| CLEARANCE MATRIX FOR TYPICAL FORT CARSON UNDERGROUND UTILITIES | |||||||||
| All separations shown are the clear horizontal distance between two objects measured surface to surface (All dimensions are in feet) | |||||||||
| TYPE OF UTILITY | Potable Water | Non-Potable Water | Wastewater | Storm Sewer | Gas Main | Gas Service | Primary Electric | Secondary Electric | Communication Lines |
| Potable Water | 10 | 10 | 10 | 6 | 3 | 10 | 10 | 10 | |
| Non-Potable Water | 10 | 10 | 10 | 6 | 3 | 10 | 10 | 10 | |
| Wastewater | 10 | 10 | 5 | 6 | 3 | 10 | 5 | 5 | |
| Storm Sewer | 10 | 10 | 5 | 6 | 3 | 10 | 5 | 5 | |
| Gas Main | 6 | 6 | 6 | 6 | 3 | 6 | 6 | 6 | |
| Gas Service | 3 | 3 | 3 | 3 | 3 | 3 | 1 | 1 | |
| Primary Electric | 10 | 10 | 10 | 10 | 6 | 3 | 1 | 1 | |
| Secondary Electric | 10 | 10 | 5 | 5 | 6 | 1 | 1 | 1 | |
| Communication Lines | 10 | 10 | 5 | 5 | 6 | 1 | 1 | 1 | |
| CLEARANCE MATRIX FOR TYPICAL FORT CARSON UNDERGROUND UTILITY CROSSINGS | |||||||||
| All separations shown are the clear vertical distance between two objects measured surface to surface (All dimensions are in feet) | |||||||||
| TYPE OF UTILITY | Potable Water | Non-Potable Water | Wastewater | Storm Sewer | Gas Main | Gas Service | Primary Electric | Secondary Electric | Communication Lines |
| Potable Water | 1.5 | 1.5 | 1.5 | 1 | 1 | 1 | 1 | 1 | |
| Non-Potable Water | 1.5 | 1.5 | 1.5 | 1 | 1 | 1 | 1 | 1 | |
| Wastewater | 1.5 | 1.5 | 1.5 | 1 | 1 | 1 | 1 | 1 | |
| Storm Sewer | 1.5 | 1.5 | 1.5 | 1 | 1 | 1 | 1 | 1 | |
| Gas Main | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
| Gas Service | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
| Primary Electric | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
| Secondary Electric | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
| Communication Lines | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
| Any deviations from the above clearances must be approved by the DPW, Operations and Maintenance Division | |||||||||
| ** Note: A potable water service line (Less than 3-inch Diameter) may be placed in a common trench with non-potable water/sewer building service under the following condition. | |||||||||
| "The water service must be placed on a solid shelf excavated at one side of the common trench a minimum 1-foot over and above the top of the sewer | |||||||||
| pipe or non-potable water pipe plus 1-foot lateral separation." |