Solicitation_questions_27_NOV.pdf
PDF 94 KB Posted
- Attached to
- Bridge Cranes (Various Tons) Federal contract opportunity
- Solicitation number
- W911RQ-18-Q-0001
About this file
Attached questions and answers
View the file
Other files for this federal contract opportunity
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. The NSN numbers associated with each line item are non the “NSN” system, they are invalid.
Reference: NSN can probably be obtained from prior contracts.
Should I proceed with using the detailed description only provided in the bid for each line item.
2. Lifting Height
Reference: CLIN: 0001, 5 Tons, 10,000 (Lbs.) Bldg. 343‐1
3.2.17. Hook Height: 21’ 06”, NOTE: (Field verification can be performed)
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1
8.2.17 Hook Height: 22’ 06” (Min), NOTE: (Field verification can be performed)
Reference: CLIN 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.18. Hook Height: 24’ 0” (Min), NOTE: (Field verification can be performed)
Reference: CLIN 0004, 10 Tons, 20,000 (Lbs.). Bldg. 345‐1
23.5.18. Hook Height 22’0” (Min) NOTE: (Field verification can be performed)
Reference: CLIN 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity NOTE: Crane System Equipped With Two (02) Each: 15 Tons. 30,000 (Lbs. total capacity of 60,000lbs) Cranes.
33.3.1.11. Hoist Lift: 14’ 0” (Min), NOTE: (Field verification can be performed.)
3. Electrical Voltage.
Reference: CLIN: 0001, 5 Tons, 10,000 (Lbs.) Bldg. 343‐1.
3.2.28. Electrical Service: 208V, (Volts), 3P (3 Phase), 60 Hz.
Electrical Control Voltage: 110/120 Volts, Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1
8.2.28. Electrical Service: 208V, (Voltage), 3P (3 Phase), 60 Hz.
8.2.29. Electrical Control Voltage: 110/120 V, (Voltage), 1 Phase, 60 Hz.
Reference: CLIN 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.28. Electrical Service: 460 Volts, 3P (3 Phase), 60 Hz.
110/120 Volts, 1 Phase Control Voltage.
Reference: CLIN: 0004, 10 Tons, 20,000 (Lbs.). Bldg. 345‐1
23.5.29. Electrical Service: 460V, 3P, 60Hz, 110/120, 1 phase, control volts
Reference: CLIN 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
36. Crane System Electrical Requirement.
36.1. Crane System Electrical
3. Span
Reference: CLIN: 0001, 5 Tons, 10,000 (Lbs.) Bldg. 343‐1.
3.2.6. Span: (Centerline to Centerline): 28’ 2 5/8”, NOTE: (Field verification can be scheduled).
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1.
8.2.7. Span: (Centerline to Centerline): 27 ½”, NOTE: (Field verification can be scheduled).
Reference: CLIN 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.7. Span: (Centerline to Centerline): 38’ (Feet)
NOTE: (Field verification can be performed).
Reference: CLIN: 0004, 10 Tons, 20,000 (Lbs.). Bldg. 345‐1
23.5.7. Span: (Centerline to Centerline): 21” 5 5/8” (Existing Rail)
Reference: CLIN 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
33.2.1.3. Bridge Span: 41’ 0”
NOTE: Runway Span, (Field verification can be scheduled)
32.1.3. The existing tactical facility lowest point of obstruction has been determined to be approximately 18’ 4”
4. Remote Control or Wireless Control
Reference: CLIN: 0001, 5 Tons, 10,000 (Lbs.)
3.2.26. Bridge Controls: Remote/Radio
3.2.27. Remote Radio: Portable (2 Each)
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1.
8.2.26. Bridge Controls: Remote/Radio
8.2.27. Remote Control: Portable (2 Each)
Reference: CLIN 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.26. Bridge Control: Remote/Radio
13.2.27. Remote Control: Portable, (2 Each)
Reference: CLIN: 0004, 10 Tons, 20,000 (Lbs.). Bldg. 345‐1
23.5.27. Bridge Controls: Remote/Radio
23.5.28. Remote Control: Portable, (2 Each)
Reference: CLIN 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
23.5.26. Bridge Controls: Remote/Radio
23.5.26. Remote Control: Portable, (2 Each)
5. What speed functions
3.2.9. Bridge Speed: 100 fpm (Steepless)
3.2.13. Hoist Speed: 2‐Speed, 10 & 20 fpm
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1
8.2.9. Bridge Speed: 100 fpm (Stepless)
8.2.13. Hoist Speed: 2‐Speed, 10 & 20 fpm, (Min)
Reference: CLIN 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.9. Bridge Speed: 100 fpm (Stepless)
13.2.13. Hoist Speed: 2‐Speed, 10 & 20 fpm, (Min)
23.5.9. Bridge Speed: 100 fpm (Stepless)
23.5.13. Hoist Speed: 2‐Speed, 10 & 20 fpm, (Min)
Reference: CLIN 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
33.2.1.4. Bridge Speed: 90 fpm (Stepless)
33.3.1.3. Trolley Speed: 65 fpm (Stepless)
5. Who is installing the runway and electrification?
Line Item # 1: Installation will be performed in house Line Item # 2: Installation will be performed in house Line Item # 3: Installation will be performed in house Line Item # 4: Installation will be performed in house Line Item # 5: Installation requested to be performed by contractor.
6. Length of runway, rail size to ordered?
3.2.7. Runway Rail, (Existing: ASCE, CW 40 (Lbs.)
3.2.2. Runway Type, (Existing: Concrete Constructed
NOTE: Site visit can be scheduled
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1
8.2.3 Runway Beam Support Columns, (Existing): 30’ (Lowest Point of Obstruction)
8.2.6. Runway Rail, (Existing): ASCE, CW 40 (Lbs.)
NOTE: Site visit can be scheduled
Reference: CLIN: 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.6. Runway Rail, (Existing): ASCE, C/W 40 (Lbs.)
13.2.2. Runway Type: (Existing): Structural Steel Constructed NOTE: A site visit can be scheduled.
23.5.6. Runway Rail, (Existing): ASCE, C/W 40 (Lbs.)
23.5.2. Runway type, (Existing): Concrete Constructed
Reference: CLIN: 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
33.1.7. Runway Rail: ASCE C/W 60 (Lbs.)
33.1.3. Crane Runway Type: Free‐Standing
33.1.5. Crane Runway Beam Length: 89’ 0” (Min)
7. Spec is calling for all cranes other than the 15Tons to be 208 volt class D. it’s unlikely we can get a class D in 208 volt. Is there an option for 230 volt?
Reference: CLIN, 0001, 5 Ton, 10,000 (Lbs.) BLDG: 343‐1
3.2.28. Electrical Service: 208V, 3P, 60 Hz, 110/120 Volts, 1 Phase, 60 Hz NOTE: Site visit can be performed to review existing facility crane electrification system.
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1
8.2.29 Electrical Service: 208 Volts, # Phase, 60 Hz.
8.2.29. Electrical Control Voltage: 110/120 Volts, 1 Phase, 60 Hz.
NOTE: Site visit can be scheduled to review existing facility crane electrification system.
Reference: CLIN: 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1
13.2.28. Electrical Service: 460 Volts, 3 Phase, 60 Hz. Control Voltage: 110/120 V, 1 Ph, 60 Hz.
NOTE: Site visit can be scheduled to review existing facility electrification system.
Reference: CLIN: 0004, 10 Tons, 20,000 (Lbs.). Bldg. 345‐1
23.5.29. Electrical Service: 460V, 3P, 60Hz, 110/120, 1 phase, control volts
Reference: CLIN: 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
36.1. Crane System Electrical Voltage: 460 Volts, 3 Phase, 60 Hz.
36.1.2. Crane System Electrical Control Voltage: 110/120 Volts, 1 Phase, 60 Hz.
36.1.3. Crane System Lock/ Out Tag /Out. Requirement.
NOTE: Site visit can be scheduled to review existing facility electrification system.
8. Can there be a site visit on the proposed 15‐Ton site where contractor installation will be required?
Reference: CLIN, 0001, 5 Ton, 10,000 (Lbs.) BLDG: 343‐1 NOTE: Site visit scheduled December 6, 2017 10:00 AM CST.
Reference: CLIN: 0002, 10 Tons, 20,000 (lbs.) Bldg. 401‐1 NOTE: Site visit scheduled December 6, 2017 10:00 AM CST.
Reference: CLIN: 0003, 20 Tons, 40,000 (Lbs.) Bldg. 412‐1 NOTE: Site visit scheduled December 6, 2017 10:00 AM CST.
Reference: CLIN: 0005, 15 Tons, 30,000 (Lbs.) 60,000 (Lbs.) Total Capacity
File details come from the government source that posted it.