Contract Drawings Sheets (Revised) Amendment 0001.pdf
PDF 9 MB Posted
- Attached to
- Lock Control System Modernization, Lock and Dam #5, Allegheny River, Freeport, PA Federal contract opportunity
- Solicitation number
- W911WN21B8005
About this file
This is a solicitation for a firm-fixed-price contract to upgrade the lock control system at Allegheny Lock and Dam #5 on the Allegheny River in Pennsylvania. The U.S. Army Corps of Engineers, Pittsburgh District, seeks to remove the existing DeviceNET infrastructure and install a new interlocked control system using hardwiring and Ethernet/IP. Key requirements include removing old PLCs, HMI displays, and cabling and installing new components; replacing valve and gate VFDs in the MCC; installing new limit switches and actuator control heads; and integrating the new system with fiber optic communication cabling. The work requires disposal of removed electrical equipment. The contract value is between $500,000 and $1,000,000, with a 365-day period of performance after notice to proceed. This is a 100% small business set-aside procurement using firm-fixed pricing. The solicitation and attachments were issued on July 20, 2021.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Results W911WN21B8005.pdf | ||
| Attendance Register Bid Opening 8-24-21.pdf | ||
| Technical Specifications Section 01 35 00.00 08 (Revised) Amendment 0001.pdf | ||
| Davis Bacon Wage Rates 7-23-21 (new updated Attachment 4).pdf | ||
| Amendment 0001 W911WN21B8005-0001.pdf | ||
| Pre-Bid Sign-In Sheet Site Visit.pdf | ||
| Pre-Bid Contracting Discussion Site Visit.pdf | ||
| Pre-Bid Site Visit Agenda.pdf | ||
| Davis Bacon Wage Rates - Attachment 4.pdf | ||
| Contract Drawings - Attachment 2.pdf | ||
| Reference Drawings - Attachment 3.pdf | ||
| Bid Schedule.xlsx | XLSX spreadsheet | |
| Technical Specifications - Attachment 1.pdf | ||
| W911WN21B8005.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T E
L
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
IO
N
CERTIFIED FINAL DOCUMENTS: RTA W911WN-21-B-8005
W W
N -2
-B
-8
T
W E
B E
R
M
D E
V
IN
E
G K
O T
C H
D R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
M
Y
E-401
J O
H N
E
N
IT
E S
P
.E
E L
E C
T R
IC
A
L S
IT
E
P L
A N
C2
SCALE: 1" = 50'
SITE PLAN
N
ALLEGHENY RIVER
CROSSOVER
BUILDING
OPERATIONS
POWERHOUSE
EL 757.0
UPPER POOL,
EL 745.4
LOWER POOL,
COUNTY ROAD
RAILROAD
FLOW
FIXED CREST DAM
RIVER WALL
WORK LIMIT
CONTRACTORS
SHELTER (CS1)
UPSTREAM CONTROL
STORAGE AREA
PARKING/
LAYDOWN/
CONTRACTOR
(CS2)
CONTROL SHELTER
DOWNSTREAM
LAND WALL
50' 100'0
S T
A
.7
A
L-13
L-12L-11
S T
A
.5
A
S T
A
.0
B
S T
A
.0
B
EXISTING CONCRETE
RETAINING WALL
PIPE TRENCH
R-7
R-6
R-5
R-2 R-3
R-1
R-8R-4 R-9 R-10
RETAINING WALL LAND WALL
M
No.2 No.3 No.4 No.5 No.6 No.7
L-15
No.8
R-7
L-14
L-16 L-17
L-18
S T
A
.8
B
56'X360'
LOCK CHAMBER
CS-1
(1ST FLOOR)
HOUSE
POWER
S T
A
.0
B
S T
A
.0
ELEV. 774.63
EXISTING RAISED LAND
ELEV. 768.7
TOP OF LOCK WALL
S T
A
.0
A
S T
A
.0
B
INSIDE RIVER WALL TRENCH (TYP)
EXISTING (2)-9"W FIBERGLASS CABLE TRAYS
FV1A
FV5A
FV1C
FV5C
FV2A FV6A
FV2C FV6C
FV3A FV7A
FV3C FV7C
FV4A FV8A
FV4C FV8C
SEE NOTE 1
(TYP FOR 8 VALVES)
ACTUATOR HEAD NO. 1
NEW FILLING VALVE
L S
USLWLS
USRWLS
TO CS-1, SEE DWG# E-106
EMBEDDED FROM TRENCH
EXISTING (5)-3"C
VC1-1 VC1-2
VC1-4VC1-3
SHELTER ON DWG# E-106
SEE UPSTREAM CONTROL
1 5
CC1P
MMMMMMMJB
CABLE RECESS
LIMIT SWITCH
(URM) LIMIT SWITCHES
(URAM) AND MITERED
ALMOST MITERED
U/S R/W MITER GATE
(URR)
LIMIT SWITCH
RECESSED
MITER GATE
U/S R/W
RECESS
ANCHORAGE
GATE
SWITCH (UMG)
MITERED LIMIT
U/S MITER GATE
LS
LSLS
JB
CABLE RECESS
LIMIT SWITCH
RECESS
ANCHORAGE
GATE
LIMIT SWITCH (DLR)
GATE RECESSED
D/S R/W MITER
(DLM) LIMIT SWITCHES
(DLAM) AND MITERED
ALMOST MITERED
D/S R/W MITER GATE
EXISTING (2)-12"W FIBERGLASS CABLE TRAYS
LSLS
LS
FLOW
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-402
J O
H N
E
N
IT
E S
P
.E
U P
S T
R E
A M
P L
A N
INSTALLING THE ACTUATORS.
BEST INSTALLATION PRACTICES AND PROCEDURES BEFORE
CONTRACTOR SHALL CONSULT WITH AN AUMA REPRESENTATIVE FOR
CABLES TO EACH ACTUATOR TO MAINTAIN THE IP68 RATING. THE
THE CONTRACTOR SHALL ENSURE THE PROPER INSTALLATION OF 8.
WORK OUTLINED IN THIS PROJECT.
THE POWERHOUSE AND CONTROL SHELTERS IMPACTED BY THE
WATERTIGHT. THE CONTRACTOR SHALL SEAL ALL CABLE ENTRIES TO
SHALL BE MADE SUBMERSIBLE AND CONNECTIONS SHALL BE
TO LIMIT SWITCHES, JUNCTION BOXES, AND VALVE CONTROL HEADS,
ALL PARTS INSTALLED BELOW GRADE, INCLUDING BUT NOT LIMITED 7.
.FLOOD EVENTS
FOR ALL LIMIT SWITCHES TO PREVENT DAMAGE FROM DEBRIS IN
CONTRACTOR SHALL DESIGN AND SUPPLY GUARDING BRACKETRY.
CONTRACTOR SHALL DESIGN AND SUPPLY NEW LIMIT SWITCH 6.
TO THE INTERLOCK PANEL.
STILL BEING RUN FROM THE VALVE CONTROL BOXES AT THAT POINT
CONTROL BOXES AND ASSOCIATED WIRING. CONNECT ANY VALVES
SYSTEM IS OPERABLE, CONTRACTOR SHALL DEMOLISH VALVE
CONTROL SYSTEM IS TESTED AND COMMISSIONED. ONCE THE NEW
ON THE POWERHOUSE, SHALL BE MAINTAINED UNTIL THE NEW
CONNECTIONS TO THE EXISTING VALVE CONTROL BOXES, LOCATED
VALVES THROUGHOUT THE REPLACEMENT PROCESS. HARDWIRED
OPERABILITY OF AT LEAST TWO FILL VALVES AND TWO EMPTY
REPLACED SIMULTANEOUSLY. CONTRACTOR SHALL MAINTAIN
FILL AND EMPTY VALVE CONTROL HEADS AND HANDWHEELS MAY BE 5.
ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY CONTRACTOR.
LIMIT SWITCH AND JUNCTION BOX (JB) LOCATIONS ON DRAWINGS 4.
CONTRACTOR SHALL REUSE EXISTING CONDUIT.
EXISTING LOCATIONS AND WIRED TO NEW JUNCTION BOXES.
MAGNETIC LIMIT SWITCHES. NEW SWITCHES SHALL BE INSTALLED IN
LIMIT SWITCHES SHALL BE REPLACED WITH NEW HARDWIRED 3.
SEE DWG# E-610.
FOR ADDITIONAL FIBER, ETHERNET, AND CONTROL SYSTEM WIRING, 2.
EXISTING POWER WIRING (FV1-FV8).
CONTROLS WIRING (CONTROL CABLE AND ANALOG CABLE). REUSE
AND HANDWHEELS. REPLACE DEVICENET WIRING WITH NEW
REPLACE WITH GOVERNMENT FURNISHED AUMA ACTUATOR HEADS
REMOVE ALL EXISTING VALVE ACTUATOR HEADS AND HANDWHEELS. 1.
SHEET KEYNOTES
B1
SCALE: 1/16" = 1'-0"
N
A1
E-505
UPSTREAM PLAN (STA. 0+71.78A TO STA. 2+27.85B)
IN TRENCH
SOLENOIDS LOCATED
AND AIR WHISTLE
EXISTING U/S BUBBLER
0 8' 32'16'
.9
B
M .J
S
T A
S T
A
.2
B
.J
S T
A
.6
R-16
S T
A
.0
B
S T
A
.7
B
56'X360'
LOCK CHAMBER
RIVER WALL
LAND WALL
M .J
S
T A
.0
LS
LSLSJB
CABLE RECESS
LIMIT SWITCH
(DRM) LIMIT SWITCHES
(DRAM) AND MITERED
ALMOST MITERED
D/S R/W MITER GATE
(DRR)
LIMIT SWITCH
RECESSED
MITER GATE
D/S R/W
SWITCH (DMG)
MITERED LIMIT
D/S MITER GATE
LS
JB
LSLS
CABLE RECESS
LIMIT SWITCH
RECESS
ANCHORAGE
GATE
LIMIT SWITCH (DLR)
GATE RECESSED
D/S R/W MITER
(DLM) LIMIT SWITCHES
(DLAM) AND MITERED
ALMOST MITERED
D/S R/W MITER GATE
S T
A
.2
(1ST FLOOR)
HOUSE
POWER
S T
A
.6
B
No.7
S T
A
.1
B
S T
A
.0
B
FIBERGLASS CABLE TRAYS
EXISTING (2)- 12"W
- PLAN ON DWG E-307
CABLE SHAFT SEE CROSSOVER
EXISTING (2)-12"W TEE TRAYS AT LW.
SEE SECTION "B" ON DWG E-307
TRAYS INSIDE CROSSOVER TUNNEL
EXISTING (3)-9"W FIBERGLASS CABLE
RIVER WALL TRENCH (TYP)
EXISTING (2)-9"W CABLE TRAYS IN EV1A
EV1C
EV2A
EV2C
EV3A
EV3C
EV4A
EV4C
EV5A
EV5C
EV6A
EV6C
EV7A
EV7C
EV8A
EV8C
DSRWLS
DSLWLS
L S
TO CS-2, SEE DWG# E-106
EMBEDDED FROM TRENCH
EXISTING (5)-3"C
VC2-1VC2-2
VC2-4VC2-3
(TYP FOR 8 VALVES)
ON DWG # E-308
SEE DETAIL" A"
ACTUATOR NO.1
EMPTYING VALVE
SHELTER ON DWG# E-106
DOWNSTREAM CONTROL
SHELTER CS-2. SEE
DOWNSTREAM CONTROL
ON DWG# E-307
SEE CROSSOVER - PLAN
RIVER WALL CABLE SHAFT
WARNING SIREN
EXISTING VALVE DISCHARGE
CC2P
R-11
M .J
S
T A
.7
B
S T
A
.6
B
M .J
S
T A
.8
B
R-12
M .J
S
T A
.0
B
RECESS
ANCHORAGE
GATE
FLOW
HEADS.
OF UNUSED ACTUATOR
CONFIRMED OPERATION
AFTER REPLACEMENT AND
BOXES. FOR DEMOLITION
EXISTING VALVE CONTROL
No.2 No.3 No.4 No.5 No.6 No.8
L-22 L-23 L-24 L-25
L-26 L-27
R-14 R-15
R-17 R-18 R-19
R-13 M M M M M M M
CS-2
POWER HOUSE
TRENCH AT
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
A3
E-505
A2
E-505
A4
E-307
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-403
J O
H N
E
N
IT
E S
P
.E
D O
W N
S T
R E
A M
P L
A N
N
D1
SCALE: 1/16" = 1'-0"
INSTALLING THE ACTUATORS.
FOR BEST INSTALLATION PRACTICES AND PROCEDURES BEFORE
CONTRACTOR SHALL CONSULT WITH AN AUMA REPRESENTATIVE
CABLES TO EACH ACTUATOR TO MAINTAIN THE IP68 RATING. THE
THE CONTRACTOR SHALL ENSURE THE PROPER INSTALLATION OF 8.
PROJECT SHALL BE SEALED TO BE WATERTIGHT.
CONTROL SHELTERS IMPACTED BY THE WORK OUTLINED IN THIS
WATERTIGHT. ALL CABLE ENTRIES TO THE POWERHOUSE AND
SHALL BE MADE SUBMERSIBLE AND CONNECTIONS SHALL BE
TO LIMIT SWITCHES, JUNCTION BOXES, AND VALVE CONTROL HEADS,
ALL PARTS INSTALLED BELOW GRADE, INCLUDING BUT NOT LIMITED 7.
.FLOOD EVENTS
FOR ALL LIMIT SWITCHES TO PREVENT DAMAGE FROM DEBRIS IN
CONTRACTOR SHALL DESIGN AND SUPPLY GUARDING BRACKETRY.
CONTRACTOR SHALL DESIGN AND SUPPLY NEW LIMIT SWITCH 6.
TO THE INTERLOCK PANEL.
STILL BEING RUN FROM THE VALVE CONTROL BOXES AT THAT POINT
CONTROL BOXES AND ASSOCIATED WIRING. CONNECT ANY VALVES
SYSTEM IS OPERABLE, CONTRACTOR SHALL DEMOLISH VALVE
CONTROL SYSTEM IS TESTED AND COMMISSIONED. ONCE THE NEW
ON THE POWERHOUSE, SHALL BE MAINTAINED UNTIL THE NEW
CONNECTIONS TO THE EXISTING VALVE CONTROL BOXES, LOCATED
VALVES THROUGHOUT THE REPLACEMENT PROCESS. HARDWIRED
OPERABILITY OF AT LEAST TWO FILL VALVES AND TWO EMPTY
REPLACED SIMULTANEOUSLY. CONTRACTOR SHALL MAINTAIN
FILL AND EMPTY VALVE CONTROL HEADS AND HANDWHEELS MAY BE 5.
SEE IMAGES FOR EXAMPLE DETAILS.
ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY CONTRACTOR.
LIMIT SWITCH AND JUNCTION BOX (JB) LOCATIONS ON DRAWINGS 4.
CONTRACTOR SHALL REUSE EXISTING CONDUIT.
EXISTING LOCATIONS AND WIRED TO NEW JUNCTION BOXES.
MAGNETIC LIMIT SWITCHES. NEW SWITCHES SHALL BE INSTALLED IN
LIMIT SWITCHES SHALL BE REPLACED WITH NEW HARDWIRED 3.
SEE DWG# E-610.
FOR ADDITIONAL FIBER, ETHERNET, AND CONTROL SYSTEM WIRING, 2.
EXISTING POWER WIRING (EV1-EV8).
CONTROLS WIRING (CONTROL CABLE AND ANALOG CABLE). REUSE
AND HANDWHEELS. REPLACE DEVICENET WIRING WITH NEW
REPLACE WITH GOVERNMENT FURNISHED AUMA ACTUATOR HEADS
REMOVE ALL EXISTING VALVE ACTUATOR HEADS AND HANDWHEELS. 1.
LIMIT SWITCH RECESS (TYP)
SCALE: NTS
A1
D/S L/W MITER GATE MAIN
CABLE RECESS
LIMIT SWITCH
CABLE FROM
LIMIT SWITCH RECESS (TYP)
SCALE: NTS
D/S L/W MITER GATE MAIN
A5
BE REPLACED (TYP)
LIMIT SWITCHES TO
AND MITERED (LEFT)
MITERED (RIGHT)
D/S L/W ALMOST
REPLACED (TYP)
LIMIT SWITCH TO BE
D/S L/W RECESSED
LIMIT SWITCH (DMG)
D/S MITER GATE
EXISTING CABLE TO
BOX
SWITCH JUNCTION
LOCATION FOR
PROPOSED
DLAM, AND DLM)
RECESS (FOR DLR,
MAIN LIMIT SWITCH
ENTRY FOR D/S L/W
EXISTING CABLE
SHEET KEYNOTES
DOWNSTREAM PLAN (STA. 2+40.78B TO STA. 5+35.65B)
LOCATED IN TRENCH
AIR WHISTLE SOLENOIDS
EXISTING U/S BUBBLER AND
C6
E-308
A6
E-308
T W
E B
E R
M D
E V
IN
E
G
K O
T
0 8' 32'16'
68 7910
7 8 9 10
5 4 3 2 1
FLOW
FLOW
FLOW
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-404
J O
H N
E
N
IT
E S
P
.E
P O
W E
R H
O U
S E
F L
O O
R P
L A
N
B1
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN
D1
SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P L
O T
D A
T E
W W
N -2
-B
-8
ENCLOSURE (ICP) TO BE INSTALLED
NEW INTERLOCK CONTROL
EXTERIOR PIPE TRENCH
EXISTING
INSTRUCTIONS
FOR ADDITIONAL
FIRESTOPPING
SEE SECTION 07 84 00
HOUSE TO BE SEALED.
WIRE ENTRY TO POWER
TO BE DEMOLISHED.
PUSH BUTTON BOXES.
EXISTING VALVE CONTROL
FIBERGLASS CABLE TRAYS
EXISTING (2)-12"W
3 1/2 "C
VC1-1 VC1-2
VC1-3 VC1-4
3 1/2 "C
USLWLS
USRWLS
3 1/2 "C
VC2-1 VC2-2
VC2-3 VC2-4
DSLWLS
DSRWLS
FV8A FV7A FV6A FV5A FV4A FV3A FV2A FV1A
FV8C FV7C FV6C FV5C FV4C FV3C FV2C FV1C
EV8A EV7A EV6A EV5A EV4A EV3A EV2A EV1A
EV8C EV7C EV6C EV5C EV4C EV3C EV2C EV1C
ON DWG # E-505
SEE TRENCH DETAIL "E" PLAN
AND CONDUIT SLEEVES THRU WALL
FOR DETAIL OF CABLE SUPPORT
(MCC)
CONTROL CENTER
EXISTING MOTOR
THROUGH THESE TRAYS.
EXITING POWERHOUSE
RUN ALL NEW CABLES
DOWN TO TRENCH.
VERTICAL SECTIONS
CABLE TRAYS
EXISTING (2)-12"W
TRAYS IN TRENCH
(2)-12"W CABLE
EXISTING
DOWN TO TRENCH.
FROM SECTION 6 (PLC) OF MCC
SECTIONS. RUN NEW CABLES
CABLE TRAYS HORIZONTAL
EXISTING (2)-12"W ALUM.
EXISTING GENERATOR
COMPRESSOR
EXISTING AIR
EXISTING MCC
CABLE RUNS.
UTILIZE FOR NEW
CABLE TRAYS.
EXISTING (2) ALUM.
EXISTING AIR TANK
EXISTING FUEL TANK
EXISTING GENERATOR
COMPRESSOR
EXISTING AIR
MCC-2 MCC-3
MCC-4 MCC-5
5 6
1 2
LPA40
ENICP
CC2P
CC1P
CONDUIT ABOVE DOORWAY
RUN NEW ICP POWER
, 2"C
BREAKER FOR 70A.
CHANGE 20A CIRCUIT
TO CIRCUIT NO. 40 (SPARE).
LPA. ADD NEW ICP CIRCUIT
EXISTING LIGHTING PANEL
07 84 00 FIRESTOPPING
ACCORDING TO SECTION
ANY CABLE RUNS
TRENCHES. FIREPROOF
WALL BETWEEN PIPE
EXISTING FIRE BRICK
WATERTIGHT.
WORK OUTLINED IN THIS PROJECT SHALL BE SEALED TO BE
ALL CABLE ENTRIES TO THE POWERHOUSE IMPACTED BY THE 8.
COMMISSIONED.
CONTRACTOR ONCE THE NEW SYSTEM IS OPERATIONAL AND
VALVE CONTROL BOXES SHALL BE DEMOLISHED BY THE 7.
SYSTEM. SEE DWG# E-628 FOR MORE DETAILS.
BYPASS SECTION SHALL BE WIRED INTO THE NEW INTERLOCK
DWG# E-609 AND E-618 FOR MORE DETAILS. CONTROLS FOR
DYNAMIC BRAKE RESISTORS. REFER TO SPECIFICATIONS AND
COMPATIBLE WITH BOTH THE NEW PLC AND THE EXISTING
MANUFACTURED BY THE SAME MCC MANUFACTURER AND ARE
SHALL BE REPLACED WITH NEW ETHERNET VFDs THAT ARE
DEMOLISHED AND HANDED OVER TO THE GOVERNMENT. THEY
AND BYPASS CIRCUITS. THE EXISTING VFDs SHALL BE
MCC SECTIONS 2-5 CONTAIN THE EXISTING MITER GATE VFDs 6.
INDICATING LIGHTS.
SECTIONS WITH APPROPRIATE CUTOUTS FOR VFD HIM AND
SECTIONS. NEW DOORS SHALL BE INSTALLED ON THESE
SHALL BE CONSULTED FOR MORE DETAIL TO THE MITER GATE
MCC WAS MANUFACTURED BY ROCKWELL. AS-BUILT DRAWINGS 5.
DWG# E-619 TO E-641.
FOR INTERLOCK CONTROL PANEL WIRING, SEE DWG# E-619 AND 4.
THE BOTTOM OF SECTION 6 OF THE MCC.
TO THE ICP SHALL BE ROUTED THROUGH THE EXISTING HOLE IN
CABLE ENTERING THE BOTTOM OF THE MCC. ALL NEW CABLES
CONTRACTOR SHALL PROVIDE CABLE SUPPORTS FOR EACH 3.
THESE PARTS SHALL BE HANDED OVER TO THE GOVERNMENT.
REMOVAL OF (5)-24VDC POWER SUPPLIES. ONCE REMOVED,
DEMOLITION IN THE PLC ENCLOSURE OF THE MCC INCLUDES 2.
618 FOR MORE DETAIL.
INSTALLED BY THE CONTRACTOR. REFER TO DWG# E-609 AND E-
NEW PLC AND ETHERNET SWITCH SHALL BE SUPPLIED AND
THE CONTRACTOR AND HANDED OVER TO THE GOVERNMENT. A
ETHERNET SWITCH. THESE DEVICES SHALL BE DEMOLISHED BY
MCC SECTION 6 IS THE LOCATION OF THE EXISTING PLC AND 1.
SECTION
SCALE: 1/8" = 1'-0"
D6
E-404
D6
E-404
D6
SHEET KEYNOTES
N
N
0 8'4' 16'
0 8'4' 16'
0 8'4' 16'
12"W CABLE TRAY
EXISTING
8" FIRE BRICK WALL
FOR ADDITIONAL INSTRUCTION
SEE SECTION 07 84 00 FIRESTOPPING
RATING OF FIREWALL (6 SLEEVES)
WITH FIRESTOP FOAM TO MAINTAIN
SEAL CABLES IN CONDUIT SLEEVES
IN POWER HOUSE
EXIST. PIPE TRENCH
W
T R
E N
C H
WALL
BUILDING
WALL
BUILDING
2'-0"
W/ALUM. COVER
ELECTRICAL TRENCH
EXISTING 2'-0"W X 1'-8"D
(LOWER TRAY)
ALUMINUM CABLE SUPPORT
EXISTING FABRICATED
CONDUIT SLEEVES THRU FIRE BRICK WALL
EXISTING (8)-4" PVC SCHEDULE 40
AIR/WATER PIPESAIR/WATER PIPES
FIRST FLOOR
POWER HOUSE
18"(W) CABLE TRAY
EXISTING
HORIZONTAL EXPANSION TEE TRAYS
EXISTING 12"X18", 21" RADIUS FIBERGLASS
IN LAND WALL TRENCH
EXISTING TWO 12"W CABLE TRAYS
AIR & WATER LINES
EXISTING PIPE SLEEVES FOR
BRICK WALL FOR UPPER TRAY CABLES
EXISTING (4)-4" CONDUIT SLEEVES THRU FIRE FOR LOWER TRAY CABLES
EXISTING (4)-4" CONDUIT SLEEVES THRU FIRE BRICK WALL
PIPE TRENCH
POWER HOUSE
LANDWALL TRENCH
T R
E N
C H
D E
P T
H
CABLE TRAYS (TYP.)
EXISTING FIBERGLASS
G
AIR/WATER PIPES
EXISTING
8" FIRE BRICK WALL
TRENCH
ELECTRICAL
FIRST FLOOR
POWER HOUSE
(3
P O
W E
R H
O U
S E
D U
E T
O B
O T
T O
M S
L O
P E
E L
E V
A T
IO
N
V A
R
IE
S 12"
(SECTION A1 - LOWER TRAY)
(SECTION A2 - LOWER TRAY)
(SECTION A3 - LOWER TRAY)
EXIST. TRENCH COVER
FV1A
FV2A
FV3A
FV4A
FV1C
FV2C
FV3C
FV4C
FV5A
FV5C
FV6A
FV6C
FV7A
FV7C
FV8A
FV8C
EV1A EV5A
EV1C EV5C
EV2A EV6A
EV2C EV6C
EV3A EV7A
EV3C EV7C
EV4A EV8A
EV4C EV8C
VC1-1
VC1-2
VC1-3
VC1-4
VC2-1
VC2-2
VC2-3
VC2-4
EV1AEV5A
FV1AFV5A
EV1CEV5C
FV1CFV5C
EV2AEV6A
FV2AFV6A
EV2CEV6C
FV2CFV6C
EV3AEV7A
FV3AFV7A
EV3CEV7C
FV3CFV7C
EV4AEV8A
FV4AFV8A
EV4CEV8C
FV4CFV8C
VC1-1 VC1-2
VC1-3 VC1-4
VC2-1 VC2-2
VC2-4
VC2-1
VC2-2
VC2-3
VC2-4
USLWLS USRWLS
DSLWLS DSRWLS
USRWLS
DSLWLS
DSRWLS
USLWLS
DSLWLS
CC1P CC2P
CC1P
CC2P
VC2-3CC2P
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-505
J O
H N
E
N
IT
E S
P
.E
P O
W E
R H
O U
S E
T R
E N
C H
C A
B L
E A
D D
IT
IO
N S
SECTIONS (TYP-LOOKING DOWNSTREAM L.W. TRENCH)
SCALE: 3/4" = 1'-0"E-403
A3 E-403
A2 E-402
A1
E-505
A1
E-505
E6
C1
SCALE: 3/4" = 1'-0"
TRENCH DETAIL "E" PLAN (TRENCH AT POWERHOUSE)
SECTION (CABLE ACCESS AT POWERHOUSE)
SCALE: 3/4" = 1'-0"E-505
A1
SCALE: 3/4" = 1'-0"
SECTION
E-505
E6
1.
OUTLINED IN THIS PROJECT SHALL BE SEALED TO BE WATERTIGHT.
ALL CABLE ENTRIES TO THE POWERHOUSE IMPACTED BY THE WORK
GENERAL SHEET NOTES
2'0 1' 4'
2'0 1' 4'
2'0 1' 4'
2'0 1' 4'
1 1
CROSSOVER TUNNEL
PIPES
EXISTING
CROSSOVER TUNNEL
LANDWALL TRENCH
CABLE SHAFT
EXISTING LANDWALL
EXISTING RIVER WALL
CABLE SHAFT
EXISTING 9"W CABLE TRAYS IN
RIVER WALL TRENCH
LANDWALL TRENCH
EXISTING CABLE TRAYS IN
EXISTING PIPES
EXISTING PIPES
RIVERWALL
EL. 714
CABLE TRAY DROP OUT (TYP)
CABLE SHAFT
EXISTING RIVER WALL
CABLE SHAFT
EXISTING LAND WALL
TOP OF LOCK WALL
TRAYS IN TRENCH
EXISTING CABLE
DROP-OUTS
CABLE TRAY
EL. + 758.50
4' DISTANCE MAX (TYP)
AND CLAMPS, SPACED AT
WITH FIBERGLASS CHANNELS
CABLES SECURED ON WALL
ACCOMMODATE ALL CABLES)
(DOUBLE RACK IF NECESSARY TO
SUPPORT CABLES EVERY 4 FEET
AT EACH SHAFT FOR ALL CABLES.
AND FIBERGLASS CABLE CLAMPS
PROVIDE FIBERGLASS CHANNELS
CABLE TRAYS
EXISTING RIVER WALL
TOP OF LOCK WALLS
RIVERWALL
LAND WALL
CROSSOVER TUNNEL
CABLE TRAYS IN
EXISTING 3-9"W FIBERGLASS
TRAY IN CROSSOVER (TYP)
EXISTING FIBERGLASS CABLE
(UPSTREAM SIDE) (DOWNSTREAM SIDE)
G
G
G
G
G
EXISTING (2)-12"W TEE- TRAYS
CABLE TRAYS IN
EXISTING (2)-12"W
CABLE TRAYS IN
EXISTING (3)-9"W FIBERGLASS
EV1A
EV5A
FV1A
FV5A
EV1C
EV5C
FV1C
FV5C
EV2A
EV6A
FV2A
FV6A
EV2C
EV6C
FV2C
FV6C
EV3A
EV7A
FV3A
FV7A
EV3C
EV7C
FV3C
FV7C
EV4A
EV8A
FV4A
FV8A
EV4C
EV8C
FV4C
FV8C
USRWLS
DSRWLS
FLOW
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-307
J O
H N
E
N
IT
E S
P
.E
C R
O S
S O
V E
R C
A B
L E
A D
D
IT
IO
N
S
SECTION (LOCK CHAMBER CROSSOVER AT TUNNEL LEVEL)
SCALE: NTS
A4 E-307
SECTION
SCALE: NTS
A8 E-307
SECTION
SCALE: NTS
D4 E-307
CABLE TRAYS AT CROSSOVER - PLAN
SCALE: 1/2" -= 1'-0"
0 2' 4'1'
E-307
D4
E-307
A4
E-307
A8
N
2.
ALL CONFINED SPACE REQUIREMENTS.
CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH
ENTRY TO CROSSOVER IS CLASSIFIED AS A CONFINED SPACE. 1.
INFORMATION, SEE SPECIFICATIONS.
WHILE CROSSOVER WORK IS NECESSARY. FOR MORE
PERSONNEL TO HAVE LOCK CHAMBER WATER LEVEL LOWERED
CONTRACTOR. CONTRACTOR SHALL COORDIANTE WITH SITE
CROSSOVER. THIS SHALL BE THE RESPONSIBILITY OF THE
WATER OUT OF ACCESS TO CROSSOVER REQUIRES PUMPING
GENERAL SHEET NOTES
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-308
J O
H N
E N
IT
E
S P
.E
R
IV
E R
W A
L L
T R
E N
C H
D E
T A
IL
A C
T U
A T
O R
S
SECTION
SCALE: NTSE-403
A6
SECTION
SCALE: NTSE-403
C6
T W
E B
E R
M D
E V
IN
E
G
K O
T
REPLACEMENT (TYP FOR 15)
VALVE ACTUATOR CONTROL HEAD FOR DEMOLITION/
REPLACEMENT (TYP FOR 15)
E1
VALVE ACTUATOR HEAD FOR DEMOLITION/
REPLACEMENT
E6
FILL VALVE #1 ACTUATOR HEAD FOR DEMOLITION/
AS EXISITNG.
HEADS IN SAME FASION
MOUNT NEW CONTROL
HEADS TO BE REPLACED.
EXISTING CONTROL
FASION AS EXISTING.
HANDWHEEL IN SAME
REPLACED. MOUNT NEW
REDUCER TO BE
MOUNTED TO GEAR
EXISTING HANDWHEEL
WHEEL.
REPLACEMENT HAND
CONTROL HEAD TO
FROM REPLACEMENT
UMBILICAL CONNECTION
REPLACE BY NEW
DEMOLISHED AND
TO HANDWHEEL. TO BE
FROM CONTROL HEAD
UMBILICAL CONNECTION
CABLING
BY NEW HARDWIRED
DEMOLISHED/REPLACED
CABLING TO BE
CONTROL CONNECTION.
EXISTING DEVICENET
CONTROL HEAD
TO BE REWIRED TO NEW
RETAIN POWER CABLING
OTHER CONDUIT SHALL
DEVICENET CABLING.
VACATED BY DEMOLISHED
THROUGH CONDUIT
CONTROL CABLING
ACCOMODATE. RUN NEW
HEAD IN POSITION TO
ACTUATOR CONTROL
REUSED. MOUNT NEW
EXISTING CONDUIT TO BE
PIPES
EXISTING
EXISTING PIPES
RIVER WALL TRENCH
G
G
2) - 9"W CABLE TRAYS
EXISTING
2)-9"W CABLE TRAYS
EXISTING
FV1A
FV5A
FV1C
FV5C
FV2A
FV6A
FV2C
FV6C
FV3A
FV7A
FV3C
FV7C
FV4A
FV8A
FV4C
FV8C
EV1A EV2A EV3A EV4A
EV1C EV2C EV3C EV4C
EV8AEV7AEV6AEV5A
EV5C EV6C EV7C EV8C
DSRWLS
USRWLS
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E
R T
Y A
V E
N U
E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
480/277V, 3PH, 4W, 60HZ
COMMERCIAL POWER
P.T. AND C.T. CABINET
3PH, 4W, 60HZ
480/277V
230KW
GENERATOR
CONTROL PANEL
GENERATOR
GEN
2-3½"C P1 P1
600AF
600AT
N
3PP2P22-3½"C
JUMPER
#2/0 BONDING
GRD BUS
N
N
S P
A R
E
L O
U V
E R
C N
T R
L
400A
3P, 4W
600A, 480V
SWITCH
TRANSFER
AUTOMATIC
P3 P3 , 2-3 1/2 "C
2-3 1/2"C, P4 P4
IN TRENCH
TO MAIN GROUND
#2/0 AWG GROUND
MOTOR CONTROL CENTER
3P
150AF
20AT
RATIO
3CT'S
600:5
MONITOR
SOLID STATE
POWER LOGIC
SUPPRESSOR
SURGE
TVSS
2PT'S
480/277V, 3PH, 4W
BUS-600A, 42000A RMS BRACING
ULMG
30HP
ACTUATOR
U.S.L.W MITER GATE
URMG
30HP
ACTUATOR
U.S.R.W MITER GATE
DLMG
30HP
ACTUATOR
D.S.L.W MITER GATE
STARTER NEMA SIZE (TYP)
DRMG
30HP
ACTUATOR
D.S.R.W MITER GATE
1 1
3P
150AF
20AT
3P
150AF
20AT
SPACE
SPARE SPARE
C O
N T
IN
U
E D
B E
L O
W L
E F
T
C O
N T
IN
U
E D
A B
O V
E R
IG
H
T
TRANSFORMER
3PH, 4W
480-208/120V
75KVA
"B"
"A" & "B"
LIGHTING PANELS
EXISTING
"A"
TF2 , 2 1/2"C
TF1 , 2 1/2"C
110AT
150AF
3P
13 14
150AF
125AT
3P
AC , 2"C
ENCL.
FUSED, NEMA 1
3 POLE NON-
200A, 600VAC
H.D. SAFETY SW
CONT. PANEL
AIR COMPR
60HP
COMPRESSOR
AIR
3P
15AT
150AF
15 16
3P
150AF
15AT
3P
150AF
15AT
3P
15AT
150AF
1817 19
3P
150AF
15AT
3P
15AT
150AF
20 21
3P
150AF
15AT
3P
15AT
150AF
22 23
3P
150AF
15AT
3P
15AT
150AF
24 25
3P
150AF
15AT 15AT
150AF
3P
26 27
3P
150AF
15AT 15AT
150AF
28 29
3P
150AF
15AT
3P 3P
15AT
150AF
CKT#(B-25,27,29)
LPB
NAV.
CLOCK
NGLNRL
LIGHTS
NAVIGATION
SPARE SPARE
3P
15AT
150AF
31 32
3P
15AT
150AF
C O
N T
IN
U
E D
B E
L O
W L
E F
T
C O
N T
IN
U
E D
A B
O V
E R
IG
H
T
150AF
3P
15AT
SPARE
LIGHTING CONTACTOR (TYP)
LATCH - UNLATCH COILS
MECHANICAL HELD WITH
ELECTRICAL OPERATED
SPARE
3P
150AF
15AT
PUSHBUTTONS (TYP)
ON
OFF
150AF
20AT
1 P
LC
LL1 LL2
LC
1 P
20AT
150AF
OFF
ON
36 37
ON
OFF
1 P
150AF
20AT
LC
LL3 LL4
LC
1 P
20AT
150AF
ON
OFF
38 39
ON
OFF
150AF
20AT
1 P
LC
SPARE
SWITCH
600VAC, SAFETY
NON-FUSIBLE, 60A
LOCAL H.D. TPDT
PUMP NO.1 PUMP NO.2
HP
HP
(5 LOCATIONS)
HOSE CABINETS
STATIONS AT
PUSHBUTTON
REMOTE
STOP
START
SWP1, 1"C SWP2 , 1"C
SWP , 1"C
O.L.
1 1/2"C, TYPICAL FOR
WPC1 WPC2 WPC3 WPC4 WPC5
RESET
O/L
ETM3P
150AF
60AT
RUN
SPACE SPACE
150AF
15AT
2P
MP , 3/4"C
AND DISC. SW.
1 PH
480/120-240V
EXIST. 5KVA XFMR
SPARE
EXISTING
CONTROL PANEL
MYERS PUMP
3P
20AT
150AF
42 43
3P
150AF
20AT
T23
EXISTING
RETRIEVER
EXISTING
JIB CRANE
HP
JC
HP
3P
150AF
20AT
44 45
3P
150AF
100AT
T1
HP
EXISTING
UNIT
HAULAGE
D.S. TOW
EXISTING
UNIT
HAULAGE
U.S. TOW
HP
T11
3P
100AT
150AF
DWG#29/21
SEE
SECTION
PLC
EXISTING
PUMPS
SERVICE WATER
EXISTING
WALL LIGHTS
LOWER GUIDE
EXISTING
WALL LIGHTS
UPPER GUIDE
EXISTING
LOCK LIGHTS
RIVER WALL
EXISTING
LOCK LIGHTS
LAND WALL
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-609
J O
H N
E
N
IT
E S
P
.E
P O
W E
R O
N E
L
IN
E
A1
SCALE: NTS
POWER ONE-LINE DIAGRAM
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P L
O T
D A
T E
W W
N -2
-B
-8
VFD
1 1 1 1
3P
80AT
150AF
ISOLATION
O.L.
(CLOSE)
REVERSE
(OPEN)
FORWARD
BYPASS
3P
150AF
80AT
ISOLATION
O.L.
(OPEN)
FORWARD
(CLOSE)
REVERSE
BYPASS
3P
150AF
80AT
ISOLATION
O.L.
(OPEN)
FORWARD
(CLOSE)
REVERSE
3 3
BYPASS
3P
150AF
80AT
ISOLATION
O.L.
(OPEN)
FORWARD
(CLOSE)
REVERSE
3 3
BYPASS
VFD VFD VFD
3 3 3 3
2 2
#1
2HP
FV1 FV2
2HP
#2 #3
2HP
FV3
2HP
FV4 FV5
2HP
#5#4
FILLING VALVE ACTUATORS
#6
2HP
FV6 FV7
2HP
#7 #8
2HP
FV8 EV1
2HP
#1 #2
2HP
EV2 EV3
2HP
#3 #4
2HP
EV4 EV5
2HP
#5
EMPTYING VALVE ACTUATORS
#6
2HP
EV6 EV7
2HP
#7 #8
2HP
EV8
DETAILS, SEE DWG# E-655, E-656, E-657, AND E-658.
ALSO PROVIDE NEW DOORS FOR REPLACED SECTIONS. FOR WIRING
NEW BUCKETS LOCATED IN EXISTING MCC. CONTRACTOR SHALL
STARTER. NEW MOTOR STARTERS AND VFDs SHALL BE HOUSED IN
CONTRACTOR SHALL REPLACE MITER GATE BYPASS MOTOR 4.
MORE DETAIL.
INTERLOCK SYSTEM. REFER TO DWG# E-628, E-645, & E-646 FOR
CONTROLS FOR MITER GATE BYPASS SHALL BE WIRED INTO NEW 3.
TO DWG# E-308 FOR MORE DETAILS.
MANUFACTURER RECOMMENDATIONS AND DESIGN CRITERIA. REFER
ACTUATOR HEADS AND HANDWHEELS ACCORDING TO
ACTUATOR HEADS AND HANDWHEELS, THEN INSTALL AND WIRE NEW
PROPERTY WITH THE COR. CONTRACTOR SHALL REMOVE EXISTING
SAR10.2/AC01.2). CONTRACTOR SHALL COORDINATE TRANSFER OF
AUMA MULTI-TURN ELECTRIC ACTUATOR CONTROLLERS (PART NO.
HANDWHEELS SHALL BE REPLACED WITH GOVERNMENT FURNISHED
FILLING AND EMPTYING VALVE ACTUATOR CONTROL HEADS AND 2.
VFDs SHALL ALSO HAVE ETHERNET/IP COMMUNICATIONS.
THE EXISTING DYNAMIC BRAKING RESISTOR AND NEW PLC. NEW
LIKE MANUFACTURER AS THE MCC AND SHALL BE COMPATIBLE WITH
EXISTING VFDs SHALL BE REPLACED. REPLACEMENTS SHALL BE OF 1.
SHEET KEYNOTES
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
PROTECTOR
CIRCUIT
MOTOR
T/L3
S/L2
R/L1 2L1
2L2
2L3
MFU
FAN
60HZ
3PH
480VAC
BUS
TO
1L1
1L2
1L3
L1
L2
L3
CB
O
O
O
C
C
C
REVERSING OPEN/CLOSE
MECHANICALLY INTERLOCKED
BYPASS CONTACTOR
OL'S
RESISTOR
DYNAMIC BRAKE
E-NET / IP
W/T3
V/T2
U/T1
3FU
120VAC
1FU 2FU
M
MOTOR
30HP
X2X1
H3H2 H4H1
REACTOR
LINE
3L1
3L2
3L3
GRD
VFD
BYPASS
OFF
U/S R/W MOTOR
OC
C
O
OLC
O
OC (CR265)
OPEN
OC
CONTACTOR
ISOLATION
OUTPUT
CO
120VAC
R
120VAC
G
BYPASS
VFD
INPUT (VFD)
+24VDC
X
X
X
X
X
X INPUT (BYPASS)
INPUT (BYPASS OPEN)
INPUT (BYPASS CLOSE)
REACTOR
LOAD
O
C
(CR266)
CLOSE
2 2
ETHERNET SWITCH IN MCC SECTION 6
ETHERNET CONNECTION FROM
NORMAL DUTY
30 HP
VFD
W
IR
IN
G
D
IA
G R
A M
(S H
E E
T
O F
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-655
J O
H N
E
N
IT
E S
P
.E
R /W
V F
D C
O N
T R
O L
E N
C L
O S
U R
E
A1
SCALE: NTS
U/S R/W MOTOR STARTER WIRING DIAGRAM
GENERAL SHEET NOTES
THE TIME OF INSTALLATION.
(DURATION) SHALL BE DETERMINED AT
THE ACCELERATION/DE-ACCELERATION SPEED AND TIMES
THE VFDS SHALL OPERATE IN CONSTANT TORQUE MODE. 6.
STOP IN THE PLC OR IF THERE IS A VFD FAULT.
THE GATES CANNOT OPERATE IF THERE IS AN ACTIVE E-5.
EXISTING MCC MANUFACTURER.
THE VFD MANUFACTURER SHALL BE THE SAME AS THE 4.
WITH THE MANUFACTURER'S RECOMMENDATIONS.
VFD WIRING AND GROUNDING SHALL BE IN ACCORDANCE 3.
ALL TERMINAL BLOCKS ARE NOT SHOWN FOR CLARITY.2.
WITH THE MANUFACTURER'S GUIDELINES.
ETHERNET COMMUNICATIONS SHALL BE IN ACCORDANCE 1.
INTERLOCK CONTROL PANEL.
SHALL BE LOCATED IN THE NEW BYPASS CONTACTORS
EXTERNAL RELAY CONTACTS FOR CONTROL OF THE 3.
APPLICATION ASSISTANCE.
CONSULT WITH VFD MANUFACTURER FOR SIZING AND
SPECIFIED AT EITHER 3% OR 5%. THE CONTRACTOR SHALL
REQUIRED LINE AND LOAD REACTORS ARE SHOWN BUT 2.
PROVIDING COMPATIBLE VFDS.
REUSED. THE CONTRACTOR IS RESPONSIBLE FOR
EXISTING DYNAMIC BRAKE RESISTORS (DBR) SHALL BE 1.
SHEET KEYNOTES
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
PROTECTOR
CIRCUIT
MOTOR
T/L3
S/L2
R/L1 2L1
2L2
2L3
MFU
FAN
60HZ
3PH
480VAC
BUS
TO
1L1
1L2
1L3
L1
L2
L3
CB
O
O
O
C
C
C
REVERSING OPEN/CLOSE
MECHANICALLY INTERLOCKED
BYPASS CONTACTOR
OL'S
RESISTOR
DYNAMIC BRAKE
E-NET / IP
W/T3
V/T2
U/T1
3FU
120VAC
1FU 2FU
X2X1
H3H2 H4H1
REACTOR
LINE
3L1
3L2
3L3
GRD
VFD
BYPASS
OFF
D/S M/W MOTOR
OC
C
O
OLC
O
OC (CR269)
OPEN
OC
CONTACTOR
ISOLATION
OUTPUT
CO
120VAC
R
120VAC
G
BYPASS
VFD
INPUT (VFD)
+24VDC
X
X
X
X
X
X INPUT (BYPASS)
INPUT (BYPASS OPEN)
INPUT (BYPASS CLOSE)
REACTOR
LOAD
O
C
(CR270)
CLOSE
M
MOTOR
30HP
ETHERNET SWITCH IN MCC SECTION 6
ETHERNET CONNECTION FROM
NORMAL DUTY
30 HP
VFD
W
IR
IN
G
D
IA
G R
A M
(S H
E E
T
O F
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-656
J O
H N
E
N
IT
E S
P
.E
R /W
V F
D C
O N
T R
O L
E N
C L
O S
U R
E
A1
SCALE: NTS
D/S R/W MOTOR STARTER WIRING DIAGRAM
GENERAL SHEET NOTES
INTERLOCK CONTROL PANEL.
SHALL BE LOCATED IN THE NEW BYPASS CONTACTORS
EXTERNAL RELAY CONTACTS FOR CONTROL OF THE 3.
APPLICATION ASSISTANCE.
CONSULT WITH VFD MANUFACTURER FOR SIZING AND
SPECIFIED AT EITHER 3% OR 5%. THE CONTRACTOR SHALL
REQUIRED LINE AND LOAD REACTORS ARE SHOWN BUT 2.
PROVIDING COMPATIBLE VFDS.
REUSED. THE CONTRACTOR IS RESPONSIBLE FOR
EXISTING DYNAMIC BRAKE RESISTORS (DBR) SHALL BE 1.
INSTALLATION.
(DURATION) SHALL BE DETERMINED AT THE TIME OF
THE ACCELERATION/DE-ACCELERATION SPEED AND TIMES
THE VFDS SHALL OPERATE IN CONSTANT TORQUE MODE. 6.
STOP IN THE PLC OR IF THERE IS A VFD FAULT.
THE GATES CANNOT OPERATE IF THERE IS AN ACTIVE E-5.
EXISTING MCC MANUFACTURER.
THE VFD MANUFACTURER SHALL BE THE SAME AS THE 4.
WITH THE MANUFACTURER'S RECOMMENDATIONS.
VFD WIRING AND GROUNDING SHALL BE IN ACCORDANCE 3.
ALL TERMINAL BLOCKS ARE NOT SHOWN FOR CLARITY.2.
WITH THE MANUFACTURER'S GUIDELINES.
ETHERNET COMMUNICATIONS SHALL BE IN ACCORDANCE 1.
SHEET KEYNOTES
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
PROTECTOR
CIRCUIT
MOTOR
T/L3
S/L2
R/L1 2L1
2L2
2L3
MFU
FAN
60HZ
3PH
480VAC
BUS
TO
1L1
1L2
1L3
L1
L2
L3
CB
O
O
O
C
C
C
REVERSING OPEN/CLOSE
MECHANICALLY INTERLOCKED
BYPASS CONTACTOR
OL'S
RESISTOR
DYNAMIC BRAKE
W/T3
V/T2
U/T1
3FU
120VAC
1FU 2FU
X2X1
H3H2 H4H1
REACTOR
LINE
3L1
3L2
3L3
GRD
VFD
BYPASS
OFF
U/S L/W MOTOR
OC
C
O
OLC
O
OC
OC
CONTACTOR
ISOLATION
OUTPUT
CO
120VAC
R
120VAC
G
BYPASS
VFD
INPUT (VFD)
+24VDC
X
X
X
X
X
X INPUT (BYPASS)
INPUT (BYPASS OPEN)
INPUT (BYPASS CLOSE)
REACTOR
LOAD
O
C
M
MOTOR
30HP
E-NET / IP
ETHERNET SWITCH IN MCC SECTION 6
ETHERNET CONNECTION FROM
(CR263)
OPEN
(CR264)
CLOSE
NORMAL DUTY
30 HP
VFD
W
IR
IN
G
D
IA
G R
A M
(S H
E E
T
O F
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-657
J O
H N
E
N
IT
E S
P
.E
L /W
V F
D C
O N
T R
O L
E N
C L
O S
U R
E
A1
SCALE: NTS
U/S L/W MOTOR STARTER WIRING DIAGRAM
GENERAL SHEET NOTES
INTERLOCK CONTROL PANEL.
SHALL BE LOCATED IN THE NEW BYPASS CONTACTORS
EXTERNAL RELAY CONTACTS FOR CONTROL OF THE 3.
AND APPLICATION ASSISTANCE.
SHALL CONSULT WITH VFD MANUFACTURER FOR SIZING
SPECIFIED AT EITHER 3% OR 5%. THE CONTRACTOR
REQUIRED LINE AND LOAD REACTORS ARE SHOWN BUT 2.
PROVIDING COMPATIBLE VFDS.
REUSED. THE CONTRACTOR IS RESPONSIBLE FOR
EXISTING DYNAMIC BRAKE RESISTORS (DBR) SHALL BE 1.
INSTALLATION.
(DURATION) SHALL BE DETERMINED AT THE TIME OF
THE ACCELERATION/DE-ACCELERATION SPEED AND TIMES
THE VFDS SHALL OPERATE IN CONSTANT TORQUE MODE. 6.
STOP IN THE PLC OR IF THERE IS A VFD FAULT.
THE GATES CANNOT OPERATE IF THERE IS AN ACTIVE E-5.
EXISTING MCC MANUFACTURER.
THE VFD MANUFACTURER SHALL BE THE SAME AS THE 4.
WITH THE MANUFACTURER'S RECOMMENDATIONS.
VFD WIRING AND GROUNDING SHALL BE IN ACCORDANCE 3.
ALL TERMINAL BLOCKS ARE NOT SHOWN FOR CLARITY. 2.
WITH THE MANUFACTURER'S GUIDELINES.
ETHERNET COMMUNICATIONS SHALL BE IN ACCORDANCE 1.
SHEET KEYNOTES
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
C H
E C
K E
D B
Y
S U
B M
IT
T
E D
B Y
S I Z
E
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
®of Engineers
US Army Corps
/2
/2
P
IT
T S
B U
R G
H D
IS
T
R
IC
T
A N
S I
D
L
IB
E R
T Y
A V
E N
U E
P
IT
T S
B U
R G
H P
A
P L
O T
D A
T
L E
G H
E N
Y R
IV
E
R B
A S
IN
A L
L E
G H
E N
Y L
O C
K
L O
C K
C O
N T
R O
L S
Y S
T E
M M
O D
E R
N
IZ
A T
W
N -2
-B
-8
PROTECTOR
CIRCUIT
MOTOR
T/L3
S/L2
R/L1 2L1
2L2
2L3
MFU
FAN
60HZ
3PH
480VAC
BUS
TO
1L1
1L2
1L3
L1
L2
L3
CB
O
O
O
C
C
C
REVERSING OPEN/CLOSE
MECHANICALLY INTERLOCKED
BYPASS CONTACTOR
OL'S
RESISTOR
DYNAMIC BRAKE
W/T3
V/T2
U/T1
3FU
120VAC
1FU 2FU
X2X1
H3H2 H4H1
REACTOR
LINE
3L1
3L2
3L3
GRD
VFD
BYPASS
OFF
D/S L/W MOTOR
OC
C
O
OLC
O
OC
OC
CONTACTOR
ISOLATION
OUTPUT
CO
120VAC
R
120VAC
G
BYPASS
VFD
INPUT (VFD)
+24VDC
X
X
X
X
X
X INPUT (BYPASS)
INPUT (BYPASS OPEN)
INPUT (BYPASS CLOSE)
REACTOR
LOAD
O
C
M
MOTOR
30HP
E-NET / IP
ETHERNET SWITCH IN MCC SECTION 6
ETHERNET CONNECTION FROM
(CR268)
CLOSE
(CR267)
OPEN
NORMAL DUTY
30 HP
VFD
W
IR
IN
G
D
IA
G R
A M
(S H
E E
T
O F
T
W E
B E
R
M
D E
V
IN
E
G K
O T
R
A W
IN
G
R E
V
IS
E D
P E
R A
M E
N D
M E
N T
Y
E-658
J O
H N
E
N
IT
E S
P
.E
L /W
V F
D C
O N
T R
O L
E N
C L
O S
U R
E
A1
SCALE: NTS
D/S L/W MOTOR STARTER WIRING DIAGRAM
GENERAL SHEET NOTES
INTERLOCK CONTROL PANEL.
SHALL BE LOCATED IN THE NEW BYPASS CONTACTORS
EXTERNAL RELAY CONTACTS FOR CONTROL OF THE 3.
APPLICATION ASSISTANCE.
CONSULT WITH VFD MANUFACTURER FOR SIZING AND
SPECIFIED AT EITHER 3% OR 5%. THE CONTRACTOR SHALL
REQUIRED LINE AND LOAD REACTORS ARE SHOWN BUT 2.
PROVIDING COMPATIBLE VFDS.
REUSED. THE CONTRACTOR IS RESPONSIBLE FOR
EXISTING DYNAMIC BRAKE RESISTORS (DBR) SHALL BE 1.
INSTALLATION.
(DURATION) SHALL BE DETERMINED AT THE TIME OF
THE ACCELERATION/DE-ACCELERATION SPEED AND TIMES
THE VFDS SHALL OPERATE IN CONSTANT TORQUE MODE. 6.
STOP IN THE PLC OR IF THERE IS A VFD FAULT.
THE GATES CANNOT OPERATE IF THERE IS AN ACTIVE E-5.
EXISTING MCC MANUFACTURER.
THE VFD MANUFACTURER SHALL BE THE SAME AS THE 4.
WITH THE MANUFACTURER'S RECOMMENDATIONS.
VFD WIRING AND GROUNDING SHALL BE IN ACCORDANCE 3.
ALL TERMINAL BLOCKS ARE NOT SHOWN FOR CLARITY.2.
WITH THE MANUFACTURER'S GUIDELINES.
ETHERNET COMMUNICATIONS SHALL BE IN ACCORDANCE 1.
SHEET KEYNOTES
| Contract Drawings - W911WN21B8005-0001 Scale Drawings |
| E-401_0001 |
| E-402_0001 |
| E-403_0001 |
| E-404_0001 |
| E-505_0001 |
| E-307_0001 |
| E-308_0001 |
| Contract Drawings - W911WN21B8005-0001 |
| E-609_0001 |
| E-655_0001 |
| E-656_0001 |
| E-657_0001 |
| E-658_0001 |
File details come from the government source that posted it. Updated .