SECTION 03 30 00 Page 1
SECTION 03 30 00
CAST-IN-PLACE CONCRETE
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONCRETE INSTITUTE INTERNATIONAL (ACI)
ACI 117 (2010; Errata 2011) Specifications for Tolerances for
Concrete Construction and Materials and Commentary
ACI 121R (2008) Guide for Concrete Construction Quality
Systems in Conformance with ISO 9001
ACI 211.1 (1991; R 2009) Standard Practice for Selecting Proportions for Normal, Heavyweight and Mass Concrete
ACI 211.2 (1998; R 2004) Standard Practice for
Selecting Proportions for Structural Lightweight
ACI 213R (2014; E2017) Guide for Structural
Lightweight-Aggregate Concrete
ACI 301 (2016) Specifications for Structural Concrete
ACI 302.1R (2015) Guide for Concrete Floor and Slab Construction
ACI 304.2R (2017) Guide to Placing Concrete by Pumping
Methods
ACI 304R (2000; R 2009) Guide for Measuring, Mixing, Transporting, and Placing Concrete
ACI 305R (2010) Guide to Hot Weather Concreting
ACI 306.1 (1990; R 2002) Standard Specification for Cold
Weather Concreting
ACI 306R (2016) Guide to Cold Weather Concreting
ACI 308.1 (2011) Specification for Curing Concrete
ACI 318 (2014; Errata 1-2 2014; Errata 3-5 2015;
Errata 6 2016; Errata 7-9 2017) Building Code Requirements for Structural Concrete (ACI 318-14)
SECTION 03 30 00 Page 2 and Commentary (ACI 318R-14)
ACI 347R (2014; Errata 1 2017) Guide to Formwork for
ACI SP-15 (2011) Field Reference Manual: Standard
Specifications for Structural Concrete ACI 301-05 with Selected ACI References
ACI SP-2 (2007; Abstract: 10th Edition) ACI Manual of Concrete
Inspection
ACI SP-66 (2004) ACI Detailing Manual
AMERICAN WELDING SOCIETY (AWS)
AWS D1.4/D1.4M (2011) Structural Welding Code - Reinforcing Steel
ASTM INTERNATIONAL (ASTM)
ASTM A1064/A1064M (2017) Standard Specification for Carbon-Steel
Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A615/A615M (2016) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
ASTM A706/A706M (2016) Standard Specification for
Low-Alloy Steel Deformed and Plain Bars for Concrete Reinforcement
ASTM A767/A767M (2016) Standard Specification for
Zinc-Coated (Galvanized) Steel Bars for Concrete Reinforcement
ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of
Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A934/A934M (2016) Standard Specification for Epoxy-
Coated Prefabricated Steel Reinforcing Bars
ASTM A955/A955M (2018) Standard Specification for Deformed and Plain
Stainless-Steel Bars for Concrete Reinforcement
ASTM A996/A996M (2016) Standard Specification for Rail-Steel and Axle-Steel Deformed Bars for
SECTION 03 30 00 Page 3
Concrete Reinforcement
ASTM C1017/C1017M (2013; E 2015) Standard Specification for Chemical Admixtures for Use in Producing Flowing Concrete
ASTM C1077 (2017) Standard Practice for Agencies Testing
Concrete and Concrete Aggregates for Use in Construction and Criteria for Testing Agency Evaluation
ASTM C1107/C1107M (2017) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM C1116/C1116M (2010a; R 2015) Standard Specification for Fiber- Reinforced Concrete
ASTM C1157/C1157M (2017) Standard Performance Specification for
Hydraulic Cement
ASTM C1218/C1218M (2017) Standard Test Method for Water-Soluble Chloride in Mortar and Concrete
ASTM C1240 (2014) Standard Specification for Silica
Fume Used in Cementitious Mixtures
ASTM C1260 (2014) Standard Test Method for Potential Alkali Reactivity of Aggregates (Mortar-Bar Method)
ASTM C138/C138M (2017a) Standard Test Method for Density (Unit
Weight), Yield, and Air Content (Gravimetric) of
ASTM C143/C143M (2015) Standard Test Method for Slump of
Hydraulic-Cement Concrete
ASTM C150/C150M (2018) Standard Specification for Portland Cement
ASTM C1567 (2013) Standard Test Method for Potential Alkali- Silica Reactivity of Combinations of Cementitious Materials and Aggregate (Accelerated Mortar-Bar Method)
ASTM C1602/C1602M (2012) Standard Specification for Mixing Water Used in Production of Hydraulic Cement Concrete
ASTM C172/C172M (2017) Standard Practice for Sampling Freshly Mixed Concrete
ASTM C173/C173M (2016) Standard Test Method for Air Content of
Freshly Mixed Concrete by the Volumetric Method
ASTM C192/C192M (2016a) Standard Practice for Making and Curing Concrete Test Specimens in the Laboratory
SECTION 03 30 00 Page 4
ASTM C231/C231M (2017a) Standard Test Method for Air Content of
Freshly Mixed Concrete by the Pressure Method
ASTM C260/C260M (2010a; R 2016) Standard Specification for Air- Entraining Admixtures for Concrete
ASTM C295/C295M (2012) Petrographic Examination of
Aggregates for Concrete
ASTM C31/C31M (2018a) Standard Practice for Making and Curing Concrete Test Specimens in the Field
ASTM C311/C311M (2017) Standard Test Methods for Sampling and
Testing Fly Ash or Natural Pozzolans for Use in Portland-Cement Concrete
ASTM C33/C33M (2018) Standard Specification for Concrete Aggregates
ASTM C330/C330M (2017a) Standard Specification for Lightweight
Aggregates for Structural Concrete
ASTM C39/C39M (2018) Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
ASTM C42/C42M (2018) Standard Test Method for Obtaining and
Testing Drilled Cores and Sawed Beams of Concrete
ASTM C494/C494M (2017) Standard Specification for Chemical Admixtures for Concrete
ASTM C552 (2017; E 2018) Standard Specification for Cellular
Glass Thermal Insulation
ASTM C567/C567M (2014) Determining Density of Structural Lightweight
ASTM C578 (2018) Standard Specification for Rigid, Cellular
Polystyrene Thermal Insulation
ASTM C591 (2017) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C595/C595M (2018) Standard Specification for Blended Hydraulic
Cements
ASTM C618 (2017a) Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in
ASTM C78/C78M (2018) Standard Test Method for Flexural Strength of Concrete (Using Simple Beam with Third-Point Loading)
ASTM C920 (2018) Standard Specification for
SECTION 03 30 00 Page 5
Elastomeric Joint Sealants
ASTM C94/C94M (2017a) Standard Specification for Ready- Mixed Concrete
ASTM C989/C989M (2018) Standard Specification for Slag Cement for
Use in Concrete and Mortars
ASTM D1751 (2004; E 2013; R 2013) Standard Specification for Preformed Expansion Joint Filler for Concrete Paving and Structural Construction (Nonextruding and Resilient Bituminous Types)
ASTM D1752 (2004a; R 2013) Standard Specification for Preformed
Sponge Rubber Cork and Recycled PVC Expansion
ASTM D2628 (1991; R 2016) Standard Specification for Preformed Polychloroprene Elastomeric Joint Seals for Concrete Pavements
ASTM D2835 (1989; R 2017) Standard Specification for Lubricant for Installation of Preformed Compression Seals in Concrete Pavements
ASTM D412 (2016) Standard Test Methods for Vulcanized
Rubber and Thermoplastic Elastomers - Tension
ASTM D471 (2016a) Standard Test Method for Rubber Property
- Effect of Liquids
ASTM D5759 (2012) Characterization of Coal Fly Ash and Clean Coal Combustion Fly Ash for Potential Uses
ASTM D6690 (2015) Standard Specification for Joint and Crack
Sealants, Hot Applied, for Concrete and Asphalt Pavements
ASTM E1155 (2014) Standard Test Method for Determining
Floor Flatness and Floor Levelness Numbers
ASTM E1643 (2018a) Standard Practice for Selection, Design, Installation, and Inspection of Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs
ASTM E1745 (2017) Standard Specification for Water Vapor
Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
ASTM E1993/E1993M (1998; R 2013; E 2013) Standard
Specification for Bituminous Water Vapor Retarders Used in Contact with Soil or Granular Fill Under Concrete Slabs
ASTM E329 (2018) Standard Specification for Agencies Engaged in
SECTION 03 30 00 Page 6 the Testing and/or Inspection of Materials Used in Construction
ASTM E96/E96M (2016) Standard Test Methods for Water Vapor
Transmission of Materials
CONCRETE REINFORCING STEEL INSTITUTE (CRSI)
CRSI 10MSP (2009; 28th Ed; Errata) Manual of Standard Practice
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST PS 1 (2009) DOC Voluntary Product Standard PS 1-07, Structural Plywood
U.S. ARMY CORPS OF ENGINEERS (USACE)
COE CRD-C 513 (1974) Corps of Engineers Specifications for Rubber
Waterstops COE CRD-C 572 (1974) Corps of Engineers Specifications for
Polyvinylchloride Waterstops
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS SS-S-200 (Rev E; Am 1; Notice 1) Sealant, Joint, Two- Component, Jet-Blast-Resistant, Cold-Applied, for Portland Cement Concrete Pavement
1.2 DEFINITIONS
a. "Cementitious material" as used herein must include all portland cement, pozzolan, fly ash, ground granulated blast-furnace slag.
b. "Exposed to public view" means situated so that it can be seen from eye level from a public location after completion of the building. A public location is accessible to persons not responsible for operation or maintenance of the building.
c. "Chemical admixtures" are materials in the form of powder or fluids that are added to the concrete to give it certain characteristics not obtainable with plain concrete mixes.
d. "Supplementary cementing materials" (SCM) include coal fly ash, [silica fume, ]granulated blast-furnace slag, natural or calcined pozzolans, and ultra-fine coal ash when used in such proportions to replace the portland cement that result in improvement to sustainability and durability and reduced cost.
e. "Design strength" (f'c) is the specified compressive strength of concrete at time(s) specified in this section to meet structural design criteria.
f. "Mass Concrete" is any concrete system that approaches a maximum temperature of 158 degrees F within the first 72 hours of placement. In addition, it includes all concrete elements with a section thickness of 3 feet or more regardless of temperature.
g. "Mixture proportioning" is the process of designing concrete mixture proportions to enable it to meet the strength, service life and constructability requirements of the project while
SECTION 03 30 00 Page 7 minimizing the initial and life-cycle cost.
h. "Mixture proportions" are the masses or volumes of individual ingredients used to make a unit measure (cubic yard) of concrete.
i. "Pozzolan" is a siliceous or siliceous and aluminous material, which in itself possesses little or no cementitious value but will, in finely divided form and in the presence of moisture, chemically react with calcium hydroxide at ordinary temperatures to form compounds possessing cementitious properties.
j. "Workability (or consistence)" is the ability of a fresh (plastic) concrete mix to fill the form/mould properly with the desired work (vibration) and without reducing the concrete's quality. Workability depends on water content, chemical admixtures, aggregate (shape and size distribution), cementitious content and age (level of hydration).
1.3 SUBMITTALS
Submit the following in accordance with submittal procedures in scope of work.
SD-01 Preconstruction Submittals
Concrete Curing Plan Quality Control Plan;
Quality Control Personnel Certifications;
Quality Control Laboratory Accreditation
SD-02 Shop Drawings
Formwork
Reinforcing Steel SD-03 Product Data
Joint Sealants Joint Filler Materials for Forms Cementitious Materials
Vapor Retarder [and Vapor Barrier] Concrete Curing Materials Reinforcement Liquid Chemical Floor Hardener Admixtures
Synthetic Reinforcing Fibers
Mechanical Reinforcing Bar Connectors Waterstops Biobased Content for Form Release Agent
SD-04 Design Data
Concrete Mix Design;
SD-05 Test Reports
SECTION 03 30 00 Page 8
Concrete Mix Design;
Fly Ash Pozzolan
Ground Granulated Blast-Furnace Slag Aggregates
Fiber-Reinforced Concrete;
Tolerance Report
Compressive Strength Tests;
Unit Weight of Structural Concrete Air Content
Slump Tests
Water SD-07 Certificates Reinforcing
Bars Welder Qualifications
1.4 MODIFICATION OF REFERENCES
Accomplish work in accordance with ACI publications except as modified herein. Consider the advisory or recommended provisions to be mandatory. Interpret reference to the "Building Official," the "Structural Engineer," and the "Architect/Engineer" to mean the Contracting Officer.
1.5 DELIVERY, STORAGE, AND HANDLING
Follow ACI 301, ACI 304R and ASTM A934/A934M requirements and recommendations. Do not deliver concrete until vapor retarder, [vapor barrier,] forms, reinforcement, embedded items, and chamfer strips are in place and ready for concrete placement. Do not store concrete curing compounds or sealers with materials that have a high capacity to adsorb volatile organic compound (VOC) emissions. Do not store concrete curing compounds or sealers in occupied spaces.
1.5.1 Reinforcement
Store reinforcement of different sizes and shapes in separate piles or racks raised above the ground to avoid excessive rusting. Protect from contaminants such as grease, oil, and dirt.
Ensure bar sizes can be accurately identified after bundles are broken and tags removed.
1.5.1.1 Epoxy Coated Reinforcing Steel
Record coating lot on each shipping notice and carefully identify and re-tag bar bundles from bending plant. Provide systems for handling coated bars which have padded contact areas such as, nylon slings, all free of dirt and grit. Lift bundled coated bars with strong back, multiple supports, or platform bridge to prevent sagging and abrasion. Pad bundling bands where in contact with bars. Do not drop or drag bars or bundles. Store coated bars both in shop and in field, aboveground, on wooden or padded cribbing. Space the dunnage close enough to prevent excessive sags. Stack large quantities of straight bars with adequate protective blocking between layers. Schedule deliveries of epoxy coated bars to the job site to avoid the need for long term storage. Protect from direct sunlight and weather. Cover bars to be stored longer than 12 hours at the job site with opaque polyethylene sheeting or other suitable equivalent protective material.
SECTION 03 30 00 Page 9
1.6 QUALITY ASSURANCE
1.6.1 Design Data
1.6.1.1 Formwork Calculations
ACI 347R. Include design calculations indicating arrangement of forms, sizes and grades of supports (lumber), panels, and related components. Furnish drawings and calculations of shoring and re-shoring methods proposed for floor and roof slabs, spandrel beams, and other horizontal concrete members. Calculations must indicate concrete pressure with both live and dead loads, along with material types.
1.6.1.2 Concrete Mix Design
Thirty days minimum prior to concrete placement, submit a mix design for each strength and type of concrete. Submit a complete list of materials including type; brand; source and amount of cement, complementary cementitious materials, [polypropylene fibers], and admixtures; and applicable reference specifications. Submit mill test and all other test for cement, complementary cementitious materials, aggregates, and admixtures. Provide documentation of maximum nominal aggregate size, gradation analysis, percentage retained and passing sieve, and a graph of percentage retained verses sieve size. Provide mix proportion data using at least three different water-cementitious material ratios for each type of mixture, which produce a range of strength encompassing those required for each type of concrete required. If source material changes, resubmit mix proportion data using revised source material. Provide only materials that have been proven by trial mix studies to meet the requirements of this specification, unless otherwise approved in writing by the Contracting Officer. Indicate clearly in the submittal where each mix design is used when more than one mix design is submitted. Resubmit data on concrete components if the qualities or source of components changes. For previously approved concrete mix designs used within the past twelve months, the previous mix design may be re-submitted without further trial batch testing if accompanied by material test data conducted within the last six months. Obtain mix design approval from the contracting officer prior to concrete placement.
1.6.2 Shop Drawings
1.6.2.1 Formwork
Drawings showing details of formwork including, but not limited to; joints, supports, studding and shoring, and sequence of form and shoring removal. Indicate placement schedule, construction, location and method of forming control joints. Include locations of inserts, conduit, sleeves and other embedded items. Reproductions of contract drawings are unacceptable. Submit form removal schedule indicating element and minimum length of time for form removal.
Design, fabricate, erect, support, brace, and maintain formwork so that it is capable of supporting without failure all vertical and lateral loads that may reasonably be anticipated to be applied to the formwork.
1.6.2.2 Reinforcing Steel
ACI SP-66. Indicate bending diagrams, assembly diagrams, splicing and laps of bars, shapes, dimensions, and details of bar reinforcing, accessories, and concrete cover. Do not scale dimensions from structural drawings to determine lengths of reinforcing bars. Reproductions of contract drawings are unacceptable.
SECTION 03 30 00 Page 10
1.6.3 Control Submittals
1.6.3.1 Concrete Curing Plan
Submit proposed materials, methods and duration for curing concrete elements in accordance with
ACI 308.1.
1.6.3.2 Pumping Concrete
Submit proposed materials and methods for pumping concrete. Submittal must include mix designs, pumping equipment including type of pump and size and material for pipe, and maximum length and height concrete is to be pumped.
1.6.3.3 VOC Content for Form Release Agents, Curing Compounds, and Penetrating Sealers
Submit certification for the form release agent, curing compounds, and concrete penetrating sealers that indicate the VOC content of each product.
1.6.3.4 Safety Data Sheets
Submit Safety Data Sheets (SDS) for all materials that are regulated for hazardous health effects.
SDS must be readily accessible during each work shift to employees when they are at the construction site.
1.6.4 Test Reports
1.6.4.1 Fly Ash and Pozzolan
Submit test results in accordance with ASTM C618 for fly ash and pozzolan. Submit test results performed within 6 months of submittal date.
1.6.4.2 Ground Granulated Blast-Furnace Slag
Submit test results in accordance with ASTM C989/C989M for ground granulated blast-furnace slag. Submit test results performed within 6 months of submittal date.
1.6.4.3 Aggregates
ASTM C1260 for potential alkali-silica reactions, ASTM C295/C295M for petrographic analysis.
1.6.4.4 Fiber-Reinforced Concrete
Test to determine flexural toughness index I5 in accordance with ASTM C1116/C1116M.
1.6.5 Quality Control Plan
Develop and submit for approval a concrete quality control program in accordance with the guidelines of ACI 121R and as specified herein. The plan must include approved laboratories.
Provide direct oversight for the concrete qualification program inclusive of associated sampling and testing. All quality control reports must be provided to the Contracting Officer, Quality Manager and Concrete Supplier. Maintain a copy of ACI SP-15 and CRSI 10MSP at project site.
1.6.6 Quality Control Personnel Certifications
SECTION 03 30 00 Page 11
The contractor must submit for approval the responsibilities of the various quality control personnel, including the names and qualifications of the individuals in those positions and a quality control organizational chart defining the quality control hierarchy and the responsibility of the various positions. Quality control personnel must be employed by the contractor.
Submit American Concrete Institute certification for the following:
a. CQC personnel responsible for inspection of concrete operations.
b. Lead Foreman or Journeyman of the Concrete Placing, Finishing, and Curing Crews.
c. Field Testing Technicians: ACI Concrete Field Testing Technician, Grade I.
1.6.6.1 Quality Manager Qualifications
The quality manager must hold a current license as a professional engineer in a U.S. state or territory with experience on at least five (5) similar projects. Evidence of extraordinary proven experience may be considered by the Contracting Officer as sufficient to act as the Quality Manager.
1.6.6.2 Field Testing Technician and Testing Agency
Submit data on qualifications of proposed testing agency and technicians for approval by the Contracting Officer prior to performing testing on concrete.
a. Work on concrete under this contract must be performed by an ACI Concrete Field Testing
Technician Grade 1 qualified in accordance with ACI SP-2 or equivalent. Equivalent certification programs must include requirements for written and performance examinations as stipulated in ACI SP-2.
b. Testing agencies that perform testing services on reinforcing steel must meet the requirements of ASTM E329.
c. Testing agencies that perform testing services on concrete materials must meet the requirements of ASTM C1077.
1.6.7 Laboratory Qualifications for Concrete Qualification Testing
The concrete testing laboratory must have the necessary equipment and experience to accomplish required testing. The laboratory must meet the requirements of ASTM C1077 and be Cement and Concrete Reference Laboratory (CCRL) inspected.
1.6.8 Laboratory Accreditation
Laboratory and testing facilities must be provided by and at the expense of the Contractor. The laboratories performing the tests must be accredited in accordance with ASTM C1077, including ASTM C78/C78M and ASTM C1260. The accreditation must be current and must include the required test methods, as specified. Furthermore, the testing must comply with the following requirements:
a. Aggregate Testing and Mix Proportioning: Aggregate testing and mixture proportioning studies must be performed by an accredited laboratory and under the direction of a registered professional engineer in New Mexico who is competent in concrete materials and must sign all
SECTION 03 30 00 Page 12 reports and designs.
b. Acceptance Testing: Furnish all materials, labor, and facilities required for molding, curing, testing, and protecting test specimens at the site and in the laboratory. Furnish and maintain boxes or other facilities suitable for storing and curing the specimens at the site while in the mold within the temperature range stipulated by
ASTM C31/C31M.
c. Contractor Quality Control: All sampling and testing must be performed by an approved, onsite, independent, accredited laboratory.
1.7 ENVIRONMENTAL REQUIREMENTS
Provide space ventilation according to manufacturer recommendations, at a minimum, during and following installation of concrete curing compound and sealer. Maintain one of the following ventilation conditions during the curing period or for 72 hours after installation:
a. Supply 100 percent outside air 24 hours a day.
b. Supply airflow at a rate of 6 air changes per hour, when outside temperatures are between
55 degrees F and 84 degrees F and humidity is between 30 percent and 60 percent.
c. Supply airflow at a rate of 1.5 air changes per hour, when outside air conditions are not within the range stipulated above.
1.8 QUALIFICATIONS FOR WELDING WORK
Welding procedures must be in accordance with AWS D1.4/D1.4M.
Verify that Welder qualifications are in accordance with AWS D1.4/D1.4M or under an equivalent qualification test approved in advance. Welders are permitted to do only the type of welding for which each is specifically qualified.
PART 2 PRODUCTS
2.1 MATERIALS FOR FORMS
Provide wood, plywood, plastic, carton, or steel. Use plywood or steel forms where a smooth form finish is required.
2.1.1 Wood Forms
Use lumber as specified in Section 06 10 00 ROUGH CARPENTRY and as follows.
Provide lumber that is square edged or tongue-and-groove boards, free of raised grain, knotholes, or other surface defects. Provide plywood that complies with NIST PS 1, B-B concrete form panels or better or AHA A135.4, hardboard for smooth form lining. Submit data verifying that composite wood products contain no urea formaldehyde resins. Virgin wood used must be FSC-certified.
2.1.1.1 Concrete Form Plywood (Standard Rough)
Provide plywood that conforms to NIST PS 1, B-B, concrete form, not less than 5/8-inch thick.
2.1.1.2 Overlaid Concrete Form Plywood (Standard Smooth)
SECTION 03 30 00 Page 13
Provide plywood that conforms to NIST PS 1, B-B, high density form overlay, not less than 5/8-inch thick.
2.1.2 Steel Forms
Provide steel form surfaces that do not contain irregularities, dents, or sags. Provide data identifying percentage of recycled content of steel forms
2.2 FORM TIES AND ACCESSORIES
Provide a form tie system that does not leave mild steel after break-off or removal any closer than 2 inches from the exposed surface. Do not use wire alone. Form ties and accessories must not reduce the effective cover of the reinforcement.
2.2.1 Waterstops
2.2.1.1 PVC Waterstop
Polyvinylchloride waterstops must conform to COE CRD-C 572.
2.2.1.2 Rubber Waterstop
Rubber waterstops must conform to COE CRD-C 513.
2.2.1.3 Thermoplastic Elastomeric Rubber Waterstop
Thermoplastic elastomeric rubber waterstops must conform to ASTM D471.
2.2.1.4 Hydrophilic Waterstop
Swellable strip type compound of polymer modified chloroprene rubber that swells upon contact with water must conform to ASTM D412 as follows: Tensile strength 420 psi minimum; ultimate elongation 600 percent minimum. Hardness must be 50 minimum on the type A durometer and the volumetric expansion ratio in distilled water at 70 degrees F must be 3 to 1 minimum.
2.2.2 Dovetail Anchor Slot
Preformed metal slot approximately 1 inch by 1 inch of not less than 22 gage galvanized steel cast in concrete. Coordinate actual size and throat opening with dovetail anchors and provide with removable filler material.
2.2.3 Perimeter Insulation
Perimeter insulation must be polystyrene conforming to ASTM C578, Type II; polyurethane conforming to ASTM C591, Type II; or cellular glass conforming to ASTM C552, Type I or IV.
2.3 CONCRETE MIX DESIGN
2.3.1 Contractor-Furnished Mix Design
ACI 211.1, ACI 301, and ACI 318 except as otherwise specified. Indicate the compressive strength (f'c) of the concrete for each portion of the structure(s) as specified below. Where faster set time is required, use Type III cement before using calcium chloride with approval from
SECTION 03 30 00 Page 14 the contracting officer.
2.3.2.1 Footings
Proportion normal-weight concrete mixture as follows:
a. Minimum Compressive Strength: 4000 psi and 3000 psi at 28 days.
b. Maximum Water-Cementitious Materials Ratio: 0.45.
c. Slump Limit: 4 inches for concrete with verified slump of 2 to 4 inches before adding high-range water-reducing admixture or plasticizing admixture, plus or minus 1 inch.
d. Air Content: 5.5 percent, plus or minus 1.5 percent at point of delivery for 1-1/2 inch nominal maximum aggregate size.
e. Air Content: 6 percent, plus or minus 1.5 percent at point of delivery for 1 inch 3/4-inch nominal maximum aggregate size.
2.3.2.2 Foundation Walls
a. Minimum Compressive Strength: 4000 psi and 3500 psi at 28 days.
b. Maximum Water-Cementitious Materials Ratio: 0.45.
c. Slump Limit: 4 inches for concrete with verified slump of 2 to 4 inches before adding high-range water-reducing admixture or plasticizing admixture, plus or minus 1 inch.
d. Air Content: 5.5 percent, plus or minus 1.5 percent at point of delivery for 1-1/2 inch nominal maximum aggregate size.
e. Air Content: 6 percent, plus or minus 1.5 percent at point of delivery for 1 inch 3/4 inch
2.3.2.3 Slab-on-Grade
a. Minimum Compressive Strength: 4000 psi and 3000 psi at 28 days.
b. Maximum Water-Cementitious Materials Ratio: 0.45.
c. Slump Limit: 4 inches for concrete with verified slump of 50 to 100 mm 2 to 4 inches before adding high-range water-reducing admixture or plasticizing admixture, plus or minus 1 inch.
d. Air Content: 5.5 percent, plus or minus 1.5 percent at point of delivery for 1-1/2 inch nominal maximum aggregate size.
e. Air Content: 6 percent, plus or minus 1.5 percent at point of delivery for 1 inch 3/4 inch
f. Air Content: Do not allow air content of trowel-finished floors to exceed 3 percent.
2.3.2.4 Mix Proportions for Normal Weight Concrete
Trial design batches, mixture proportioning studies, and testing requirements for various classes and types of concrete specified are the responsibility of the contractor. Base mixture proportions on compressive strength as determined by test specimens fabricated in accordance with ASTM
SECTION 03 30 00 Page 15
C192/C192M and tested in accordance with ASTM C39/C39M. Samples of all materials used in mixture proportioning studies must be representative of those proposed for use in the project and must be accompanied by the manufacturer's or producer's test report indicating compliance with these specifications. Base trial mixtures having proportions, consistencies, and [air content] suitable for the work on methodology described in ACI 211.1. In the trial mixture, use at least three different water-cementitious material ratios for each type of mixture, which must produce a range of strength encompassing those required for each class and type of concrete required on the project. The maximum water-cementitious material ratio allowed must be based on equivalent water-cementitious material ratio calculations as determined by the conversion from the weight ratio of water to cement plus pozzolan by weight equivalency method. Design laboratory trial mixture for maximum permitted slump and air content. Each combination of material proposed for use must have separate trial mixture, except for accelerator or retarder use can be provided without separate trial mixture. Report the temperature of concrete in each trial batch. For each water-cementitious material ratio, at least three test cylinders for each test age must be made and cured in accordance with ASTM C192/C192M and tested in accordance with ASTM C39/C39M for 7, 28, 56 days. From these results, plot a curve showing the relationship between water-cementitious material ratio and strength for each set of trial mix studies. In addition, plot a curve showing the relationship between 7 and 28 day strengths.
2.3.2.5 Lightweight Concrete Proportion
ACI 211.2, using weight method. Provide ASTM C330/C330M aggregates for concrete.
2.3.2.6 Required Average Strength of Mix Design
The selected mixture must produce an average compressive strength exceeding the specified strength by the amount indicated in ACI 301, but may not exceed the specified strength at the same age by more than 20 percent. When a concrete production facility has a record of at least 15 consecutive tests, the standard deviation must be calculated and the required average compressive strength must be determined in accordance with ACI 301.
2.3.2 Ready-Mix Concrete
Provide concrete that meets the requirements of ASTM C94/C94M. Ready-mixed concrete manufacturer must provide duplicate delivery tickets with each load of concrete delivered.
Provide delivery tickets with the following information in addition to that required by ASTM C94/C94M:
Type and brand cement; cement and complementary cementitious materials content in 94-pound bags per cubic yard of concrete; maximum size of aggregate; amount and brand name of admixtures; total water content expressed by water cementitious material ratio
2.3.3 Concrete Curing Materials
Provide concrete curing material in accordance with ACI 301 Section 5 and ACI 308.1 Section
2. Submit product data for concrete curing compounds. Submit manufactures instructions for placement of curing compound.
2.4 MATERIALS
2.4.1 Cementitious Materials
For exposed concrete, use one manufacturer and one source for each type of cement, ground slag, fly ash, and pozzolan. Provide data identifying percentage of recycled content (fly ash, pozzolan, slag, silica fume).
SECTION 03 30 00 Page 16
2.4.1.1 Fly Ash
ASTM C618, Class F, except that the maximum allowable loss on ignition must not exceed 3-6 percent. Class F fly ash for use in mitigating Alkali-Silica Reactivity must have a Calcium Oxide (CaO) content of less than 8 percent and a total equivalent alkali content less than 1.5 percent.
Add with cement. Fly ash content must be a minimum of [20] [30] [35] percent by weight of cementitious material, provided the fly ash does not reduce the amount of cement in the concrete mix below the minimum requirements of local building codes. Where the use of fly ash cannot meet the minimum level, provide the maximum amount of fly ash permittable that meets the code requirements for cement content. Report the chemical analysis of the fly ash in accordance with ASTM C311/C311M. Evaluate and classify fly ash in accordance with ASTM D5759.
2.4.1.2 Raw or Calcined Natural Pozzolan
Natural pozzolan must be raw or calcined and conform to ASTM C618, Class N, including the optional requirements for uniformity and effectiveness in controlling Alkali-Silica reaction and must have an ignition loss not exceeding 3 percent. Class N pozzolan for use in mitigating Alkali-Silica Reactivity must have a Calcium Oxide (CaO) content of less than 13 percent and total equivalent alkali content less than 3 percent.
2.4.1.3 Ultra Fine Fly Ash and Ultra Fine Pozzolan
Ultra Fine Fly Ash (UFFA) and Ultra Fine Pozzolan (UFP) must conform to ASTM C618, Class F or N, and the following additional requirements:
a. The strength activity index at 28 days of age must be at least 95 percent of the control specimens.
b. The average particle size must not exceed 6 microns.
c. The sum of SiO2 + Al2O3 + Fe2O3 must be greater than 77 percent.
2.4.1.4 Ground Granulated Blast-Furnace Slag
ASTM C989/C989M, Grade [100] [120]. Slag content must be a minimum of [25][50][70] percent by weight of cementitious material.
2.4.1.5 Portland Cement
Provide cement that conforms to ASTM C150/C150M, Type I, II or III, low alkali with tri-calcium aluminates (C3A) content less than 10 percent and a maximum cement-alkali content of 0.80 percent Na2Oe (sodium oxide) equivalent. Use one brand and type of cement for formed concrete having exposed-to-view finished surfaces.
For portland cement manufactured in a kiln fueled by hazardous waste, maintain a record of source for each batch. Supplier must certify that no hazardous waste is used in the fuel mix or raw materials.
2.4.1.6 Blended Cements
Blended cement must conform to ASTM C595/C595M and ASTM C1157/C1157M, Type IP or IS, including the optional requirement for mortar expansion [and sulfate soundness] and consist
SECTION 03 30 00 Page 17 of a mixture of ASTM C150/C150M Type I, or Type II cement and a complementary cementing material. The slag added to the Type IS blend must be ASTM C989/C989M ground granulated blast-furnace slag. The pozzolan added to the Type IP blend must be ASTM C618 Class F and must be interground with the cement clinker. The manufacturer must state in writing that the amount of pozzolan in the finished cement will not vary more than plus or minus 5 mass percent of the finished cement from lot-to-lot or within a lot. The percentage and type of mineral admixture used in the blend must not change from that submitted for the aggregate evaluation and mixture proportioning.
2.4.2 Water
Water must comply with the requirements of ASTM C1602/C1602M. Minimize the amount of water in the mix. Improve workability by adjusting the grading rather than by adding water.
Water must be free from injurious amounts of oils, acids, alkalis, salts, organic materials, or other substances deleterious to concrete. Submit test report showing water complies with
ASTM C1602/C1602M.
2.4.3 Aggregates
ASTM C33/C33M, except as modified herein. Furnish aggregates for exposed concrete surfaces from one source. Provide aggregates that do not contain any substance which may be deleteriously reactive with the alkalies in the cement. Submit test report showing compliance with ASTM C33/C33M.
Fine and coarse aggregates must show expansions less than 0.08 percent at 28 days after casting when testing in accordance with ASTM C1260. Should the test data indicate an expansion of 0.08 percent or greater, reject the aggregate(s) or perform additional testing using ASTM C1567 using the Contractor's proposed mix design. In this case, include the mix design low alkali portland cement and one of the following supplementary cementitious materials:
1. GGBF slag at a minimum of 40 percent of total cementitious
2. Fly ash or natural pozzolan at a minimum of total cementitious of
a. 30 percent if (SiO2 plus Al2O3 plus Fe2O3) is 65 percent or more,
b. 25 percent if (SiO2 plus Al2O3 plus Fe2O3) is 70 percent or more,
c. 20 percent if (SiO2 plus Al2O3 plus Fe2O3) is 80 percent or more,
d. 15 percent if (SiO2 plus Al2O3 plus Fe2O3) is 90 percent or more.
If a combination of these materials is chosen, the minimum amount must be a linear combination of the minimum amounts above. Include these materials in sufficient proportion to show less than 0.08 percent expansion at 28 days after casting when tested in accordance with
ASTM C1567.
Aggregates must not possess properties or constituents that are known to have specific unfavorable effects in concrete when tested in accordance with ASTM C295/C295M.
2.4.3.1 Aggregates/Combined Aggregate Gradation (Floor Slabs Only)
ASTM C33/C33M, uniformly graded and as follows: Nominal maximum aggregate size of 1 inch. A combined sieve analysis must indicate a well graded aggregate from coarsest to finest with not more than 18 percent and not less than 8 percent retained on an individual sieve, except that less than 8 percent may be retained on coarsest sieve and on No. 50 (0.3mm) sieve, and less than 8 percent may be retained on sieves finer than No. 50 (0.3mm). Provide sand that is at least 50 percent natural sand.
2.4.4 Nonshrink Grout ASTM C1107/C1107M.
SECTION 03 30 00 Page 18
2.4.5 Admixtures
ASTM C494/C494M: Type A, water reducing; Type B, retarding; Type C, accelerating; Type D, water-reducing and retarding; and Type E, water-reducing and accelerating admixture. Do not use calcium chloride admixtures. Submit product data for admixtures used in concrete.
2.4.5.1 Air-Entraining
Use for concrete exposed to freeze-thaw conditions. Do not use to enhance workability.
ASTM C260/C260M.
2.4.5.2 High Range Water Reducer (HRWR) (Superplasticizers)
ASTM C494/C494M, Type F [and Type G (HRWR retarding admixture)] and ASTM C1017/C1017M. HRWR must come from the same manufacturer.
2.4.6 Vapor Retarder [and Vapor Barrier]
ASTM E1745 Class C [A] [B] polyethylene sheeting, minimum 15 mil thickness or other equivalent material with a maximum permeance rating of 0.04 perms per ASTM E96/E96M.
ASTM E1745 Class C [A] [B] polyethylene sheeting, minimum 15 mil thickness or ASTM E1993/E1993M bituminous membrane or other equivalent material with a maximum permeance rating of 0.01 perms per ASTM E96/E96M.
2.4.7 Expansion/Contraction Joint Filler
ASTM D1751 or ASTM D1752 Type I or II. Material must be 1/2 inch thick[, unless otherwise indicated.
2.4.8 Joint Sealants
2.4.8.1 Horizontal Surfaces, 3 Percent Slope, Maximum ASTM D6690 or ASTM C920, Type M, Class 25, Use T.
2.4.8.2 Vertical Surfaces Greater Than 3 Percent Slope
ASTM C920, Type M, Grade NS, Class 25, Use T [NT].[FS SS-S-200, no sag].
2.4.8.3 Preformed Polychloroprene Elastomeric Type ASTM D2628.
2.4.8.4 Lubricant for Preformed Compression Seals
ASTM D2835.
2.4.9 Biodegradable Form Release Agent
Provide form release agent that is colorless, biodegradable, and rapeseed oil-based, soy oil-based, water-based, with zero VOC content. A minimum of 85 percent of the total product must be biobased material. Provide data identifying percentage of biobased content for form release agent. Provide product that does not bond with, stain, or adversely affect concrete surfaces and does not impair subsequent treatments of concrete surfaces. Provide form release agent that does not contain diesel fuel, petroleum-based lubricating oils, waxes, or kerosene. Submit documentation indicating type of biobased material in product and biobased content. Indicate
SECTION 03 30 00 Page 19 relative dollar value of biobased content products to total dollar value of products included in project.
2.5 REINFORCEMENT
2.5.1 Reinforcing Bars
ACI 301 unless otherwise specified. ASTM A615/A615M with the bars marked A, Grade [420][520][690] [60][75][100]; or ASTM A996/A996M with the bars marked R, Grade [350][420] [50][60], or marked A, Grade [300][420] [40][60]. Cold drawn wire used for spiral reinforcement must conform to ASTM A1064/A1064M. Provide data identifying percentage of recycled content for reinforcing bar. Submit mill certificates for reinforcing bars.
2.5.1.1 Galvanized Reinforcing Bars
Provide galvanized reinforcing bars that conform to ASTM A767/A767M, Class II with galvanizing after fabrication.
2.5.1.2 Weldable Reinforcing Bars
Provide weldable reinforcing bars that conform to ASTM A706/A706M and ASTM A615/A615M and Supplement S1, Grade 60, except that the maximum carbon content must be 0.55 percent.
2.5.1.3 Epoxy-Coated Reinforcing Bars
Provide epoxy-coated reinforcing bars that conform to ASTM A934/A934M, Grade [60][75][100].
2.5.1.4 Stainless Steel Reinforcing Bars ASTM A955/A955M.
2.5.2 Mechanical Reinforcing Bar Connectors
ACI 301. Provide 125 percent minimum yield strength of the reinforcement bar.
2.5.3 Wire
2.5.3.1 Welded Wire Reinforcement
ASTM A1064/A1064M. Wire reinforcement may contain post-consumer or post-industrial recycled content. Provide data identifying percentage of recycled content for welded wire reinforcement. Provide flat sheets of welded wire reinforcement for slabs and toppings.
2.5.3.2 Steel Wire
Wire must conform to ASTM A1064/A1064M.
2.5.4 Reinforcing Bar Supports
Supports include bolsters, chairs, spacers, and other devices necessary for proper spacing, supporting, and fastening reinforcing bars and welded wire reinforcement in place. Use engineered resins from recycled ABS plastic, polycarbonates, and fiberglass.
Provide wire bar type supports of coated or non-corrodible material conforming to ACI SP-66 and CRSI 10MSP. For epoxy-coated reinforcement, use epoxy-coated or other dielectric-polymer-coated wire bar support. For zinc-coated reinforcement, use galvanized wire or
SECTION 03 30 00 Page 20 dielectric-polymer coated wire bar supports.
Legs of supports in contact with formwork must be hot-dip galvanized, or plastic coated after fabrication, or stainless-steel bar supports.
Minimum 10 percent post-consumer recycled content, or minimum 2040 percent post-industrial recycled content. Provide data identifying percentage of recycled content for reinforcing bar support.
2.5.5 Dowels for Load Transfer in Floors
Provide greased dowels for load transfer in floors of the type, design, weight, and dimensions indicated. Provide dowel bars that are plain-billet steel conforming to ASTM A615/A615M, Grade 40. Provide dowel pipe that is steel conforming to ASTM A53/A53M.
Plate dowels must conform to ASTM A36/A36M, and must be of size and spacing indicated.
Plate dowel system must minimize shrinkage restraint by [using a tapered shape] [or] [formed void] [or] [by having compressible material on the vertical faces with a thin bond breaker on the top and bottom dowel surfaces.]
2.6 FLOOR FINISH MATERIALS
2.6.1 Liquid Chemical Floor Hardener
Hardener must be a colorless aqueous solution containing a blend of inorganic silicate or siliconate material and proprietary components combined with a wetting agent; that penetrates, hardens, and densifies concrete surfaces. Submit manufactures instructions for placement of liquid chemical floor hardener.
Use concrete penetrating sealers with a low (maximum 100 grams/liter, less water and less exempt compounds) VOC content.
2.6.2 Abrasive Aggregate for Nonslip Aggregate Finish
Aggregate must be packaged, factory-graded fused aluminum oxide grits, or it may be crushed emery containing not less than 40-percent aluminum oxide and not less than 25-percent ferric oxide. Aggregate must be rust proof and nonglazing and must be unaffected by freezing, moisture, and cleaning materials.
Aggregate must be packaged, factory-graded, silicon carbide grits. Aggregate must be rust proof and must be unaffected by freezing, moisture, and cleaning materials.
Aggregate must be well-graded in size from particles retained on 600 micrometer sieve No. 30 sieve 0.0236 inch to particles passing 2.36 mm sieve No. 8 sieve 0.0929 inch.
PART 3 EXECUTION
3.1 EXAMINATION
Do not begin installation until substrates have been properly constructed; verify that substrates are level.
If substrate preparation is the responsibility of another installer, notify Contracting Officer of unsatisfactory preparation before processing.
SECTION 03 30 00 Page 21
Check field dimensions before beginning installation. If dimensions vary too much from design dimensions for proper installation, notify Contracting Officer and wait for instructions before beginning installation.
3.2 PREPARATION
Determine quantity of concrete needed and minimize the production of excess concrete.
Designate locations or uses for potential excess concrete before the concrete is poured.
3.2.1 General
Surfaces against which concrete is to be placed must be free of debris, loose material, standing water, snow, ice, and other deleterious substances before start of concrete placing.
Remove standing water without washing over freshly deposited concrete. Divert flow of water through side drains provided for such purpose.
3.2.2 Subgrade Under Foundations and Footings
When subgrade material is semiporous and dry, sprinkle subgrade surface with water as required to eliminate suction at the time concrete is deposited, or seal subgrade surface by covering surface with specified vapor retarder. When subgrade material is porous, seal subgrade surface by covering surface with specified vapor retarder.
3.2.3 Subgrade Under Slabs on Ground
Before construction of slabs on ground, have underground work on pipes and conduits completed and approved.
Previously constructed subgrade or fill must be cleaned of foreign materials. Finish surface of capillary water barrier under interior slabs on ground must not show deviation in excess of 1/4 inch when tested with a 10-foot straightedge parallel with and at right angles to building lines.
Finished surface of subgrade or fill under exterior slabs on ground must not be more than 0.02-foot above or 0.10-foot below elevation indicated.
3.2.4 Edge Forms and Screed Strips for Slabs
Set edge forms or bulkheads and intermediate screed strips for slabs to obtain indicated elevations and contours in finished slab surface and must be strong enough to support vibrating bridge screeds or roller pipe screeds if nature of specified slab finish requires use of such equipment. Align concrete surface to elevation of screed strips by use of strike-off templates or approved compacting-type screeds.
3.2.5 Reinforcement and Other Embedded Items
Secure reinforcement, joint materials, and other embedded materials in position, inspected, and approved before start of concrete placing.
3.3 FORMS
Provide forms, shoring, and scaffolding for concrete placement in accordance with ACI 301 Section 2 and 5 and ACI 347R. Set forms mortar-tight and true to line and grade. Chamfer
SECTION 03 30 00 Page 22 above grade exposed joints, edges, and external corners of concrete 0.75 inch unless otherwise indicated. Provide formwork with clean-out openings to permit inspection and removal of debris.
3.3.1 Coating
Before concrete placement, coat the contact surfaces of forms with a form release agent.
3.3.2 Reshoring
Reshore concrete elements in accordance with ACI 301 Section 2.
3.3.3 Reuse
Reuse forms providing the structural integrity of concrete and the aesthetics of exposed concrete are not compromised. Wood forms must not be clogged with paste and must be capable of absorbing high water-cementitious material ratio paste.
3.3.4 Forms for Standard Rough Form Finish
Provide formwork in accordance with ACI 301 Section 5 with a surface finish, SF-1.0, for formed surfaces that are to be concealed by other construction.
3.3.5 Form Ties
Provide ties in accordance with ACI 301 section 2.
3.3.6 Forms for Concrete Pan Joist Construction
Pan-form units for one-way or two-way concrete joist and slab construction must be factory-fabricated units of the approximate section indicated. Units must consist of steel or molded fiberglass concrete form pans. Closure units must be furnished as required.
3.3.7 Tolerances for Form Construction
Construct formwork to ensure that after removal of forms and prior to patching and finishing of formed surfaces, provide concrete surfaces in accordance with tolerances specified in ACI 301 Section 5 and ACI 117.
3.3.8 Removal of Forms and Supports
After placing concrete, removal of forms must be in accordance with ACI 301 Section 2 except as modified by approved form removal schedule.
3.4 WATERSTOP INSTALLATION AND SPLICES
Provide waterstops in construction joints as indicated.
Install waterstops to form a continuous diaphragm in each joint. Make adequate provisions to support and protect waterstops during progress of work. Protect waterstops protruding from joints from damage.
3.4.1 PVC Waterstop
Make splices by heat sealing the adjacent waterstop edges together using a thermoplastic
SECTION 03 30 00 Page 23 splicing iron utilizing a non-stick surface specifically designed for waterstop welding. Reform waterstops at splices with a remolding iron with ribs or corrugations to match the pattern of the waterstop. The spliced area, when cooled, must show no signs of separation, holes, or other imperfections when bent by hand in as sharp an angle as possible.
3.4.2 Rubber Waterstop
Rubber waterstops must be spliced using cold bond adhesive as recommended by the manufacturer.
3.4.3 Thermoplastic Elastomeric Rubber Waterstop
Fittings must be shop made using a machine…