This is a Request for Proposal from the Mission and Installation Contracting Command at Fort Leonard Wood, Missouri seeking proposals to provide facilities operation and maintenance services at the United States Army Chemical Defense Training Facility. The solicitation is for a single-award, firm-fixed-price contract with a one-year base period and four one-year options. Services required include comprehensive facilities maintenance, operation and maintenance of chemical testing sites, decontamination of equipment and facilities, disposal of chemical waste, and decontamination and maintenance of personal protective equipment. The North American Industry Classification System code is 561210 and the Product Service Code is S216. The performance location is Fort Leonard Wood, Missouri. The deadline for proposal submission is February 5, 2020 at 3:00 PM Central Time. The document provides point of contact information for any questions.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J-1
SECTION J TECHNICAL EXHIBITS
Exhibit Page
FACILITY SYSTEMS AND EQUIPMENT J-4
WORKLOAD PLANNING DATA J-61
MAINTENANCE SCHEDULES J-76
CONSUMABLES – LISTING J-93
SUB-CONTRACT REQUIREMENTS – LISTING J-108
PROTECTIVE CLOTHING & EQUIPMENT QUALITY CONTROL J-109
REPORTS BY CONTRACTOR – LISTING J-116
CONTRACT AWARD DELIVERBLES – LISTING J-117
GOVERNMENT QUALITY CONTROL J-118
PERFORMANCE REQUIREMENTS SUMMARY J-129
J-2
Exhibit Number and Description Reference
1.0 Facility Systems and Equipment
1.0 Critical Systems
1.1 Plumbing Equipment 3.11.1
1.2 Air Distribution System Equipment 3.11.2
1.3 Heating System Equipment 3.11.3
1.4 Chilled Water Cooling System Equipment 3.11.4
1.5 Filter Exhaust System and Equipment 3.10.1.29
1.6 V-Bed Carbon Filter Specifications 3.10.1.30
1.7 Facility Ventilation System and Equipment 3.10.1.28
1.8 Terminal Heating System and Equipment 3.10.1.20
1.9 Unitary Air Conditioning System and Equipment 3.10.1.21
1.10 Electrical System 3.11.6
1.11 Sewer System 3.11.8
1.12 Water Treatment System 3.10.1.22
1.13 Autoclave System 3.10.1.37
1.14 Miniature Chemical Agent Monitoring System (MINICAMS) 3.19.3.1
1.15 Enterprise Building Integrator (EBI) Direct Digital Control (DDC) 3.12.5
1.16 Government Furnished Equipment 3.4
1.17 ASTROClean 300 3.10.1.34
2.0 Workload Planning Data
2.1 Task and Frequency Chart for Custodial Services 3.14
2.2 Historical Workload Data for Level 1 Services NA
2.3 Annual Training Loads (Projected) NA
2.4 Facility Footprint Diagram 3.7.1
3.0 Maintenance Schedules
3.1 600kW and 300kW Generators 3.10.1.7
3.2 Facility Ventilation System 3.10.1.28
3.3 Electrical System: Annual 3.11.6
3.4 Electrical System: Semi-Annual 3.11.6
3.5 Electrical System: Periodic or As Required 3.11.6
3.6 Autoclave 3.10.1.37
3.7 Chilled Water Cooling System 3.11.4
3.8 Filter Exhaust System 3.10.1.29
3.9 Fire Alarm System 3.11.7
3.10 Heating System 3.10.1.20
3.11 Unit Heater/Cabinet Unit Heater System 3.10.1.20
3.12 Plumbing and Fire Protection System 3.11.1
3.13 Sewer System 3.11.8
3.14 Unitary Air Conditioning System 3.10.1.21
3.15 3X Waste Water Treatment System 3.10.1.33
3.16 Potable Water Treatment System 3.10.1.22
3.17 ASTROClean 300 3.10.1.34
J-3
4.0 Consumables – Listing 3.19.3.2
Exhibit Number and Description Reference
5.0 Sub-Contract Requirements – Listing NA
6.0 Protective Clothing and Equipment Quality Control
6.1 Processes and Equipment Supported by Contractor Quality Control 3.17.3
6.2 Operator Performance Validation Schedule 4.9.4
6.3 Quality Control Coordinator (QCC) Inspection Schedule 4.9.4
6.4 Quality Control Coordinator (QCC) Summary Report 4.9.4
7.0 Reports by Contractor – Listing 3.20
8.0 Contract Award Deliverables – Listing NA
9.0 Government Quality Control
9.1 PC&E Quality Control: Protective Masks NA
9.2 PC&E Quality Control: JSLIST Coat NA
9.3 PC&E Quality Control: JSLIST Trouser NA
9.4 PC&E Quality Control: Chemical Protective Gloves NA
9.5 PC&E Quality Control: AFS Chemical Boots NA
9.6 OCSC Quality Control: Entry Control NA
9.7 OCSC Quality Control: Pre-Operations NA
9.8 OCSC Quality Control: Maintenance, Laundry, Equipment Destruction NA
9.9 TST Quality Control: DAAMS Chain of Custody NA
9.10 O&M Quality Control: Custodial Quality Control NA
9.11 O&M Quality Control: Facility Exterior NA
10.0 Performance Requirements Summary NA
J-4
Table 1.0 Critical Systems
Table 1.0
Critical Systems References Air Distribution System 3.11.2.
Air Monitoring 3.19.2.
Back-Up Power Generator 3.10.1.7.
Closed-Circuit Television (CCTV) System 3.10.1.12.
Electrical Systems 3.11.6.
Facility Ventilation Systems 3.10.1.28.
Filter Exhaust System 3.10.1.29.
Fire Alarm System 3.11.7.
Honeywell EBI 4.8.1.10.
Hot Water Heating System 3.11.3.
Intrusion Detection System 3.10.1.10.
Terminal Heating System 3.10.1.20.
Training Audio/Visual System 3.10.1.14.
Unitary Air Conditioning System 3.10.1.21.
J-5
Technical Exhibit 1.1 Plumbing Equipment
Tag Number Equipment Name Manufacturer Location Model Remarks
Technical Exhibit 1.1: Plumbing Equipment
FP-AL-CV Alarm check valve Unknown Quad B Rm 016
FP-DCBP-1 Backflow preventer Unknown Quad E Rm 085 10" double check double gate backflow preventer
FP-DCBP-2 Backflow preventer Unknown Quad E Rm 097 2" anti-freeze system reduced pressure principle
FP-DCBP-3 Backflow preventer Unknown Quad B Rm 016 6" double check double gate FP-FH-1 Fire Hydrant Unknown Area 1 Access Rd FP-FH-2 Fire Hydrant Unknown Area 2 E of Quad A FP-FH-3 Fire Hydrant Unknown Area 2 W of Quad E FP-FH-4 Fire Hydrant Unknown Area 2 E of Quad E FP-FH-5 Fire Hydrant Unknown Area 2 N of Quad D FP-FH-6 Fire Hydrant Unknown Area 2 N of Safe Ctrl FP-FH-7 Fire Hydrant Unknown Area 2 S of Safe Ctrl FP-FHC-1 Fire hose cabinet Unknown Quad C Rm 031 cabinet & extinguisher FP-FHC-10 Fire hose cabinet Unknown Quad E Rm 097 cabinet & extinguisher FP-FHC-2 Fire hose cabinet Unknown Quad C Rm 057 cabinet & extinguisher FP-FHC-3 Fire hose cabinet Unknown Quad C Rm 067 cabinet & extinguisher FP-FHC-4 Fire hose cabinet Unknown Quad C Rm 068 cabinet & extinguisher FP-FHC-5 Fire hose cabinet Unknown Quad D Rm 077 cabinet & extinguisher FP-FHC-6 Fire hose cabinet Unknown Quad D Rm 078 cabinet & extinguisher FP-FHC-7 Fire hose cabinet Unknown Quad D Rm 079A cabinet & extinguisher FP-FHC-8 Fire hose cabinet Unknown Quad D Rm 72A cabinet & extinguisher FP-FHC-9 Fire hose cabinet Unknown Quad E Rm 101 cabinet & extinguisher
FP-FP-1 Fire pump Patterson Quad E Rm 085 8x6 MI 1250 gpm; 40 psi; 40 hp;
1780 rpm; 460v 3ph
FP-FP-1-MTR Fire pump motor Quad E Rm 085 fire pump motor
FP-JP-1 Jockey pump Grundfos Quad E Rm 085 CR2-50U 15 gpm; 16psi; 5 hp; 1760 rpm; 460 v 3ph; vertical multi-stage
FP-JP-1-MTR Jockey pump motor Unknown Quad E Rm 085 jockey pump motor
PL-BFP-1
Reduced pressure backflow preventer
Unknown Quad C Rm 071 4" flanged; Training Bldg.- Main
PL-BFP-10
Reduced pressure backflow preventer
Unknown Quad A 2" threaded; Guard House- Sprinklers (Fire Protection)
PL-BFP-11
Reduced pressure backflow preventer
Unknown Quad C Rm 068 1" threaded; Drink tube station
PL-BFP-2
Reduced pressure backflow preventer
Unknown Quad C Rm 071 2.5" flanged; Irrigation Supply
PL-BFP-3
Reduced pressure backflow preventer
Unknown Quad C Rm 071 2" threaded; Training Bays
PL-BFP-4
Reduced pressure backflow preventer
Unknown Quad E Rm 093 2" threaded; Waste Containment
PL-BFP-5
Reduced pressure backflow preventer
Unknown Mechanical Makeup 2" threaded; Mechanical Make-up
PL-BFP-6
Reduced pressure backflow preventer
Unknown Quad E - Rm 084 1" threaded;Autoclave Room
PL-BFP-7
Reduced pressure backflow preventer
Unknown Quad B Rm 016 2" threaded; Training Pads Supply
PL-BFP-8
Reduced pressure backflow preventer
Unknown Quad B Rm 016 3" flanged; Admin Bldg
J-6
Technical Exhibit 1.1: Plumbing Equipment
PL-BFP-9
Reduced pressure backflow preventer
Unknown Quad A 2" threaded; Guard House- Domestic
PL-CP-1
Circulating pump PL- WH-1 domestic HW
Unknown Quad C Rm 071 with WH-1
PL-CP-1-MTR
Circulating pump motor
Unknown Quad C Rm 071
PL-CP-2
Drum pump to drink tube station
Unknown Quad C Rm 068 Drum pump - Drink tube sanitizing pump; stainless steel, 10 gpm
PL-CP-2-MTR Drum pump motor Unknown Quad C Rm 068 Drink tube sanitizing pump motor
PL-CP-3
Circulating pump to
PL-WH-2
Unknown Quad C Rm 068
PL-CP-3-MTR
Circulating pump motor
Unknown Quad C Rm 068
PL-CP-4
Circulating pump to
PL-WH-3
Unknown Quad C Rm 068
PL-CP-4-MTR
Circulating pump motor
Unknown Quad C Rm 068
PL-ET
Domestic hot water expansion tank
Unknown Quad C Rm 071 20 gal.
PL-EYE-1
Eyewash/safety shower
Unknown Quad C Rm 034 P-17 eyewash & safety shower
PL-EYE-10
Eyewash/safety shower
Unknown Quad E Rm 098 P-17 eyewash/safety shower
PL-EYE-2
Eyewash/safety shower
Unknown Quad C Rm 072 P-17 eyewash & safety shower
PL-EYE-3
Eyewash/safety shower
Unknown Quad C Rm 033 P-17 eyewash & safety shower
PL-EYE-4
Eyewash/safety shower
Unknown Quad C Rm 043 P-17 Eyewash/safety shower
PL-EYE-5
Eyewash/safety shower
Unknown Quad C Rm 037 P-17 eyewash/safety shower
PL-EYE-6 Eyewash Unknown Quad C Rm 037 P-16 eyewash PL-EYE-7 Eyewash Unknown Quad C Rm 037 P-16 eyewash PL-EYE-8 Eyewash Unknown Quad C Rm 038 P-16 eyewash PL-H2O-C-1 Water cooler Unknown Quad B Corr 012 P-15 water cooler PL-H2O-C-2 Water cooler Unknown Quad C Rm 030 P-15 water cooler PL-H2O-C-3 Water cooler Unknown Quad C Rm 059 P-15 water cooler PL-H2O-C-4 Water cooler Unknown Quad C Rm 053 P-15 water cooler PL-H2O-C-5 Water cooler Unknown Quad C Rm 067 P-15 water cooler
PL-H2-T
Helium tanks manifold system
Unknown Quad E Rm 086
PL-HD-T
Hydrogen tank manifold system
Unknown Quad E Rm 086
PL-HWP-1
Hot water return pump
Unknown Quad C Rm 071
PL-HWP-1-MTR
Hot water return pump motor
Unknown Quad C Rm 071
PL-IP-1 Irrigation pump Unknown Quad C Rm 071 irrigation system pump PL-IP-1-MTR Irrigation pump motor Unknown Quad C Rm 071
J-7
PL-LAV-1 Lavatory Unknown Quad A P-6 lavatory wall hung PL-LAV-2A Lavatory Unknown Quad B Rm 014 P-5 lavatory countertop PL-LAV-2B Lavatory Unknown Quad B Rm 014 P-5 lavatory countertop PL-LAV-2C Lavatory Unknown Quad B Rm 014 P-5 lavatory countertop PL-LAV-3A Lavatory Unknown Quad B Rm 015 P-5 lavatory countertop PL-LAV-3B Lavatory Unknown Quad B Rm 015 P-5 lavatory countertop PL-LAV-4A Lavatory Unknown Quad C Rm 059 P-6 lavatory wall hung PL-LAV-4B Lavatory Unknown Quad C Rm 059 P-6 lavatory wall hung PL-LAV-5A Lavatory Unknown Quad C Rm 053 P-6 lavatory wall hung PL-LAV-5B Lavatory Unknown Quad C Rm 053 P-6 lavatory wall hung PL-LAV-6 Lavatory Unknown Quad C Rm 066 P-6 lavatory wall hung PL-LAV-7 Lavatory Unknown Quad E Rm 089 P-6 lavatory wall hung PL-PAC-1 Air Compressor Unknown Quad C Rm 071 air compressor PL-PAC-FLTR Air Compressor filter Unknown Quad C Rm 071 air compressor filter PL-PIPE Pipe Unknown PL-SHWR-1 Column Shower Unknown Quad C Rm 063 HS P-13 column shower (hot)
PL-SHWR-2 Column Shower Unknown Quad C Rm 062 Hyg P-13 Column Shower (hygienic)
PL-SHWR-3 Column Shower Unknown Quad C Rm 046 HS P-13 column shower (hot) PL-SHWR-4 Column Shower Unknown Quad C Rm 046 HS P-13 column shower (hot)
PL-SHWR-5 Column Shower Unknown Quad C Rm 047 Hyg P-13 column shower (hygenic)
PL-SHWR-6 Column Shower Unknown Quad C Rm 047 Hyg P-13 column shower (hygenic)
PL-SINK-1 Sink Unknown Quad B Rm 008 P-7A stainless steel counter top
PL-SINK-10 Sink Unknown Quad E Rm 088 P-7A countertop sink stainless steel
PL-SINK-2 Sink Unknown Quad B Rm 009 P-7 stainless steel counter top
PL-SINK-3 Sink Unknown Quad B Rm 011 P-7 stainless steel counter top
PL-SINK-4 Sink Unknown Quad B Rm 017 P-8 service sink
PL-SINK-5 Sink Unknown Quad C Rm 033 P-7A stainless steel counter top
PL-SINK-6 Sink Unknown Quad C Rm 055 P-8 service sink PL-SINK-7 Sink Unknown Quad C Rm 037 P-10 lab sink resin PL-SINK-8 Sink Unknown Quad C Rm 037 P-10 lab sink resin PL-SINK-9 Sink Unknown Quad C Rm 038 P-10 lab sink resin
PL-ST-1
Domestic hot water storage tank
Unknown Quad C Rm 071 750 gal.
PL-ST-1-RV Relief valve Quad C Rm 071
PL-ST-2
Domestic hot water storage tank
Unknown Quad C Rm 071 750 gal.
PL-ST-2-RV Relief valve Quad C Rm 071 PL-URN-1A Urinal Unknown Quad B Rm 014 P-3A urinal ada accessible PL-URN-1B Urinal Unknown Quad B Rm 014 P-3 urinal PL-URN-1C Urinal Unknown Quad B Rm 014 P-3 urinal PL-URN-2A Urinal Unknown Quad C Rm 053 P-3 urinal
J-8
PL-URN-2B Urinal Unknown Quad C Rm 053 P-3 urinal PL-URN-2C Urinal Unknown Quad C Rm 053 P-3 urinal PL-WC-1 Water closet Unknown Quad A P-1 water closet PL-WC-2A Water closet Unknown Quad B Rm 014 P-1 water closet PL-WC-2B Water closet Unknown Quad B Rm 014 P-1 water closet
PL-WC-2C Water closet Unknown Quad B Rm 014 P-2 water closet ada accessible
PL-WC-3A Water closet Unknown Quad B Rm 015 P-1 water closet
PL-WC-3B Water closet Unknown Quad B Rm 015 P-2 water closet ada accessible
PL-WC-4A Water closet Unknown Quad C Rm 059 P-1 water closet PL-WC-4B Water closet Unknown Quad C Rm 059 P-1 water closet PL-WC-5A Water closet Unknown Quad C Rm 053 P-1 water closet PL-WC-5B Water closet Unknown Quad C Rm 053 P-1 water closet PL-WC-6 Water closet Unknown Quad C Rm 066 P-1 water closet PL-WC-7 Watercloset Unknown Quad E Rm 089 P-1 watercloset PL-WH-1 Water Heater A.O. Smith Quad C Rm 071 LW-500 PL-WH-1-RV Relief valve Quad C Rm 071
PL-WH-2
Water heater, gas fired
Unknown Quad C Rm 068 670000 btu, gas; w/CP-3
PL-WH-2-RV Relief valve Quad C Rm 068
PL-WH-3
Water heater, gas fired
Unknown Quad C Rm 068 300,000 btu, gas; w/CP-4
PL-WH-3-RV Relief valve Quad C Rm 068
PL-WH-4 Water heater Unknown Quad B Rm 007 Gas fired water heater; 75 gal; 75,100 BTU
PL-WH-4-RV Relief valve Quad B Rm 007 PL-WS-1 Water softener Unknown Quad C Rm 071
J-9
Technical Exhibit 1.2 Air Distribution Equipment
Tag Number Equipment Name Manufacturer Location Serial Number Model Number
Technical Exhibit 1.2: Air Distribution Equipment
AD-AB-5 Air Blender Kees Air Mixer 20
AD-AB-8 Air Blender Kees Air Mixer 28
AD-AB-9 Air Blender Kees Air Mixer 20
AD-AHU-1 AHU-1 Temtrol West Interstitial 70876 WF-DH40
AD-AHU-10 AHU-10 Temtrol East Interstitial WF-DH12
AD-AHU10-F Fan, AHU-10 AF-16
AD-AHU10-FL Filters
AD-AHU10-PC Preheat Coil Wing IFB D-60
AD-AHU10-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-12 Air Handling Unit Temtrol WF-DH17
AD-AHU12-F Fan, AHU-12 AF-12
AD-AHU12-FL Filters
AD-AHU12-PC Preheat Coil Wing IFB B-42
AD-AHU12-VI Vibration Isolator Amber/Booth SWSR
AD-AHU1-CC Cooling Coil - AHHU-1 5WC6-33x88x8-12AL
AD-AHU1-F Fan - AHU-1 AF-27
AD-AHU1-FL Filters
AD-AHU1-PC Preheat Coil - AHU-1 Wing VIFB VC-8W
AD-AHU1-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 30hp
AD-AHU1-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-2 AHU-2 Temtrol East Interstitial 70877 WF-DH40
AD-AHU2-CC Cooling coil, AHU-2
AD-AHU2-F Fan, AHU-2 AF-27
AD-AHU2-FL Filters
AD-AHU2-PC Preheat Coil Wing VIFB VC-8W
AD-AHU2-VFD
Variable Frequency Drive
Toshiba q-Flowsaver 30hp
AD-AHU2-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-3 AHU-3 Temtrol Above Lab 70878 WF-DH16
AD-AHU3-CC Cooling Coil
5WC 12-43.5X52X8-
6AL
AD-AHU3-F Fan, AHU-3 AF-15
AD-AHU3-FL Filters
AD-AHU3-PC Preheat Coil Wing VIFB VA-5W
AD-AHU3-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 10 hp
AD-AHU3-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-4 Air Handling Unit Temtrol WF-DH16
AD-AHU4-CC Cooling Coil 5WB0701H
J-10
AD-AHU4-FL Filters AmAir 300X
AD-AHU4-HC Heating Coil 5WH1208C
AD-AHU-5 AHU-5 Temtrol West Interstitial 70879 WF-DH13
AD-AHU5-CC Cooling Coil
5WC16-42X46X8-
12AL
AD-AHU5-F Fan, AHU-5 AF-16
AD-AHU5-FL Filters
AD-AHU5-PC Preheat Coil Wing VIFB VA-4
AD-AHU5-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 10 hp
AD-AHU5-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-6 AHU-6 Temtrol East Interstitial 70880 WF-DH26
AD-AHU6-CC Cooling Coil 5WC6-42X88X8-7AL
AD-AHU6-F Fan, AHU-6 AF-20
AD-AHU6-FL Filters
AD-AHU6-PC Preheat Coil Wing VIFB VA-8W
AD-AHU6-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 15 hp
AD-AHU6-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-7 Air Handling Unit McQuay CAH006FHAC
AD-AHU7-FL Filters AmAir 300X
AD-AHU7-HC Heating Coil 5WQ1401H
AD-AHU7-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-8 AHU-8 Temtrol Mech Room 70881 WF-DH27
AD-AHU8-CC Cooling Coil
5WC6-51X76X10-
12AL
AD-AHU8-F Fan, AHU-8 AF-22
AD-AHU8-FL Filtters
AD-AHU8-PC Preheat Coil Wing VIFB VA-5W
AD-AHU8-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 20 hp
AD-AHU8-VI Vibration Isolator Amber/Booth SWSR
AD-AHU-9 AHU-9 Temtrol East Interstitial 70882 WF-DH17
AD-AHU9-CC Cooling coil
5WC8-37.5X64X6-
7AL
AD-AHU9-F Fan, AHU-9 AF-16
AD-AHU9-FL Filters
AD-AHU9-PC Preheat Coil Wing VIFB B-48
AD-AHU9-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 15hpp
AD-AHU9-VI Vibration Isolator Amber/Booth SWSR
AD-FTU 8-1
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 811
J-11
AD-FTU 8-10
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1011
AD-FTU 8-11
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1218
AD-FTU 8-12
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1221
AD-FTU 8-13
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 806
AD-FTU 8-2
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1640
AD-FTU 8-3
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1640
AD-FTU 8-4
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1011
AD-FTU 8-5
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 606
AD-FTU 8-6
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 1018
AD-FTU 8-7
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 811
AD-FTU 8-8
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 806
AD-FTU 8-9
VAV fan terminal unit with hot water coil
Environmental Technologies
CFR-WC 606
AD-H-1 Electric Humidifier Dri-Steem VLC-42-2
AD-L-13 Louver Ruskin ELF375DX
AD-L-14 Louver Ruskin ELF375DX
AD-R1 Air Devices EH Price 610
AD-R2 Air Devices EH Price 610
AD-R3 Air Devices EH Price PDDR
AD-R4 Air Devices EH Price PDDR
AD-R5 Air Devices EH Price PDDR
AD-R6 Air Devices EH Price PDDR
AD-R7 Air Devices EH Price PDDR
AD-R8 Air Devices EH Price PDDR
AD-R9 Air Devices EH Price 610
AD-RAV 5-1
VAV return air damper unit
Phoenix Controls EXVA112M-AAEHO
AD-RAV 5-2
VAV return air damper unit
Phoenix Controls EXVA112M-AAEHO
AD-RAV 5-3
VAV return air damper unit
Phoenix Controls EXVA112M-AAEHO
AD-RAV 9-1
VAV return air damper unit
Phoenix Controls EXVA112M-AAEHO
AD-RAV 9-2
VAV return air damper unit
Phoenix Controls EXVA112M-AAEHO
J-12
AD-RAV 9-3
VAV return air damper unit
Phoenix Controls EXVA112M-AAEHO
AD-RAV 9-4
VAV return air damper unit
Phoenix Controls EXVA312M-AAEHO
AD-RF-1 Return Fan Penn Ventilator REX-27B
AD-RF1-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 5 hp
AD-RF-2 Return Fan Penn Ventilator REX-27B
AD-RF2-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 5hp
AD-RF-3 Return Fan Penn Ventilator REX-27B
AD-RF3-VFD
Variable Frequency Drive
Toshiba Q-Flowsaver 7.5 hp
AD-S1 Air Devices EH Price 520
AD-S10 Air Devices EH Price PDN
AD-S11 Air Devices EH Price PDN
AD-S12 Air Devices EH Price SMD
AD-S13 Air Devices EH Price SMD
AD-S14 Air Devices EH Price SMD
AD-S15 Air Devices EH Price SMD
AD-S16 Air Devices EH Price SMD
AD-S17 Air Devices EH Price SMD
AD-S18 Air Devices EH Price SMD
AD-S19 Air Devices EH Price SMD
AD-S2 Air Devices EH Price 520
AD-S20 Air Devices EH Price LFD
AD-S21 Air Devices EH Price 520D
AD-S3 Air Devices EH Price 520
AD-S4 Air Devices EH Price 520
AD-S5 Air Devices EH Price 520
AD-S6 Air Devices EH Price 520
AD-S7 Air Devices EH Price PDN
AD-S8 Air Devices EH Price PDN
AD-S9 Air Devices EH Price PDN
AD-VAV 1-1
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 1-2
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC16
AD-VAV 1-3
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 16
AD-VAV 1-4
VAV Terminal unit with hot water coil
Environmental
SDR-WC 14
J-13
AD-VAV 1-5
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 1-6
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 14
AD-VAV 1-7
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 1-8
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 2-1
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 2-2
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 16
AD-VAV 2-3
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 16
AD-VAV 2-4
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 14
AD-VAV 2-5
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 14
AD-VAV 2-6
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 2-7
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 2-8
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 3-1
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 14
AD-VAV 3-2
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 3-3
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 08
AD-VAV 5-1
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 5-2
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 08
AD-VAV 5-3
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 5-4
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 5-5
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 6-1
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 05
AD-VAV 6-10
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 10
AD-VAV 6-2
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 08
AD-VAV 6-3
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 08
AD-VAV 6-4
VAV Terminal unit with hot water coil
Environmental
SDR-WC 08
J-14
AD-VAV 6-5
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 04
AD-VAV 6-6
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 6-7
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 08
AD-VAV 6-8
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 05
AD-VAV 6-9
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 9-1
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 9-2
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 08
AD-VAV 9-3
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 9-4
VAV Terminal unit with hot water coil
Environmental Technologies
SDR-WC 12
AD-VAV 9-5
VAV Terminal unit with hot water coil
Environmental
SDR-WC 12
J-15
Technical Exhibit 1.3 Heating System Equipment
Tag Number Equipment Name Manufacturer Location Model
HS-AS Air Separator TACO AC6F
HS-EF-23
Combustion air/exhaust gas removal fan
Exhausto CASV315
HS-ET-1 Expansion Tank TACO Mech Room CAX254
HS-HWB-1 Boiler 1 Fulton Quad C Mech Room PHW-1000
HS-HWB-2 Boiler 2 Fulton Mech Room PHW-1000
HS-HWB-3 Boiler 3 Fulton Mech Room PHW-1000
HS-HWB-4 Boiler 4 Fulton Mech Room PHW-1000
HS-HWB-5 Boiler 5 Fulton Mech Room PHW-1000
HS-HWB-6 Boiler 6 Fulton Mech Room PHW-1000
HS-P-10 Boiler Circulation Pump TACO Mech Room 1632C
HS-P-11 Boiler Circulation Pump TACO Mech Room 1632C
HS-P-12 Boiler Circulation Pump TACO Mech Room 1632C
HS-P-3
Hot Water Distribution Pump
TACO Quad C Mech Room FE 4008
HS-P3-VFD
Variable frequency drive for P-3
Toshiba Q-Flowsaver 20hp
HS-P-4
Hot Water Distribution Pump
TACO Mech Room FE 4008
HS-P4-VFD
Variable frequency drive for P-3
Toshiba Q-Flowsaver 20hp
HS-P-7 Boiler Circulation Pump TACO Mech Room 1632C
HS-P-8 Boiler Circulation Pump TACO Mech Room 1632C
HS-P-9 Boiler Circulation Pump TACO Mech Room 1632C
Exhibit 1.3: Heating System Equipment
J-16
Technical Exhibit 1.4 Chilled Water Cooling System Equipment
Tag Number Equipment Name Manufacturer Location Model Number
CW-CH-1 Water Cooled Chiller Trane Mech Room CVHE0450
CW-CH-2 Water Cooled Chiller Trane Mech Room CVHE0450
CW-CT-1 Cooling Tower Baltimore AirCoil Outside Mech Rm 3458
CW-CT1-VFD
Variable frequency drive for CT-1 Toshiba Q-Flowsaver 20hp
CW-ET-2 Expansion Tank TACO Mech Room CAX-130
CW-P-1 Condenser Water Pump TACO Mech Room FE4010
CW-P-2 Condenser Water Pump TACO Mech Room FE4010
CW-P-5 Chilled Water Pump TACO Mech Room FE-4010
CW-P-6 Chilled Water Pump TACO Mech Room FE 4010
CW-RF Refrigerant sensor Kele & Associates RLD-123-IR
Exhibit 1.4: Chilled Water Cooling System Equipment
J-17
Technical Exhibit 1.5 Filter Exhaust System and Equipment
J.1.5.1 Filter Blowers, FB-1 and FB-6. These two exhaust blowers exhaust air from each of the two large training bays; FB-1 exhausts training bay 7 and FB-6 exhausts training bay 8. These centrifugal, industrial, radial blade fans are variable frequency controlled and volume of air exhausted is controlled to maintain training bays at a negative pressure relationship to adjoining cold corridor and service gallery areas.
J.1.5.2 Filter Blowers, FB-2 and FB-5. These two exhaust blowers exhaust air from the smaller training bays, service gallery areas and cold corridor; FB-2 exhausts air from training bays 1, 2 and 3 and the west half of the service gallery and service rotunda and FB-5 exhausts air from training bays 4, 5, and 6 and the east half of the service gallery and service rotunda. These centrifugal, industrial, radial blade fans are variable frequency controlled and each space exhausted by these systems is provided with variable volume exhaust control damper units to maintain required pressure relationships with adjoining spaces.
J.1.5.3 Filter Blower, FB-3A and 3B. These two exhaust blowers (one-100% standby) exhaust air from the laboratory, the laboratory hoods and glove box. These centrifugal, industrial, radial blade fans are variable frequency controlled and the volume of air exhausted from hoods and laboratory space is controlled by variable air volume exhaust damper units. The exhaust damper units on the fume hoods control air flow at 100% constant volume flow during occupied mode and 50% flow during unoccupied mode. The general laboratory area exhaust damper unit maintains laboratory at desired pressure relationship.
J.1.5.4 Filter Blower, FB-4. This exhaust blower exhausts air from the remaining hot areas of the facility. These areas include the hot shower areas, men doff/outer garment drop, women doff, women outer garment drop, hot laundry, mask check, monitor devices room, medical room, ante room, and equipment destruction area. This centrifugal, industrial, radial blade fan shall be variable frequency controlled and each zone exhausted by these systems is provided with variable volume exhaust damper units to maintain required pressure relationships with adjoining spaces.
J-18
Tag Number Equipment Name Manufacturer Model Number Remarks
Technical Exhibit 1.5 Filter Exhaust System Equipment
FE-E1 Air Devices Kees R45
FE-E2 Air Devices Kees R45
FE-E3 Air Devices Kees R45
FE-E4 Air Devices Kees R45
FE-E5 Air Devices Kees R45
FE-E6 Air Devices Kees R45
FE-E7 Air Devices Kees R45
FE-E8 Air Devices Kees R45
FE-E9 Air Devices Kees R45
FE-EAV 2-1 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-EAV 2-2 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 2-3 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 2-4 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 2-5 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-EAV 3-1 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 3-2 VAV exhaust air damper Phoenix Controls EXCV106M-ZAEHO
FE-EAV 3-3 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-EAV 3-4 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-EAV 3-5 VAV exhaust air damper Phoenix Controls EXVC110M-AAEHO
FE-EAV 4-1 VAV exhaust air damper Phoenix Controls EXVC110M-AAEHO
FE-EAV 4-10 VAV exhaust air damper Phoenix Controls EXVC112M-AAEHO
FE-EAV 4-11 VAV exhaust air damper Phoenix Controls EXVC112M-AAEHO
FE-EAV 4-2 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-EAV 4-3 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-EAV 4-4 VAV exhaust air damper Phoenix Controls EXVC112M-AAEHO
FE-EAV 4-5 VAV exhaust air damper Phoenix Controls EXCV M-AAEHO
FE-EAV 4-6 VAV exhaust air damper Phoenix Controls EXVC106M-ZAEHO
FE-EAV 4-7 VAV exhaust air damper Phoenix Controls EXVC112M-AAEHO
FE-EAV 4-8 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 4-9 VAV exhaust air damper Phoenix Controls EXVC110M-AAEHO
FE-EAV 5-1 VAV exhaust air damper Phoenix Controls EXVC112M-AAEHO
FE-EAV 5-2 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 5-3 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 5-4 VAV exhaust air damper Phoenix Controls EXVC212M-AAEHO
FE-EAV 5-5 VAV exhaust air damper Phoenix Controls EXVC210M-AAEHO
FE-F-1-CA
Bag-in/bag-out filter system Carbon Adsorber Barnebey & Sutcliffe FV-1662 24 adsorbers
FE-F-1-HEPA
Bag-in/bag-out filter system HEPA American Air Filter
Astrocel I Part No. 105- 1689868-11 12 filters
J-19
FE-F-1-HSNG
Bag-in/bag-out filter system housing Barnebey & Sutcliffe
KEP3S-3x2-2/TS-12-
16-16-TS-16-16-12-TS
FE-F-2-CA
Bag-in/bag-out filter system Carbon Adsorber Barnebey & Sutcliffe FV-1662 36 adsorbers
FE-F-2-HEPA
Bag-in/bag-out filter system HEPA American Air Filter
Astrocel I Part No. 105- 1689868-11 18 filters
FE-F-2-HSNG
Bag-in/bag-out filter system housing Barnebey & Sutcliffe
KEP3S-3x3-2/TS-12-
16-16-TS-16-16-12-TS
FE-F-3-CA
Bag-in/bag-out filter system Carbon Adsorber Barnebey & Sutcliffe FV-1662V 24 adsorbers
FE-F-3-HEPA
Bag-in/bag-out filter system HEPA American Air Filter
Astrocel I Part No. 105- 1689868-11 12 filters
FE-F-3-HSNG
Bag-in/bag-out filter system housing Barnebey & Sutcliffe
KEP3S-3x2-2/TS-12-
16-16-TS-16-16-12-TS
FE-F-4-CA
Bag-in/bag-out filter system Carbon Adsorber Barnebey & Sutcliffe FV-1662 36 adsorbers
FE-F-4-HEPA
Bag-in/bag-out filter system HEPA American Air Filter
Astrocel I Part No. 105- 1689868-11 118 filters
FE-F-4-HSNG
Bag-in/bag-out filter system housing Barnebey & Sutcliffe
KEP3S-3x3-2/TS-12-
16-16-TS-16-16-12-TS
FE-F-5-CA
Bag-in/bag-out filter system Carbon Adsorber Barnebey & Sutcliffe FV-1662 36 adsorbers
FE-F-5-HEPA
Bag-in/bag-out filter system HEPA American Air Filter
Astrocel I Part No. 105- 1689868-11 18 filters
FE-F-5-HSNG
Bag-in/bag-out filter system housing Barnebey & Sutcliffe
KEP3S-3x3-2/TS-12-
16-16-TS-16-16-12-TS
FE-F-6-CA
Bag-in/bag-out filter system Carbon Adsorber Barnebey & Sutcliffe FV-1662 24 adsorbers
FE-F-6-HEPA
Bag-in/bag-out filter system HEPA American Air Filter
Astrocel I Part No. 105- 1689868-11 12 filters
FE-F-6-HSNG
Bag-in/bag-out filter system housing Barnebey & Sutcliffe
KEP3S-3x2-2/TS-12-
16-16-TS-16-16-12-TS
FE-FB-1 Filter exhaust blowers Barry Blower IND-19-61
FE-FB1-VFD Variable frequency drive Toshiba Q-Flowsaver 40 hp
FE-FB-2 Filter exhaust blowers Barry Blower IND-21-61
J-20
FE-FB2-VFD Variable frequency drive Toshiba Q-Flowsaver 50 hp
FE-FB-3A Filter exhaust blowers Barry Blower IND-17-61
FE-FB3A-VFD Variable frequency drive Toshiba Q-Flowsaver 30 hp
FE-FB-3B Filter exhaust blowers Barry Blower IND-17-61
FE-FB3B-VFD Variable frequency drive Toshiba Q-Flowsaver 30 hp
FE-FB-4 Filter exhaust blowers Barry Blower IND-23-61
FE-FB4-VFD Variable frequency drive Toshiba Q-Flowsaver 60 hp
FE-FB-5 Filter exhaust blowers Barry Blower IND-21-61
FE-FB5-VFD Variable frequency drive Toshiba Q-Flowsaver 50 hp
FE-FB-6 Filter exhaust blowers Barry Blower IND-19-61
FE-FB6-VFD Variable frequency drive Toshiba Q-Flowsaver 40 hp
FE-FSID
Filter system isolation dampers United McGill UVC563-5
FE-T1 Air Devices Kees R45
FE-T2 Air Devices Kees R45
FE-T3 Air Devices Kees R45
FE-T4 Air Devices Kees R45
FE-T5 Air Devices Kees R45
FE-T6 Air Devices Kees R45
J-21
Technical Exhibit 1.6 V-Bed Carbon Filter Specifications
J.1.6.1 The V-Bed Carbon Absorber cells shall be constructed of 14 gauge Type 304 stainless steel. The screens on the carbon beds shall be constructed of 26 gauge perforated stainless steel.
All joints and seams shall be welded and pop-riveted and ground free of all burrs and sharp edges. Manufacture of the unit shall be in accordance with the procedures of ANSI/ASME
NQA-1.
J.1.6.2 The Carbon Absorbers, both primary and secondary sections, shall have a minimum residence time of 0.25 seconds. The carbon which shall be utilized shall be proven to meet required efficiencies for the following lethal nerve agents which have the potential to be in the air stream entering the carbon absorbers:
J.1.6.2.1 Trade Name: VX; Chemical Family: Sulfonated organophosphorus compound;
Formula/Chemical Structure: C11 H26 N 02 P S
J.1.6.2.2 Trade Name: GB; Chemical Family: Fluorinated organ phosphorous compound;
Formula/Chemical Structure: C4 H10 F02 P
J.1.6.3 Absorbers shall be designed for use in fluid seal housings and shall be equipped with a fluid seal channel on one side of the absorber cell. The channel shall be filled with a non-drying gel seal compound formulated for high efficiency applications. A continuous knife-edge component located on the housing shall mate into the gel seal compound to effect a leak-tight interface between the absorber and its housing. The absorber shall be equipped with T-clips on its air-existing side. A mechanical device in the housing shall hook into the T-clips to move the absorber in and out of its sealing position on the knife edge.
J.1.6.4 Each absorber shall be factory-tested to determine the mechanical efficiency of the assembled unit and must exhibit a minimum efficiency of 99.9% per IES-RP-CC008-84.
J-22
Technical Exhibit 1.7 Facility Ventilation System and Equipment
J.1.7.1 The facility ventilation systems consist of supply fans, exhaust fans (EF), air handling units (AHU), intake louvers, relief louvers, filter sections, distribution ductwork and associated controls.
J.1.7.2 Exhaust fan EF-1 and EF-2 work in conjunction with AHU-10 to ventilate the main Mechanical Room. EF-1 runs when AHU-10 is on low speed and both fans run when AHU-10 is on high speed. Switchover from low to high speed is initiated through the Direct Digital Control (DDC) System based on space temperature. A refrigerant leak detected will also force AHU-10 to high speed and run both fans.
J.1.7.3 Exhaust fans EF-3 and EF-4 together with intake louvers L-18 and L-19 ventilate the Filter Room. Fans are two-speed with wall mounted two-stage thermostats controlling operation.
Controls are not tied into DDC system.
J.1.7.4 Exhaust fan EF-5 together with intake louver L-38 ventilate the Generator Room. A wall mounted thermostat controls operation. Controls are not tied into DDC system.
J.1.7.5 Exhaust fans EF-6 (two-speed), EF-7 (two-speed), EF-8 (two-speed), EF-9, EF-10, EF- 12, EF-13 and EF-14 together with intake louvers L-1 through L-4 ventilate the contractor and shop areas of Quad E. These systems are controlled through the DDC system in conjunction with the operation of AHU-12. When outdoor air temperature is below 55 degrees EF-6, 7 and 8 shall run at low speed and the other fans shall be off. When outdoor air temperature is above 55 degrees or if a combustible gas leak is detected, louvers L-1 through 4 shall open, EF-6, 7, and 8 shall run at high speed and EF-9, 10, 12, 13, and 14 shall run. EF-12 and louver L-8 ventilate the Tank Room. When space temperature is above 65 degrees or if a combustible gas leak has been detected L-8 shall open and EF-12 shall run.
J.1.7.6 Exhaust fan EF-11 together with intake louver L-9 ventilate the Fire Pump Room. A wall mounted thermostat controls operation. Controls are not tied into DDC system.
J.1.7.7 Exhaust fan EF-15 exhaust fumes and heat from the laundry area wash tanks. Fan operation is controlled by a local start/stop station. Interlock from DDC system shuts down fan if fan is running during unoccupied hours.
J.1.7.8 Exhaust fan EF-16 exhausts the restrooms of the Training Building. This fan shall run during occupied hours and an interlock from the DDC system shall shut this fan down during unoccupied hours.
J.1.7.9 Exhaust fan EF-17 exhausts the toilet areas of the Administration Building. This fan shall run during occupied hours and an interlock from the DDC system shall shut this fan down during unoccupied hours.
J-23
J.1.7.10 Exhaust fan EF-18 exhausts the fumes and mist from the Mask Test Equipment. Fan operation is controlled by a local start/stop station. Interlock from DDC system shuts down fan if fan is running during unoccupied hours.
J.1.7.11 Exhaust fan EF-19 exhaust the restroom of the Site Access Center. This fan is controlled from the light switch circuit.
J.1.7.12 Exhaust fan EF-20 together with intake louvers L-5 and L-6 ventilate the Holding Tank Room. A wall mounted thermostat controls operation. Controls are not tied into DDC system.
J.1.7.13 Exhaust fan EF-21 together with intake louver L-7 ventilate the Maintenance Equipment Storage Room. A wall mounted thermostat controls operation. Controls are not tied into DDC system.
J.1.7.14 Exhaust fan EF-22 exhaust the toilet area in the Quad E contractor area. This fan is controlled from the light switch circuit.
J.1.7.15 Supply fan SF-1 in conjunction with relief louver L-14 ventilate the Mechanical Room of the Administration Building. Fan is two speed with wall mounted two stage thermostat controlling operation. Controls are not tied into DDC system.
J.1.7.16 Supply fan SF-2 in conjunction with relief louver L-15 ventilate the Storage Room of the Administration Building. Fan is two speed with wall mounted two stage thermostat controlling operation. Controls are not tied into DDC system.
J.1.7.17 Supply fans SF-3 through SF-7 with their respective filter section F-18 through F-22 in conjunction with relief louvers L-20 through L-37 ventilate the Quad C and D Interstitial Areas of the Training Building. Fans are two speed with wall mounted two stage thermostats controlling operation. Only tie-in to DDC system is for Supply Fans SF-3, 4, and 5 which shall go into emergency high speed operation if a combustible gas leak has been detected.
J.1.7.18 Supply fan SF-8 in conjunction with relief hood AH-1 ventilate the Autoclave Room.
Fan is two speed with wall mounted two stage thermostat controlling operation. Controls are not tied into DDC system.
J-24
Exhibit 1.7: Facility Ventilation System Equipment
EF-23
Combustion Air Exhaust Removal Exhausto Mech Room CASV315
VFD-P3
Variable Frequency Drive Toshiba Mech Room Q-Flow Saver
VFD-P4
Variable Frequency Drive Toshiba Mech Room Q-Flow Saver
VS-AH-1 Air Hood Penn Ventilator Roof Quad E Airette Gravity 36x36
VS-AH-2 Air Hood Penn Ventilator Roof Quad E DR-12
VS-AH-3 Air Hood Penn Ventilator Roof Quad E DR-12
VS-E-10 Air Devices EH Price Quad C 610
VS-E-11 Air Devices EH Price Quad C 610
VS-E-12 Air Devices EH Price Quad C 610
VS-E-13 Air Devices EH Price Quad C 610
VS-E-14 Air Devices EH Price Quad C 610
VS-E-15 Air Louver EH Price Quad C SMD
VS-E-16 Air Louver EH Price Quad C SMD
VS-E-17 Air Louver EH Price Quad C SMD
VS-E-18 Air Louver EH Price Quad C SMD
VS-EF-1 Exhaust Fan Penn Ventilator Mech Room BF-24
VS-EF-10 Exhaust Fan Penn Ventilator Waste Storage FX-16B
VS-EF-11 Exhaust Fan Penn Ventilator Fire Pump FX-11QL
VS-EF-12 Exhaust Fan Penn Ventilator Tank Room FX-8B
VS-EF-13 Exhaust Fan Penn Ventilator Receiving FX-18B
VS-EF-14 Exhaust Fan Penn Ventilator Receiving FX-18B
VS-EF-15 Exhaust Fan Penn Ventilator Cold Laundry FX-13B
VS-EF-16 Exhaust Fan Penn Ventilator Toilets Rms. 53, 58, FX-8B
VS-EF-17 Exhaust Fan Penn Ventilator Toilets Rms. 014, 01 SX-125BC
VS-EF-18 Exhaust Fan Penn Ventilator Mask Test Equip. FX-8B
VS-EF-19 Exhaust Fan Penn Ventilator Guard House Z6HL
VS-EF-2 Exhaust Fan Penn Ventilator Mech Room BF-24
VS-EF-20 Exhaust Fan Penn Ventilator Holding Tank FX-24B
VS-EF-21 Exhaust Fan Penn Ventilator Outside Storage FX-11QL
VS-EF-22 Exhaust Fan Penn Ventilator Toilet Rm. 089 26HL
VS-EF-3 Exhaust Fan Penn Ventilator Filter Room BF-36
VS-EF-4 Exhaust Fan Penn Ventilator Filter Room BF-36
VS-EF-5 Exhaust Fan Penn Ventilator Generator Room DFP-360-AK2
VS-EF-6 Exhaust Fan Penn Ventilator Shop Room 94 FX-16B
VS-EF-7 Exhaust Fan Penn Ventilator Storage Room 92 FX-16B
J-25
VS-EF-8 Exhaust Fan Penn Ventilator Receive Storage FX-16B
VS-EF-9 Exhaust Fan Penn Ventilator Waste Storage FX-16B
VS-F-18 Filter Housing Air Seal Interstitial
12-24X24 AAF
AmAir 300X 3HX2W
VS-F-19 Filter Housing Air Seal Interstitial
4-24X24 AAF AM
AIR 300X 1HX2W
VS-F-20 Filter Housing Air Seal Interstitial
4-24X24 AAF AM
AIR 300X 1HX2W
VS-F-21 Filter Housing Air Seal Interstitial
8-24X24 AAF AM
AIR 300X 2HX2W
VS-F-22 Filter Housing Air Seal Interstitial
8-24X24 AAF AM
AIR 300X 2HX2W
VS-L-1 Louver Ruskin Quad C ELC6375D
VS-L-10 Louver Ruskin Quad C ELC6375D
VS-L-11 Louver Ruskin Quad C ELF375DX
VS-L-12 Louver Ruskin Quad C ELF375DX
VS-L-15 Louver Ruskin Quad C ELF375DX
VS-L-16 Louver Ruskin Quad C ELF375DX
VS-L-17 Louver Ruskin Quad C ELF375DX
VS-L-18 Louver Ruskin Quad C ELF375DX
VS-L-19 Louver Ruskin Quad C ELF375DX
VS-L-2 Louver Ruskin Quad C ELC6375D
VS-L-20 Louver Ruskin Quad C ELF375DX
VS-L-21 Louver Ruskin Quad C ELF375DX
VS-L-22 Louver Ruskin Quad C ELF375DX
VS-L-23 Louver Ruskin Quad C ELF375DX
VS-L-24 Louver Ruskin Quad C ELF375DX
VS-L-25 Louver Ruskin Quad C ELF375DX
VS-L-26 Louver Ruskin Quad C ELF375DX
VS-L-27 Louver Ruskin Quad C ELF375DX
VS-L-28 Louver Ruskin Quad C ELF375DX
VS-L-29 Louver Ruskin Quad C ELF375DX
VS-L-3 Louver Ruskin Quad C ELC6375D
VS-L-30 Louver Ruskin Quad C ELF375DX
VS-L-31 Louver Ruskin Quad C ELF375DX
VS-L-32 Louver Ruskin Quad C ELF375DX
VS-L-4 Louver Ruskin Quad C ELC6375D
VS-L-5 Louver Ruskin Quad C ELC6375D
VS-L-6 Louver Ruskin Quad C ELC6375D
VS-L-7 Louver Ruskin Quad C ELC6375D
VS-L-8 Louver Ruskin Quad C ELC6375D
VS-L-9 Louver Ruskin Quad C ELC6375D
J-26
VS-SF-1 Supply Fan Penn Ventilator Mech Rm BF-24
VS-SF-2 Supply Fan Penn Ventilator Storage Rm BF-24
VS-SF-3 Supply Fan Barry Blower Interstitial TUB-402
VS-SF-4 Supply Fan Penn Ventilator Interstitial REX-27B
VS-SF-5 Supply Fan Penn Ventilator Interstitial REX-27B
VS-SF-6 Supply Fan Penn Ventilator Interstitial REX-33B
VS-SF-7 Supply Fan Penn Ventilator Interstitial REX-33B
VS-SF-8 Supply Fan Penn Ventilator Auto Clave Rm BF-24
J-27
Technical Exhibit 1.8 Terminal Heating System and Equipment
J.1.8.1 Unit heaters provide heat to offset heat loss from exterior exposures and infiltration. Wall mounted thermostats control operation. Controls are not tied into DDC system. See Table below for unit heater location by area served.
PLAN MARK AREA SERVED
UH-1 & UH-2 Filter Room UH-3 & UH-4 Holding Tank Room UH-5 Generator Room UH-7 Service Gallery Quad E UH-9 & UH-10 Decon. Waste Storage UH-11 Fire Pump Room UH-12 Tank Room UH-13 & UH-14 Receiving/Disposal/Staging Area UH-15 Mech. Room - Admin. Building UH-16 Storage Room - Admin. Building UH-17 Break Room Quad E UH-18 Maint. Equip. Storage Area Quad E UH-19 through UH-32 Interstitial Space UH-33 Autoclave Room
J.1.8.2 Cabinet unit heaters provide heat to offset heat loss from exterior exposures and infiltration in building entry vestibules. Wall mounted thermostats control operation. Controls are not tied into DDC system. See Table below for cabinet unit heater location by area served.
PLAN MARK AREA SERVED
CUH-1 Vestibule 001 - Admin. Building CUH-2 Vestibule 013 - Admin. Building CUH-3 Vestibule 028 - Training Building CUH-4 Vestibule 001 - Admin. Building
Tag Number Equipment Name Manufacturer Model Number
Technical Exhibit 1.8: Terminal Heating System Equipment
TH-CUH-1 Cabinet Unit Heater McQuay TSF061G
TH-CUH-2 Cabinet Unit Heater McQuay TSF061G
TH-CUH-3 Cabinet Unit Heater McQuay TSF061G
TH-CUH-4 Cabinet Unit Heater McQuay TSF061G
TH-UH-1 Unit Heater McQuay UHH-062B
TH-UH-10 Unit Heater McQuay UHH-028B
TH-UH-11 Unit Heater McQuay UHH-028B
TH-UH-12 Unit Heater McQuay UHH-044B
TH-UH-13 Unit Heater McQuay UHH-062B
TH-UH-14 Unit Heater McQuay UHH-062B
J-28
Technical Exhibit 1.8 Terminal Heating System and Equipment
Technical Exhibit 1.8: Terminal Heating System Equipment
TH-UH-15 Unit Heater McQuay UHH-058B
TH-UH-16 Unit Heater McQuay UHH-058B
TH-UH-17 Unit Heater McQuay UHH-028B
TH-UH-18 Unit Heater McQuay UHH-044B
TH-UH-19 Unit Heater McQuay UHH-044B
TH-UH-2 Unit Heater McQuay UHH-062B
TH-UH-20 Unit Heater McQuay UHH-044B
TH-UH-21 Unit Heater McQuay UHH-044B
TH-UH-22 Unit Heater McQuay UHH-044B
TH-UH-23 Unit Heater McQuay UHH-044B
TH-UH-24 Unit Heater McQuay UHH-044B
TH-UH-25 Unit Heater McQuay UHH-044B
TH-UH-26 Unit Heater McQuay UHH-044B
TH-UH-27 Unit Heater McQuay UHH-052B
TH-UH-28 Unit Heater McQuay UHH-052B
TH-UH-29 Unit Heater McQuay UHH-052B
TH-UH-3 Unit Heater McQuay UHH-044B
TH-UH-30 Unit Heater McQuay UHH-052B
TH-UH-31 Unit Heater McQuay UHH-052B
TH-UH-32 Unit Heater McQuay UHH-052B
TH-UH-33 Unit Heater McQuay UHH-052B
TH-UH-4 Unit Heater McQuay UHH-044B
TH-UH-5 Unit Heater McQuay UHH-044B
TH-UH-7 Unit Heater McQuay UHH-044B
TH-UH-9 Unit Heater McQuay UHH-028B
J-29
Technical Exhibit 1.9 Unitary Air Conditioning System and Equipment
J.1.9.1 Air conditioning unit ACU-1 is a packaged through the wall air conditioning unit which cools and heats the Control Room in Quad E. System uses self contained direct expansion system for cooling and electric heat for heating. System is provided with unit mounted controls for fan speed and staging of cooling and heating.
J.1.9.2 The split system which cools and heats the Guard house consists of a ceiling space mounted air handling unit, AHU-11, and an outdoor slab mounted air cooled condensing unit, ACCU-1. Cooling is provided by direct expansion and the heating is provided by electric heating coils located in AHU-11. A remote programmable, automatic changeover , dual set-point thermostat shall control the cooling and heating of the system.
AC-ACCU-1 Split system air cooled condensing unit McQuay BRNS060
AC-ACU-1 Packaged terminal through the wall AC unit McQuay MEK022
AC-AHU-11 Split system air handling unit McQuay AH20P
Technical Exhibit 1.9: Unitary Air Conditioning System Equipment
J-30
Technical Exhibit 1.10 Electrical System Equipment
Tag Number Equipment Name Manufacturer Location Model Number Remarks
Technical Exhibit 1.10: Electrical System Equipment
EL-ERP10 Panel board Unknown Quad B Rm 007 120/280V; 125A bus; 3520 total connected load (VA); 810 total demand load (VA)
EL-ERP6 Panel board Unknown Guard Office 120/280V; 225A bus; 34967 total connected load (VA);
16674 total demand load (VA)
EL-ERP7 Panel board Unknown Quad C Rm 039 120/280V; 225A bus; 43220 total connected load (VA);
21610 total demand load (VA)
EL-ERP8 Panel board Unknown Quad C Rm 039 120/280V; 225A bus; 49150 total connected load (VA);
24575 total demand load (VA)
EL-ERP9 Panel board Unknown Quad C Rm 031 120/280V; 125A bus; 31232 total connected load (VA);
11980 total demand load (VA)
EL-G1 Generator 600kW Katolight D600-FRX4
EL-G2 Generator Unknown
EL-IC-CP
Intercom system control panel
Bogen Quad C Rm 067A Multicom 2000
EL-LP1 Panel board Unknown Quad B Rm 007 277/480V; 125A bus; 26835 total connected load (VA);
24400 total demand load (VA)
EL-LP2 Panel board Unknown Quad C Rm 070 277/480V; 225A bus; 72460 total connected load (VA);
72460 total demand load (VA)
EL-LS1 Panel board Unknown Quad B Rm 007 277/480V; 125A bus; 4100 total connected load (VA);
3280 total demand load (VA)
EL-LS2 Panel board Unknown Quad C Rm 070 277/480V; 125A bus; 52222 total connected load (VA);
41778 total demand load (VA)
EL-LS3 Panel board Unknown Quad C Rm 070
Dimmer control panel;
277/480V; 125A bus; 12090 total connected load (VA);
12090 total demand load (VA)
EL-MCC-1 Motor Control Center General Electric
8000 (2 vert.
Sec.)
200 amp main switch
EL-MCC-2 Motor Control Center General Electric
8000 (7 vert.
Sec.)
600 amp main switch
EL-MCC-3 Motor Control Center General Electric
8000 (5 vert.
Sec.)
400 amp main switch
EL-MCC-4A Motor Control Center General Electric
8000 (2 vert.
Sec.)
400 amp main switch
EL-MCC-4B Motor Control Center General Electric
8000 (1 vert.
Sec.)
200 amp main switch
EL-MCC-5 Motor Control Center General Electric
8000 (7 vert.
Sec.)
600 amp main switch
EL-MSWB Main switchboard Unknown
EL-RP11 Panel board Unknown Quad C Rm 068 120/280V; 125A bus; 17013 total connected load (VA);
17013 total demand load (VA)
J-31
Technical Exhibit 1.10 Electrical System Equipment
Tag Number Equipment Name Manufacturer Location Model Number Remarks
Technical Exhibit 1.10: Electrical System Equipment
EL-RP1-1 Panel board Unknown Quad B Rm 007 120/280V; 225A bus; 55540 total connected load (VA);
27770 total demand load (VA)
EL-RP1-2 Panel board Unknown Quad B Rm 007 120/280V; 225A bus; 26190 total connected load (VA);
13095 total demand load (VA)
EL-RP2-1 Panel board Unknown Quad C Rm 070 120/280V; 225A bus; 42560 total connected load (VA);
21280 total demand load (VA)
EL-RP2-2 Panel board Unknown Quad C Rm 070 120/280V; 225A bus; 11512 total connected load (VA);
5756 total demand load (VA)
EL-RP3 Panel board Unknown Quad C Rm 070 120/280V; 225A bus; 13916 total connected load (VA);
6958 total demand load (VA)
EL-RP4 Panel board Unknown Quad D Rm 077 120/280V; 125A bus; 5260 total connected load (VA);
4208 total demand load (VA)
EL-RP5-1 Panel board Unknown Quad E Rm 097 120/280V; 225A bus; 29323 total connected load (VA);
16322 total demand load (VA)
EL-RP5-2 Panel board Unknown Quad E Rm 097 120/280V; 225A bus; 23643 total connected load (VA);
16322 total demand load (VA)
EL-T1 Dry type transformer Unknown Quad B Rm 007
EL-T11 Dry type transformer Unknown Quad C Rm 068
EL-T13 Dry type transformer Unknown Quad C Rm 070
EL-T14A Dry type transformer Unknown Quad D Rm 077
EL-T14B Dry type transformer Unknown Quad D Rm 077
EL-T2 Dry type transformer Unknown Quad C Rm 070
EL-T3 Dry type transformer Unknown Quad C Rm 070
EL-T4 Dry type transformer Unknown Quad D Rm 077
EL-T5 Dry type transformer Unknown Quad E Rm 097
EL-T7 Dry type transformer Unknown Quad C Rm 039
EL-T8 Dry type transformer Unknown Quad B Rm 007
EL-T9 Dry type transformer Unknown Quad C Rm 039
J-32
Technical Exhibit 1.11 Sewer System Equipment
Tag Number Equipment Name Manufacturer Serial Number Model Number Remarks
SS-FM-C
Force mains -contaminated
Unknown
SS-FM-NC
Force mains non-contaminated
Unknown
SS-LS Lift station Unknown
SS-LSP-1 Lift station pump Unknown
SS-LSP-1-MTR Lift station pump motor Unknown
SS-LSP-2 Lift station pump Unknown
SS-LSP-2-MTR Lift station pump motor Unknown
SS-SP-1A Submersible pump Gould LDL2034
Duplex pumps w/alternation thru building control system - 4 float switches; Lab storage room
SS-SP-1A-MTR Sump pump motor Unknown
SS-SP-1B Sump pump Gould
SS-SP-1B-MTR Sump pump motor Unknown
SS-SP-2 Submersible pump Gould LDL2034 Simplex operation - 3 float switches
SS-SP-2-MTR Sump pump motor Unknown
SS-SP-3 Submersible pump Gould LDL2034 Simplex operation - 3 float switches
SS-SP-3-MTR Sump pump motor Unknown
SS-SP-4A Submersible pump Gould LDL2034
Training Bay 8; Duplex pumps w/alternation thru building control system - 4 float switches
SS-SP-4A-MTR Sump pump motor Unknown
SS-SP-4B Sump pump Gould
SS-SP-4B-MTR Sump pump motor Unknown
SS-SP-5 Submersible pump Gould LDL2034 Waste Containment Rm;Simplex operation - 3 float switches
SS-SP-5-MTR Sump pump motor Unknown
SS-SP-6 Submersible pump Gould LDL2034 Equipment Destruction Rm; Simplex operation - 3 float switches
SS-SP-6-MTR Sump pump motor Unknown
WS-T1 Waste Tank
WS-T1-AP1-ENA Agitation Pump Ingersoll Dresser
1297-1717B
WS-T1-AP1-MTR Agitation pump motor Unknown
WS-T1-AP2-MTR Agitation pump motor Unknown
WS-T1…