Environmental Review Report This report is provided by the Directorate of Public Works, Environmental Division (ENV) at the request of the project proponent. This review expires 12 months from the date of approval or if site conditions or project descriptions change. If archeological remains or evidence of endangered species are found during the course of a project, stop the activity and contact ENV at (831) 386-2763.

ENV Review No. 16046

Project Summary: 1391: 79297 (2016). Secure Microgrid Control System. Design-build (contractor will develop final designs based upon RFP design). Construct a secure, integrated smart grid control system (Supervisory, Control and Data Acquisition System (SCADA)) and 1 MW storage battery to coalesce existing photovoltaic arrays, an existing 1MW storage battery, and an existing standby 435 kW

National Environmental Policy Act Compliance Review

Project Line Items Final

RECNEPARequired

The following summary includes proponent actions required for compliance with environmental laws, as well as actions ENV has taken. Failure to implement compliance requirements may result in the proponent violating federal or State law.

This review is for the project as described above and no additional actions. Activities not described in the project description will require an additional review. Excavation, grading, trenching or other digging on FHL requires a FHL Dig Permit; contact FHL DPW Engineering at 831-386-2429.

Action re-reviewed to consider 2018 revisions to RFP package. Project will go out for design and construction.

Avoid floodplains in final design. PWE review is required for design for construction, trenching, or ground disturbance.

New trenching to be monitored by PWE. Please notify PWE x2520 one week prior to work.

Avoid trenching with the drip-line of trees.

Conclusion: Permit and consultation requirements are addressed - see Attachment 1.

Categorical exclusion: Routine procurement of goods and services (complying with applicable procedures for sustainable or ``green'' procurement) to support operations and infrastructure, including routine utility services and contracts.

NEPA Summary Citation 651.30(e)(1)

Categorical exclusion: Acquisition, installation, and operation of utility and communication systems, mobile antennas, data processing cable and similar electronic equipment that use existing right-of-way, easement, distribution systems, and/or facilities (REC required).

NEPA Summary Citation 651.30(e)(2)-REC

Installation FHL TimelineWork Order 79297

Friday, May 4, 2018 Page 1 of 4

ENV Review No. 16046

Project Summary: 1391: 79297 (2016). Secure Microgrid Control System. Design-build (contractor will develop final designs based upon RFP design). Construct a secure, integrated smart grid control system (Supervisory, Control and Data Acquisition System (SCADA)) and 1 MW storage battery to coalesce existing photovoltaic arrays, an existing 1MW storage battery, and an existing standby 435 kW

Proponent Information

This REC is reviewed and approved as meeting the standards of 32 CFR 651. The undersigned concurs with the findings of this review - see NEPA comments above for limitations and concerns.

Place Electronic Signature Below in PDF

Environmental Chief Review and Signature

Signature of the proponent validates that screening criteria (32 CFR 651.29) have been met:

Proponent Signature (Required for REC) Date

Proponent Signature (Record of Environmental Consideration)

Greg Vallery gregory.l.vallery.civ@mail.Proponent POC POC Email Kristi Yu kristi.m.yu.civ@mail.milProponent POC POC Email

Friday, May 4, 2018 Page 2 of 4

CLARK.ELIZABET

H.R.1231929017

Digitally signed by

CLARK.ELIZABETH.R.1231929017

Date: 2018.05.04 11:08:26 -07'00'

VALLERY.GREGORY.L.1257482916 Digitally signed by VALLERY.GREGORY.L.1257482916 Date: 2018.05.04 17:02:11 -07'00'

Project Summary: 1391: 79297 (2016). Secure Microgrid Control System. Design-build (contractor will develop final designs based upon RFP design). Construct a secure, integrated smart grid control system (Supervisory, Control and Data Acquisition System (SCADA)) and 1 MW storage battery to coalesce existing photovoltaic arrays, an existing 1MW storage battery, and an existing standby 435 kW

Natural Resources Compliance Review

Integrated Natural Resources Management Plan Coordination Review

Cultural Resources Review

Environmental Compliance Review

Environmental Review Report, Attachments Part 1 Project Information

Section 7 Requirement Informal ConsultationStatus Complete

Date Completed 6/14/2016

Reviewer Liz Clark Section 7 Process Programmatic Consultation

Site Visit Resource Survey Conducted

Complete 6/14/2016Robert PikeStatus Date CompletedReviewer

Site Visit Resource Survey Conducted

Compliant w/ Integrated Nat. Res. Mgmt. Plan Compliant w/ Migratory Bird Treaty Act

Complete

6/13/2016 Lisa Cipolla

Status

Date Completed Reviewer

Section 106 Process: Other

Site Visit Professional Survey Conducted?

Complete 6/13/2016Mike MoellerStatus Date CompletedReviewer

Drinking Water Permit Storm Water Plan/NOI

Clean Water Act 401/402 Permit Waste Water Permit

Air Permit Restoration/clean up

Other Permit Site Visit

Resource Survey Conducted

Requires Lead Survey

Requires Asbestos Survey Requires PCB Survey

All Surveys Conducted

ENV Review No. 16046 Installation FHL Timeline

Location(s) Cantonment

Project Summary 1391: 79297 (2016). Secure Microgrid Control System. Design-build (contractor will develop final designs based upon RFP design). Construct a secure, integrated smart grid control system (Supervisory, Control and Data Acquisition System (SCADA)) and 1 MW storage battery to coalesce existing photovoltaic arrays, an existing 1MW storage battery, and an existing standby 435 kW Syngas generator into an electrical microgrid system.

Upgrade the existing electrical distribution system to provide greater connectivity and sectionalizing capability. Upgrade the existing energy generation control systems to incorporate generation control by the new SCADA to match electricity generation and available load, and make tham compliant with DoD 8500 guidelines.

Project Comment Includes trenching for underground ductbank loop adjacent to Route Tampa, installation of fiber optic telecommunications, concrete pads and fencing as needed.

Track Vehicles 0 Wheeled Vehicles 0 Personnel 0 Ammo

Work Order 79297

Friday, May 4, 2018 Page 3 of 4

Project Summary: 1391: 79297 (2016). Secure Microgrid Control System. Design-build (contractor will develop final designs based upon RFP design). Construct a secure, integrated smart grid control system (Supervisory, Control and Data Acquisition System (SCADA)) and 1 MW storage battery to coalesce existing photovoltaic arrays, an existing 1MW storage battery, and an existing standby 435 kW

Correspondence Log Environmental Review Report, Attachments Part 2

6/10/2016 ER Received

Comment POCDate Type

Friday, May 4, 2018 Page 4 of 4

Environmental Review Report

This report is provided by the Directorate of Public Works, Environmental Division (ENV) at the request of the project proponent. This review expires 12 months from the date of approval or if site conditions or project descriptions change. If archeological remains or evidence of endangered species are found during the course of a project, stop the activity and contact ENV at (831) 386-2763.

ENV Review No. 16047

Project Summary: 1391 82028, (2016). Install 5MW of Solar PV consisting of roof mounted, canopy mounted, and ground mounted arrays with 3 MWhr battery storage. There are over 40 buildings to be considered for roof mounted Solar PV. Total square footage of roof space is approximately 500K SF. There are five acres of land available for ground mounted/canopy mounted arrays. This project will also

National Environmental Policy Act Compliance Review

Project Line Items Final

RECNEPARequired

The following summary includes proponent actions required for compliance with environmental laws, as well as actions ENV has taken. Failure to implement compliance requirements may result in the proponent violating federal or State law.

This review is for the project as described above and no additional actions. Activities not described in the project description will require an additional review. Excavation, grading, trenching or other digging on FHL requires a FHL Dig Permit; contact FHL DPW Engineering at 831-386-2429.

Action re-reviewed to consider 2018 revisions to RFP package. Project will go out for design and construction.

Avoid floodplains in final design. PWE review is required for design for construction, trenching, or ground disturbance.

Per preliminary plans and discussion, this action is for rooftop solar on non-hisotirc buildings, and canopy mounted over existing parking areas. No new ground mounted arrays are proposed or reviewed. This review should be updated when design plans become available.

Conclusion: Permit and consultation requirements are addressed - see Attachment 1.

Categorical exclusion: Modification, product improvement, or configuration engineering design change to materiel, structure, or item that does not change the original impact of the materiel, structure, or item on the environment (REC required).

NEPA Summary

Citation 651.30(e)(4)-REC

Categorical exclusion: Acquisition, installation, and operation of utility and communication systems, mobile antennas, data processing cable and similar electronic equipment that use existing right-of-way, easement, distribution systems, and/or facilities (REC required).

NEPA Summary

Citation 651.30(e)(2)-REC

Installation FHL TimelineWork Order 82028

16047-01

Rooftop - among most cantonment buildings. (DPW has list, Hacienda is excluded).

Line Item #

Line Item

Review Status

Comment

16047-02

Canopy mounted (carport photovoltaic) --PX parking lot (parking for buildings 79, 80, 81) --HQ parking lot (parking lot for HQ building 238) --SW of bowling alley (fenced MEP).

Pages 489 (C-137), 490 (C-138), and 492 (C-140) of April 2018 Final Corrected RFP - Appendices - Part 3.

Line Item #

Line Item

Review Status

Comment

16047-03

Ground mounted photovoltaic - -Former O&M storage yard

Page 491 (C-139) of April 2018 Final Corrected RFP - Appendices - Part 3.

Line Item #

Line Item

Review Status

Comment

Friday, May 4, 2018 Page 1 of 4

ENV Review No. 16047

Project Summary: 1391 82028, (2016). Install 5MW of Solar PV consisting of roof mounted, canopy mounted, and ground mounted arrays with 3 MWhr battery storage. There are over 40 buildings to be considered for roof mounted Solar PV. Total square footage of roof space is approximately 500K SF. There are five acres of land available for ground mounted/canopy mounted arrays. This project will also

Proponent Information

This REC is reviewed and approved as meeting the standards of 32 CFR 651. The undersigned concurs with the findings of this review - see NEPA comments above for limitations and concerns.

Place Electronic Signature Below in PDF

Environmental Chief Review and Signature

Signature of the proponent validates that screening criteria (32 CFR 651.29) have been met:

Proponent Signature (Required for REC) Date

Proponent Signature (Record of Environmental Consideration)

Greg Vallery gregory.l.vallery.civ@mail.Proponent POC POC Email

Kristi Yu kristi.m.yu.civ@mail.milProponent POC POC Email

Friday, May 4, 2018 Page 2 of 4

Project Summary: 1391 82028, (2016). Install 5MW of Solar PV consisting of roof mounted, canopy mounted, and ground mounted arrays with 3 MWhr battery storage. There are over 40 buildings to be considered for roof mounted Solar PV. Total square footage of roof space is approximately 500K SF. There are five acres of land available for ground mounted/canopy mounted arrays. This project will also

Natural Resources Compliance Review

Integrated Natural Resources Management Plan Coordination Review

Cultural Resources Review

Environmental Compliance Review

Environmental Review Report, Attachments Part 1

Project Information

Signature of the proponent validates that screening criteria (32 CFR 651.29) have been met:

Proponent Signature (Required for REC) Date

Section 7 Requirement No ConsultationStatus Complete

Date Completed 6/14/2016

Reviewer Liz Clark Section 7 Process

Site Visit Resource Survey Conducted

Complete 6/14/2016Robert PikeStatus Date CompletedReviewer

Site Visit Resource Survey Conducted

Compliant w/ Integrated Nat. Res. Mgmt. Plan Compliant w/ Migratory Bird Treaty Act

Complete

6/13/2016 Lisa Cipolla

Status

Date Completed Reviewer

Section 106 Process: Undertaking not pursuant to 36CFR800

Site Visit Professional Survey Conducted?

Complete 6/13/2016Mike MoellerStatus Date CompletedReviewer

Drinking Water Permit

Storm Water Plan/NOI

Clean Water Act 401/402 Permit

Waste Water Permit

Air Permit

Restoration/clean up

Other Permit

Site Visit

Resource Survey Conducted

Requires Lead Survey

Requires Asbestos Survey

Requires PCB Survey

All Surveys Conducted

ENV Review No. 16047 Installation FHL Timeline

Location(s)

Project Summary 1391 82028, (2016). Install 5MW of Solar PV consisting of roof mounted, canopy mounted, and ground mounted arrays with 3 MWhr battery storage. There are over 40 buildings to be considered for roof mounted Solar PV. Total square footage of roof space is approximately 500K SF. There are five acres of land available for ground mounted/canopy mounted arrays. This project will also construct a 3MWHr battery energy storage system (BESS). **Ground mounted not planned, canopy mounted over existing parking areas by PX and HQ.**

Project Comment

Track Vehicles 0 Wheeled Vehicles 0 Personnel 0 Ammo

Work Order 82028

Friday, May 4, 2018 Page 3 of 4

Project Summary: 1391 82028, (2016). Install 5MW of Solar PV consisting of roof mounted, canopy mounted, and ground mounted arrays with 3 MWhr battery storage. There are over 40 buildings to be considered for roof mounted Solar PV. Total square footage of roof space is approximately 500K SF. There are five acres of land available for ground mounted/canopy mounted arrays. This project will also