About this file

Attachment Rd

View the file

Other files

File Type Posted
Amendment-7.pdf PDF
Amendment-7-Guardian-60kW.pdf.pdf PDF
Amendment-6.pdf PDF
Amendment-5.pdf PDF
Attachment_T_v2.pdf PDF
Amendment-4.pdf PDF
Amendment_3.pdf PDF
Sign-In_Sheet.pdf PDF
REC.pdf PDF
Amendment_2.pdf PDF
Amendment_1.pdf PDF
Attachment_U.pdf PDF
Attachment_I.pdf PDF
Attachment_K.pdf PDF
Attachment_E.pdf PDF
Attachment_Ra.pdf PDF
Attachment_H.pdf PDF
Attachment_D.pdf PDF
Attachment_L.pdf PDF
W911SF-12-R-0020.pdf PDF
Attachment_F.pdf PDF
Attachment_A.pdf PDF
Attachment_O.pdf PDF
Attachment_C.pdf PDF
Attachment_B.pdf PDF
Attachment_R.pdf PDF
Attachment_M.pdf PDF
Attachment_Rb.pdf PDF
Attachment_P.pdf PDF
Attachment_J.pdf PDF
Attachment_Q.pdf PDF
Attachment_Rc.pdf PDF
Attachment_T.pdf PDF
Attachment_N.pdf PDF
Attachment_G.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

15 KVA

ELECTRICAL KEYED NOTES:

1 EXISTING ELECTRICAL SITE PLAN SCALE: 30’ = 1’-0"

E0

SCALE OF FEET

030 30 60

EXISTING ELECTRICAL SITE PLAN

43105-E0

E0

SEE PHOTOGRAPH C

P1

P2

P3

P4

P5

PHOTOGRAPH C PHOTOGRAPH D

PHOTOGRAPH A PHOTOGRAPH B

ELECTRICAL KEYED NOTES:

ATMOS ENERGY WILL SUPPLY LIQUID PROPANE FOR GENERATOR.

FLINT ELECTRIC WILL REMOVE THE AERIAL SECONDARY CABLES.

EXISTING POWER POLE (P5) TO REMAIN.

EXISTING POWER POLE (P1) TO REMAIN.

EXISTING POWER POLE (P4) TO REMAIN.

EXISTING POWER POLE (P2) TO REMAIN.

EXISTING AERIAL PRIMARY CABLE TO REMAIN.

EXISTING POWER POLE (P3) TO REMAIN.

EXISTING COVER TRAINING AREA. 10

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

1-1000-3

U G

#2, #2N

UG

KV

KV

2, 2N

S M I

L E

Y

C T

P NEUTRAL

ELEC G S1

P NEUTRAL

ELEC G S1

PARKING

PARKING

P NEUTRAL

ELEC G S1

CUTOUT S1

6 FUSE-

P NEUTRAL

ELEC G S1

JOHNSTON DRIVE

G

G

TANK

LIQUIDE PROPANE

1000 GALLONS

15’

GENERATOR

EMERGENCY

60 KW LP

TANK

1000 GALLONS

PIPE TO

PROPANE

THE EMERGENCY 60 KW GENERATOR.

PROVIDE AND INSTALL A LIQUID PROPANE GAS LINE FOR

SHEET 43105-E9.

VIA AUTOMATIC TRANSFER SWITCH (ATS). SEE DRAWING

CONNECT EMERGENCY GENERATOR TO EMERGENCY PANEL "EA"

CONNECT TO 60 KW LIQUID PROPANE EMERGENCY GENERATOR.

CONNECT TO 1000 GALLONS LIQUID PROPANE TANK

0’ 5’12" 10’ 15’ 20’ 25’

SCALE: 1/8 INCH = 1 FOOT

43105-E1

E1

E1

SCALE: 1/8" = 1’-0"1 ELECTRICAL DEMOLITION PLAN

ELECTRICAL DEMOLITION PLAN

SPECIAL ELECTRICAL KEYED NOTES:

PHOTOGRAPH 6PHOTOGRAPH 5

PHOTOGRAPH 4PHOTOGRAPH 3

PHOTOGRAPH 1 PHOTOGRAPH 2

PHOTOGRAPH 3

AS INDICATED ON THE

GOTO NEXT POWER POLE

TYPICAL

TYPICAL

POWER POLE

GOTO NEXT

CAULKING AROUND THE REPAIRED AREA.

PATCH THE PENETRATED AREA IN THE ROOF AND APPLY ADEQUATE WATERPROOFING AND

CONTRACTOR WILL REMOVE THE WEATHER-HEAD AND CONDUIT.

FLINT ELECTRIC WILL DISCONNECT THE AERIAL SECONDARY CABLE AND ELECTRICAL

EXISTING AERIAL PRIMARY TO REMAIN.

EXISTING POWER POLE TO REMAIN. SEE PHOTOGRAPH 2.

PHOTOGRAPH 6.

WIRING, CONDUIT, WEATHER-HEAD FROM THE STRUCTURE. SEE PHOTOGRAPH 4 AND

COMPLETELY REMOVE EXISTING 120/240 VOLT, 1 PHASE, 3 WIRE, 125 AMPS PANEL,

THE FREEZER WILL BE RELOCATED BY THE OWNER.

STRUCTURE.

WIRING, CONDUITS, ENCLOSURES, AND ETC.) ASSOCIATED WITH THE FREEZER ON THE

COMPLETELY REMOVE ELECTRICAL EQUIPMENT (J-BOXES, MOTOR, DISCONNECT SWITCHES,

FROM THE STRUCTURE. SEE PHOTOGRAPH 5.

COMPLETELY REMOVE ALL EXISTING RECEPTACLES, J-BOXES, WIRING AND CONDUITS

LAMPS, SWITCHES, J-BOXES, WIRING, AND CONDUITS FROM THE STRUCTURE.

COMPLETELY REMOVE ALL EXISTING 2’X4’ SURFACE-MOUNTED FLUORESCENT FIXTURES,

15 KVA

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

E2

ELECTRICAL LIGHTING PLAN SCALE: 1/8" = 1’-0"

ELECTRICAL LIGHTING PLAN

10 11

15 16 17

181920

SPECIAL ELECTRICAL KEYED NOTES:

S S

S

S S S

SSS

S

S

S

S

S

S S

S S

S3

S

S

TYPE LAMP MOUNTING

E LED SURFACE

F

FIXTURE SCHEDULE

WALL

B

C

D

400W MH

400W MH

OR BEAM

PENDANT

OR BEAM

PENDANT

3-F32T8

3-F32T8BE

RECESS

RECESS

COLUMBIA LIGHTING CAT# 4PS24-332G-FSA12.125M-3E-PAF

STEEL DOOR, ACRYLIC PRISMATIC LENS, ELECTRONIC BALLAST, UNIVERSAL VOLTAGE

2X4 FLUORESCENT FIXTURE, 4PS LENSED TROFFER, RECESSED-MOUNTED 3-LAMP, FLUSH

STEEL DOOR, ACRYLIC PRISMATIC LENS, ELECTRONIC BALLAST, EMERGENCY BATTERY PACK

2X4 FLUORESCENT FIXTURE, 4PS LENSED TROFFER, RECESSED-MOUNTED 3-LAMP, FLUSH

B BB

B

B B B B

B B

B B

B

B

B

B

B B

BB

B

B

B

B

B

B

B B

B

B B B B

B

B

B B

B

B B

B

B

B

B

C

B

B

B

B

BE

BE

BE

BE

BE BE

B

4-F32T8 RECESS COLUMBIA LIGHTING CAT# 4PS24-432G-FSA12.125M-4E-PAF

STEEL DOOR, ACRYLIC PRISMATIC LENS, ELECTRONIC BALLAST, UNIVERSAL VOLTAGE

2X4 FLUORESCENT FIXTURE, 4PS LENSED TROFFER, RECESSED-MOUNTED 4-LAMP, FLUSH

3-F32T8

OR BEAM

PENDANT

3-F32T8

OR BEAM

PENDANT

FORMED STEEL, CHAIN HANGER, UNIVERSAL VOLTAGE, EMERGENCY BATTERY PACK

INDUSTRIAL FLUORESCENT FIXTURE, NO UPLIGHT, ELECTRONIC T8, INSTANT START, DIE

DE

FORMED STEEL, CHAIN HANGER, UNIVERSAL VOLTAGE

INDUSTRIAL FLUORESCENT FIXTURE, NO UPLIGHT, ELECTRONIC T8, INSTANT START, DIE

COLUMBIA LIGHTING CAT# CSR-4-3-32T8-ST-3E-U-PAF

COLUMBIA LIGHTING CAT# CSR-4-3-32T8-ST-3E-U-PAF-EL

HOUSING, UNIVERSAL, VANDAL RESISTANCE LENS

DIA CAST LED EXT, AC ONLY, SINGLE AND/OR DOUBLE, RED LETTER, BRUSHED ALUMINUM

WALL

HALOGEN

CONSTANT CURRENT TYPE BATTERY CHARGER, ABS THERMOPLASTIC HOUSING.

10 WATT HALOGEN LAMPS, 120 VAC, 12 VOLT NICKEL CADMIUM BATTERY, SOLID STATE

G 100W MH HUBBELL LIGHTING - OUTDOOR: CAT# WGH-100H-120V-BRONZE-PBT-1

WGH METAL HALIDE FIXTURE, POLYCARBONATE GLASS WALL PACK WITH PHOTO-CELL OPTION

DE

D

E

E

E

E

F

GGG

G

G G G

G

G

TYP.

TYP.

C

C

TYP.

5 TYP.6

TYP.

TYP.

43105-E2

E2

LITHONIA LIGHTING - LOW BAY INDUSTRIAL LIGHTING: CAT# TX-400MP-A23-120-SCWA

LITHONIA LIGHTING - LOW BAY INDUSTRIAL LIGHTING: CAT# TX-400MP-A23-120-SCWA-QRS

175W MHH WALL

H

H H

H

S

S

TYP.

G

TYP.

LEGEND

PACK

WITH 3-LAMP AND BATTERY

2’X4’ FLUORESCENT FIXTURE

WITH 3-LAMP

2’X4’ FLUORESCENT FIXTURE

FIXTURE

175W MH WALL-MOUNTED

100W MH WALL PACK

EMERGENCY LIGHT FIXTURE

SINGLE/DOUBLE FACE

LED EXIT SIGN FIXTURE

ALERT RED LIGHT FIXTURE

WITH 4-LAMP

2’X4’ FLUORESCENT FIXTURE

PACK

WITH 3-LAMP AND BATTERY

2’X4’ FLUORESCENT FIXTURE

WITH 3-LAMP

2’X4’ FLUORESCENT FIXTURE

TO EMERGENCY PANEL

400W MH LOW BAY CONNECT

400W MH LOW BAY

SPECIAL ELECTRICAL KEYED NOTES CONTINUATION:

13 14

TYP.

15 16

A1

A1

A1 A1 A1 A1

A1

A1

A2

A2

A2 A2

A1

A2

CLEAR, IMPACT RESISTANT, TEMPERED GLASS LENS.

175W METAL HALIDE, EXTRUDED ALUMINUM BODY, SPECULAR ANODIZED ALUMINUM REFLECTOR,

S

S

EA-1

EA-1

EA-3

EA-2

EA-5

EA-6

EA-7

EA-7

EA-8

EA-9

F F

654321

1 2 3 4 5 6

B

A A

B

I

I I I

I

I

II

I

EA-1

TO EA-3

CONNECT

EA-4

EA-11

EA-13

TYP.

C

TYP.

OFFICE/ROOM AREA KEYED NOTES:

106A

100C

100B

100A

LAUNDRY JAN,

PPE STORAGE

EMT STORAGE

SHOWER

MEN’S

WOMEN’S

VEHICLE BAY

APPARATUS STORAGE

EMT OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

KITCHEN

SUPERVISOR’S OFFICE

FITNESS

DORM 6 ROOM

DORM 5 ROOM

DORM 4 ROOM

DORM 3 ROOM

DORM 2 ROOM

DORM 1 ROOM

MECH. ROOM

COMM. ROOM1

S

S

TYP.

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

COLUMBIA LIGHTING CAT# 4PS24-332G-FSA12.125M-3E-PAF (TO SWITCHING CIRCUITS)

ISOLITE CAT#LPDC-NB-S-R-B-BAC-VR OR APPROVED EQUAL (TO UN-SWITCHING CIRCUITS)

HUBBELL LIGHTING: DUAL LITE CAT# LZ25N-12V (TO UN-SWITCHING CIRCUITS)

B

TYPE LAMP MOUNTING DESCRIPTION

I ZENON WALL HUBBELL INDUSTRIAL LIGHTING CAT# NVSZMFG01RBG

FLASHING IN RED COLOR, 120VAC, FLASH RATE 60 TO 80 FLASHES PER MINUTE

FIXTURE SCHEDULE CONTINUATION

CAT# WFL2-175M-FT-120-SCWA-BBW-LPI

LITHONIA LIGHTING - ARCHITECTURAL WALL-MOUNTED LIGHTING:

THAT SPECIFICATION, BUT RATHER IT IS INTENDED TO ESTABLISH A MINIMUM LEVEL OF PRODUCT QUALITY AND OPERATION.

THE MENTION OF A MANUFACTURER’S PRODUCT BY NAME AND PART NUMBER IN THE LUMINAIRE SCHEDULE IS NOT INTENDED TO CLOSE

FIXTURE SCHEDULE NOTE:

E

CC

E

B

E

S

B

D

J

J

J

J

J

J

J LED RECESSED LITHONIA LIGHTING CAT# REAL6-D6-MW

6-INCH LED RECESSED DOWNLIGHT MODULE WITH COMPATIBLE DIMMER SWITCH

CC

PULSE-START ARC KEEPER (HID BACKUP BALLAST) MODEL #AK400PLS-120 VAC.

400W METAL HALIDE, SUPER CONSTANT WATTAGE AUTOTRANSFORMER, 120 VOLT, WITH

PROVIDE AND INSTALL 175W MH WALL-MOUNTED FIXTURES (FIXTURE H) IN THE VEHICLE BAY AREA.

PROVIDE AND INSTALL LOCAL SWITCHING FOR EACH OFFICE, ROOM, AND HALLWAY.

PROVIDE AND INSTALL A CEILING FAN CONTROL SWITCH ON THE WALL IN THE DAY ROOM AS INDICATED ON THE DRAWING.

PROVIDE AND INSTALL EXTERIOR 100W METAL HALIDE WALL PACK WITH PHOTO-CELL CONTROL CIRCUIT.

FINISHED FLOOR.

PROVIDE AND INSTALL WALL-MOUNTED EXTERIOR 100W METAL HALIDE WALL PACK FIXTURES (FIXTURE G) AND MOUNT 9’-0" ABOVE

PROVIDE AND INSTALL WALL-MOUNTED EMERGENCY LIGHT FIXTURES (FIXTURE F) AS INDICATED ON THE DRAWING.

SHOWN ON THE DRAWING.

PROVIDE AND INSTALL CEILING- AND/OR WALL-MOUNTED LED EXIT SIGN FIXTURE (FIXTURE E) WITH SINGLE AND/OR DOUBLE FACE AS

WITH 3-LAMP AND ACRYLIC LENS AS INDICATED ON THE DRAWING.

PROVIDE AND INSTALL PENDANT-, CHAIN- AND/OR BEAM- MOUNTED, 2’X4’ FLUORESCENT FIXTURE, (FIXTURE D AND FIXTURE DE)

ACRYLIC LENS AS INDICATED ON THE DRAWING.

PROVIDE AND INSTALL 2’X4’ GRID RECESS (LAY-IN) CEILING-MOUNTED FLUORESCENT FIXTURES (FIXTURE C) WITH 4-LAMP AND

3-LAMP AND ACRYLIC LENS AS INDICATED ON THE DRAWING.

PROVIDE AND INSTALL 2’X4’ GRID RECESS (LAY-IN) CEILING-MOUNTED FLUORESCENT FIXTURES (FIXTURE B AND FIXTURE BE) WITH

VEHICLE BAY AREA AS SHOWN ON THE DRAWING. PROVIDE THREE-WAY SWITCHES TO CONTROL THE LIGHT FIXTURES.

PROVIDE AND INSTALL PENDANT- OR BEAM-MOUNTED 400W MH LOW BAY INDUSTRIAL FIXTURES (FIXTURE A1 AND FIXTURE A2) IN THE

PROVIDE SIX (6) REMOTE CONTROL KEYS FOR DRIVER TO OPEN/CLOSE THE RETRACTABLE BAY DOOR.

SYSTEM WITH VEHICLE BAY DOOR OPENER USING ELECTRIC EYES SENSING SYSTEM (OPEN DOOR = GREEN, CLOSE DOOR = RED).

FULLY RAISED DOOR FOR THE DRIVER. MOUNT THE SIGNALING SYSTEM 72-INCH ABOVE FINISHED FLOOR. INTEGRATE THE SIGNALING

PROVIDE AND INSTALL A TWO SIGNALING SYSTEM AS SHOWN ON THE DRAWING. THE RED/GREEN SIGNALING SYSTEM SHALL INDICATE A

KEEPER (HID BACKUP BALLAST) MODEL #AK400PLS-120 VAC.

400W METAL HALIDE, SCWA, QUARTZ RESTRIKE SYSTEM, 120 VOLT WITH PULSE-START ARC

MANAGER AND THE USER.

COORDINATE THE FIRE FIGHTER ALERT SYSTEM INSTALLATION REQUIREMENT WITH PROJECT

THE ALERT SYSTEM OR CONTRACTOR SHALL PROVIDE AND INSTALL THE ACTIVATOR BUTTON.

EMERGENCY TONE SIGNAL BY THE SUPERVISOR. THE ACTIVATOR BUTTON MAYBE COME WITH

SUPERVISOR’S OFFICE TO ALLOW ACTIVATING THE FLASHING RED LIGHTS AND BROADCAST

IS REQUIRED TO PROVIDE AND INSTALL A FIRE ALERT SYSTEM ACTIVATOR BUTTON IN THE

BUILT-IN TONE GENERATOR AND CONNECT BOTH TO THE ACTIVATOR BUTTON. CONTRACTOR

SHALL INSTALL THE RED LIGHTS (FIXTURE I), INTEGRATE THE RED LIGHTS WITH THE

ALREADY BUILT-IN TO THE 911 RADIO SYSTEM OR ALERT SYSTEM; THEREFORE, CONTRACTOR

LIGHTS AND A TONE GENERATOR TO ALERT FIRE FIGHTER. THE TONE GENERATOR IS

911 DISPATCH MESSAGES THRU THE PA SYSTEM). THE ALERT SYSTEM INCLUDES RED

FIRE FIGHTER ALERT SYSTEM OR 911 RADIO SYSTEM TO THE PA SYSTEM (BROADCAST THE

ELECTRICAL CONTRACTOR IS REQUIRED TO INSTALL/CONNECT THE GOVERNMENT FURNISHED

GENERAL NOTE:

IN DAY ROOM.

PROVIDE AND INSTALL 6-INCH RECESSED LED DOWNLIGHTS WITH COMPATIBLE DIMMER SWITCH

PER MANUFACTURER’S RECOMMENDATION.

THE NUMBER OF SENSORS, LOCATION OF THE SENSORS AND MOUNTING HEIGHT OF THE SENSORS

INCLUDING CORRIDOR 100A, CORRIDOR 100B, AND CORRIDOR 100C. CONTRACTOR SHALL DETERMINE

PROVIDE AND INSTALL HALLWAY OCCUPANCY MOTION SENSOR IN THE FIRE STATION HALLWAYS

LIGHT FIXTURES.

FIXTURE. PROVIDE AND INSTALL SEPARATE LIGHT SWITCHES FOR THE SHOWER AND RESTROOM

UL LABELED AND SUITABLE FOR USE IN WET LOCATION. PROVIDE POWER TO EACH SHOWER

PROVIDE AND INSTALL RECESSED CAN LIGHTS IN THE SHOWER AREA. THE CAN LIGHT SHALL BE

GENERAL NOTE THIS SHEET.

ALL ALERT FIXTURES WILL BE CONTROLLED BY THE CONTROL SWITCH IN ROOM 119. SEE

FIXTURES TO CIRCUIT EA-3. SEE GENERAL NOTE THIS SHEET.

PROVIDE POWER TO ALL DEDICATED ALERT FIXTURES (FIXTURE I) IN ONE CIRCUIT AND CONNECT

CONTROL SWITCH WITH USER AND DPW PROJECT MANAGER. SEE GENERAL NOTE THIS SHEET.

TO CONTROL ON/OFF OPERATION OF THE ALERT FIXTURES. COORDINATE THE LOCATION OF THE

PROVIDE A CONTROL SWITCH AND MOUNT SWITCH 48-INCH ABOVE FINISHED FLOOR IN ROOM 119

THIS SHEET.

MOUNT THE FIXTURE 7’-6" ABOVE FINISHED FLOOR (WALL-MOUNTED). SEE GENERAL NOTE

PROVIDE AND INSTALL DEDICATED ALERT FIXTURES (FIXTURE I) AS SHOWN ON THE DRAWING.

ELECTRICAL POWER PLAN

43105-E3

E3

106A

100C

100B

100A

LAUNDRY JAN,

PPE STORAGE

EMT STORAGE

SHOWER

MEN’S

WOMEN’S

VEHICLE BAY

APPARATUS STORAGE

EMT OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

KITCHEN

SUPERVISOR’S OFFICE

FITNESS

DORM 6 ROOM

DORM 5 ROOM

DORM 4 ROOM

DORM 3 ROOM

DORM 2 ROOM

DORM 1 ROOM

MECH. ROOM

COMM. ROOM1

OFFICE/ROOM AREA KEYED NOTES:

10 11

SPECIAL ELECTRICAL KEYED NOTES:

EF-1

EF-2

EF-3

EF-4

J J

J

J J

J

UH-1

UH-5

J

J

CONDENSER

12.5 TON

CONDENSER

1/2 TON

UH-2

UH-4

UH-6

GFI GFI

19 20

GFI

22 22

GFI

WP

GFI

WP

GFI

WP

GFI

WP

GFI

WP

EF-7

EF-6

UH-3

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

A-7,9,11 A-7,9,11

A-8,10,12

A-8,10,12

A-13,15,17

A-13,15,17

B-13,15

EA-10

EA-16

EA-14

EA-18

EA-22

EA-24

EA-37,39,41

EA-37,39,41

EA-31,33,35EA-31,33,35

EA-15

GFI

A-1,3,5

A-2,4,6

A-37,39,41

NOTES

CIRCUIT

DOORS CONTROL

RETRACTABLE BAY

CONNECT TO BOTH

SPECIAL ELECTRICAL KEYED NOTES CONTINUATION:

B-10,12EA-7

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

654321

A

B

1 2 3 4 5 6

B

A

33 33

B-6,8

B-1,3

B-5,7

B-9,11

B-17

B-19

B-21

B-20

B-22

B-28

B-28

GFI

WP

B-28

B-28

B-28

B-28

B-30

48" AFF

GFI

B-29

B-29

COMPRESSOR

INSTALL 5HP

B-31

EA-12

EA-29

EA-27EA-25

GFI

AFF

48"

B-26

LEGEND

RANGE RECEPTACLE

DUPLEX RECEPTACLE

QUAD RECEPTACLE

E3

SCALE: 1/8" = 1’-0"ELECTRICAL POWER PLAN

J

EA-26

A-32,34,36

EA-38

DEVICE PERMITTING THE DOOR TO BE CLOSED BY THE DOOR CLOSER. THE DEVICE SHALL BE UL LISTED.

INITIATION OF ANY FIRE ALARM SHALL CAUSE THE RELEASE OF THE ELECTROMAGNETIC DOOR HOLDING

DOOR). THE ELECTROMAGNETIC HOLDING DEVICE SHALL BE DESIGNED TO OPERATE ON 120 VAC. THE

PROVIDE AND INSTALL A MAGNETIC FIRE DOOR HOLD OPEN DEVICE (A MAGNETIC HOLDER FOR FIRE RATED

BAY AREA.

SIX REMOTE CONTROL KEYS FOR DRIVERS TO OPEN/CLOSE THE RETRACTABLE BAY DOORS IN VEHICLE

SYSTEM. IN ADDITION TO THE SWITCH CONTROL OPERATING THE RETRACTABLE BAY DOORS, PROVIDE

INTEGRATE THE SIGNALING SYSTEM WITH VEHICLE BAY DOOR OPENER USING ELECTRIC EYES SENSING

WITH THE USER FOR THE MOUNTING HEIGHT OF THE DVD PLAYER.

PROVIDE AND INSTALL WALL MOUNT BRACKETS FOR BOTH 60-INCH HD TV AND DVD PLAYER. COORDINATE

THE SWITCH TO CIRCUIT B-24.

PROVIDE AND INSTALL A WALL SWITCH TO CONTROL ON/OFF OF THE RANGE HOOD’S FAN AND CONNECT

PLUMBING CONTRACTOR TO DETERMINE THE LOCATION OF THE RECEPTACLE.

VEHICLE BAY AREA AND MOUNT THE RECEPTACLE 36-INCH ABOVE FINISHED FLOOR. COORDINATE WITH

PROVIDE AND INSTALL A DEDICATED 120V, 20A RECEPTACLE CIRCUIT FOR THE ICE MACHINE IN THE

48 X48 WALL LOUVER ELECTRIC MOTOR OPERATED CONTROLLED BY EF-7. 48 X 48 WALL LOUVER ELECTRIC MOTOR OPERATED CONTROLLED BY EF-6.

THE 120 VAC RELAY COILS (STARTER). SEE DRAWING SHEET E5, NOTES 22, 23 & 24 FOR DETAILS.

CONNECT EXHAUST FAN (EF-6) AND EXHAUST FAN (EF-7) TO CARBON MONOXIDE CONTROL PANEL VIA

THE MECHANICAL ROOM.

PROVIDE AND INSTALL TWO (2) NEW 175 AMPS, 3-PHASE, 4-WIRE, 120/208V, 42-CIRCUIT PANELS IN

DRAWING SHEET 43105-E9.

MECHANICAL ROOM. CONTRACTOR SHALL PROVIDE A J-BOX MOUNTED ON THE BEAM AS SHOWN ON

PROVIDE AND INSTALL A NEW 400 AMPS, 3-PHASE, 4-WIRE, 120/208V, 42-CIRCUIT PANEL IN THE

PROVIDE BACK-UP POWER TO EMERGENCY POWER PANEL (EA) THRU AN AUTOMATIC TRANSFER SWITCH, NECESSARY LIQUID PROPANE GAS LINES FOR THE EMERGENCY GENERATOR. THE GENERATOR WILL

LOCATION). CONTRACTOR SHALL PROVIDE A HOUSING PAD FOR THE GENERATOR AND INSTALL ALL

PROVIDE AND INSTALL 60 KW LIQUID PROPANE GENERATOR AS SHOWN IN THE DRAWING (APPRROX.

MOUNT THE RECEPTACLES ON THE TELECOM BACKBOARD. CONNECT TO CIRCUITS EA-40 AND EA-42.

PROVIDE AND INSTALL DEDICATED 120V, 20A, QUADPLEX RECEPTACLE AS SHOWN ON THE DRAWING AND

COORDINATE THE LOCATION OF CONTROL SWITCHES/BUTTONS WITH USER AND PROJECT MANAGER.

A CONTROL SWITCH IN ROOM 119 TO OPEN AND/OR CLOSE EACH RETRACTABLE BAY DOOR SEPARATELY.

BAY DOOR SHALL BE EQUIPPED WITH ELECTRIC EYE AND/OR AUTOMATIC REVERSE DEVICE. PROVIDE

MOTOR STARTER, PROPER WIRING, CONDUIT, CIRCUIT BREAKER, AND ENCLOSURE. EACH VEHICLE

PROVIDE POWER TO EACH VEHICLE BAY DOOR (RETRACTABLE BAY DOOR) WITH DISCONNECT SWITCH, PROVIDE SIX (6) REMOTE KEYS TO CONTROL OPEN/CLOSE THE RETRACTABLE BAY DOORS.

SWITCH 48-INCH ABOVE FINISHED FLOOR IN ROOM 119 (SUPERVISOR’S OFFICE). IN ADDITION, CONTROL THE OPERATION OF RETRACTABLE BAY DOORS IN VEHICLE BAY AREA. MOUNT THE CONTROL

PROVIDE AND INSTALL A SWITCH/BUTTON (OPEN DOOR, CLOSE DOOR, AND/OR STOP POSITION) TO

LAUNDRY ROOM.

PROVIDE AND INSTALL 2-POLE, 30A, 4-WIRE RECEPTACLE CIRCUIT FOR THE CLOTHES DRYER IN THE

PROVIDE AND INSTALL 120V, 20A RECEPTACLE CIRCUIT FOR THE CLOTHES WASHER IN THE LAUNDRY.

RECEPTACLE OUTLET AT 7’-6" ABOVE FINISHED FLOOR NEXT TO THE CATV OUTLET.

PROVIDE AND INSTALL 120V, 20A, RECEPTACLE CIRCUIT FOR FLAT SCREEN TV. MOUNT THE TV

STAINLESS STEEL NATURAL GAS GRILL. USE STANDARD GAS TANK.

MOUNT RECEPTACLE OUTLET 36-INCH ABOVE FINISHED FLOOR.

PROVIDE 208 VOLTS, 60 HZ, 3 PHASE POWER TO UNIT HEATER IN VEHICLE BAY AREA.

SIZES FOR EQUIPMENT ACTUALLY INSTALLED.

CIRCUIT BREAKER, AND ENCLOSURE. CONNECT TO CIRCUIT EA-21,23. ADJUST BREAKER AND CIRCUIT

INSTALL DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER WIRING, CONDUIT, PROVIDE 208 VOLTS, 60 HZ, 2 POLE POWER TO CEILING-MOUNTED AIR HANDLER. CONTRACTOR SHALL

FOR EQUIPMENT ACTUALLY INSTALLED.

BREAKER, AND ENCLOSURE. CONNECT TO CIRCUIT EA-17,19. ADJUST BREAKER AND CIRCUIT SIZES

DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER WIRING, CONDUIT, CIRCUIT

PROVIDE 208 VOLTS, 60 HZ, 2 POLE POWER TO 1/2 TON CONDENSER. CONTRACTOR SHALL INSTALL

CIRCUIT BREAKER, AND ENCLOSURE.

INSTALL DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER WIRING, CONDUIT, PROVIDE 208 VOLTS, 60 HZ, 3 PHASE POWER TO AIR HANDLER’S BLOWER MOTOR. CONTRACTOR SHALL

CONDUIT, CIRCUIT BREAKER, AND ENCLOSURE.

SHALL INSTALL DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER WIRING, PROVIDE 208 VOLTS, 60 HZ, 3 PHASE POWER TO AIR HANDLER’S TWO STAGE HEATING. CONTRACTOR

BREAKER, AND ENCLOSURE.

DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER WIRING, CONDUIT, CIRCUIT

PROVIDE 208 VOLTS, 60 HZ, 3 PHASE POWER TO 12.5 TON CONDENSER. CONTRACTOR SHALL INSTALL

PROVIDE AND INSTALL A DEDICATED RECEPTACLE CIRCUIT FOR ELECTRIC RANGE IN THE KITCHEN.

PROVIDE AND INSTALL 120V, 20A, DEDICATED GFI RECEPTACLE CIRCUIT FOR THE WATER FOUNTAIN.

CONDUIT, CIRCUIT BREAKER, AND ENCLOSURE. CONNECT TO CIRCUIT B-2,4.

SHALL INSTALL DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER WIRING, PROVIDE POWER TO A 80 GALLON ELECTRIC WATER HEATER IN MECHANICAL ROOM. CONTRACTOR

48-INCH ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL 120V, 20A, COUNTER-TOP RECEPTACLE CIRCUIT AND MOUNT RECEPTACLE

RECEPTACLE 48-INCH ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL 120V, 20A, COUNTER-TOP GFI RECEPTACLE CIRCUIT AND MOUNT THE

PROVIDE AND INSTALL 120V, 20A, DEDICATED RECEPTACLE CIRCUIT FOR THE REFRIGERATOR.

PROVIDE AND INSTALL 120V, 20A, RECEPTACLE CIRCUIT FOR DISHWASHER.

DISPOSER PER MANUFACTURER’S RECOMMENDATION.

PROPERLY GROUNDED). PROVIDE WALL SWITCH TO CONTROL THE DISPOSER. INSTALL

PROVIDE AND INSTALL FOOD WASTE DISPOSER UNDER THE SINK (THE DISPOSER MUST BE

CONNECT ALL EXHAUST FAN MOTOR TO LIGHTING CIRCUIT (INTERLOCK WITH LIGHT SWITCH).

E4

SCALE: 1/8" = 1’-0"

43105-E4

E4

ELECTRICAL COMMUNICATIONS PLAN

ELECTRICAL COMMUNICATIONS PLAN

LEGEND

SPECIAL ELECTRICAL KEYED NOTES:

106A

100C

100B

100A

LAUNDRY JAN,

PPE STORAGE

EMT STORAGE

SHOWER

MEN’S

WOMEN’S

VEHICLE BAY

APPARATUS STORAGE

EMT OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

KITCHEN

SUPERVISOR’S OFFICE

FITNESS

DORM 6 ROOM

DORM 5 ROOM

DORM 4 ROOM

DORM 3 ROOM

DORM 2 ROOM

DORM 1 ROOM

MECH. ROOM

COMM. ROOM1

OFFICE/ROOM AREA KEYED NOTES:

3 3

10 11

12 13

15 16 17

181920

DE

M

TYP.

TYP.

9 10 11

12TYP.

TYP.

TYP.6

TYP.

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

654321

A

B

1 2 3 4 5 6

B

A

DE

DE

DE

DE

M

WP

WPWP

WP WP

WP

WP

CAMERA (FUTURE)

WEATHERPROOF CCTV

FUTURE CCTV CAMERA

MICROPHONE JACK

FLUSH-MOUNTED

CABLE TV OUTLET

TELEPHONE DROP

DROP

EMERGENCY PHONE

VOICE/DATA DROP

QUAD RECEPTACLE

SIDE OF THE CONDUIT) FOR FUTURE CCTV CAMERAS.

PROVIDE AND INSTALL CCTV CONDUITS AND J-BOXES WITH PULL STRINGS (CAP BOTH

FINISHED FLOOR. MOUNT DATA AND VOICE OUTLET 7’-6" ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL CATV OUTLET AND MOUNT THE CATV OUTLET 7’-6" ABOVE

DRAWING AND MOUNT THE OUTLETS 54-INCH ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL OUTLETS WITH VOICE AND DATA JACKS AS SHOWN ON THE

GROUNDING.

ENSURE THE TELECOM BACKBOARD CONNECTING TO THE BUILDING GROUND WITH #6

THE RECEPTACLES ON THE TELECOM BACKBOARD. SEE DRAWING SHEET 43105-E3.

PROVIDE AND INSTALL DEDICATED 120V, 20A, QUADPLEX RECEPTACLES AND MOUNT

THE CATV OUTLETS 18-INCH ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE.

PROVIDE AND INSTALL A CATV OUTLETS AS SHOWN ON THE DRAWING AND MOUNT

UTP CABLE.

THE TELECOM TERMINAL BACKBOARD WITH ONE 4-PAIR, TIA/EIA 568-B CAT 6,

NEC CONTRACTOR WILL CONNECT ALL SINGLE 8-POSITION TELEPHONE DROPS FROM

SOLID COPPER CABLES

PAIR, TIA/EIA 568-B CATEGORY 6 (CAT 6), UNSHIELDED TWISTED PAIR (UTP)

TERMINAL BACKBOARD AND/OR COMMUNICATIONS EQUIPMENT RACK WITH TWO 4-

NEC CONTRACTOR WILL CONNECT ALL VOICE/DATA DROPS FROM THE TELEPHONE

POSITION FOR VOICE/DATA AND SINGLE 8-POSITION FOR TELEPHONE).

NEC CONTRACTOR WILL PROVIDE 8-POSITION CONNECTORS OUTLET (DUAL 8-

MOUNT THE OUTLETS 54-INCH ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL A TELEPHONE OUTLETS AS SHOWN ON THE DRAWING AND

THE DRAWING AND MOUNT THE OUTLETS 18-INCH ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL OUTLETS WITH VOICE AND DATA JACKS AS SHOWN ON

THE DRAWING AND MOUNT THE OUTLETS 54-INCH ABOVE FINISHED FLOOR.

PROVIDE AND INSTALL DEDICATED EMERGENCY PHONE OUTLETS AS SHOWN ON

INTERFERENCE BETWEEN CABLE TRAYS AND NEW DUCT WORKS.

ELECTRICAL CONTRACTOR SHALL COORDINATE WITH HVAC CONTRACTOR TO AVOID

RETARDANT PLYWOOD IN THE NEC ROOM.

PROVIDE AND INSTALL A 4’X8’ TELECOM BACKBOARD WITH 3/4" THICK FIRE

5 FOOT BEYOND BUILDING FOUNDATION.

CONDUIT FOR CATV) FROM THE TELECOM BACKBOARD IN NEC ROOM. EXTEND

PROVIDE 3-4" EMT CONDUITS (2-4" CONDUIT FOR COMMUNICATIONS AND 1-4"

PROVIDE AND INSTALL 18-INCH CABLE TRAYS ABOVE CEILING.

FASTENED SECURELY AND BE EQUIPPED WITH ANTI-CHAFING GROMMET.

OUTLETS THROUGHOUT THE BUILDING WITH PULL STRING. CONDUIT TO BE

PROVIDE AND INSTALL ONE 1-INCH EMT CONDUIT FOR VOICE AND/OR DATA

WP

E5

SCALE: 1/8" = 1’-0"

43105-E5

E5

FIRE ALARM AND MASS NOTIFICATION PLAN

F

S

V

LOC

FACP

MNS

ANN

GENERAL FIRE ALARM & MASS NOTIFICATION NOTES:

LEGENDLEGEND

FIRE ALARM & MASS NOTIFICATION NOTES:

S B

CS

S

S

WP

S

D

106A

100C

100B

100A

LAUNDRY JAN,

PPE STORAGE

EMT STORAGE

SHOWER

MEN’S

WOMEN’S

VEHICLE BAY

APPARATUS STORAGE

EMT OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

KITCHEN

SUPERVISOR’S OFFICE

FITNESS

DORM 6 ROOM

DORM 5 ROOM

DORM 4 ROOM

DORM 3 ROOM

DORM 2 ROOM

DORM 1 ROOM

MECH. ROOM

COMM. ROOM1

OFFICE/ROOM AREA KEYED NOTES:

2 2

3 3

10 11

181920

TYP.

TYP.

TYP.

TYP.

9 10

TYP.

TYP.

TYP.

FIRE ALARM AND MASS NOTIFICATION SYSTEMS

S

S

S

S

S

S

S

CO

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

654321

A

B

1 2 3 4 5 6

B

A

F

F A

C P

M N S

A N

N

L O

C

V V

V

V

V

F

S

S

S

S

F

FV

V

S S

S

S S

S S S

S S

V

V

S

V

S

SS

V

CS

B

B

S B

S B

S B

F

S

S

S

S

WP WP

WP

WP

WPWP

WP

WP

S S

V

V

V

V

V

S

B

TS

FS

V

CO

CO

S

S

SS S S

S S

SPEAKER (TYP)

INSTALL FA/MNS

V

MANUFACTURER’S RECOMMENDATIONS.

DEVICES AND/OR DETECTORS SHALL BE PERFORMED IN ACCORDANCE WITH THE

4. INSTALLATION OF CARBON DIOXIDE DETECTOR, DUCT DETECTOR, OTHER FIRE ALARM

FORT BENNING SHALL MEET THE MINIMUM REQUIREMENT OF THIS NEW UFC.

NOTIFICATION SYSTEM AT FORT BENNING. MNS SYSTEM THAT BEING INSTALLED AT

DATED JANUARY 2010 IS OUR CURRENT REQUIREMENT USED TO IMPLEMENT THE MASS

MENTIONED IN THE LATEST VERSION OF UFC 4-021-01. UFC 4-021-01 CHANGE 1

SYSTEM (MNS). NEW MNS INSTALLATION SHALL MEET THE MINIMUM REQUIREMENT

3. UFC 4-021-01 IS THE GUIDANCE USED TO IMPLEMENT MASS NOTIFICATION

SYSTEM.

OCCUPIED BY 11 OR MORE DOD PERSONNEL TO INSTALL THE MASS NOTIFICATION

AND MAJOR RENOVATION PROJECTS INVOLVING BUILDING FACILITIES WHICH IS

FOR BUILDING. THE STANDARDS REQUIRE ALL NEW MILITARY CONSTRUCTION

2. UFC 4-010-01 IS USED TO SPECIFY DOD MINIMUM ANTI-TERRORISM STANDARDS

PROCEDURE (SOP), AND THE LATEST VERSION OF 13855N SPECIFICATION.

THE LATEST VERSION OF FORT BENNING FIRE ALARM STANDARD OPERATING

1. THE WORK FOR THE FIRE ALARM SYSTEM SHALL BE DONE IN ACCORDANCE WITH

F

V

S S S

SS

SSS

SSS

S S S

S

S S S

S S S

FIRE ALARM & MASS NOTIFICATION KEYED NOTES:

CO

CO

CO

CO

CO

CO

FIRE ALARM & MASS NOTIFICATION KEYED NOTES:

EF-6

EF-7

22 23 24

22 23 24

22 23 24

222324

PANEL

CO CONTROL

222324

J

TYP.

V

V

SS SS

S SS

DUCT DETECTOR

BEAM-MOUNTED SPEAKER

CEILING-MOUNTED SPEAKER

4 HORNS, BEAM-MOUNTED

CLUSTER SPEAKER WITH

SPEAKER, WALL-MOUNTED

WEATHERPROOF FA/MNS

PANEL

AND LOC (COMPACT SIZE)

COMBINATION ANNUNCIATOR

BEAM-MOUNTED

FA SPEAKER STROBE

BEAM-MOUNTED

MNS SPEAKER STROBE

CEILING-MOUNTED

FA SPEAKER STROBE

CEILING-MOUNTED

MNS SPEAKER STROBE,

S

B

B

S B

S B

B

B

WIRES TO ENSURE A SINGLE ACCIDENT CANNOT IMPAIR THE ENTIRE FIRE ALARM SYSTEM.

13) PROVIDE TWO SEPARATE CONDUITS, ONE FOR OUTGOING AND ANOTHER FOR RETURNING CIRCUIT

WIRING IN ACCORDANCE WITH STANDARDS AND CODES.

12) PROVIDE A MINIMUM 3/4" ELECTRICAL METALLIC TUBING (EMT) CONDUIT FOR ALL FIRE ALARM

11) ENSURE SMOKE DETECTOR SPACING NOT EXCEED 30 FEET IN DIAMETER.

10) PROVIDE SMOKE DETECTOR NOT CLOSER THAN 12 INCHES FROM ANY PART OF LIGHTING FIXTURE.

OPENING.

9) PROVIDE SMOKE DETECTOR NOT CLOSER THAN 3 FEET FROM AIR-SUPPLY DIFFUSER OR RETURN-AIR

FOR CONNECTION TO BUILDING WIRING.

TWIST-LOCK MODULE THAT CONNECTS TO A FIXED BASE. PROVIDE TERMINALS IN THE FIXED BASE

8) SMOKE/HEATER DETECTORS AND ASSOCIATED ELECTRONIC COMPONENTS SHALL BE MOUNTED IN A

7) ENSURE EACH MANUAL PULL STATION BE ACCESSIBLE, UNOBSTRUCTED, AND VISIBLE TO PUBLIC.

ROOMS, MECHANICAL ROOMS, AND UTILITY ROOMS.

6) PAINT RED ENAMEL ON ALL CONCEALED FIRE ALARM CONDUIT AND CONDUIT LOCATED IN STORAGE

NFPA 101 LIFE SAFETY REQUIREMENTS.

5) CONTRACTOR SHALL INSTALL SMOKE DETECTORS, HORNS AND LIGHTS IN THE BUILDING TO MAINTAIN

DISCONNECT SWITCHES.

4) OBTAIN 120V AC SERVICE FROM INCOMING POWER SOURCE AHEAD OF ALL BUILDING SERVICES AND

AND MAINTENANCE INSTRUCTIONS TO GOVERNMENT PERSONNEL AS REQUIRED.

ADJUSTMENT, PRELIMINARY TESTING, AND FINAL TESTING OF THE SYSTEM AND TO PROVIDE OPERATION

3) A CERTIFIED FIRE ALARM TECHNICIAN IS REQUIRED TO SUPERVISE THE FIRE ALARM INSTALLATION, FIRE ALARM SYSTEM.

2) A CERTIFIED FACTORY TRAINED FIRE ALARM DESIGNER IS REQUIRED TO DESIGN THE COMPLETE WORKING

THE FIRE ALARM CONTROL UNIT. THE NOTIFICATION SPEAKERS WILL BE PART OF THE FIRE ALARM SYSTEM.

1) FIRE ALARM CONTRACTOR SHALL DESIGN THE MASS NOTIFICATION SYSTEM AND INTEGRATE THE SYSTEM TO

STROBE LIGHTS

HEAT DETECTOR

WALL SPEAKER STROBE

COMBINATION FA & MNS

CO DETECTOR

SOUNDER BASE

SMOKE DETECTOR WITH

MANUAL PULL STATION

VOICE EVACUATION DEVICE

PANEL

NOTIFICATION SYSTEMS

FIRE ALARM AND MASS

LIGHTS

COMBINATION HORNS/STROBE

15 16 17

V

CO

CO

PROVIDE AND INSTALL CARBON MONOXIDE DETECTOR (CO) IN MECHANICAL ROOM. MOUNT CO DETECTOR 2’-0" ABOVE FINISHED FLOOR. CONTRACTOR SHALL CONNECT CO DETECTOR TO A FIRE ALARM SYSTEM.

FLOW SWITCH PER MANUFACTURER’S RECOMMENDATION.

PROVIDE WALL MOUNTED JUNCTION BOX WITH 3/4" FLEX CONDUIT TO TAMPER SWITCH. ROUTE 3/4" CONDUIT FROM JUNCTION BOX TO THE FIRE ALARM CONTROL PANEL. INSTALL TAMPER SWITCH AND WATER

PROVIDE AND INSTALL TAMPER SWITCH FOR EACH FIRE PROTECTION SYSTEM CONTROL VALVE AS WELL AS PROVIDE AND INSTALL VANE TYPE WATER FLOW DETECTORS FOR WET PIPE SPRINKLER SYSTEMS.

CONNECT THE ELECTROMAGNETIC HOLDING DEVICE TO THE FIRE ALARM CONTROL PANEL TO CLOSE THIS FIRE RATED DOOR AUTOMATICALLY UPON ACTIVATION OF THE FIRE ALARM.

INSTALL CARBON MONOXIDE TRANSDUCER (SENSOR) 3-6" ABOVE FINISHED FLOOR IN VEHICLE BAY AREA AND 2’-0" ABOVE FINISHED FLOOR INSIDE CORRIDORS.

AS REQUIRED BY THE MANUFACTURER.

CARBON MONOXIDE DETECTORS ARE POWERED FROM CARBON MONOXIDE CONTROL PANEL. PROVIDE UNSHIELDED FOUR CONDUCTOR CABLES FOR CARBON MONOXIDE TRANSDUCERS AND ISOLATED GROUND POWER SOURCE

WITH TWO EXHAUST FANS (EX-6 AND EX-7) AND TWO WALL LOUVER ELECTRIC MOTORS IN THE VEHICLE BAY AREA.

INSTALL A COMPLETE CARBON MONOXIDE DETECTION SYSTEM (EIGHT CARBON MONOXIDE TRANSDUCERS AND ONE CONTROL PANEL) INCLUDING CONDUITS, CABLES, AND INTERLOCK THE CARBON MONOXIDE DETECTION SYSTEM

CARBON MONOXIDE TRANSDUCERS AND CONTROL PANEL , EQUAL TO MACURCO CARBON MONOXIDE TRANSDUCERS #SS102HC-1, AND MACURCO CONTROL PANEL #SS103-10A. ELECTRICAL CONTRACTOR SHALL PROVIDE AND

FAN (EF-7) SHALL OPERATE AT HIGH SPEED AND ASSOCIATED MOTOR OPERATED DAMPER SHALL OPEN.

48 X 18 WALL LOUVER ELECTRIC MOTOR OPERATED CONTROLLED BY EF-7. INTERLOCK THE CARBON MONOXIDE DETECTION SYSTEM WITH THE EXHAUST FAN (EX-7). UPON DETECTION OF CARBON MONOXIDE, THE EXHAUST

FAN (EF-6) SHALL OPERATE AT HIGH SPEED AND ASSOCIATED MOTOR OPERATED DAMPER SHALL OPEN.

48 X 18 WALL LOUVER ELECTRIC MOTOR OPERATED CONTROLLED BY EF-6. INTERLOCK THE CARBON MONOXIDE DETECTION SYSTEM WITH THE EXHAUST FAN (EF-6). UPON DETECTION OF CARBON MONOXIDE, THE EXHAUST

48 X 18 FRESH AIR DUCT DOWN TO 12 INCHES ABOVE FLOOR.

PROVIDE AND INSTALL A CEILING-MOUNTED MASS NOTIFICATION (MNS) SPEAKER STROBE IN THE KITCHEN.

PROVIDE AND INSTALL A CEILING-MOUNTED FIRE ALARM (FA) SPEAKER STROBE LIGHT IN THE KITCHEN.

PROVIDE AND INSTALL CEILING-MOUNTED SPEAKER THROUGHOUT THE FIRE STATION.

PROVIDE AND INSTALL BEAM-MOUNTED SPEAKER IN THE VEHICLE BAY AREA.

PROVIDE AND INSTALL CLUSTER SPEAKER WITH FOUR HORNS AND MOUNT THE SPEAKER ON THE BEAM.

PROVIDE AND INSTALL A DEDICATED 120V, 20A QUADPLEX RECEPTACLE ON THE TELECOM BACKBOAED.

PROVIDE AND INSTALL WEATHER-PROOF ALARM SPEAKER AS SHOWN ON THE DRAWING.

PROVIDE AND INSTALL A MANUAL PULL STATION AS SHOWN ON THE DRAWING.

PROVIDE AND INSTALL SMOKE DETECTOR ABOVE THE FIRE ALARM CONTROL PANEL.

AND VOICE RECORDING MESSAGE THROUGHOUT THE BUILDING.

NEW SYSTEM SHALL BE ABLE TO BROADCAST AUDIBLE MESSAGE, LIVE VOICE MESSAGE, FIRE MESSAGE, PROVIDE A NEW MASS NOTIFICATION SYSTEM INTEGRATING WITH NEW FIRE ALARM CONTROL PANEL. THE

PROVIDE AND INSTALL GROUND WIRE FROM THE MAIN SERVICE GROUND TO FIRE ALARM CONTROL UNIT.

PROVIDE AND INSTALL STROBE SPEAKER FOR VOICE EVACUATION SYSTEM AS SHOWN ON THIS DRAWING.

PROVIDE AND INSTALL NEW SMOKE AND/OR HEAT DETECTORS AS SHOWN ON THIS DRAWING.

PROVIDE AND INSTALL NEW COMBINATION HORNS/STROBE LIGHTS AS SHOWN ON THIS DRAWING.

EQUIPMENT. COORDINATE WITH MECHANICAL HVAC CONTRACTOR FOR INSTALLING THE DUCT DETECTORS.

PROVIDE AND INSTALL NEW DUCT DETECTORS PER MANUFACTURER’S RECOMMENDATION FOR THE NEW HVAC

PROVIDE AND INSTALL A COMBINATION OF ANNUNCIATOR AND LOC PANEL AT THE MAIN ENTRANCE IN LOBBY.

EMT CONDUIT FROM THE FIRE ALARM PANEL WITH PULL STRING TO THE TELECOM BACKBOARD.

FIRE STATIONS’ TELEPHONE. COORDINATE THE SERVICE WITH NEC REPRESENTATIVE. PROVIDE 1-INCH

PROVIDE TWO DEDICATED PHONE LINES IN NEC ROOM BETWEEN FIRE ALARM CONTROL PANEL AND POST

PROVIDE A CLASS "A", 4-WIRES FULLY ADDRESSABLE FIRE ALARM SYSTEM.

LIGHTNING PROTECTION SCOPE OF WORKS:

REAR ELEVATION

LEFT SIDE ELEVATION RIGHT SIDE ELEVATION

FRONT ELEVATION

43105-E6

E6

LIGHTNING PROTECTION - ELEVATION PLAN

SPLICER

CABLE

PARALLEL

CABLE SPLICER

COMBINATION

BAR JOIST

METAL DECK

OR COUPLING

LOCK NUTS

RIDGE VENT

AIR TERMINAL

SPECIFICATION

SHALL MEET ROOF

ROOF PENETRATION

WEATHER PROOF SEAL

END CONNECTORS

WITH APPROVED TYPE

BONDING CONDUCTOR

CLIP CABLE SUPPORT

ROOF

ROOF

AIR TERMINAL

RAFTERS

MAIN CONDUCTOR

CABLE CONNECTOR

RISER BAR

SEALING WASHER

M I

N

GROUND ROD

CONDUCTOR

COUNTERPOISE

#1/0 CU

DOWN CONDUCTOR

CONCEALED

PVC CONDUIT

EXOTHERMIC BONDING CONNECTION

EDGE OF BUILDING

COUNTERPOISE 3-6’ OUTSIDE DRIP

PVC CONDUIT THROUGH CONCRETE SLAB

GRADE

M I

N

M I

N

MIN.

3’-0"

SECONDARY BONDING CONDUCTOR

CONDUCTOR

ROOF LIGHTNING PROTECTION

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

A A A A

A A

AA

AAA

A

654321

6 5 4 3 2 1

BA AB

ON LIGHTNING PROTECTION APPLICATIONS.

SURGE PROTECTIVE DEVICE SUITABLE FOR ELECTRICAL SERVICE ENTRANCE

3. PROVIDE AND INSTALL TRANSIENT VOLTAGE SURGE SUPPRESSOR (TVSS) OR

ACCORDANCE WITH UL 96A.

2. THE LIGHTNING PROTECTION SYSTEM (LPS) SHALL BE INSTALLED IN

1. CONTRACTOR SHALL DESIGN THE LIGHTNING PROTECTION SYSTEM.

LIGHTNING PROTECTION NOTES:

LIGHTNING PROTECTION SYSTEM USING SECONDARY CONDUCTOR.

16. ALL METAL EQUIPMENT ON THE ROOF SHALL BE BONDED TO THE

DETAIL 4, THIS SHEET.

GROUND ROD WILL BE AT LEAST 3/4" X 10’-0" LONG. SEE

15. COUNTERPOISE WILL EXTEND 10’ BEYOND BUILDING PERIMETER AND

USING AGENCY.

14. GROUNDING WILL CONFORM TO UL96A, EXCEPT AS REQUIRED BY THE

13. CONNECTOR BONDING BELOW GRADE SHALL BE EXOTHERMIC WELD TYPE.

12. ALL CONDUCTORS (PRIMARY AND SECONDARY) SHALL NOT BE PAINTED.

HAVE A RADIUS OF BEND LESS THAN 8-INCHES.

11. NO CONDUCTOR SHALL FORM AN ANGLE THAT EXCEEDS 90 DEGRESS, NOR

TERMINALS TO FORM A TWO WAY PATH TO GROUND.

10. ALL LIGHTNING PROTECTION CONDUCTORS SHALL INTERCONNECT ALL AIR

INTERVALS NOT TO EXCEED 3’-0" O.C.

9. ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED AT

CORROSION OF DISSIMILAR METALS.

COMPONENTS ARE MOUNTED TO ALUMINUM SURFACES TO AVOID GALVANIC

8. ALUMINUM COMPONENTS SHALL BE USED IN LOCATIONS WHERE SYSTEM

7. ALL METAL SHALL BE COPPER, BRONZE, OR STAINLESS STEEL.

WITH UL 96A AND NFPA 780 MATERIAL CODE REQUIREMENTS.

6. ALL LIGHTNING PROTECTION MATERIALS AND COMPONENTS SHALL COMPLY

5. PROVIDE AND INSTALL DOWNCONDUCTORS OUTSIDE OF THE STRUCTURE.

AND VERTICAL TUBE WITH NEOPRENE SEAL.

4. THRU ROOF FLASHING SHALL BE COPPER WITH 8-INCH ROUND BASE

WATERPROOFING AND CAULKING AROUND PENETRATED AREA.

3. PROVIDE ROOF PENETRATION IF NECESSARY AND APPLY ADEQUATE

UL 96A.

2. ALL LIGHTNING PROTECTION DEVICES WILL BE IN ACCORDANCE WITH

DETAILS 2, 3, 4, 5 AND 6 THIS SHEET.

THEM ON THE ROOF WITH CABLE SUPPORT AND CONNECTOR. SEE

PRIMARY (ROOF) CONDUCTOR TO THE AIR TERMINAL, AND SECURE

1. PROVIDE AND INSTALL AIR TERMINAL ON THE ROOF. CONNECT THE

1 LIGHTNING PROTECTION PLAN SCALE: 1/8" = 1’-0"

E6

NO SCALE3

E6 DETAIL

AIR TERMINAL

NO SCALETHROUGH ROOF RIDGE VENT

TYPICAL MOUNTING OF TERMINALS2

E6

NO SCALE

E6 DETAIL

EXOTHERMIC BOND

NO SCALE5

E6 DETAIL

CABLE SPLICERS

4 GROUNDING DETAIL

E6

NO SCALE

CADWELD LOOP CONDUCTOR

CADWELD

CADWELD

M I

N

AIR TERMINAL

AND CONNECTOR

CABLE SUPPORT

CONDUCTOR

PRIMARY

AIR TERMINAL

PRIMARY CONDUCTOR

CLIP CABLE SUPPORT

WASHER

SEALING

FLAT ROOF

CONDUCTOR

COPPER CABLE

5’ INTERVAL

BRICK AT

CONCRETE

ROOFING

MOP-IN WITH

BRICK

LOOP CABLE HOLDER

ROOF

SIDE VIEWPLAN

SLOPED ROOF

REAR ELEVATION

43105-E7

E7

LIGHTNING PROTECTION - ROOF PLAN

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

- SEE MECH.

EXHAUST VENTS, TYP.

EXISTING MTL. ROOF TO REMAIN

- SEE MECH.

EXHAUST VENTS, TYP.

- SEE MECH.

EXHAUST VENTS, TYP.

- SEE MECH.

EXHAUST VENTS, TYP.

- SEE MECH.

EXHAUST VENTS, TYP.

ON LIGHTNING PROTECTION APPLICATIONS.

SURGE PROTECTIVE DEVICE SUITABLE FOR ELECTRICAL SERVICE ENTRANCE

3. PROVIDE AND INSTALL TRANSIENT VOLTAGE SURGE SUPPRESSOR (TVSS) OR

ACCORDANCE WITH UL 96A.

2. THE LIGHTNING PROTECTION SYSTEM (LPS) SHALL BE INSTALLED IN

1. CONTRACTOR SHALL DESIGN THE LIGHTNING PROTECTION SYSTEM.

LIGHTNING PROTECTION NOTES:

LIGHTNING PROTECTION SCOPE OF WORKS:

LIGHTNING PROTECTION SYSTEM USING SECONDARY CONDUCTOR.

16. ALL METAL EQUIPMENT ON THE ROOF SHALL BE BONDED TO THE

DETAIL 4, THIS SHEET.

GROUND ROD WILL BE AT LEAST 3/4" X 10’-0" LONG. SEE

15. COUNTERPOISE WILL EXTEND 10’ BEYOND BUILDING PERIMETER AND

USING AGENCY.

14. GROUNDING WILL CONFORM TO UL96A, EXCEPT AS REQUIRED BY THE

13. CONNECTOR BONDING BELOW GRADE SHALL BE EXOTHERMIC WELD TYPE.

12. ALL CONDUCTORS (PRIMARY AND SECONDARY) SHALL NOT BE PAINTED.

HAVE A RADIUS OF BEND LESS THAN 8-INCHES.

11. NO CONDUCTOR SHALL FORM AN ANGLE THAT EXCEEDS 90 DEGRESS, NOR

TERMINALS TO FORM A TWO WAY PATH TO GROUND.

10. ALL LIGHTNING PROTECTION CONDUCTORS SHALL INTERCONNECT ALL AIR

INTERVALS NOT TO EXCEED 3’-0" O.C.

9. ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED AT

CORROSION OF DISSIMILAR METALS.

COMPONENTS ARE MOUNTED TO ALUMINUM SURFACES TO AVOID GALVANIC

8. ALUMINUM COMPONENTS SHALL BE USED IN LOCATIONS WHERE SYSTEM

7. ALL METAL SHALL BE COPPER, BRONZE, OR STAINLESS STEEL.

WITH UL 96A AND NFPA 780 MATERIAL CODE REQUIREMENTS.

6. ALL LIGHTNING PROTECTION MATERIALS AND COMPONENTS SHALL COMPLY

5. PROVIDE AND INSTALL DOWNCONDUCTORS OUTSIDE OF THE STRUCTURE.

AND VERTICAL TUBE WITH NEOPRENE SEAL.

4. THRU ROOF FLASHING SHALL BE COPPER WITH 8-INCH ROUND BASE

WATERPROOFING AND CAULKING AROUND PENETRATED AREA.

3. PROVIDE ROOF PENETRATION IF NECESSARY AND APPLY ADEQUATE

UL 96A.

2. ALL LIGHTNING PROTECTION DEVICES WILL BE IN ACCORDANCE WITH

DETAILS 2, 3, 4, 5 AND 6 THIS SHEET.

THEM ON THE ROOF WITH CABLE SUPPORT AND CONNECTOR. SEE

PRIMARY (ROOF) CONDUCTOR TO THE AIR TERMINAL, AND SECURE

1. PROVIDE AND INSTALL AIR TERMINAL ON THE ROOF. CONNECT THE

E7

LIGHTNING PROTECTION PLAN SCALE: 1/8" = 1’-0"

E7

GROUNDING DETAIL NO SCALE

E7

NO SCALE

E7

NO SCALEAIR TERMINAL DETAILS

SUPPORT DETAILS

NO SCALEDETAIL

TEE-SPLICER CONNECTOR

E7

43105-E8

E8

V

F

LOC

ANN

TSFS

111111

F F F F F

100A 121 100C 111 100C 104

100A100B100B100C100C102103104104104

104 104 105 106 111 118 119 120 121

100A 100B 100B 100C 100C 102 103 104 104 104

105106111118119121

V V V V V V V V V

VVVVVV

SSSSSS

100A100A100B100B100C100C100C 107108104104 109110

S

D

S

118120

FACP/MNS

S

WP

MANUFACTURERS.

3. PROVIDE AUDIO POWER AMPLIFIERS AS SPECIFIED BY

2. EACH ZONE SHALL HAVE A MASTER VOLUME CONTROL.

BY MANUFACTURERS.

1. ALL WIRING AND COMPATIBILITY AS SPECIFIED

OUTPUT NOTES:

S S S S S S S

SSSSSSS

SS

104104104105106107108

100A100B100B100C100C102103

112 113 114 115 116 117 118

O/D O/D O/D O/D O/D O/D O/D

(OPTIONAL)

CD DECK

(OPTIONAL)

TUNER

(OPTIONAL)

TAPE DECK

UNIT

ANNOUNCEMENT

PROGRAMMED

SYSTEM

NOTIFICATION

MASS

SYSTEM

NOTIFICATION

MASS

ADAPTER

PAGING

MICROPHONE

S

S S

104104

S B

S B

CS S

B

SS

B

S B

109111

S S

119 120

S

S

WP

S

WP

S

WP

S

WP

S

WP

S

WP

S

WP

O/D

POWER

120V OR PBX FOR PAGING/ALERT.

SYSTEM PANEL AND FROM THE STAND ALONE TELEPHONE

TO RECEIVE PAGING INPUT FROM MASS NOTIFICATION

3. PROVIDE ALL ACCESSORIES AND CONNECTIONS

TO BALANCE ALL INPUTS.

2. INSTALL PREAMPLIFIERS AND GAIN CONTROLS

BY MANUFACTURERS.

1. ALL WIRING AND COMPATIBILITY AS SPECIFIED

INPUT NOTES:

AMPLIFIER

WITH

CONSOLE

PA

PUBLIC ADDRESS SYSTEM RISER DIAGRAM

NO SCALERISER DIAGRAM

FIRE ALARM AND MASS NOTIFICATION SYSTEMS

E8

E8

INSIDE CCTV

OUTSIDE CCTV

CEILING-MOUNT ADAPTER

STRUCTURE WITH COMPATIBLE

MOUNT CAMERA ON CEILING

ADAPTER

COMPATIBLE WALL-MOUNT

WALL STRUCTURE WITH

MOUNT CAMERA ON EXTERIAL

INSIDE CCTV

OUTSIDE CCTV

100A

100B

100C

FRONT

O/D

FRONT

O/D

RIGHT

O/D

RIGHT

O/D

REAR

O/D

REAR

O/D

ROUTE IN 3/4" CONDUIT

CONDUIT

IN 3/4"

ROUTE

POWER

120V

RECEIVERS

MONITOR

DISPLAY/

RECORDER W/

JOYSTICK

KEYBOARD AND

ROOM 119

NO SCALEE8

3 CCTV SYSTEM SCHEMATIC DIAGRAM

GENERAL NOTES:

FIRE ALARM AND MASS NOTIFICATION/PA SYSTEMS.

2. PROVIDE AND INSTALL ALL NECESSARY WIRING TO PROVIDE A COMPLETE

ARE TO BE CONNECTED.

PURPOSES ONLY. THEY DEPICT THE MANNER IN WHICH THE COMPONENTS

1. RISER DIAGRAMS SHOWN ON THIS DRAWING ARE FOR DIAGRAMMATIC1

SPECIAL KEYED NOTES:

RISER DIAGRAM, AND CCTV SCHEMATIC DIAGRAM

FIRE ALARM, MASS NOTIFICATION, & PA SYSTEMS

ROOM 119

ROOM 110

FIRE ALARM CONTROL PANEL AND 911 CENTER.

SEE FIRE ALARM AND MASS NOTIFICATION SYSTEMS, DRAWING SHEET 43105-E5 FOR COMMUNICATIONS BETWEEN

SHUT TRIP BREAKER TO SHUT OFF ELECTRIC STOVE/RANGE POWER.

ALARM STATUS MODE.

ALARM SIGNAL TO HVAC CONTROL PANEL TO CHANGE THE HVAC SYSTEM CONTROL FROM NORMAL MODE TO FIRE

PROVIDE #6 CU AWG INSULATED GROUND IN 3/4" CONDUIT AND CONNECT TO BUILDING GROUND ELECTRODE.

CO CO

100B100C

ABOUT THE PA SYSTEM REQUIREMENT BEFORE SUBMITTING YOUR BID.

* INDICATES THE MINIMUN COMPONENTS FOR THIS PUBLIC ADDRESS SYSTEM. COORDINATE WITH THE USER AND PROJECT MANAGER

CONNECT TO CIRCUIT EA-36

CCTV CAMERA

FOR FUTURE

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

LEFT

O/D

IN THE FUTURE.

THE DRAWING. USER WILL DETERMINE INSTALLING THE COMPLETE CCTV SYSTEM

INFRASTRUCTURE) WITH PULL STRINGS FOR THE CCTV SYSTEM INDICATED ON

5. CONTRACTOR SHALL PROVIDE J-BOX, J-BOX COVER AND CONDUIT ONLY (THE

FUNDS WILL BE PROVIDED FOR A COMPLETE AND USABLE CCTV SYSTEM.

4. THE USER (PROGRAM MANAGER) WILL DETERMINE IF DESIGN AND CONSTRUCTION

3. O/D MEANS EXTERIAL OR OUTSIDE.

(C) POWER SUPPLY

(B) TRANSMITTER

(A) CCTV CAMERA

2. EVERY CAMERA LOCATION IS (TYPICAL) EQUIPPED WITH THE FOLLOWINGS:

1. ALL WIRING AND COMPATIBILITY AS SPECIFIED BY MANUFACTURERS.

NOTES:

NO SCALE

THE EXACT LOCATION OF EACH DEVICE. THIS RISER DIAGRAM NEEDS TO BE UPDATED.

* THE RISER DIAGRAM IS FOR INFORMATION ONLY. THE RISER DIAGRAM DOES NOT SHOW

THE EXACT LOCATION OF EACH DEVICE. THIS RISER DIAGRAM NEEDS TO BE UPDATED.

* THE RISER DIAGRAM IS FOR INFORMATION ONLY. THE RISER DIAGRAM DOES NOT SHOW

43105-E9

E9

NO SCALEE9

GENERATOR

EMERGENCY

NEW

60 KW

(EA)

PANEL

NEW

(A)

PANEL

NEW

ATS

AUTOMATIC TRANSFER SWITCH

PROVIDE A BYPASS-ISOLATION

1 WEATHER-HEAD SERVICE

ALONG THE BEAM STRUCTURE

RUN AND SECURE THE 4-INCH CONDUIT

ALONG THE BEAM STRUCTURE

RUN AND SECURE THE 4-INCH CONDUIT

ROOM 1112

5 6

ROOF

EMERGENCY SERVICE SCHEMATIC LAYOUT

AERIAL POWER SERVICE ENTRANCE AND POWER

EMERGENCY SERVICE SCHEMATIC LAYOUT

AERIAL POWER SERVICE ENTRANCE & POWER

J-BOX

STRUCTURE

ON THE BEAM

MOUNT J-BOX

BEAM BEAM

PENETRATE THE ROOF BEHIND THIS

NEW WEATHER-HEAD CONDUIT SHALL

AND CONDUIT PENETRATION.

REMOVE EXISTING WEATHER-HEAD

WILL PROVIDE NEW AERIAL CABLES.

EXISTING AERIAL SECONDARY AND

FLINT ELECTRIC WILL DISCONNECT

J-BOX

BEHIND THIS BEAM

MOUNT J-BOX ON THE BEAM STRUCTURE

12345 SWITCH

DIS.

ELECTRICAL KEYED NOTES:

BACK OF BUILDING

METER

SWITCH

DISCONNECT

400 A

PANEL

400 A

ROOM 111

NO SCALEE9 CONNECTION

SIDE VIEW OF POWER SERVICE2

OUTSIDE

CAULKING AROUND PENETRATED AREA

APPLY ADEQUATE WATERPROOFING AND

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

(B)

PANEL

NEW

PROVIDE AND INSTALL A POWER METER AND A 400 AMPS DISCONNECT SWITCH.

CONNECT NEW AERIAL SECONDARY CABLE TO THE WEATHER-HEAD.

ELECTRICAL CONTRACTOR PROVIDES WEATHER-HEAD AND FLINT ELECTRIC WILL

42-CIRCUIT PANELS IN MECHANICAL ROOM 111.

PROVIDE AND INSTALL TWO (2) NEW 175 AMPS, 3-PHASE, 4-WIRE, 120/208 VOLTS,

MECHANICAL ROOM 111.

PROVIDE AND INSTALL A BYPASS-ISOLATION AUTOMATIC TRANSFER SWITCH IN

42-CIRCUIT PANEL IN MECHANICAL ROOM 111.

PROVIDE AND INSTALL A NEW 400 AMPS, 3-PHASE, 4-WIRE, 120/208 VOLTS,

REGISTER IN MECHANICAL ROOM 111.

PROVIDE AND INSTALL A WALL-MOUNTED KILOWATT HOUR METER WITH DEMAND

PANEL.

LP GAS LINE TO THE GENERATOR AND CONNECT GENERATOR TO EMERGENCY

A NEW LIQUID PROPANE GAS LINE TO 60 KW GENERATOR, INSTALL THE

NEW LIQUID PROPANE GAS EMERGENCY GENERATOR. CONTRACTOR SHALL RUN

PANEL (A) IN MECHANICAL ROOM 111. SEE DETAIL 2 THIS SHEET.

(ABOVE THE CEILING) TOWARD POWER METER, DISCONNECT SWITCH AND NEW

RUN AND SECURE THE NEW 4-INCH CONDUIT ALONG THE STRUCTURE BEAM

PROVIDE AND INSTALL A NEW WEATHERHEAD SERVICE PENETRATING THE ROOF.

ELECTRICAL DETAILS

43105-E10

E10

PANEL SCHEDULE

NO.

CIRC

AMPS

TRIP

POLES

NO.

LOAD SERVED

PHASE LOAD VA

A B C

LOAD SERVED

NO.

CIRC

AMPS

TRIP

POLES

NO.

SURFACE MOUNTED PHASE 3 WIRES 4

TOTAL

TOTAL CONNECTED LOAD

ESTIMATED DEMAND LOAD

VOLTS 120/208

PANEL AIC RATING: 22,000 AMPS

PANEL SCHEDULE

NO.

CIRC

AMPS

TRIP

POLES

NO.

LOAD SERVED

PHASE LOAD VA

A B C

LOAD SERVED

NO.

CIRC

AMPS

TRIP

POLES

NO.

SURFACE MOUNTED PHASE 3 WIRES 4

TOTAL

TOTAL CONNECTED LOAD

ESTIMATED DEMAND LOAD

20 2

20 2

20 1

20 1

20 1

20 3

20 3

20 1

20 1

20 1

20 1

20 1

20 1

20 1

20 1

25 1

20 1

VOLTS 120/208

PANEL AIC RATING: 14,000 AMPS

20 1

20 1

20 1

20 1

20 1

20 1

20 1

PANEL: A

BY: KMC BY: KMC

2020 3

20 3

UH-5 & UH-6

PANEL: EA

EMERGENCY LIGHT

VEHICLE BAY LIGHT1

14280 11940

100% 40.36 KVA

80% 32.29 KVA

MLO: 175 A

52054 50024

MCB: 400 A

20 3

20 1

20 1

20 1

20 1

1 20 1

20 1

20 1

VEHICLE BAY LIGHT VEHICLE BAY LIGHT

ALERT LIGHT + WP

UH-1 & UH-2 UH-3 & UH-4

2KW FOR EACH UH

2KW FOR EACH UH

2KW FOR EACH UH

PANEL SCHEDULE

NO.

CIRC

AMPS

TRIP

POLES

NO.

LOAD SERVED

PHASE LOAD VA

A B C

LOAD SERVED

NO.

CIRC

AMPS

TRIP

POLES

NO.

SURFACE MOUNTED PHASE 3 WIRES 4

TOTAL

TOTAL CONNECTED LOAD

ESTIMATED DEMAND LOAD

VOLTS 120/208

PANEL AIC RATING: 22,000 AMPS

BY: KMC

2020 3

20 3

UH-5 & UH-6

51484

20 3

UH-1 & UH-2 UH-3 & UH-4

2KW FOR EACH UH

2KW FOR EACH UH

2KW FOR EACH UH

LIGHT FIXTURE

LIGHT FIXTURE

LIGHT FIXTURE

LIGHT FIXTURE

LIGHT FIXTURE

RECEPTACLES (6)

VEHICLE BAY LIGHT

RECEPTACLES (7)

DOOR CONTROL CCT

RECEPTACLES (7)

RECEPTACLES (7)

RECEPTACLES (4)

RECEPTACLES (5)

EF-6 & EF-7

MOTOR DOOR

WATER COOLER

12.5 TON CONDENSER

20 3

60 3 AHU-1 (12.5 TONS) 100

AHU-1 MOTOR20

1/2 TON CONDENSER

AHU-2 (1/2 TONS)

14140

17080

15540

17740

100% 153.56 KVA

70% 107.49 KVA

FIRE ALARM

SPARE

D A

T E

S Y

M B

O L

R E

V

IS

IO

N S

B Y

DRAWN BY

APPROVED

DRAWING NUMBER SCALE

DATE

L&E NO:

NOTED

D. SAYLOR

K. CHAN

21 JAN 11

DIRECTORATEDIRECTORATE

OF PUBLIC WORKS

FORT BENNING, GEORGIA

FORT BENNING, GEORGIA

SAND HILL

CONSTRUCT FIRE STATION IN EXISTING CTA

PANEL SCHEDULE

NO.

CIRC

AMPS

TRIP

POLES

NO.

LOAD SERVED

PHASE LOAD VA

A B C

LOAD SERVED

NO.

CIRC

AMPS

TRIP

POLES

NO.

SURFACE MOUNTED PHASE 3 WIRES 4

TOTAL

TOTAL CONNECTED LOAD

ESTIMATED DEMAND LOAD

20 1

VOLTS 120/208

BY: KMC

18990 14760

MCB: 175 A

RECEPTACLE (2)

RECEPTACLE (2)

RECEPTACLE (2)

PANEL SCHEDULE

NO.

CIRC

AMPS

TRIP

POLES

NO.

LOAD SERVED

PHASE LOAD VA

A B C

LOAD SERVED

NO.

CIRC

AMPS

TRIP

POLES

NO.

SURFACE MOUNTED PHASE 3 WIRES 4

TOTAL

TOTAL CONNECTED LOAD

ESTIMATED DEMAND LOAD

20 2

20 2

20 2

20 1

VOLTS 120/208

PANEL AIC RATING: 14,000 AMPS

PANEL: B

BY: KMC

16880

RECEPTACLE (2)

RECEPTACLE (2)

RECEPTACLE (2)

20 1SPARE

2) ADJUST BREAKER AND CIRCUIT SIZES FOR EQUIPMENT ACTUALLY INSTALLED.

NAMEPLATE, IT MUST BE USED TO SIZE THE HVAC CIRCUIT.

DEVICE, AND DISCONNECTING MEANS. IF THE BRANCH-CIRCUIT SELECTION CURRENT (BCSC) IS SHOWN ON THE

INFORMATION PROVIDED ON THE NAMEPLATE TO DETERMINE THE RATING OF CONDUCTORS, OVERCURRENT PROTECTION

1) THIS PANEL SCHEDULE IS USED TO ESTIMATE THE SERVICE LOAD ONLY. HVAC CONTRACTOR SHALL USE THE

NOTES:

2) ADJUST BREAKER AND CIRCUIT SIZES FOR EQUIPMENT ACTUALLY INSTALLED.

NAMEPLATE, IT MUST BE USED TO SIZE THE HVAC CIRCUIT.

DEVICE, AND DISCONNECTING MEANS. IF THE BRANCH-CIRCUIT SELECTION CURRENT (BCSC) IS SHOWN ON THE

INFORMATION PROVIDED ON THE NAMEPLATE TO DETERMINE THE RATING OF CONDUCTORS, OVERCURRENT PROTECTION

1) THIS PANEL SCHEDULE IS USED TO ESTIMATE THE SERVICE LOAD ONLY. HVAC CONTRACTOR SHALL USE THE

NOTES:

2) ADJUST BREAKER AND CIRCUIT SIZES FOR EQUIPMENT ACTUALLY INSTALLED.

NAMEPLATE, IT MUST BE USED TO SIZE THE HVAC CIRCUIT.

DEVICE, AND DISCONNECTING MEANS. IF THE BRANCH-CIRCUIT SELECTION CURRENT (BCSC) IS SHOWN ON THE

INFORMATION PROVIDED ON THE NAMEPLATE TO DETERMINE THE RATING OF CONDUCTORS, OVERCURRENT PROTECTION

1) THIS PANEL SCHEDULE IS USED TO ESTIMATE THE SERVICE LOAD ONLY. HVAC CONTRACTOR SHALL USE THE

NOTES:

ELECTRIC WH

80-GALLON

CLOTHES DRYER 30 2

50 2RANGE

20 RECEPTACLE (2)2 RECEPTACLE (2)

175 PANEL B

20 1

20 1

20 1 SPARE

SPARE

SPARE

SPACE

SPACE

SPACE

SPARE 20 1

SPARE

SPARE 20 1

20 1

SPACE

SPACE

SPACE

20 1

20 1

20 1

20 1

20 1

20 1

20 1

20 1

20 1 SPARE

REFRIGATOR REC

REFRIGATOR REC

WASTE DISPOSER

20 1

20 1

20 1 SPARE

SPARE

SPARE

20 1 SPARE

20 1SPARE

20 1SPARE

20 1SPARE

SPARE

20 1

20 1

20 1SPARE

20 1

SPARE

SPARE

SPARE

SPACE

SPACE

SPACE

WASHER

20 1

20 1

EXTERIOR REC (6)

RECEPTACLES (2)

SPARE

RECEPTACLES (6)

RECEPTACLES (8)

RECEPTACLES (6)

SPARE

SPARE

SPACE

RECEPTACLES (5)

DISHWASHER

RECEPTACLES (4)

100% 50.63 KVA

80% 40.50 KVA

DEMAND LINE AMPS = 112.5 A

16880

18990

14760

PANEL EA (VIA ATS)

20 1

1RANGE HOOD’S FAN

DEMAND LINE AMPS = 298.58 A

GYM TV RECEPTACLE

HOLDER

FIRE-RATED DOOR

COMPRESSOR 5HP 35 3

DEMAND LINE AMPS = 89.70 A

NEC QUAD REC

NEC QUAD REC

ICE MACHINE 20 1

20 1

20 1

SPARE

SPARE

SPARE

5 NO SCALEFIXTURE E

LED STENCIL FACE EXIT SIGN

(USE RED LETTERS)

ON FACE OF SIGN

OTHER: MINIMUM BRIGHTNESS 20 CD/SQ METER

FINISH: BLACK

ELECTRICAL: 120 OR 277 VOLT

REQUIRED

STROKE. DIRECTIONAL ARROWS AS

152 mm (6") H LETTERS WITH 19 mm (3/4")

FINISH TO MATCH HOUSING FINISH.

COLD ROLLED STEEL, HARDWARE

HOUSING: DIE-CAST ALUMINUM OR 20 GA.

GENERAL DESCRIPTION

DIMENSIONS: (11 3/8" W X 7 7/8" H X 1 3/4" D)

NOM. 289 mm X 200 mm X 44 mm

WHITE AND BRONZE

OTHER: BRUSHED ALUMINUM,

LETTERS: RED

OPTIONS

LETTERS: GREEN

SHIELDING: FLAT SHEET ACRYLIC

MOUNTING: UNIVERSAL

LAMP TYPE: LED

FEATURES

TYPE: XL1

CORPS OF ENGINEERS DEPARTMENT OF THE ARMY

7 NO SCALEFIXTURE G

FIXTURES A AND AE1 NO SCALE

TYPE: EH6A

PROFILE: 1 LAMP

SHIELDING: TEMPERED PRISMATIC

BOROSILICATE GLASS

BALLAST: HIGH POWER FACTOR,

CORE & COIL, CWA

LAMP TYPE: MH: 150W

OTHER: KNUCKLE WALL MOUNT OR

SLIP FITTER. FIELD

INSTALLED PHOTO-CELL

CONTROL KIT, THREADED

TOP CONDUIT ENTRANCE.

NOM. DIMENSIONS 394 mm X 305 mm X 252 mm

HOUSING: DIE CAST ALUMINUM HOUSING, HINGED DOOR

REFLECTORS: FACETED ALUMINUM

ELECTRICAL: 120, 277, 208, 240, 347 & 480 VOLT MULTI TAP BALLAST

FINISH: PAINTED DARK BRONZE FINISH

(15 1/2" L X 12" D X 9 15/16" H)

LAMP TYPE: 100W INDUCTION

HPS: 150W

TYPE: SF8

LAMP TYPE: F32T8/75 CRI

SHIELDING: PRISMATIC LENS

BALLAST: ELECTRONIC

SHIELDING: OPAL WHITE, 3.2 mm

(0.125") PATTERN 12,

PATTERN 19, RFI

SUPPRESSION

BALLAST: HIGH POWER FACTOR

MAGNETIC, DIMMING,

EMERGENCY

HOUSING: COLD ROLLED STEEL WITH NO VISIBLE HOLES OR KNOCKOUTS;

EXTRUDED ALUMINUM HINGED LENS FRAME WITH SPRING-LOADED

CATCHES

MOUNTING: FIXTURE IS LONGER THAN METRIC GRID

REFLECTORS: GLOSS WHITE

ELECTRICAL: 120 OR 277 VOLT BALLAST

FINISH: BAKED WHITE ENAMEL OR POLYESTER POWDER COAT

EFFICIENCY: 80%

PROFILE: 3 LAMP

PROFILE: 3 LAMP

NOM. DIMENSIONS 600 mm X 1219 mm X 102 mm

(24" W X 4’ L X 4" D)

(3-LAMP)

FIXTURE D AND DE

FLUORESCENT TROFFER FIXTURE

BEAM-MOUNTED LENSED 2’X4’

12. LOW VOLTAGE, DEEP DISCHARGE DISCONNECT.

ON WALL.

MOUNTING BRACKETS OR HOLES IN HOUSING FOR MOUNTING UNIT

11. PROVIDE MINIMUM 0.032" THICK STEEL WALL MOUNTING SHELF, OR

10. 3/C #16, SO CORD SET - (HARD WIRE TO CIRCUIT)

9. VOLTMETER.

8. INPUT VOLTAGE AS INDICATED IN SCHEDULE.

INDICATED IN SCHEDULE.

7. SEALED BEAM HALOGEN LAMPS MINIMUM 8 WATT OR WATTAGE AS

6. HEADS SHALL BE FULLY ADJUSTABLE VERTICALLY AND HORIZONTALLY.

5. AUTOMATIC OVERLOAD PROTECTION - FUSE OR CIRCUIT BREAKER.

4. "AC ON" PILOT LIGHT.

3. TEST SWITCH.

ON EITHER HOUSING.

- LIC PLASTIC HOUSING WITH DECORATIVE WOOD GRAIN FRONT PANEL

2. MINIMUM 0.032" THICK BAKED ENAMEL PAINTED BEIGE, OR NONMETAL

CALCIUM OR LEAD ACID SEALED BATTERIES.

CADMIUM BATTERY AND TWO RATE HIGH/LOW CHARGER FOR LEAD

SOLID STATE FULLY AUTOMATIC - THREE RATE CHARGER FOR NICKEL

1. SEALED BATTERY, SPECIFICALLY DESIGN FOR EMERGENCY LIGHTING,

EMERGENCY LIGHTING UNIT

REFLECTORS: HIGH REFLECTANCE GLOSS WHITE

MOUNTING: RECESSED INTO STANDARD NON METRIC GRID

LOADED CATCHES

EXTRUDED ALUMINUM LENS FRAME, HINGED REMOVAL AND SPRING-

HOUSING: COLD ROLLED STEEL, FLANGE TO COORDINATE WITH CEILING;

(24" W X 4’ L X 6" D)

NOM. DIMENSIONS 610 mm X 1219 mm X 152 mm

AND/OR HEAT REMOVAL

OTHER: GASKETED; AIR HANDLING

EMERGENCY

MAGNETIC, DIMMING,

BALLAST: HIGH POWER FACTOR

19, RFI SUPPRESSION

PATTERN 12, PATTERN

SHIELDING: 3.2 mm (0.125")

PROFILE: 4 LAMP

SHIELDING: ACRYLIC PRISMATIC LENS

PROFILE: 4 LAMP

TYPE: RF9

NO SCALE

RECESSED 2’ X 4’ FLUORESCENT (4-LAMP)

FIXTURES B AND BE2 NO SCALE FIXTURES C

RECESSED 2’ X 4’ FLUORESCENT (3-LAMP)

REFLECTORS: HIGH REFLECTANCE GLOSS…