W911SA22B2006 Attachment 6 Exhaust Drawings.pdf

PDF 2 MB Posted

Attached to
Bldg 200 Repair by Replacement Boiler and Controls and Repair Air Compressor Exhaust
Solicitation number
W911SA22B2006
Issued by

About this file

This solicitation is for a repair and replacement project at Building 200 at Fort McCoy, Wisconsin. The work includes replacement of the boiler and controls system and repair of the air compressor exhaust. Sealed bids in accordance with FAR Part 14 will be accepted, with award going to the lowest responsive and responsible bidder. An organized site visit has been scheduled for March 9, 2022 at 10:00 AM CST at Building 1108 on Fort McCoy. The solicitation is issued by the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort McCoy. Bidders should read all information and directions within the solicitation fully.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G0.1

C O

V E

R

S

H E

E T

I N

D E

X

B U

I L D

I N

G

A

I R

C O

M P

R E

S S

O R

X H

A U

S T

S E

H

P H

F

P H

F

J R

L

F O

M c C

Y

S

O U

H

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

F

P

U B

L

W

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

S

D

E S

C R

I P

T I O

N M

D

A

T E

DPW

FORT MCCOY, WI

SHEET of

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

K A

J

Fort McCoy, Wisconsin

BUILDING 200 AIR

COMPRESSOR EXHAUST

GENERAL NOTES:

1. ALL LABOR, EQUIPMENT, MATERIALS, PRODUCTS FOR INSTALLATION, TESTING

AND VERIFICATION, AND WORK MUST COMPLY WITH SPECIFICATIONS AND

DRAWINGS.

2. THE CONTRACTOR IS RESPONSIBLE TO OBTAIN ALL PERMITS, LICENSES AND

CERTIFICATIONS NEEDED TO PERFORM THE WORK AT THE CONTRACTOR'S

EXPENSE.

3. ALL EQUIPMENT INSTALLATIONS MUST BE IN ACCORDANCE WITH THE

MANUFACTURER'S PUBLISHED DATA AND RECOMMENDATIONS.

4. CONTRACTOR MUST PERFORM ALL WORK IN ACCORDANCE WITH THE MOST

RECENT EDITION OF EM 385-1-1 SAFETY AND HEALTH REQUIREMENTS MANUAL

(2014 EDITION)

5. CONTRACTOR SHALL OBTAIN SPECIFIC UTILITY REQUIREMENTS FOR EACH

UTILITY. EACH UTILITY MAY REQUIRE ADDITIONAL ADVANCE NOTIFICATION.

6. CONTRACTOR IS RESPONSIBLE TO OBTAIN UTILITY LOCATES PRIOR TO THE

START OF EXCAVATION OPERATIONS AND MAINTAIN UTILITY MARKINGS DURING

CONSTRUCTION.

7. CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING UTILITIES.

CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING SITE CONDITIONS.

GOVERNMENT INFORMATION, DATA AND DRAWINGS ARE FOR REFERENCE ONLY,

NOT FOR CONSTRUCTION, AND DO NOT CONTAIN ALL EXISTING UTILITIES AND

SITE CONDITIONS. CONTRACTOR MUST NOT REPLY UPON GOVERNMENT

INFORMATION, DATA AND DRAWINGS AS SUBSTITUTE FOR CONTRACTOR

VERIFICATION.

8. SCALES SHOWN APPLY ONLY WHEN DRAWINGS ARE PRINTED ON 22" X 34"

PAPER. SCALES ARE HALF SIZED WHEN PRINTED ON 11" X 17" PAPER.

9. ALL MATERIALS, LABOR, EQUIPMENT AND WORK MUST BE IN ACCORDANCE WITH

SPECIFICATIONS, STANDARDIZED CONSTRUCTION METHODS AND PRACTICES,

MANUFACTURER'S PUBLISHED DATA AND RECOMMENDATIONS, AND ALL

FEDERAL, STATE, AND LOCAL LAWS, REGULATIONS, STATUES, AND CODES.

10. THE CONTRACTOR MUST PROVIDE WRITTEN NOTIFICATION TO COR WITHIN

THREE DAYS OF DISCOVERING DISCREPANCIES BETWEEN EXISTING SITE

CONDITIONS, DRAWINGS, SPECIFICATIONS, AND CONTRACT DOCUMENTS. THE

CONTRACTOR MUST PROVIDE A WRITTEN REQUEST FOR CLARIFICATION TO

ADDRESS EACH DISCREPANCY.

11. THE GOVERNMENT IS NOT RESPONSIBLE FOR THE CONTRACTOR'S CONSTRUCTION

PRACTICES, MEANS AND METHODS. THE CONTRACTOR MUST PROVIDE A WRITTEN

REQUEST TO COR A MINIMUM OF SEVEN CALENDAR DAYS PRIOR TO THE START OF

CONSTRUCTION FOR APPROVAL OF ANY DEVIATIONS FROM STANDARDIZED

CONSTRUCTION PRACTICES, MEANS AND METHODS WHETHER STATED OR IMPLIED ON

DRAWINGS AND IN SPECIFICATIONS.

12. MECHANICAL AND ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. CROSS-REFERENCE

ARCHITECTURAL DRAWINGS WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL

DRAWINGS TO ASSURE COORDINATION OF LOCATIONS, SIZES, AND MATERIALS.

13. VERIFY LOCATION, SIZE AND WALL THICKNESS REQUIRED TO RECESS MECHANICAL AND

ELECTRICAL ITEMS AND MAINTAIN FIRE RATING REQUIREMENTS OF THE WALL AT THESE

BUILT-INS: UNIT HEATERS, CONVECTORS, ELECTRICAL PANELS, FIRE EXTINGUISHER

CABINETS, DUCTS, PIPING, AND ALL OTHER RECESSES.

14. WOOD USED AT ROOF AREAS AND ROOF EDGES SHALL BE WEATHER-TREATED - UNO.

15. MAINTAIN BUILDING FIRE EXITS DURING CONSTRUCTION.

16. EQUIPMENT, MATERIALS AND MANUFACTURERS LISTED IN THESE DRAWINGS MAY BE

SUBSTITUTED FOR EQUAL PRODUCTS IN COMPLIANCE WITH SPECIFICATIONS AND

FEDERAL PURCHASING REQUIREMENTS.

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SHEET INDEX TABLE

AutoCAD SHX Text Sheet #

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text G0.1

AutoCAD SHX Text

COVER SHEET / INDEX

AutoCAD SHX Text A1.1

AutoCAD SHX Text

EXTERIOR ELEVATIONS

AutoCAD SHX Text M0.1

AutoCAD SHX Text

NOTES, LEGENDS AND ABBREVIATIONS

AutoCAD SHX Text M1.2

AutoCAD SHX Text

MECHANICAL FLOOR PLAN

AutoCAD SHX Text M6.0

AutoCAD SHX Text

MECHANICAL SCHEDULES AND DETAILS

AutoCAD SHX Text E0.1

AutoCAD SHX Text E1.1

AutoCAD SHX Text

ELECTRICAL PLAN

AutoCAD SHX Text

NOTES, LEGENDS AND ABBREVIATIONS

AutoCAD SHX Text S1.0

AutoCAD SHX Text

MEZZANINE ROOF FRAMING PLAN

A1.1

X

T E

R I O

R

E

L E

V A

T I O

N S

S E

H

P H

F

P H

F

J R

L

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

SHEET of

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

K A

J

Scale: 1/8" = 1'-0"

EXTERIOR ELEVATION

B U

I L

D I N

G

A

R

C O

M P

R E

S S

H

A U

S T

AutoCAD SHX Text

AutoCAD SHX Text 11.1

AutoCAD SHX Text 12.8

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text KEYNOTES 1. NEW EXHAUST LOUVER. SEE MECHANICAL PLANS FOR SIZE, NEW EXHAUST LOUVER. SEE MECHANICAL PLANS FOR SIZE, LOCATION AND DETAILS. PROVIDE FRAMING FOR NEW OPENING IN WALL. FLASH AND SEAL FOR WATERTIGHT INSTALLATION.

AutoCAD SHX Text x

AutoCAD SHX Text

SHEET NOTE:

1. PROVIDE LOUVER AS INDICATED AND IN COMPLIANCE PROVIDE LOUVER AS INDICATED AND IN COMPLIANCE WITH SPECIFICATIONS.

Scale: 1/4":1'-0"

MEZZANINE ROOF FRAMING PLAN

S1.0

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

SHEET of

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

M E

Z Z

A N

I N

E

R

O O

F

F

R A

M I N

G

P

L A

N

3 8

S E

H

B W

O L

F

P H

F

N S

I E

M S

K A

J

B U

I L D

I N

G

A

M

P R

E S

S O

R

E

X H

A U

S T

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

FRAMING PLAN NOTES:

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

1. NOTIFY C.O.R. PRIOR TO PROCEEDING WITH NOTIFY C.O.R. PRIOR TO PROCEEDING WITH STRUCTURAL FABRICATION AND FRAMING INSTALLATION IF DESIGN LOADS EXCEED THESE WEIGHTS TYPICAL HOOD AND ACCESSORIES: 750 LBS TYPICAL FAN: 300 LBS 2. PROVIDE FRAMING AS INDICATED AND IN COMPLIANCE PROVIDE FRAMING AS INDICATED AND IN COMPLIANCE WITH SPECIFICATIONS.

AutoCAD SHX Text

FRAMING PLAN KEYNOTES:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text L4x4x ANGLE SUSPENDED FROM BOTTOM FLANGE OF 38 ANGLE SUSPENDED FROM BOTTOM FLANGE OF EXISTING STEEL BEAM TO SUPPORT HOODS, FANS, AND DUCTWORK. SUPPORT HOODS AND FANS VIA FOUR POINT SUPPORT PER MANUFACTURER. TWO WELDS TO BOTTOM FLANGE OF EACH BEAM - MINIMUM " FILLET 14" FILLET WELD x 4" LONG 12"Ø THREADED HANGER ROD TO HANGER BRACKET ON DUCTWORK BY DUCTWORK SUPPLIER. COORDINATE LOCATIONS WITH DUCTWORK DESIGN AND JOINT LAYOUT. 800S200-054 LIGHT GAUGE CHANNEL EACH SIDE OF NEW WALL OPENING. SECURE TO EXISTING WALL GIRTS WITH 3"x3" - 16ga. ANGLE x 5" LONG, (3) NO. 12 SCREWS TO EACH MEMBER. SECURE METAL PANEL SIDING, TRIM, AND LOUVER FRAMING TO NEW CHANNELS.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

AutoCAD SHX Text

W12 BEAM (E)

W12 BEAM (E)

M0.1

I B

C

T K

T K

M V

K A

J

B U

I L D

I N

G

A

I R

C O

M P

R E

S S

H

A U

S T

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

AP ACCESS PANEL

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

CA COMBUSTION AIR

COND CONDENSATE DRAIN

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CR LOW PRESSURE STEAM CONDENSATE RETURN

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

DE DISHWASHER EXHAUST

DN DOWN

EA EXHAUST AIR

EF EXHAUST FAN

GSHXR GROUND SOURCE HEAT EXCHANGER

RETURN

GSHXS GROUND SOURCE HEAT EXCHANGER

SUPPLY

HPS HIGH PRESSURE STEAM

HWR HOT WATER RETURN

HW HOT WATER SUPPLY

KE KITCHEN EXHAUST

L LOUVER

LPS LOW PRESSURE STEAM

MPS MEDIUM PRESSURE STEAM

NC NORMALLY CLOSED

NG NATURAL GAS

NO NORMALLY OPEN

OA OUTSIDE AIR

RA RETURN AIR

RCOVR ENERGY RECOVERY RETURN

RCOVS ENERGY RECOVERY SUPPLY

RELF RELIEF AIR

RL REFRIGERATION LIQUID

RS REFRIGERATION SUCTION

SA SUPPLY AIR

SOLR SOLAR THERMAL RETURN

SOLR SOLAR THERMAL SUPPLY

TA TRANSFER AIR

VFD VARIABLE FREQUENCY DRIVE

X EXISTING

CONTROLS LEGEND

I/O POINT

PRESSURE DIFFERENTIAL SENSOR

CO2 MONITOR

FLOW SWITCH

TEMPERATURE SENSOR, POINT SETTING

THERMOSTAT

VARIABLE FREQUENCY DRIVE CONTROL

BOX

AIRFLOW DISCHARGE

AIRFLOW INTAKE

AIRFLOW METER

CONTROL BOX

DUCT MOUNTED TEMPERATURE SENSOR

DUCT MOUNTED HUMIDITY SENSOR

C

PUMP

MOTOR OPERATED DAMPER

FAN

FILTER

COIL

CONTROL VALVE, FLOW

CONTROL VALVE, 3-WAY

T

H

T

CO2

FS

T

VFD

F

BALL VALVE

BUTTERFLY VALVE

GATE VALVE

CHECK VALVE

CIRCUIT SETTER

HOSEBIBB/DRAIN VALVE

2-WAY ELECTRONIC CONTROL VALVE

3-WAY ELECTRONIC CONTROL VALVE

NEW SUPPLY PIPING (ALL SYSTEM TYPES)

DEMOLISHED PIPING (ALL SYSTEM TYPES)

NEW RETURN PIPING PIPING (ALL SYSTEM

TYPES)

EXISTING SUPPLY PIPING (ALL SYSTEM

TYPES)

EXISTING RETURN PIPING PIPING (ALL

SYSTEM TYPES)

PIPING LEGEND

PLUG VALVE

PRESSURE REGULATING VALVE

OS&Y VALVE

TRIPLE DUTY VALVE

PRESSURE & TEMPERATURE RELIEF

VALVE

STRAINER

AIR VENT

PUMP

TEMPERATURE GAUGE

P-T PLUG

PIPE BREAK

PRESSURE GAUGE

FLOW GAUGE

TEMPERATURE SENSOR

PRESSURE SENSOR

FLOW SENSOR

UNION

REDUCER

FLEX PIPE

PIPE CAPPED END

PIPE ELBOW/TEE UP

PIPE ELBOW/TEE DOWN

FS

PS

TS

GENERAL NOTES

1. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL

REQUIRED OFFSETS FOR A COMPLETE INSTALLATION.

CONTRACTOR MUST PROVIDE EQUIPMENT, MATERIALS,

SUPPORT AND APPURTENANCES TO CONFORM TO

STRUCTURE AND MAINTAIN APPROPRIATE CLEARANCES.

2. ALL WORK MUST COMPLY WITH FEDERAL, STATE, AND

LOCAL LAWS, REGULATIONS, STATUES, CODES, AND

REQUIREMENTS OF LOCAL AUTHORITIES HAVING

JURISDICTION.

3. CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER

TRADES PRIOR TO INSTALLATION AND DURING

CONSTRUCTION AS NEEDED TO FACILITATE THE WORK AND

AS REQUIRED FOR TESTING AND VERIFICATION.

4. THE CONTRACTOR SHALL VISIT THE SITE TO DETERMINE

THE FULL EXTENT OF WORK AND PROJECT CONDITIONS.

FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR OF

THE OBLIGATIONS OF THE CONTRACT.

5. COORDINATE EXACT LOCATION OF CEILING DIFFUSERS AND

GRILLES WITH REFLECTED CEILING PLAN.

6. ALL BRANCH DUCTS SHALL MATCH DIFFUSER NECK SIZES

UNLESS OTHERWISE NOTED.

7. ALL CONTROL WIRING SHALL BE RUN IN CONDUIT.

8. KEYNOTES PERTAIN ONLY TO THE DRAWING THEY ARE

LOCATED ON.

9. DUCT SIZES ARE CLEAR INSIDE DIMENSIONS.

10. ALL HOT WATER BRANCH LINES ARE 3/4" UNLESS NOTED

OTHERWISE.

11. MAINTAIN 10' MINIMUM DISTANCE FROM OUTSIDE AIR INTAKE

TO ANY EXHAUST OR PLUMBING VENTS.

12. FLEXIBLE DUCTWORK SHALL NOT EXCEED 5'-0" IN LENGTH.

13. ALL SUPPLY AND RETURN DUCTWORK IN UNINSULATED

ATTIC SPACE SHALL BE WRAPPED WITH 3" INSULATION.

14. CLEAN ALL EXISTING DUCTWORK, COILS AND DIFFUSERS

DESIGNATED TO REMAIN WITHIN THE PROJECT'S SCOPE OF

WORK.

NEW SUPPLY DIFFUSER

NEW RETURN/TRANSFER GRILLE

WALL SWITCH

AIR FLOW INDICATOR

STATIC PRESSURE CONTROLLER

DOOR UNDER CUT

FIRE DAMPER

COMBINATION FIRE/SMOKE DAMPER

BALANCING DAMPER

NEW EXHAUST GRILLE

SMOKE DAMPER

TRANSFER/DOOR GRILLE

CO2 SENSOR

CONTROL WIRE

BACK DRAFT DAMPER

S-*

R-*/T-*

E-*

DAMPER WITH SEQUENCING NUMBER

POINT OF CONNECTION

HVAC EQUIPMENT TAG

ELECTRICALLY POWERED

HVAC EQUIPMENT TAG

NOT ELECTRICALLY POWERED

DUCT OFFSET

TEMPERATURE /CO2 SENSOR

PRESSURE DIFFERENTIAL SENSOR

TEMPERATURE SENSOR

THERMOSTAT

THERMOSTAT /CO2 SENSOR

EQUIPMENT

EQUIPMENT

FLOOR

FLOOR

TAG

TAG

NEW HVAC EQUIPMENT

NEW DUCTWORK

EXISTING MECHANICAL COMPONENT

ELBOW WITH TURNING VANES

SUPPLY AIR DUCT UP

SUPPLY AIR DUCT DOWN

FLEX DUCT

MOTORIZED DAMPER

DEMOLISHED MECHANICAL COMPONENT

RETURN AIR DUCT UP

RETURN AIR DUCT DOWN

OUTSIDE AIR DUCT UP

OUTSIDE AIR DUCT DOWN

EXHAUST AIR DUCT UP

EXHAUST AIR DUCT DOWN

MECHANICAL EQUIPMENT SERVICE AREA

HVAC LEGEND

KEY NOTEM##

M

BD

FD

SD

FSD

XX-1

UC

C

PD

SP

T

T

TC

TC

DN

S

RTU

X-X

VAV

X-X

CFM

XX"xXX"A1

TYP. #TAG

NECK

SIZE

DIFFUSER/GRILLE TAG

MECHANICAL SHEET INDEX

NUMBER SHEET NAME

M0.1 NOTES, LEGENDS AND ABBREVIATIONS

M1.2 MECHANICAL FLOOR PLAN

M6.0 MECHANICAL SCHEDULES AND DETAILS

84SHEET of

AutoCAD SHX Text

NOTES, LEGENDS AND ABBREVIATIONS

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

EF

EF

M1

L

M2

M2

M3

M1.2

I B

C

T K

T K

M V

K A

J

B U

I L

D I N

G

R

C O

M P

R E

S S

H

A U

S T

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

85SHEET of

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

%%UX-HV-3

AutoCAD SHX Text

X-HW

AutoCAD SHX Text

X-HWR

AutoCAD SHX Text

X-AIR SEPARATOR (TYP.)

AutoCAD SHX Text X-6"

AutoCAD SHX Text X-6"

AutoCAD SHX Text

X-VAV-14

AutoCAD SHX Text

X-VAV-9

AutoCAD SHX Text X-6"

AutoCAD SHX Text X-6"

AutoCAD SHX Text X-6"

AutoCAD SHX Text X-1"

AutoCAD SHX Text

X-HWR

AutoCAD SHX Text

X-HW

AutoCAD SHX Text

X-HW

AutoCAD SHX Text

X-HWR

AutoCAD SHX Text X-1"

AutoCAD SHX Text

HORIZONTAL UNIT HEATER X-HUH-4X-HUH-4

AutoCAD SHX Text M-201

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text M-202

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text M-203

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text M-204

AutoCAD SHX Text

BLDG. M & E

AutoCAD SHX Text

EQUIP. ROOM

AutoCAD SHX Text M-205

AutoCAD SHX Text X-6"

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

X-VAV-8

AutoCAD SHX Text

X-HWR

AutoCAD SHX Text

X-HW

AutoCAD SHX Text

OA

AutoCAD SHX Text

%%UX-AC-2

AutoCAD SHX Text

X-AC-1

AutoCAD SHX Text T

AutoCAD SHX Text

84"X44" EXHAUST LOUVER BOTTOM OF LOUVER EL: 14' - 0" A.F.F

AutoCAD SHX Text

48"X84" OVERHEAD CANOPY HOOD ABOVE EXISTING AIR COMPRESSOR. (TYP OF 2.)

AutoCAD SHX Text

INLINE FAN TO BE INSTALLED VERTICALLY.

AutoCAD SHX Text

22X22 EA

AutoCAD SHX Text

22X22 EA

AutoCAD SHX Text

22X22 EA

AutoCAD SHX Text

EXISTING 96"X 44" OUTSIDE-AIR LOUVER WITH MOTORIZED DAMPER. INTERLOCK W/HV-3

AutoCAD SHX Text X-34"X34"

AutoCAD SHX Text

%%UX-RF-1

AutoCAD SHX Text X-P-6

AutoCAD SHX Text X-P-7

AutoCAD SHX Text

22/22 EA DOWN TO OVERHEAD CANOPY HOOD

AutoCAD SHX Text

X-44" X 44" INTAKE LOUVER W/MOTORIZED DAMPER. INTERLOCKED WITH X-EF-4.X-EF-4..

AutoCAD SHX Text X-34"X34"

AutoCAD SHX Text

X-RG-4 3500 CFM

AutoCAD SHX Text

X-72"X36" RELIEF LOUVER WITH MOTORIZED DAMPER. INTERLOCK W/HV-3

AutoCAD SHX Text

X-RG-4 3500 CFM

AutoCAD SHX Text

EF-1,2

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

MECHANICAL FLOOR PLAN

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale: 1/4":1'-0"

AutoCAD SHX Text

MECHANICAL FLOOR PLAN

AutoCAD SHX Text

AutoCAD SHX Text

KEY NOTES

AutoCAD SHX Text M1

AutoCAD SHX Text

RELOCATE CONDUITS AS NEEDED.

AutoCAD SHX Text M2

AutoCAD SHX Text SEE SHEET S1.0 FOR FAN AND HOOD SUPPORT REQUIREMENTS. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION AND WARRANTY REQUIREMENTS.

AutoCAD SHX Text M3

AutoCAD SHX Text SEE SHEET S1.0, A1.1, AND DETAIL 2 ON SHEET M6.0 FOR LOUVER AND SUPPORT REQUIREMENTS.

AutoCAD SHX Text M4

AutoCAD SHX Text

SEE DETAIL 1 ON SHEET M6.0 FOR DUCT FITTING DETAILS.

CONTROL SEQUENCE NOTES: 1. EXHAUST FANS, EF-1 & EF-2, EXHAUST FANS, EF-1 & EF-2, AND MOTORIZED DAMPERS AT L-1 TO BE CONTROLLED VIA WALL MOUNTED THERMOSTAT TO MAINTAIN SPACE TEMPERATURE BELOW 80° F (ADJ). 2. WHEN ANTI-TERRORISM ALARM IS WHEN ANTI-TERRORISM ALARM IS ENGAGED, FANS SHALL BE DE-ENERGIZED AND ALL OUTSIDE AIR, RELIEF AND EXHAUST DAMPERS SHALL CLOSE.

M6.0

I B

C

T K

T K

M V

K A

J

B U

I L

D I N

G

R

C O

M P

R E

S S

H

A U

S T

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

86SHEET of

RECTANGULAR DUCT FITTINGS

N.T.S.

W R

R ≥ 0.5 WLESS THAN

1000 NO TURNING VANES

AIR VELOCITY

(FPM)

R ≥ W 1,000

TO

1,500

R ≥ 0.5 W

WITH TWO VANES

SINGLE-THICKNESS

TURNING VANES AT

3-1/4 INCH SPACING

R ≥ 1.5 W1,500 & UP R ≥ W

WITH TWO VANES

SINGLE-THICKNESS

TURNING VANES AT

1-1/2 INCH SPACING

NOTES:

1. PROVIDE FITTINGS AS INDICATED ON PLANS UNLESS NOTED OTHERWISE. IF FITTINGS ARE NOT SHOWN ON PLANS, OR

FIELD CONDITIONS PRECLUDE INSTALLATION OF FITTINGS SHOWN ON PLANS, THEN PROVIDE FITTINGS TO COMPLY WITH

REQUIREMENTS SHOWN ABOVE AND OBTAIN DESIGN ENGINEER'S APPROVAL.

2. FOR TURNING VANES LONGER THAN 36 INCHES, DOUBLE-WALL VANES AT 2-1/8 INCH SPACING MAY BE USED.

3. DO NOT INSTALL TURNING VANES ON MITERED ELBOWS (TYPE RE2/RE4) FOR RETURN-AIR OR EXHAUST-AIR SYSTEMS.

4. CONICAL TAPS MAY BE USED FOR ALL ROUND BRANCH CONNECTIONS FOR RETURN-AIR AND EXHAUST-AIR SYSTEMS.

SMACNA ELBOW

RE1 RE2 / RE4 RE3

W W R

BRANCH CONNECTION

STRAIGHT TAP

45 DEG ENTRY HIGH-EFFICIENCY

TAKE-OFF

RECTANGULAR

BRANCH FROM

RECTANGULAR

MAIN

ROUND

BRANCH FROM

RECTANGULAR

MAIN

CONICAL TAP

2 LOUVER WITH AUTOMATIC CONTROL DAMPER

N.T.S.

DRAINABLE HORIZONTAL

BLADES

DUCT PLENUM

BIRDSCREEN

WATER STOP WITH WEEP

HOLES

SEAL JOINTS

EXTENDED SILL

WATERTIGHT PAN

MOTORIZED

BACKDRAFT

DAMPER

ANGLE (TYP)

CLOSURE ANGLE

(TYP)

AutoCAD SHX Text

MECHANICAL SCHEDULES AND DETAILS

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

E0.1

I B

C

D H

D H

C M

M

K A

J

B U

I L

D I N

G

R

C O

M P

R E

S S

H

A U

S T

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

SHEET of

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

DUPLEX RECEPTACLE 6" ABOVE

COUNTER OR BACKSPLASH OR AT

HEIGHT INDICATED

DOUBLE DUPLEX RECEPTACLE

TOP SWITCHED DUPLEX RECEPTACLE

SPECIAL PURPOSE OUTLET

DUPLEX FLOOR OUTLET

DOUBLE DUPLEX FLOOR OUTLET

TOP SWITCHED DUPLEX FLOOR OUTLET

CEILING MOUNTED DUPLEX RECEPTACLE

CEILING MOUNTED DOUBLE DUPLEX

RECEPTACLE

POKE THRU

POWER POLE

CIRCUIT BREAKER

FUSE

GROUND

TRANSOCKET

RECESSED PANEL

METER

CURRENT TRANSFORMER

MANUAL DISCONNECT

NON-FUSED DISCONNECT

FUSED DISCONNECT

MAGNETIC STARTER

COMBINATION STARTER

MOTOR

PUSH BUTTON

SINGLE RECEPTACLE

POWER LEGEND

SURFACE MOUNT PANEL

DUPLEX RECEPTACLE

POWER ASSIST OPERATOR PUSH PLATE

JUNCTION BOXJ

M

PP

M

GENERAL LEGEND

KEY NOTE

TYPICAL CIRCUIT

UNSWITCHED CIRCUIT

NEW ELECTRICAL COMPONENT

EXISTING ELECTRICAL COMPONENT

DEMOLISHED ELECTRICAL COMPONENT

E##

ELECTRICAL SHEET INDEX

NUMBER SHEET NAME

E0.1 NOTES, LEGEND AND ABBREVIATIONS

E1.1 ELECTRICAL PLAN

ABBREVIATIONS

1P SINGLE POLE

1PH SINGLE PHASE

2/* 120/240V OR 120/208V PANEL

2P TWO POLE

2W TWO WIRE

3P THREE POLE

3PH THREE PHASE

3W THREE WIRE

4/* 277/480V PANEL

4W FOUR WIRE

A AMPERE

AC ALTERNATING CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AGL ABOVE GROUND LEVEL

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMP AMPERE

AOR AREA OF REFUGE

AORM AREA OF REFUGE MASTER STATION

AORR AREA OF REFUGE REMOTE STATION

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BLDG BUILDING

BOT BOTTOM

BRKR BREAKER

C CONDUIT

CAB CABINET

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA OR CONSTRUCTION DOCUMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CL MOUNTED ON CEILING

CLG CEILING

COAX COAXIAL CABLE

CONT CONTINUE

CP CONTROL PANEL

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

D DEDICATED

DB DECIBEL OR DIRECT BURIAL

DCP DIMMER CONTROL PANEL

DD DOUBLE DUPLEX

DEMO DEMOLITION

DISC DISCONNECT

DIST DISTRIBUTION

DM DIMMING

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DS DAYLIGHT SENSOR

DWG DRAWING

EBU EMERGENCY BATTERY UNIT

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

ER ELEVATOR RECALL

ERL EXISTING TO BE RELOCATED

ES ELECTRIC STRIKE

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EVR ELEVATOR RECALL

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOT-CANDLE

FLA FULL LOAD AMPERE

FLT FLOODLIGHT

FP FIRE PROTECTION

FSS FUSED SAFETY SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G GENERATOR

G/GND GROUND

GC GENERAL CONTRACTOR

GFI / GFCI GROUND FAULT CIRCUIT INTERRUPTER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTO

HP HORSE POWER

HZ HERTZ

IR IN ROOM

IG INSULATED GROUND

IU IN UNIT

K KEY OPERATED

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

KWH KILOWATT HOUR

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FOOT (FEET)

LM LUMEN

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPERAGE

LS LIFE SAFETY

LTG LIGHTING

LV LOW VOLTAGE

MAG MAGNETIC STARTER

MAN MANUAL STARTER

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MFAAP MASTER FIRE ALARM ANNUNCIATOR PANEL

MFG MANUFACTURER

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUG ONLY

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

N NEUTRAL

NA NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CIRCUIT

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NFPA NATIONAL FIRE PROTECTION AGENCY

NFSS NON-FUSED SAFETY SWITCH

NIC NOT INCLUDED IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

NU NEAR UNIT

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

OS OPTIONAL STANDBY

OU ON UNIT

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PL PILOT LIGHT

PNL PANEL

PP POWER PANEL

PVC POLYVINYL CHLORIDE (PLASTIC)

PW PRE-WIRED

PWR POWER

RC REMOTE CONTROL

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RFAAP REMOTE FIRE ALARM ANNUNCIATOR PANEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR OR SMOKE DAMPER

SF SQUARE FOOT (FEET)

SPD SURGE PROTECTION DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SS SWITCH STATION

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

T TAMPERPROOF OR THERMOSTAT

TC TIMECLOCK

TO TIME OPERATED

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

TYP TYPICAL

UL UNDERWRITERS LABORATORY

UNV UNIVERSAL

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERE

VAC VOLT AMPERE CURRENT

VFD VARIABLE FREQUENCY DRIVE

W WATT OR WIRE

WAP WIRELESS ACCESS POINT

WF WATER-TIGHT FIXTURE

WH WATER HEATER

WP WEATHERPROOF

X- EXISTING

XC EXTRA CAPACITY

XFER TRANSFER

XFMR TRANSFORMER

Z ZONE

GENERAL NOTES

1. ALL LABOR, EQUIPMENT, MATERIALS, PRODUCTS FOR

INSTALLATION, TESTING AND VERIFICATION, AND WORK

MUST COMPLY WITH SPECIFICATIONS AND DRAWINGS.

2. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL

EXISTING SITE CONDITIONS AND REQUIRE COMPONENTS

FOR INSTALLATION. CONTRACTOR MUST PROVIDE

EQUIPMENT, MATERIALS, DEVICES, POWER, CONTROLS,

FIXTURES, SUPPORT, APPURTENANCES AND WORK

NECESSARY TO CONFORM TO STRUCTURE AND

CONNECTIONS FOR COMPLETE, USEABLE INSTALLATIONS

AND SYSTEMS, AND MAINTAIN APPROPRIATE CLEARANCES.

3. ALL WORK MUST COMPLY WITH FEDERAL, STATE AND LOCAL

LAWS, REGULATIONS, STATUTES AND CODE AND

REQUIREMENTS OF LOCAL AUTHORITIES HAVING

JURISDICTION. ALL PRODUCTS FOR INSTALLATION AND

WORK MUST COMPLY WITH SPECIFICATIONS.

4. CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER

TRADES PRIOR TO INSTALLATION AND DURING

CONSTRUCTION TO FACILITATE THE WORK, AND AS

REQUIRED FOR TESTING AND VERIFICATION.

5. THE CONTRACTOR SHALL VISIT THE SITE TO DETERMINE

THE FULL EXTENT OF WORK AND PROJECT CONDITIONS.

FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR OF

THE OBLIGATIONS OF THE CONTRACT.

6. THE CONTRACTOR SHALL CHECK ALL DRAWINGS AND

SPECIFICATIONS OF OTHER TRADES AND INCLUDE IN THEIR

BID ANY ADDITIONAL WORK REQUIRED BY THIS TRADE.

7. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT

LOCATIONS AND MOUNTING HEIGHTS OF ALL LIGHT

SWITCHES, POWER, AND COMMUNICATIONS OUTLETS. ALL

OUTLETS SHALL BE MOUNTED VERTICALLY UNLESS

OTHERWISE NOTED. COORDINATE ALL FINAL DEVICE

REQUIREMENTS WITH ARCHITECT PRIOR TO INSTALLATION.

8. ALL CONDUITS MUST BE SUPPORTED IN COMPLIANCE WITH

NFPA 70 AND INSTALLED IN A WORKMANLIKE MANNER TO

MINIMIZE INTERFERENCE WITH OTHER TRADES. ALL

CONDUITS ABOVE CEILING SHALL BE RIGIDLY SUPPORTED

BY SUITABLE HANGERS FROM THE STRUCTURAL SLAB DECK

OR FRAMING ABOVE INDEPENDENT OF THE CEILING, CEILING

SUPPORT SYSTEM AND OTHER TRADE COMPONENTS. ALL

CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE

NOTED ON DRAWINGS.

9. FIRE RATED SEALS SHALL BE PROVIDED FOR ALL CONDUIT

PENETRATIONS THROUGH FIRE RATED FLOORS, WALLS,

AND CEILINGS.

10. CONTRACTOR MUST VERIFY CONFIGURATIONS,

DIMENSIONS, AND COMPATIBILITY OF ALL EQUIPMENT AND

DEVICES PRIOR TO PRODUCT SUBMISSION AND PRIOR TO

PURCHASE. ALL EQUIPMENT AND DEVICES SHOWN ARE FOR

REFERENCE ONLY AND FINAL LOCATIONS MUST BE

VERIFIED PRIOR TO INSTALLATION. THIS NOTE APPLIES TO

ALL ITEMS FOR INSTALLATION INCLUDING BUT NOT LIMITED

TO EQUIPMENT UNITS, RECEPTACLES, SWITCHES, POWER,

DATA PORTS, AUDIO/VIDEO DEVICES AND TELEPHONE

JACKS.

11. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL

ABOVE CEILING REQUIREMENTS (PLENUM, NON-PLENUM,

AIR HANDLING, ETC.) AS REQUIRED BY LOCAL AUTHORITY

BEFORE THE INSTALLATION AND PURCHASE OF ELECTRICAL

EQUIPMENT, MATERIALS AND DEVICES, WIRING, CABLING,

AND THE ORDERING OF LIGHTING FIXTURES.

12. CONDUCTOR SIZES INDICATED ARE MINIMUM SIZES BASED

ON 60°C COPPER CONDUCTOR 100 AMPS OR LESS AND 75°C

COPPER CONDUCTOR GREATER THAN 100 AMPS.

AMPACITIES OF CONDUCTORS DO NOT TAKE VOLTAGE

DROP INTO CONSIDERATION. CONTRACTOR SHALL SIZE

CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS TO

PREVENT A VOLTAGE DROP EXCEEDING 3 PERCENT AT THE

FARTHEST OUTLET OF POWER, HEATING, AND LIGHTING

LOADS, OR COMBINATION OF SUCH LOADS, AND WHERE THE

MAXIMUM TOTAL VOLTAGE DROP ON BOTH FEEDERS AND

BRANCH CIRCUITS TO THE FARTHEST OUTLET DOES NOT

EXCEED 5 PERCENT, TO PROVIDE REASONABLE EFFICIENCY

OF OPERATION.

AutoCAD SHX Text

NOTES, LEGENDS AND ABBREVIATIONS

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

EF-1

EF-2

EPCA1

EF-2 EF-1

EF-1

EF-2

EPCA1

EF-2 EF-1

E1.1

I B

C

D H

D H

C M

K A

J

B U

I L

D I N

G

R

C O

M P

R E

S S

H

A U

S T

F O

C

S

O U

H

A

V E

F O

C

O Y

W

I

D I R

E C

T O

R A

P

U B

L

R

K S

SHEET

NUMBER:

D w n b y

D e s i g n e d b y

R e v i e w e d b y

D a t e

C k d b y

S u b m i t t e d b y

W o r k

O r d e r

N o

P r o j e c t

N u m b e r

P l o t d a t e

M A

R K

M O

D

R

E Q

U E

D

E S

C R

I P

T I O

N M

A

T E

DPW

FORT MCCOY, WI

SHEET of

D P

W

R e v

F O

C

O Y

W

I S

C O

N S

I N

Scale: 1/4":1'-0"

ELECTRICAL PLAN

E1

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text M-201

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text M-202

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text M-203

AutoCAD SHX Text M-204

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text M & E

AutoCAD SHX Text

EQUIP. ROOM

AutoCAD SHX Text M-205

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text M-201

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text M-202

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text M-203

AutoCAD SHX Text M-204

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text M & E

AutoCAD SHX Text

EQUIP. ROOM

AutoCAD SHX Text M-205

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text M-201

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text M-202

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text M-203

AutoCAD SHX Text M-204

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text M & E

AutoCAD SHX Text

EQUIP. ROOM

AutoCAD SHX Text M-205

AutoCAD SHX Text

ELECTRICAL PLAN

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SHEET NOTES

AutoCAD SHX Text 1.

AutoCAD SHX Text REMOVE, RELOCATE AND EXTEND EXISTING EXISTING EQUIPMENT AND CONDUITS AS REQUIRED TO MAINTAIN CLEARANCES AND ACCOMMODATE NEW CONSTRUCTION.

AutoCAD SHX Text 2.

AutoCAD SHX Text PROVIDE REVISED, TYPED CIRCUIT DIRECTORY FOR EXISTING PANELBOARD EPCA1 FOR NEW BRANCH CIRCUITS.

AutoCAD SHX Text

KEY NOTES

AutoCAD SHX Text E1

REPLACE 15A/3P SPARE BREAKER, SPACES 13,15,17 IN 240V/3P PANEL EPCA1 WITH 20A/3P BREAKER. CONNECT NEW 1-1/2 HP MOTORS EF-1 AND EF-2 TO NEW 20A BREAKER. REFER TO MOTOR WIRING SCHEDULE NOTES.

Sheets and Views
G0.1 COVER SHEET 11x17
A1.1 Exterior Elevations.pdf
Sheets and Views
A1.1 EXTERIOR ELEVATIONS 11x17
S1.0 Framing Plan B200 Air Compressor.pdf
Sheets and Views
S1.0 Framing Plan 11x17
M0.1 Notes Legend and Abbreviations.pdf
Sheets and Views
M0.1 Cover 11x17
M1.2 Mechanical Floor Plan.pdf
Sheets and Views
M1.2 Mech 11x17
M6.0 Mechanical Schedules and Details.pdf
Sheets and Views
M6.0 Details 17x11
E0.1 NOTES LEGENDS AND ABB.pdf
Sheets and Views
E0.1 Cover 11x17
E1.1 Electrical Plan.pdf
Sheets and Views
E1.1 Elec Plan 11x17
G0.1 Cover Sheet.pdf
Sheets and Views
G0.1 COVER SHEET 11x17
A1.1 Exterior Elevations.pdf
Sheets and Views
A1.1 EXTERIOR ELEVATIONS 11x17
S1.0 Framing Plan B200 Air Compressor.pdf
Sheets and Views
S1.0 Framing Plan 11x17
M0.1 Notes Legend and Abbreviations.pdf
Sheets and Views
M0.1 Cover 11x17
M1.2 Mechanical Floor Plan.pdf
Sheets and Views
M1.2 Mech 11x17
M6.0 Mechanical Schedules and Details.pdf
Sheets and Views
M6.0 Details 17x11
E0.1 NOTES LEGENDS AND ABB.pdf
Sheets and Views
E0.1 Cover 11x17
E1.1 Electrical Plan.pdf
Sheets and Views
E1.1 Elec Plan 11x17
M1.2 Mechanical Floor Plan.pdf
Sheets and Views
M1.2 Mech 11x17

File details come from the government source that posted it. Updated .