W911SG24Q0074 0002 Amendment.pdf

PDF 146 KB Posted

Attached to
Ventilated Enclosure/Paint Booth Federal contract opportunity
Solicitation number
W911SG24Q0074
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood

About this file

This document is an amendment to Solicitation W911SG24Q0074, which is for an Air Filtration System Requirements (Ventilated Enclosure/Paint Booth).

The key details are:

  • The offer due date has been extended from 27 June 2024 to 28 June 2024.
  • The Product Description has been updated with detailed requirements for the ventilation system, including minimum cross-sectional velocities, exhaust system specifications, enclosure requirements, fire suppression, replacement filters, lighting, and warranty. The requirements are based on ACGIH, ANSI/ASSP, and NESHAP standards.
  • All other terms and conditions remain unchanged. The solicitation is being issued by the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort Hood.

View the file

Other files for this federal contract opportunity

Other files attached to Ventilated Enclosure/Paint Booth, newest first.
File Type Posted
W911SG24Q0074 0003 Conformed.pdf PDF
W911SG24Q0074 0003 Amendment.pdf PDF
W911SG24Q0074 0002 Conformed.pdf PDF
Vendor Questions with Answers (Updated 6.27.24).docx DOCX document
W911SG24Q0074001 Conformed.pdf PDF
W911SG24Q0074 001 Amendment.pdf PDF
Vendor Questions with Answers.docx DOCX document
booth location.pdf PDF
W911SG24Q0074 (Ventilation Paint System).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

0012110055

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provi ded herei n, all t erms and condit ions of t he document referenced in Item 9A or 10A, as heretofore changed, remai ns unchanged and in ful l force and effect .

15A. NAME AND TIT LE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

ST ANDARD FORM 30 (Rev. 10-83) Prescr ibed by GSA

FAR (48 CFR) 53.243

The purpose of this amendment is to update the Product Description.

A. The offer due date is extended from 27 June 2024 at 4:00 PM MST to 28 June 2024 at 4:00 PM MST.

B. The Product Description has been updated.

C. All other terms and conditions remain in effect and unchanged.

1. CONTRACT ID CODE P AGE OF P AGES

J 1 3

16A. NAME AND T ITLE OF CONTRACTING OFFICER (Type or print)

16C. DAT E SIGNED

BY 27-Jun-2024

16B. UNITED ST AT ES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contract ing Officer)(Signature of person author ized t o sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, Count y, Stat e and Zip Code) X W911SG24Q0074

X 9B. DAT ED (SEE IT EM 11)

14-Jun-2024

10B. DAT ED (SEE IT EM 13)

9A. AMENDMENT OF SOLICITAT ION NO.

11. THIS IT EM ONLY APPLIES T O AMENDMENT S OF SOLICITATIONS

X The above numbered soli cit ati on i s amended as set forth in It em 14. The hour and date specified for rece ipt of Offer X is ext ended, is not extended.

Offer must acknowl edge rece ipt of t his amendment pri or to the hour and date specified in the sol ici tat ion or as amended by one of t he fol lowing methods:

(a) By compl eti ng Items 8 and 15, and returning 1 copi es of the amendment ; (b) By acknowledgi ng recei pt of thi s amendment on each copy of t he offer submit ted;

or (c) By s epara te let ter or t elegram whi ch i ncludes a refe rence t o t he s olic ita tion and amendment numbers . FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE P LACE DESIGNATED FOR THE RECEIPT OF OFFERS P RIOR TO THE HOUR AND DATE SP ECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of thi s amendment you desire t o change an offer already submit ted, s uch change may be made by t elegram or let ter, provided each t elegram or l ett er makes re ference to the sol ici tat ion and this amendment , and is received prior to the openi ng hour and dat e speci fi ed.

12. ACCOUNTING AND APPROPRIATION DAT A (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORT H IN ITEM 14 ARE MADE IN THE

CONT RACT ORDER NO. IN ITEM 10A.

B. T HE ABOVE NUMBERED CONT RACT /ORDER IS MODIFIED T O REFLECT THE ADMINIST RATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORT H IN ITEM 14, PURSUANT TO T HE AUTHORITY OF FAR 43.103(B).

C. T HIS SUPPLEMENT AL AGREEMENT IS ENT ERED INTO PURSUANT TO AUTHORITY OF:

D. OT HER (Specify type of modification and authorit y)

E. IMPORTANT: Contract or is not, is required to sign this document and return copies t o the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/cont ract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/ MODIFICATION NO. 5. P ROJECT NO.(If appli cable )

6. ISSUED BY

3. EFFECTIVE DATE

27-Jun-2024

CODE

MICC - FORT BLISS (919TH CBN)

111 PERSHING RD

FT BLISS TX 79916

W911SG 7. ADMINISTERED BY (If other t han item 6)

4. REQUISITION/P URCHASE REQ. NO.

CODE

See I tem 6

FACILITY CODECODE

EMAIL:TEL:

W911SG24Q0074

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 1449 - CONTINUATION SHEET

SOLICITATION/CONTRACT FORM

The required response date/time has changed from 27-Jun-2024 04:00 PM to 28-Jun-2024 04:00 PM.

The following have been modified:

PRODUCT DESCRIPTION

Product Description

AIR FILTRATION SYSTEM REQUIREMENTS

(VENTILATED ENCLOSURE/PAINT BOOTH)

Many ventilation systems exist and could potentially be used to control the Cr(VI) hazard during aviation maintenance processes. Selection should be done in collaboration with Industrial Hygiene and Safety professionals to ensure the ventilation system meets minimum design criteria.

Defense Centers for Public Health-Aberdeen recommends the following minimum design criteria:

• American Conference of Governmental Hygienists (ACGIH)® Industrial Ventilation Manual Figure VS-75-01 Large Paint Booth: Minimum cross-sectional velocity of 100 feet per minute (fpm) for a large deep booth with a cross-sectional area greater than 150 square feet (ft2). Airless electrostatic and high velocity low pressure spray paint operations require an air velocity of 100 fpm.

• ACGIH® Industrial Ventilation Manual Figure VS-80-01 Abrasive Blasting Room: Cross-sectional minimum velocity of 100 fpm. • American National Standards Institute/American Society of Safety Professionals (ANSI/ASSP) Z9.4-201 I (R2021): Requires a cross-sectional velocity of 100 fpm.

Exhaust System

- 18,000 Cubic Feet per Minute or higher to achieve ACGIH recommended TLVs

- Must verify accurate testing and sampling data that system will provide clean air below the ACGIH TLVs of 0.0002mg/m3

- Multi-stage Particulate filtration exceeds the National Emission Standards for Hazardous Air Pollutants

(NESHAP) 319 to ensure Soldiers working outside of the enclosure are not exposed to hexavalent chromium levels in excess of .0002mg/m3.

Enclosure

- Enclosure must be Cross Draft Negative

- Material NFPA 701 Compliant

- Recommend size: 10’H X 18’W X 45”L (based on hangar size and unit requirements)

Fire Suppression

- Dry Chemical to protect both the enclosure and exhaust

- Pre-engineered meeting NFPA 17 Standard for Dry Chemical extinguishing

Replacement Filters

- 18 Month Supply

Lighting

- Eight (8) Lights: 10,000 lumens per light

Warranty

- 5-year warranty

W911SG24Q0074

(End of Summary of Changes)