Mod. 6 ‐ Navigation 2

Graphic Usage Floorplans

• Floorplan graphics provide a graphical representation of your building’s architecture.

• When actual plan drawings are provided in electronic format, the floorplan graphics will be to scale and complete.

• Floorplan graphics may contain textual sensor information indicating values such as the space temperature sensor value connected to the HVAC equipment serving that space.

• Floorplan graphics may contain labels identifying various spaces, site name etc...

• The different colors of the spaces represent different HVAC equipment serving those spaces.

Link to individual equipment

TEC-HP-2Back

HP Mode Auto

Cool Demand = 100.00 %

Heat Demand = 0.00 %

Status

Return Air

73.5 °F

70.5 °FActive Heating Setpt

84.0 °FSpace Temperature Occupancy Status Occupied

Active Cooling Setpt

Heating/Cooling Deadband = 3 deg.

Selected Schedule = Building Schedule

Local Schedule

Reversing Valve = Cooling

Compressor Stage 1 = On

Compressor Stage 2 = On

Aux Heat Stage 1 = Off

Gound Loop Supply Temp = 78.6 °F

Ground Loop Return Temp = 83.0 °F

Setpoints Occupancy Request Occupied BAS Space Setpt 72.0 °F

Setpoint Source BAS Unocc Cooling Setpt 80.0 °F Unocc Heating Setpt 60.0 °F

Failures/Safteys Frost Alarm Filter Status Service Alarm

Fan Lockout Alarm

White = default condition Green = an event time block

Scheduler Pane The Weekly Schedule Tab

Mod. 5 ‐ Schedules 22

Special Events Tab Use this Weekly Scheduler view tab to enter all exceptions to the schedule’s weekly schedule, broadly called “special events”.

Scheduler Pane The Special Events Tab

Mod. 5 ‐ Schedules 23

Mod. 7 ‐ Utility Monitoring 24

Utility Monitoring

The kilowatt hour (symbol kWh, kW∙h, or kW h) is a derived unit of energy equal to 3.6 megajoules. If the energy is being transmitted or used at a constant rate (power) over a period of time, the total energy in kilowatt‐hours is the product of the power in kilowatts and the time in hours. The kilowatt‐hour is commonly used as a billing unit for energy delivered to consumers by electric utilities

Electric Meter

Cubic Feet – Total volume of Gas in Cubic Feet that has been used Gas Meter

Gallons – Total volume of Water in Gallons that has been used Water Meter

The kilowatt (symbol kW) is a derived unit of power. It is defined as 1,000 joules per second. It expresses the rate of energy conversion or transfer with respect to time

Mod. 7 ‐ Utility Monitoring 25