AS SHOWN.
2. INSTALL FLANGE ISOLATION KITS WHERE SHOWN IN MECHANICAL DRAWING & AT ANY OTHER LOCATIONS
DEEMED NECESSARY BY THE PROJECT CATHODIC PROTECTION SPECIALIST.
3. FLANGE ISOLATION KITS ARE REQUIRED ANYWHERE UNDERGROUND FUEL PIPES CONNECT TO ABOVE GROUND
PIPE OR GROUNDED EQUIPMENT IN VAULTS.
4. FUEL PIPE MUST PASS THROUGH CONCRETE VAULT WALLS AND SLABS IN METALLIC SLEEVES WITH INSULATING
LINK SEALS TO INSULATE THE FUEL PIPE FROM REBAR & STRUCTURAL METAL.
5. INSULATE STEEL FUEL PIPE FROM METAL PIPE STANDS USING PHENOLIC AND NEOPRENE PADS AS NECESSARY.
6. ALL PIPE MUST BE INSTALLED IN SUCH A MANNER THAT IT DOES NOT CONTACT OTHER METALLIC
STRUCTURES SUCH AS ELECTRICAL GROUNDS, STRUCTURAL STEEL, ARE NOT PLACE TEST STATIONS IN ROAD.
7. INSTALL RECTIFIERS, ANODE TERMINAL BOXES AND NEGATIVE BOND BOXES WHERE SHOWN.
8. PULL 115/230 VAC FROM PUMP HOUSE TO RECTIFIERS.
9. INSTALL ANODES IN APPROXIMATE LOCATION SHOWN.
10. MINIMUM HORIZONTAL SEPARATION DISTANCE BETWEEN THE ANODES AND CLOSEST FUEL PIPE IS 50 FEET.
11. MINIMUM HORIZONTAL SEPARATION DISTANCE BETWEEN ANODES AND EXISTING UNDERGROUND METALLIC
PIPE IS 40 FEET.
12. RUN A SEPARATE #8 HMWPE NEGATIVE WIRE FROM EACH PIPE TO NEGATIVE BOND BOX, DIRECT BURY.
13. ANODE LEAD WIRES AND NEGATIVE WIRES TO PIPE ARE DIRECT BURY. MAKE SURE WIRE TRENCH IS FREE FROM
SHARP OBJECTS, LARGE ROCKS AND DEBRIS.
14. EXERCISE CAUTION NOT TO DAMAGE HMWPE INSULATION DURING INSTALLATION AND BACKFILL.
15. UNDERGROUND SPLICES IN ANODE LEAD WIRES ARE NOT PERMITTED.
16. ANODE LEAD WIRES MUST BE ROUTED INTO ANODE TERMINAL BOX WITHOUT SPLICES.
17. WIRE BETWEEN RECTIFIERS AND TERMINAL BOXES MUST BE IN CONDUIT.
18. FIELD ROUTE 2-INCH CONDUITS BETWEEN NEMA 4X TERMINAL BOXES ADJACENT TO TANK RECTIFIERS &
EXPLOSION PROOF TERMINAL BOXES AT TANK RING WALLS.
19. FOLLOW NEC AND UFGS GUIDELINES FOR CONDUIT AND WIRES IN CONDUIT.
EXOTHERMICALLY WELD 1-#8 HMWPE WIRE TO EACH OF THE
TWO STAINLESS STEEL HYDRANT LOOP PIPES.
ROUTE THE 2-#8 HMWPE NEGATIVE WIRES
UNSPLICED INTO NEGATIVE BOND BOX ADJACENT TO
RECTIFIER. SEE DETAILS #4 & #5 ON SHEET EC-501.
EXOTHERMICALLY WELD 1-#8 HMWPE WIRE TO EACH OF THE
3 TRUCK STAND PIPES. (8-INCH SUPPLY, 8-INCH RETURN &
8-INCH FILL) ROUTE THE 3-#8 HMWPE NEGATIVE WIRES
UNSPLICED INTO NEGATIVE BOND BOX ADJACENT TO
RECTIFIER. SEE DETAILS #4 & #5 ON SHEET EC-501.
EXOTHERMICALLY WELD 1-#8 HMWPE WIRE TO THE PRT
SUPPLY PIPE AND THE PRT RETURN PIPE.
ROUTE THE 2-#8 HMWPE NEGATIVE WIRES
UNSPLICED INTO NEGATIVE BOND BOX ADJACENT TO
RECTIFIER. SEE DETAILS #4 & #5 ON SHEET EC-501.
FUEL PIPE RECTIFIER, NEGATIVE BOND
BOX AND ANODE TERMINAL BOX DETAILS
#1, #3 AND #4 ON SHEET EC-501
MONITORING TEST STATION
DETAIL #6 ON SHEET EC-502
(TYPICAL FOR 25)
| Sheets and Views |
| ST102 OPERATING TANK ROOF PLAN AND ELEVATION |
| ST301 TANK FOUNDATION SECTIONS AND DETAILS (1 OF 2) |
| ST302 TANK FOUNDATION SECTIONS AND DETAILS (2 OF 2) |
| ST501 TANK CONTAINMENT AREA TYP DETAILS |
| ST502 TANK APPURTENANCE DETAILS |
| ST503 TANK STAIRWAY AND GUARDRAIL DETAILS |
| ST504 PIPE SUPPORTS IN TANK CONTAINMENT AREA |
| EC101 OVERALL CATHODIC PROTECTION PLAN |
| EC102 ENLARGED PUMP SHELTER CATHODIC PROTECTION PLAN |
| EC103 TANK BOTTOM CATHODIC PROTECTION LAYOUT |
| EC501 CATHODIC PROTECTION DETAILS (1 OF 2) |
| EC502 CATHODIC PROTECTION DETAILS (2 OF 2) |