GENERAL
REF. NO. SHEET TITLE
G-101 COVER SHEET
G-101A EXTERIOR RENDERING
G-101B EXTERIOR RENDERING
G-102 STANDARD ABBREVIATIONS
G-103 LEVEL 1 LIFE SAFETY PLAN
G-104 LEVEL 2 LIFE SAFETY PLAN
G-105 CODE SUMARY
SHEET TITLE
CIVIL
LANDSCAPE
SHEET TITLE
SHEET TITLE
ARCHITECTURAL / INTERIOR
SHEET TITLE
ELECTRICAL
SHEET TITLE
FIRE PROTECTION
A-101 VERTICAL ASSEMBLY TYPES
A-102 HORIZONTAL ASSEMBLY TYPES
A-103 AREA CALCULATION PLANS
A-111 DEMOLITION PLANS
A-112 DEMOLITION ELEVATIONS
A-201 REFERENCE FLOOR PLAN - LEVEL 1
A-202 REFERENCE FLOOR PLAN - LEVEL 2
A-203 ROOF PLAN
A-204 SOUND WALL PLANS
A-211 FLOOR PLAN - LEVEL 1 - AREA A
A-212 FLOOR PLAN - LEVEL 1 - AREA B
A-221 FLOOR PLAN - LEVEL 2 - AREA A
A-222 FLOOR PLAN - LEVEL 2 - AREA B
A-301 ENLARGED PLANS
A-302 ENTRY CANOPY PLANS AND DETAILS
A-303 ENTRY CANOPY SECTION AND DETAILS
A-304 ENLARGED PLANS - OML AND DATA
A-305 ENLARGED PLANS - TYPICAL EML CLASSROOM
A-401 BUILDING ELEVATIONS
A-402 BUILDING ELEVATIONS
A-403 BUILDING ELEVATIONS
A-501 BUILDING SECTIONS
A-502 BUILDING SECTIONS
A-503 BUILDING SECTIONS
A-504 BUILDING SECTIONS
A-601 WALL SECTIONS
A-602 WALL SECTIONS
A-603 WALL SECTIONS
A-604 WALL SECTIONS
A-621 EXTERIOR DETAILS
A-622 EXTERIOR DETAILS
A-623 EXTERIOR DETAILS
A-624 EXTERIOR DETAILS
A-625 MISCELLANEOUS DETAILS
A-626 DOOR DETAILS
A-627 MISCELLANEOUS DETAILS
A-628 ROOF DETAILS
A-629 MISCELLANEOUS DETAILS
A-630 AIR BARRIER DETAILS
A-701 DOOR SCHEDULE
A-702 DOOR AND WINDOW TYPES
A-703 SIGN LEGEND
A-801 STAIR ST1 PLANS AND SECTION
A-802 STAIR ST2 PLANS AND SECTION
A-803 STAIR ST3 PLANS AND SECTION
A-804 STAIR ST4 PLANS AND SECTIONS
I-211 INTERIOR FINISH PLAN - LEVEL 1
I-212 INTERIOR FINISH PLAN - LEVEL 2
I-213 ENLARGED FINISH FLOOR PLANS
I-221 FURNITURE FOOTPRINT PLAN - LEVEL 1
I-222 FURNITURE FOOTPRINT PLAN - LEVEL 2
I-223 ENLARGED FURNITURE PLANS
I-311 REFLECTED CEILING PLAN - LEVEL 1
I-312 REFLECTED CEILING PLAN - LEVEL 2
I-401 INTERIOR ELEVATIONS
I-402 INTERIOR ELEVATIONS
I-403 INTERIOR ELEVATIONS
I-404 INTERIOR ELEVATIONS - PLUMBING
I-405 INTERIOR ELEVATIONS
I-501 INTERIOR DETAILS
I-502 INTERIOR DETAILS - CASEWORK
I-601 INTERIOR SCHEDULES
C-001 CIVIL NOTES, LEGEND & ABBREVIATIONS
C-002 PROJECT AREA MAP
C-101 DEMOLITION, STAGING AND PROTECTION PLAN
C-102 EXCAVATION & VIBRO-COMPACTION PLAN
C-103 SITE PLAN
C-104 GRADING INDEX PLAN
C-105 GRADING & DRAINAGE PLAN
C-106 GRADING & DRAINAGE PLAN
C-107 GRADING & DRAINAGE PLAN
C-108 SIGNING, STRIPING & ELECTRICAL FIXTURE SITE PLAN
C-301 SITE SECTIONS
C-302 SITE SECTIONS
C-401 SERVICE UTILIDOR PLAN & PROFILE
C-402 COMMUNICATION CONDUIT PLAN & PROFILE
C-403 FIBER OPTIC CONDUIT PLAN & PROFILE
C-404 ELECTRICAL CONDUIT PLAN & PROFILE
C-501 CIVIL DETAILS
C-502 CIVIL DETAILS
C-503 CIVIL DETAILS
C-504 CIVIL DETAILS
C-505 CIVIL DETAILS
C-506 SERVICE UTILIDOR MANHOLE PLAN & SECTIONS, MANHOLE 751-1
C-507 SERVICE UTILIDOR AT MECHANICAL PIT PLAN & SECTIONS
C-508 STRUCTURAL NOTES
C-509 TYPICAL UTILIDOR DETAILS
C-510 TYPICAL MANHOLE DETAILS
C-511 MANHOLE 751-1 STRUCTURAL PLAN
C-512 MANHOLE 751-1 STRUCTURAL SECTIONS
C-513 MECHANICAL PIT DETAILS
C-514 UTILIDOR PIPE SUPPORT DETAILS
C-515 UTILIDOR PIPE SUPPORT DETAILS
L-101 SOILS & LAYOUT PLAN
L-102 LANDSCAPE PLAN
L-501 LANDSCAPE DETAILS
FA001 FIRE ALARM GENERAL NOTES
FA100 FIRE ALARM AND MASS NOTIFICATION I/O MATRIX
FA101 LEVEL 1 FIRE ALARM PLAN
FA102 LEVEL 2 FIRE ALARM PLAN
FP100 FIRE PROTECTION GENERAL NOTES
FP101 LEVEL 1 DESIGN DENSITY PLAN
FP102 LEVEL 2 DESIGN DENSITY PLAN
MECHANICAL
SHEET TITLE
M-001 LEGENDS AND ABBREVIATIONS
M-002 LEGENDS
M-003 PLUMBING SCHEDULES
M-004 HYDRONIC EQUIPMENT SCHEDULES
M-005 HYDRONIC TERMINAL SCHEDULES
M-006 VENTILATION EQUIPMENT SCHEDULES
M-007 VENTILATION TERMINAL UNIT SCHEDULES
M-008 SPACE DESIGN SCHEDULE
M-101 MECHANICAL DEMOLITION PLAN
M-201 UNDERFLOOR PLUMBING PLAN - AREA A
M-202 UNDERFLOOR PLUMBING PLAN - AREA B
M-211 FIRST FLOOR PLUMBING PLAN - AREA A
M-212 FIRST FLOOR PLUMBING PLAN - AREA B
M-221 SECOND FLOOR PLUMBING PLAN - AREA A
M-222 SECOND FLOOR PLUMBING PLAN - AREA B
M-231 ROOF PLUMBING PLAN - AREA A
M-232 ROOF PLUMBING PLAN - AREA B
M-301 RADIANT SLAB PLAN - AREA A
M-302 RADIANT SLAB PLAN - AREA B
M-311 FIRST FLOOR HYDRONIC HEATING PLAN - AREA A
M-312 FIRST FLOOR HYDRONIC HEATING PLAN - AREA B
M-313 FIRST FLOOR HYDRONIC COOLING PLAN - AREA A
M-314 FIRST FLOOR HYDRONIC COOLING PLAN - AREA B
M-321 SECOND FLOOR HYDRONIC HEATING PLAN - AREA A
M-322 SECOND FLOOR HYDRONIC HEATING PLAN - AREA B
M-323 SECOND FLOOR HYDRONIC COOLING PLAN - AREA A
M-324 SECOND FLOOR HYDRONIC COOLING PLAN - AREA B
M-411 FIRST FLOOR VENTILATION PLAN - AREA A
M-412 FIRST FLOOR VENTILATION PLAN - AREA B
M-421 SECOND FLOOR VENTILATION PLAN - AREA A
M-422 SECOND FLOOR VENTILATION PLAN - AREA B
M-501 ENLARGED FIRST FLOOR RESTROOM PLAN
M-502 ENLARGED SECOND FLOOR RESTROOM PLAN
M-503 ENLARGED OML PLANS
M-510 ENLARGED FIRST FLOOR MECHANICAL OVERALL PLAN
M-511 ENLARGED FIRST FLOOR MECHANICAL PLUMBING PLAN
M-512 ENLARGED FIRST FLOOR MECHANICAL HYDRONIC PLAN
M-513 ENLARGED FIRST FLOOR MECHANICAL VENTILATION PLAN
M-514 ENLARGED EXISTING MECHANICAL ROOM PLAN
M-515 ENLARGED EXISTING MECHANICAL ROOM PLAN
M-516 ENLARGED EXISTING MECHANICAL ROOM PLAN
M-521 ENLARGED SECOND FLOOR MECHANICAL PLAN
M-522 ENLARGED SECOND FLOOR MECHANICAL PLAN
M-601 OML ELEVATIONS
M-602 HYDRONIC HEATING ELEVATIONS
M-710 PLUMBING DIAGRAMS
M-711 PLUMBING DIAGRAMS
M-712 PLUMBING - TOILET ROOM ISOMETRICS
M-713 PLUMBING - TOILET ROOM ISOMETRICS
M-714 COMPRESSED AIR DIAGRAMS
M-720 STEAM PIPING DIAGRAM
M-721 HEATING GLYCOL DIAGRAM
M-722 CHILLED GLYCOL DIAGRAM
M-723 HYDRONIC TERMINAL UNIT PIPING DIAGRAMS
M-724 HYDRONIC CABINET UNIT HEATER PIPING DIAGRAMS
M-725 HEATING TERMINAL UNIT SCHEMATIC
M-726 COOLING TERMINAL UNIT SCHEMATIC
M-727 HEATING DETAILS
M-735 VENTILATION DETAILS
M-801 FIRST FLOOR PRESSURIZATION PLAN
M-802 SECOND FLOOR PRESSURIZATION PLAN
M-803 CONTROL SCHEMATICS
M-804 CONTROL SCHEMATICS
M-810 SEQUENCE OF OPERATION - GENERAL
M-811 SEQUENCE OF OPERATION - HYDRONIC HEATING
M-812 SEQUENCE OF OPERATION - HYDRONIC COOLING
M-813 SEQUENCE OF OPERATION - VENTILATION
M-814 SEQUENCE OF OPERATION - TERMINAL UNITS & MISC
M-901 ADDITION MECHANICAL ROOM PERSPECTIVE VIEWS
M-902 OML LAB PERSPECTIVE VIEWS
M-903 ADDITION FAN ROOM PERSPECTIVE VIEWS
M-904 EXISTING BUILDING MECHANICAL PERSPECTIVE VIEWS
E-001 LEGEND AND ABBREVIATIONS
ED101 SITE ELECTRICAL PLAN - DEMOLITION
ES101 SITE LIGHTING PLAN
ES102 SITE POWER PLAN
E-002 LUMINAIRE SCHEDULE
E-111 LIGHTING - LEVEL 1 - AREA A
E-112 LIGHTING - LEVEL 1 - AREA B
E-113 LIGHTING - LEVEL 2 - AREA A
E-121 POWER - LEVEL 1 - AREA A
E-122 POWER - LEVEL 1 - AREA B
E-123 POWER - LEVEL 2 - AREA A
E-131 POWER - LEVEL 1 - CONDUIT ROUTING
E-401 LARGE SCALE PLANS
E-501 GROUNDING DETAIL
E-502 DETAILS
E-503 HEAT TRACE DETAILS
E-601 ONE-LINE DIAGRAM - POWER
E-701 ELECTRICAL PANEL SCHEDULES
E-702 ELECTRICAL PANEL SCHEDULES
E-703 ELECTRICAL PANEL SCHEDULES
E-704 ELECTRICAL PANEL SCHEDULES
E-705 ELECTRICAL PANEL SCHEDULES
E-706 ELECTRICAL PANEL SCHEDULES
ES501 SITE ELECTRICAL DETAILS
ES502 ELECTRICAL DETAILS
SHEET TITLE
TELECOMMUNICATIONS
T-001 LEGEND AND ABBREVIATIONS
TD101 SITE TELECOM PLAN - DEMOLITION
TS101 SITE TELECOM PLAN
T-111 TELECOMMUNICATIONS - LEVEL 1 - AREA A
T-112 TELECOMMUNICATIONS - LEVEL 1 - AREA B
T-113 TELECOMMUNICATIONS - LEVEL 2 - AREA A
T-401 LARGE SCALE PLANS
T-501 TELECOM DETAILS
T-601 ONE-LINE DIAGRAMS TELECOM AND SECURITY
REF. NO.
REF. NO.
REF. NO.
REF. NO.
REF. NO.
REF. NO.
S-101 GENERAL STRUCTURAL NOTES AND INTERPRETATION OF
DRAWINGS
S-102 GENERAL STRUCTURAL NOTES
S-103 GENERAL STRUCTURAL NOTES
S-104 WIND PRESSURE ZONE SCHEDULES
S-105 WALL COMPONENT AND CLADDING WIND PRESSURE
ZONE ELEVATIONS
S-106 WALL COMPONENT AND CLADDING WIND PRESSURE
ZONE ELEVATIONS
S-107 WALL COMPONENT AND CLADDING WIND PRESSURE ZONE
ELEVATIONS - AREA B
S-108 ROOF COMPONENT AND CLADDING WIND PRESSURE ZONES
S-111 SPECIAL INSPECTION TABLES
S-112 SPECIAL INSPECTION TABLES
S-113 SPECIAL INSPECTION TABLES
S-121 TYPICAL DETAILS
S-122 TYPICAL DETAILS
S-123 TYPICAL DETAILS
S-124 TYPICAL DETAILS
S-131 SCHEDULES
S-132 SCHEDULES
S-133 SCHEDULES
S-134 SCHEDULES
S-201 REFERENCE FOUNDATION PLAN
S-202 FOUNDATION PLAN - AREA A
S-203 FOUNDATION PLAN - AREA B
S-204 SLAB PLAN
S-211 REFERENCE SECOND FLOOR/LOW ROOF FRAMING PLAN
S-212 SECOND FLOOR/LOW ROOF FRAMING PLAN - AREA A
S-213 SECOND FLOOR/LOW ROOF FRAMING PLAN - AREA B
S-221 REFERENCE ROOF FRAMING PLAN
S-222 ROOF FRAMING PLAN - AREA A
S-223 ROOF FRAMING PLAN - AREA B
S-301 BRACED FRAME ELEVATIONS
S-311 EXTERIOR WALL ELEVATIONS
S-312 EXTERIOR WALL ELEVATIONS
S-401 FOUNDATION DETAILS
S-402 FOUNDATION DETAILS
S-501 FRAMING DETAILS
S-502 FRAMING DETAILS
S-503 FRAMING DETAILS
S-504 FRAMING DETAILS
S-505 FRAMING DETAILS
S-601 BRACED FRAME DETAILS
S-602 BRACED FRAME DETAILS
S-603 BRACED FRAME DETAILS
SHEET TITLE
STRUCTURAL (CONTINUED)
REF. NO.
SHEET TITLE
SURVEY / MAPPING
V-101 EXISTING CONDITIONS
SHEET TITLE
GEOTECHNICAL
B-301 BORING LOGS 1 OF 6
B-302 BORING LOGS 2 OF 6
B-303 BORING LOGS 3 OF 6
B-304 BORING LOGS 4 OF 6
B-305 BORING LOGS 5 OF 6
B-306 BORING LOGS 6 OF 6
VOLUME 1 VOLUME 2
GENERAL
SHEET TITLEREF. NO.
G-101 COVER SHEET
SHEET TITLE
HAZARDOUS MATERIAL ABATEMENT
REF. NO.
H-101 GENERAL & SHEET NOTES AND QUANTITIES
H-102 ABATEMENT PLAN
HGFEDCBA
SCHEDULE OF DRAWINGS
EIE377 F-35A ADAL FIELD TRAINING DETACHMENT FACILITY
EIELSON AFB, ALASKA
CONTRACT NUMBER: W911KB-17-R-0002
DESIGN COMPLETE
US ARMY CORPS
OF ENGINEERS
ALASKA DISTRICT
Reference number:
W
K B
-1 -R
-0
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CONTRACT NO.
CONTRACTOR
STATE
Recom m ended:
Approved:
Date:
RESIDENT ENG
INEER
A L A
S K
A
J T
W
A S
S H
O W
N
:1
D ate
D escription
A ction
S ym
O
T S
E A T th49
OF
PR
G
SI T
E R
ER
E
D
AS
ALF
K A
S I ONA
L
ES
RA
E C T
C T
H I
E
IE
A F
-1
-6
-0
G E
N E
R A
L
ALASKA DISTRICT U.S. ARMY CORPS OF ENGINEERS
D E
S
IG
N C
O M
P L E
T E
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
Scott E. Brodt
No. 9194
G-101
C O
V E
R S
H E
E T
E
IE
F -3
A
A D
A L
F
IE
L D
T R
A
IN
IN
G
D E
T A
C H
M E
N T
E
IE
L S
O N
A F
B , A
L A
S K
A
-2
-2
D D
M P
C /S
E B
DESIGN COMPLETE
2-22-2017
G -1
VOLUME 2 - MECHANICAL / ELECTRICAL / FIRE PROTECTION
sbrodt Text Box sbrodt Typewritten Text
NOT USED
sbrodt Typewritten Text sbrodt Typewritten Text
V B C
F S
CONTROLS LEGEND
AVERAGE TEMPERATURE SENSOR
VFD
SELECTRIC ACTUATOR
S
P
COCO
M
HP
DP
H
COCOCARBON MONOXIDE
DIFFERENTIAL PRESSURE
SENSOR
MANUAL SWITCH
CARBON DIOXIDE
PRESSURE SENSOR
TEMPERATURE SENSOR
VARIABLE FREQUENCY DRIVE
HIGH-PRESSURE SWITCH
LT
LOW-TEMP SWITCH
HUMIDITY SENSOR
FIELD LEVEL CONTROLLER CTRL
BUILDING LEVEL CONTROLLER CTRL
PANEL
CONTROL POINT WIRING
BUILDING LEVEL NETWORK/
FIELD LEVEL NETWORK CABLE
ABBREVIATIONS
PIPING SYSTEM LEGEND
DUCT AND DUCT ACCESSORIES LEGEND
24" X 20" (+2)
24" X 20" (-2)
24" X 20"DUCT (1ST FIGURE, SIDE SHOWN
2ND FIGURE, SIDE NOT SHOWN)
DIRECTION OF FLOW
INSULATED DUCTWORK
DIMENSIONS = INTERIOR
FACE OF SHEET METAL
THICKNESS OF INSULATION
IN INCHES
LINED DUCTWORK
DIMENSIONS = INTERIOR
FACE OF SHEET METAL
THICKNESS OF LINING IN
INCHES
SUPPLY RETURN EXHAUST
FLAT OVAL DUCTWORK - X" X Y" FO
WHERE X = DIMENSION ON THE PAGE
AND Y = DIMENSION INTO THE PAGE
RECTANGULAR DUCTWORK - X" X Y"
WHERE X = DIMENSION ON THE PAGE
AND Y = DIMENSION INTO THE PAGE
ROUND DUCTWORK - X"ø
WHERE X = THE DIAMETER OF THE DUCT
RECTANGULAR MITERED ELBOW
WITH TRUNING VANES
RECTANGULAR ELBOW
DOWN (INTO THE PAGE)
RECTANGULAR ELBOW UP
(OUT OF THE PAGE)
ROUND RADIUS ELBOW
ROUND ELBOW DOWN
(INTO THE PAGE)
ROUND ELBOW UP (OUT OF THE PAGE)
FLAT OVAL GORED ELBOW
FLAT OVAL ELBOW UP
(OUT OF THE PAGE)
FLAT OVAL ELBOW DOWN (INTO THE PAGE)
FLEXIBLE DUCT CONNECTION
VOLUME DAMPER
BACKDRAFT DAMPER
MOTORIZED CONTROL DAMPER
DUCT SMOKE DETECTOR (PENDING)
FIRE DAMPER
SMOKE DAMPER
CEILING DIFFUSER
4-WAY BLOW
CEILING DIFFUSER
3-WAY BLOW
AIRFLOW IN DIRECTION OF ARROWS
CEILING DIFFUSER
2-WAY BLOW
AIRFLOW IN DIRECTION OF ARROWS
CEILING DIFFUSER
1-WAY BLOW
AIRFLOW IN DIRECTION OF ARROW
AIR TERMINAL FLOW ARROW LEGEND
NOTE:
RETURN, EXHAUST DEFFUSERS SIMILAR
3.
DETAIL IDENTIFICATION
DRAWING ON WHICH
DETAIL IS SHOWN
SECTION
IDENTIFICATION
DRAWING ON WHICH
SECTION IS SHOWN
A101
A A101
DETAIL SYMBOL
GENERAL
SECTION SYMBOL
ROOM NAME AND
NUMBER DESIGNATION
ROOM NAME
SHEET KEYNOTE
GENERAL SHEET NOTE
POINT OF CONNECTION
1/M-102A
DETAIL IDENTIFICATION
DRAWING ON WHICH
CONTINUATION OF VIEW IS
SHOWN
MATCHLINE VIEW REFERENCE
NORTH ARROW
NORTH
FINNED TUBE
DESIGNATION
LINEAL FEET
GPM
T-1
PLUMBING FIXTURE DESIGNATION, SEE
FIXTURE CONNECTION SCHEDULE
MECHANICAL TAGS
P-01
FT-1
16' 7
EQUIPMENT DESIGNATION,
SEE EQUIPMENT SCHEDULE
FINNED TUBE DESIGNATION
SEE FINNED TUBE SCHEDULE
UNIT HEATER
DESIGNATION
UH-1
UNIT HEATER DESIGNATION
SEE UNIT HEATER SCHEDULE
EQUIPMENT
DESIGNATION
FIXTURE
DESIGNATION
DIFFUSER / REGISTER / GRILLE TAG
SEE DIFFUSER, REGISTERS, &
GRILLES SCHEDULE
LOUVER TAG
SEE LOUVER SCHEDULE
SG-1
200 CFM
8"ø
GRD DESIGNATION
NECK SIZE
FLOW THROUGH GRD
EL-01
1000 CFM
24"x24"
CHILLED BEAM TAG
SEE ACTIVE CHILLED BEAM SCHEDULE
LOUVER
DESIGNATION
CHILLED BEAM
DESIGNATION
FLOW THROUGH LOUVER
CB-01
DUCT CONNECTION SIZE
AIR TERMINAL LEGEND
PLAN DESCRIPTION
LOUVER
SUPPLY AIR DIFFUSER
SQUARE NECK
WALL MOUNTED GRILLE
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
ELEVATION/
SECTION
VEHICLE EXHAUST HOSE
CHILLED BEAM
CEILING EXHAUST SNORKEL
SUPPLY AIR DIFFUSER-
ROUND NECK
US ARMY CORPS
OF ENGINEERS
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-001
LEG
EN
D
S AN
D
ABBR
EVATIO
N
S
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -001
C D
F
SYSTEM TYPE ABBREVIATION LINE TYPE
COMPRESSED AIR CA
CHILLED BEAM RETURN CBR
CHILLED BEAM SUPPLY CBS
CHILLER CONDENSER RETURN CDR
CHILLER CONDENSER SUPPLY CDS
STEAM CONDENSATE RETURN CR
DOMESTIC COLD WATER CW
GLYCOL COOLING RETURN GCR
GLYCOL COOLING SUPPLY GCS
GLYCOL HEATING RETURN GHR
GLYCOL HEATING SUPPLY GHS
DOMESTIC HOT WATER HW
RADIANT FLOOR HEATING RFH
STEAM ST
TRAP PRIMER TP
TEMPERED WATER TW
VENT V
SANITARY WASTE W
LF LINEAL FEET
LGT LEAVING GLYCOL TEMPERATURE
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MCA MAXIMUM CURRENT AMPACITY
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MOP MAXIMUM OVERCURRENT PROTECTION
NC NORMALLY CLOSED
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO. NUMBER
NPSH NET PUMP SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAT OUTSIDE AIR TEMPERATURE
OBVD OPPOSED BLADE VOLUME DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OSA OUTSIDE AIR
P&T PRESSURE AND TEMPERATURE
PD PRESSURE DROP
PDI PLUMBING AND DRAINAGE INSTITUTE
PH PHASE
POC POINT OF CONNECTION
PRDV PRESSURE REDUCING VALVE
PRV PRESSURE RELIEF VALVE
PW PUMPED WASTE
RA RETURN AIR
RPBP REDUCED PRESSURE ZONE BACKFLOW PREVENTER
RPM REVOLTIONS PER MINUTE
S/S START/STOP
SA SUPPLY AIR
SIM SIMILAR
SP STATIC PRESSURE
SPEC SPECIFICATIONS
SS STAINLESS STEEL
SWSI SINGLE WIDTH, SINGLE INLET
TA TRANSFER AIR
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UL UNDERWRITER'S LABORATORY
UON UNLESS OTHERWISE NOTED
V VOLTS
VAV VARIABLE AIR VOLUME
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VTR VENT THROUGH ROOF
W/ WITH
W/O WITHOUT
WB WETBULB
WCO WALL CLEAN OUT
WHA WATER HAMMER ARRESTOR
WPD WATER PRESSURE DROP
WRT WITH RESPECT TO
ø DIAMETER
% PERCENT
& AND
(E) EXISTING
@ AT
AFF ABOVE FINISHED FLOOR
AGT AVERAGE GLYCOL TEMPERATURE
APD AIR PRESSURE DROP
APPR APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASSOC ASSOCIATED
AUTO AUTOMATIC
BAL BALANCING
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTOR
C COMMON
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CIRC CIRCULATION
CO CLEAN OUT
CONT CONTINUATION, CONTINUED
CU COPPER
Cv VALVE COEFFICIENT
DB DECIBEL
DB DRYBULB
DDC DIRECT DIGITAL CONTROLS
DI DUCTILE IRON
DIA DIAMETER
DN DOWN
DWDI DOUBLE WIDTH, DOUBLE INLET
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG ETHYLENE GLYCOL
EGT ENTERING GLYCOL TEMPERATURE
ELEC ELECTRICAL
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FC FOWARD CURVED
FCO FLOOR CLEANOUT
FLA FULL LOAD AMPERAGE
FLEX FLEXIBLE
FM FORCED MAIN
FP FIRE PROTECTION
FPF FINS PER FOOT
FPI FINS PER INCH
FPM FEET PER MINUTE
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GFOI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GI GALVANIZED IRON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
ID INSIDE DIAMETER
IE INVERT ELEVATION
INSUL INSULATION
IPS IRON PIPE SIZE
LAT LEAVING AIR TEMPERATURE
UNITS ABBREVIATIONS
# POUNDS PER SQUARE INCH (STEAM PRESSURE)
A AMPS
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
CFM CUBIC FEET PER MINUTE
F DEGREES FAHRENHEIT
FPM FEET PER MINUTE
FT FEET
FT2 SQUARE FEET
FT WG FEET OF WATER GAUGE
GAL LIQUID GALLONS (US)
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HP HORSEPOWER
HR HOUR
HZ HERTZ
IN INCH
IN WG INCHES OF WATER GAUGE
KW KILOWATT
LB POUNDS
LF LINEAR FOOT
M MINUTES
MBH ONE THOUSAND BRITISH THERMAL UNITS PER HOUR
PH PHASE
PSI POUNDS PER SQUARE INCH
S SECONDS
V VOLTS
W WATTS
WG WATER GAUGE
S ym
A c tio n
D e sc rip tio n
D a te
EH
T
SD
T
SD
ELBOW, TURNED DOWN
ELBOW, TURNED UP
TEE, OUTLET DOWN
TEE, OUTLET UP
FLOW DIRECTION
CONCENTRIC REDUCER
ISOLATION VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
STRAINER
STRAINER W/ BLOWDOWN
PRESSURE TEMPERATURE TAP
("PETE'S PLUG")
BALANCE VALVE
MOTORIZED 2-WAY CONTROL VALVE
MOTORIZED 3-WAY CONTROL VALVE
RELIEF OR SAFETY VALVE
DRAIN ISOLATION VALVE AND
HOSE ADAPTOR
DRAIN ISOLATION VALVE AND
CAP
UNION
FLANGE CONNECTION
PIPE ANCHOR
PIPE GUIDE
METER
2-WAY TEMPERING VALVE
3-WAY TEMPERING VALVE
THERMOMETER
PRESSURE GAUGE W/
ISOLATION VALVE
PUMP - CIRC
M
SCHEMATIC PIPE FITTINGS & VALVES
PLUMBING LEGEND
S C
H
EM
AT
IC
LI
N E
P
LA
N
VI
EW
LI
N E
P
LA
N
VI
EW
E
LE
VA
TI
O N
SE
C
TI
O
N
HOSE BIBB
FLOOR CLEAN OUT
WALL CLEAN OUT
WATER HAMMER
ARRESTOR
PIPE FITTINGS LEGEND
S C
H
EM
AT
IC
LI
N E
VI
EW
E
LE
VA
TI
O N
SE
C
TI
O
N
PIPE ELBOW
PIPE ELBOW LONG RADIUS
TEE FITTING
TEE REDUCING SANATARY FITTING
TEE SANATARY FITTING
TEE REDUCING VENT FITTING
TEE VENT FITTING
P-TRAP FITTING
BEND FITTING
TRANSITION FITTING
LI
N E
VI
EW
CONCENTRIC REDUCER FITTING
BALL VALVE
BALANCE VALVE
MOTORIZED 2-WAY CONTROL
VALVE (SMALL DIAMETER)
MOTORIZED 3-WAY CONTROL
VALVE (LARGE DIAMETER)
PRESSURE REDUCING VALVE
FLANGED CHECK VALVE
SWING CHECK VALVE
OS&Y GATE VALVE
(FLANGED)
OS&Y GATE VALVE
(THREADED)
PIPE VALVES
1-
LI
N E
VI
EW
E
LE
VA
TI
O N
SE
C
TI
O
N
2-
LI
N E
VI
EW
S C
H
EM
A T
IC
ISOLATION VALVE
BUTTERFLY VALVE
DOUBLE CHECK VALVE
RELIEF OR SAFETY VALVE
2-WAY TEMPERING VALVE
CIRC PUMP
PIPE ACCESORY LEGEND
S C
H
EM
AT
IC
LI
N E
V
IE
W
E
LE
VA
TI
O N
SE
C
TI
O
N
FLEXIBLE PUMP CONNECTOR (CRV FLEX)
"Y" STRAINER
SEISMIC EXPANSION JOINT (PIPE)
F&T STEAM TRAP
BALANCE COCK
THERMOMETER
PRESSURE GAUGE
UNION
REDUCER
SUCTION DIFFUSER
"Y" STRAINER, WITH BLOWDOWN
FLANGE
LI
N E
V
IE
W
US ARMY CORPS
OF ENGINEERS
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-002
LEG
EN
D S
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -002
C D
F
S ym
A c tio n
D e sc rip tio n
D
US ARMY CORPS
OF ENGINEERS
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-003
PLU
M
BIN
G
SC
H
E D U
LES
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -003
C D
F
REVERSE OSMOSIS SCHEDULE
MARK DESCRIPTION
CAPACITY
(GPM)
ELECTRICAL DATA BASIS OF DESIGN
NOTESPOWER (A) VOLTAGE (V) PHASE MANUFACTURER MODEL
RO-01 HUMIDIFIER REVERSE OSMOSIS
WATER TREATMENT SYSTEM
1 5.5 120 1 DRI-STEEM RO-402 PROVIDE WITH PACKED DECHLORINATOR AND 88 GALLON PRESSURE TANK
PLUMBING FIXTURE SCHEDULE
UNIT TAG FIXTURE DESCRIPTION
ROUGH IN BASIS OF DESIGN
NOTESCOLD WATER HOT WATER TRAP WASTE VENT MANUFACTURER MODEL
DF-01 DUAL LEVEL WATER COOLER 3/4" - 1-1/4" 1-1/2" 1-1/2" ELKAY LZSTL8WS(VR)K WITH BOTTLE FILLER, VANDAL RESISTANT EEW-01 EMERGENCY EYEWASH 3/4" 3/4" 1-1/2" 2" 1-1/2" GUARDIAN G-1753-T PROVIDE WITH ASSE-1071 CERTIFIED TEMPERING VALVE. PROVIDE WITH 4" DEEP SEAL TRAP.
CW CONNECTION INDIATED IS FOR TEMPERING VALVE ONLY, HW CONNECTION IS FOR TEMPERING VALVE AND EEW FD-01 LIGHT DUTY FLOOR DRAIN - - 2" 2" 1-1/2" ZURN FD-2290-NH2-P- PROVIDE TRAP PRIMER CONNECTION FD-02 MEDIUM DUTY FLOOR DRAIN - - 2" 2" 1-1/2" ZURN Z554-P PROVIDE TRAP PRIMER CONNECTION FD-03 MEDIUM DUTY FLOOR DRAIN - - 3" 3" 1-1/2" ZURN Z554-P PROVIDE TRAP PRIMER CONNECTION FD-04 MEDIUM DUTY FLOOR DRAIN - - 4" 4" 2" ZURN Z554-P PROVIDE TRAP PRIMER CONNECTION
HB-01 DUAL TEMPERATURE HOSE BIB 3/4" 3/4" - - - ACORN ACORN ENGINEERING 8106
LV-01 SINGLE FAUCET LAVATORY 3/4" 3/4" 1-1/4" 1-1/2" 1-1/2" BRADLEY LVSD1 PROVIDE WITH SLOAN EAF-275-ISM FAUCET AND EAF-51 AERATOR LV-02 DOUBLE FAUCET LAVATORY 3/4" 3/4" 1-1/2" 2" 2" BRADLEY LVSD2 PROVIDE WITH SLOAN EAF-275-ISM FAUCET AND EAF-51 AERATOR LV-03 TRIPLE FAUCET LAVATORY 3/4" 3/4" 1-1/2" 2" 2" BRADLY LVSD3 PROVIDE WITH SLOAN EAF-275-ISM FAUCET AND EAF-51 AERATOR SK-01 SERVICE SINK 3/4" 3/4" 3" 3" 1-1/2" JUST MFG. B-33213 MOEN 8230 FAUCET FITTNG SK-02 TWO-COMPARTMENT BREAK SINK 3/4" 3/4" 1-1/2" 2" 1-1/2" JUST MFG. DL-ADA-2233-A-GR MOEN 8792 FAUCET FITTING TP-01 FLOOR DRAIN TRAP PRIMER 1/2" - - - - PRECISION PLMB MPB-500-115V COORDINATE WITH ELECTRICAL FOR POWER CIRCUIT UR-01 WALL MOUNTED URINAL 3/4" - - 2" 2" KOHLER K-4904-ET SLOAN 8186-0.5 FLUSH VALVE UR-02 ADA, WALL MOUNTED URINAL 3/4" - - 2" 2" KOHLER K-4904-ET SLOAN 8186-0.5 FLUSH VALVE
WB-01 RECESSED WALL BOX 1/2" - - - - GUY GRAY MIB1AB
WC-01 WALL MOUNTED WATER CLOSET 1" - - 4" 2" KOHLER K-4325 SLOAN 8111 1.28 FLUSH VALVE WC-02 ADA WALL MOUNTED WATER CLOSET 1" - - 4" 2" KOHLER K-4325 SLOAN 8111 1.28 FLUSH VALVE
AIR COMPRESSOR SCHEDULE
MARK DESCRIPTION
COMPRESSED AIR DATA COOLING DATA ELECTRICAL DATA
OPERATING
WEIGHT (LBS)
BASIS OF DESIGN
COMMENTS
DESIGN
CAPACITY
(CFM)
DESIGN
PRESSURE (PSI)
WORKING
PRESSURE
(PSI)
AIR RECEIVER
(GAL)
ENTERING FLUID
TEMP (°F)
FLOW RATE
(GPM)
FLUID
PRESSURE
DROP (FT)
POWER
HP (KW) VOLTAGE (V) PHASE VFD MANUFACTURER MODEL
CA-01 WATER COOLED, VARIABLE
SPEED AIR COMPRESSOR
400 125 100 400 75 41 33.8 100 (92.8) 460 3 - 3014 INGERSOLL RAND R75N-X145 PROVIDE WITH INTEGRAL REFRIGERATED DRYER AND 10 MICRON FILTER
NOTE:
ALL SCHEDULED ITEMS REFLECT BASIS OF DESIGN MANUFACTURER AND MODEL ONLY.
CONTRACTOR TO SUBMIT BASIS OF DESIGN PRODUCT OR EQUAL, UNLESS OTHERWISE
NOTED ON DRAWINGS OR IN SPECIFICATIIONS.
STEAM GENERATOR SCHEDULE
UNIT TAG DESCRIPTION
STEAM CAPACITY
(LB/HR) FLUID TYPE
ELECTRICAL BASIS OF DESIGN
NOTES
POWER
(A)
VOLTAGE
(V) PHASE MANUFACTURER MODEL
SH-01 LOW PRESSURE STEAM GENERATOR FOR
HUMIDIFIER GRID
253 RO WATER 120 460 3 DRI-STEEM VAPORSTREAM
100-4
SUMP PUMP SCHEDULE
MARK LOCATION SERVICE
FLOW
(GPM)
HEAD
(FT) FLUID TYPE RPM
ELECTRICAL BASIS OF DESIGN
NOTESPOWER (HP) VOLTAGE (V) PHASE VFD MANUFACTURER MODEL
SP-01 ELEVATOR ELEVATOR PIT SUMP 50 20 WATER SUBMERSIBLE 3450 1/2 115 1 No ZOELLER 153 PROVIDE AUTOMATIC SENSOR AND CONTROL SYSTEM TO EXCLUDE HYDROCARBONS FROM EFFLUENT STREAM (SEEWATER OR EQUAL)
TEMPERING VALVE SCHEDULE
UNIT TAG LOCATION DESCRIPTION LISTING
FLOW RATE
(GPM)
DISCHARGE
TEMPERATURE
(°F)
PRESSURE
DROP
(PSI)
BASIS OF DESIGN
NOTESMANUFACTURER MODEL
TV-01 WOMEN 211 LAVATORY SINK ASSE 1070-2004 1.0 110 5 LEONARD VALVE 370-LF
TV-01 LEONARD VALVE 370-LF
TV-02 MEN 209 LAVATORY SINK ASSE 1070-2004 1.5 110 5 LEONARD VALVE 370-LF
TV-03 MEN 113 LAVATORY SINK ASSE 1070-2004 1.0 110 5 LEONARD VALVE 370-LF
TV-04 WOMEN 114 LAVATORY SINK ASSE 1070-2004 0.5 110 5 LEONARD VALVE 370-LF
TV-05 OML 111 EMERGENCY FIXTURE ASSE 1071-2012 3.0 85 15 GUARDIAN G3807LF
TV-06 ENGINE TRAINING /
MAINTENANCE 110
EMERGENCY FIXTURE ASSE 1071-2012 3.0 85 15 GUARDIAN G3807LF
TV-07 MECHANICAL 104C EMERGENCY FIXTURE ASSE 1071-2012 3.0 85 15 GUARDIAN G3807LF
TV-08 FLSC 104B EMERGENCY FIXTURE ASSE 1071-2012 3.0 85 15 GUARDIAN G3807LF
ELECTRIC WATER HEATER SCHEDULE
UNIT TAG
WATER CONDITION HEATING ELEMENT
TANK SIZE
(GAL)
ELECTRICAL BASIS OF DESIGN
NOTES
COLD WATER TEMP
(°F)
HOT WATER TEMP
(°F)
RECOVERY
(GPH)
FIRST HOUR
RATING (GAL)
ELEMENT
CAPACITY
(W)
VOLTAGE
(V) PHASE MANUFACTURER MODEL
WH-01 40 140 18 98 80 4500 208 3 RHEEM ELD80
WH-02 40 140 6 36 30 1500 115 1 RHEEM EGSP30
S ym
A c tio n
D e sc rip tio n
D
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-004
H
YD
R O
N
IC
E Q U
IPM
EN
T SC
H
ED
U
LE S
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -004
C D
F
EXPANSION TANK SCHEDULE
MARK SYSTEM
VOLUME
(GAL)
ACCEPTANCE VOLUME
(GAL) PRESSURE (PSI)
BASIS OF DESIGN
COMMENTSMANUFACTURER MODEL
ET-01 HEATING - BUILDING 40 22 12 AMTROL ST-80V
ET-02 COOLING - EVAPORATOR 8 4 12 AMTROL ST-25V
ET-03 COOLING - CONDENSER 11 6 12 AMTROL ST-30V
ET-04 DOMESTIC - HOT WATER 4.0 2.0 50 AMTROL ST-12 NSF/ANSI 61 LISTED FOR POTABLE WATER ET-05 DOMESTIC - HOT WATER 2.0 0.9 50 AMTROL ST-5 NSF/ANSI 61 LISTED FOR POTABLE WATER
GLYCOL MAKEUP TANK SCHEDULE
MARK SERVICE FUILD
TANK ELECTRICAL BASIS OF DESIGN
NOTES
VOLUME
(GAL)
DIMENSIONS
(H" X DIA")
POWER
(A)
VOLTAGE
(V) PH MANUFACTURER MODEL
GMT-01 HEATING SYSTEM 60% EG 55 49 x 24 0.7 115 1 MEYERS QP7 LABEL TANK "60% ETHYLENE GLYCOL ONLY" , PROVIDE WITH BRASS PUMP IMPELLER GMT-02 COOLING SYSTEM 60% EG 55 49 x 24 0.7 115 1 MEYERS QP7 LABEL TANK "60% ETHYLENE GLYCOL ONLY" , PROVIDE WITH BRASS PUMP IMPELLER
CHILLER SCHEDULE
MARK DESCRIPTION
COOLING CAPACITY
(TONS)
EVAPORATOR COOLING EFFICIENCY
(kW/TON)
WORKING
REFRIGERANT
REFRIGERANT CHARGE
(LB)
OPERATING WEIGHT
(LBS)
EVAPORATOR CONDENSER ELECTRICAL DATA BASIS OF DESIGN
COMMENTSFLUID TYPE LWT (°F) FLUID FLOW (GPM) WPD (FT) EWT (°F) FLUID FLOW (GPM) WPD (FT) MCA (A) MOP (A) VOLTAGE (V) PHASE MANUFACTURER MODEL
CH-01 MODULAR, DIGITAL SCROLL,
WATER COOLED CHILLER
89.2 60% EG NPLV 17 (0.707) R-410A 104.4 4,400 45 270 17 93 221 8.3 182 225 460 3 CLIMACOOL (2) UCH050AF TWO MODULES WITH SINGLE POINT CONNECTIONS
FLUID COOLER SCHEDULE
MARK DESCRIPTION
TOTAL
CAPACITY
(MBH) FLUID TYPE LWT (°F)
FLUID FLOW
(GPM)
COIL COIL ELECTRICAL DATA BASIS OF DESIGN
COMMENTS
AMBIENT AIR TEMP
(°F)
FIN HEIGHT
(IN)
FIN LENGTH
(IN) ROWS
FACE AREA
(FT2) FAN QUANTITY
POWER
(HP)
VOLTAGE
(V) PHASE MANUFACTURER MODEL
DC-01 GLYCOL FLUID COOLER 1535 60% EG 93 221 83 90 270 6 168 10 1.5 460 3 COLMAC COIL AFV-90270-8106R-G-30-1.5-BT PROVIDE WITH BASIC CONTROL PANEL AND FAN CYCLING CONTROLS WITH A SINGLE POWER CONNECTION AT
DISCONNECT PROVIDED ON EQUIPMENT
NOTE:
ALL SCHEDULED ITEMS REFLECT BASIS OF DESIGN MANUFACTURER AND MODEL ONLY.
CONTRACTOR TO SUBMIT BASIS OF DESIGN PRODUCT OR EQUAL, UNLESS OTHERWISE
NOTED ON DRAWINGS OR IN SPECIFICATIIONS.
AIR SEPARATOR SCHEDULE
MARK SERVICE FLUID CONNECTION (IN) FLOW (GPM) MAX WPD (FT)
BASIS OF DESIGN
COMMENTSMANUFACTURER MODEL
AS-01 HEATING - BUILDING 60% EG 3 131 2 TACO 4903AD PROVIDE WITH AIR/DIRT SEPARATION AND REMOVABLE HEAD AS-02 COOLING - EVAPORATOR 60% EG 6 270 1 TACO 4906AD PROVIDE WITH AIR/DIRT SEPARATION AND REMOVABLE HEAD AS-03 COOLING - CONDENSER 60% EG 4 221 3 TACO 4904AD PROVIDE WITH AIR/DIRT SEPARATION AND REMOVABLE HEAD
CIRCULATOR PUMP SCHEDULE
UNIT TAG ASSOCIATED SYSTEM
PUMP ELECTRICAL
MANUFACTURER MODEL NOTESTYPE
DESIGN FLOW
RATE
(GPM)
DESIGN PUMP HEAD
(FT) PERCENT END OF CURVE
POWER
(HP)
VOLTAGE
(V) PHASE RPM CONTROLLER
CP-01A HEATING - BUILDING END SUCTION 150 81 50% 7.5 460 3 1750 VFD BELL & GOSSETT e-1510 2BD PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-01B HEATING - BUILDING END SUCTION 150 81 50% 7.5 460 3 1750 VFD BELL & GOSSETT e-1510 2BD PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-02A COOLING - CHILLER EVAPORATOR END SUCTION 270 86 50% 15 460 3 1750 VFD BELL & GOSSETT e-1510 3EB PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-02B COOLING - CHILLER EVAPORATOR END SUCTION 270 86 50% 15 460 3 1750 VFD BELL & GOSSETT e-1510 3EB PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-03A COOLING - CHILLER CONDENSER END SUCTION 221 58 50% 7-1/2 460 3 1750 VFD BELL & GOSSETT e-1510 2.5BB PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-03B COOLING - CHILLER CONDENSER END SUCTION 221 58 50% 7-1/2 460 3 1750 VFD BELL & GOSSETT e-1510 2.5BB PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-05 RADIANT MANIFOLD 1 WET ROTOR 6 18 -- 178 W 115 1 1750 ECM GRUNDFOS MAGNA1 32-100F PROVIDE WITH I/O PACKAGE FOR ALARM OUTPUT RELAY CP-06 RADIANT MANIFOLD 2 WET ROTOR 2 22 -- 614 W 115 1 1750 ECM GRUNDFOS MAGNA3 32-180F PROVIDE WITH I/O PACKAGE FOR ALARM OUTPUT RELAY CP-07 RADIANT MANIFOLD 3 WET ROTOR 8 22 -- 107 W 115 1 1750 ECM GRUNDFOS MAGNA 32-60F PROVIDE WITH I/O PACKAGE FOR ALARM OUTPUT RELAY CP-08 RADIANT MANIFOLD 4 WET ROTOR 4 18 -- 178 W 115 1 1750 ECM GRUNDFOS MAGNA1 32-100F PROVIDE WITH I/O PACKAGE FOR ALARM OUTPUT RELAY
CP-09A COOLING - ADDITION CHILLED BEAMS END SUCTION 66 54 78% 3 HP 460 3 1750 VFD BELL & GOSSETT e-1510 1.25BC PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-09B COOLING - ADDITION CHILLED BEAMS END SUCTION 66 54 78% 3 HP 460 3 1750 VFD BELL & GOSSETT e-1510 1.25BC PROVIDE WITH 60% ETHYLENE GLYCOL RATED SEALS (B&G OR EQUAL) CP-10 COOLING - EXISITING CHILLED BEAMS WET ROTOR 6 36 -- 614 W 115 1 1750 ECM GRUNDFOS MAGNA3 40-180 CP-11 COOLING - AIR COMPRESSOR CANNED ROTOR 57 45 -- 1436 W 208 3 1750 -- GRUNDFOS UPS 40-240
STEAM HEAT EXCHANGER SCHEDULE
MARK DESCRIPTION
SHELL SIDE TUBE SIDE BASIS OF DESIGN
NOTES
STEAM FLOW RATE
(LB/HR)
STEAM PRESSURE
(PSI)
FOULING
FACTOR
SHELL DIAMETER
(IN)
SHELL LENGTH
(FT) FLUID TYPE
FLUID FLOW
(GPM)
FLUID PRESSURE DROP
(FT H2O)
ENTERING FLUID TEMP
(°F)
LEAVING FLUID TEMP
(°F)
HEATING CAPACITY
(MBH)
FOULING
FACTOR NUMBER OF PASSES MANUFACTURER MODEL
HX-01 SHELL AND TUBE,
STEAM TO GLYCOL
2222 LB/HR 2 PSI 0.001 12 IN 6 FT 60% EG 177 GPM 8.48 FT H2O 150 180 2146 MBH 0.001 4 BELL & GOSSETT SU 12 8-4
S ym
A c tio n
D e sc rip tio n
D
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-005
H
YD
R O
N
IC
TER
M
IN
AL S C
H
ED
U
LES
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -005
C D
F
COMPUTER ROOM AIR CONDITIONER SCHEDULE
UNIT TAG SYSTEM TYPE
SPACE CONDITIONS AIR SIDE WATER SIDE HUMIDIFIATION SYSTEM ELECTRICAL BASIS OF DESIGN
NOTES
DRY BULB
TEMP
RELATIVE
HUMIDITY
AIR FLOW
(CFM)
EXTERNAL
STATIC
PRESSURE (IN
WC)
DISCHARGE
DIRECTION FLUID TYPE
TOTAL
CAPACITY FLUID FLOW
FLUID
PRESSURE
DROP
ENTERING
FLUID TEMP TYPE CAPACITY
MAX CURRENT
AMPACITY
MIN
OVERCURRENT
PROTECTION VOLTAGE PHASE
MANUFACTUR
ER MODEL
CRAC-01 COMPUTER ROOM AIR
CONDITIONER
75 °F 40 % 4800 CFM 0.20 DOWNFLOW 60% EG 89.2 MBH 20 GPM 25 FT 45 F STEAM - INFRARED 10.8 LB/HR 10.6 A 15 A 460 3 LIEBERT PW029 PROVIDE WITH MERV 8 FILTERS
CRAC-02 COMPUTER ROOM AIR
CONDITIONER
75 °F 40 % 4800 CFM 0.20 DOWNFLOW 60% EG 89.2 MBH 20 GPM 25 FT 45 F STEAM - INFRARED 10.8 LB/HR 10.6 A 15 A 460 3 LIEBERT PW029 PROVIDE WITH MERV 8 FILTERS
CRAC-03 COMPUTER ROOM AIR
CONDITIONER
75 °F 40 % 1200 CFM 0.00 - 60% EG 12.2 MBH 9 GPM 23 FT 58 F - - 2.8 A 15 A 208 1 LIEBERT DME044C
FINNED TUBE SCHEDULE
MARK
ENCLOSURE ELEMENT
FLUID
AVERAGE FLUID TEMP
(°F)
WATER
CAPACITY
(BTU/H/FT)
GLYCOL
DE-RATE
(BTU/H/FT)
ENTERING AIR
TEMP (°F)
BASIS OF DESIGN
NOTESTYPE GAUGE HEIGHT
FIN TUBE
MANUFACTURER MODELSIZE (INxIN) SPACING (FPF) MATERIAL DIAMETER ROWS MATERIAL FT-01 SLOPED TOP 14 14" 4-1/4 x 4-1/4 32 ALUMINUM 3/4" 1 COPPER 60% EG 170 1660 946 65 RITTLING FS5 INSTALL BARE FIN WITHIN ARCHITECTURAL ENCLOSURE.
FT-02 SLOPED TOP 14 24" 4-1/4 x 4-1/4 48 ALUMINUM 1" 1 COPPER 60% EG 170 2180 1243 65 RITTLING FS5 INSTALL BARE FIN WITHIN ARCHITECTURAL ENCLOSURE. RETURN PIPED IN
ENCLOSURE W/O FINS.
FT-03 SLOPED TOP 14 14" 4-1/4 x 4-1/4 32 ALUMINUM 3/4" 1 COPPER 60% EG 170 1660 946 65 RITTLING FS5 PROVIDE WITH MANUFACTURER'S ENCLOSURE.
NOTE:
ALL SCHEDULED ITEMS REFLECT BASIS OF DESIGN MANUFACTURER AND MODEL ONLY.
CONTRACTOR TO SUBMIT BASIS OF DESIGN PRODUCT OR EQUAL, UNLESS OTHERWISE
NOTED ON DRAWINGS OR IN SPECIFICATIIONS.
CONTROL VALVE SCHEDULE
UNIT TAG ASSOCIATED UNIT TYPE FLOW RATE
PRESSURE
DROP
(MINIMUM) FAILURE MODE NOTES
CA-01 AIR COMPRESSOR THREE-POSITION, MODULATING 40 GPM 3 FT LAST POSITION
CB-X CHILLED BEAM TWO-POSITION, MODULATING VARIES 3 FT CLOSED
CC-01 COOLING COIL THREE-POSITION, MODULATING 91 GPM 6 FT CLOSED
CUH-X CABINET UNIT HEATER TWO-POSITION, MODULATING VARIES 3 FT OPEN
DC-01 DRY COOLER THREE-POSITION, MODULATING 221 GPM 3 FT OPEN
FT-X FINNED TUBE TWO-POSITION, MODULATING VARIES 3 FT OPEN
HC-01 HEATING COIL THREE-POSITION, MODULATING 42 GPM 3 FT OPEN
PHC-01 PRE-HEAT COIL TWO-POSITION, MODULATING 83 GPM 4 FT OPEN
RH-X REHEAT COIL TWO-POSITION, MODULATING 1 GPM 3 FT LAST POSITION
RM-01 RADIANT MANIFOLD 1 THREE-POSITION, MODULATING 6 GPM 5 FT LAST POSITION
RM-02 RADIANT MANIFOLD 2 THREE-POSITION, MODULATING 2 GPM 5 FT LAST POSITION
RM-03 RADIANT MANIFOLD 3 THREE-POSITION, MODULATING 8 GPM 5 FT LAST POSITION
RM-04 RADIANT MANIFOLD 4 THREE-POSITION, MODULATING 4 GPM 5 FT LAST POSITION
UH-X UNIT HEATER TWO-POSITION, MODULATING VARIES 3 FT OPEN
RADIANT FLOOR ZONE SCHEDULE
MANIFOLD
TAG ASSOCIATED SPACE FLOOR AREA
HEATING
LOAD
NUMBER OF
LOOPS
TUBE
SPACING
TUBE
DIAMETER
MAXIMUM LOOP
LENGTH
MAXIMUM TUBE
PRESSURE DROP
AVERAGE FLUID
TEMPERATURE
ASSOCIATED
CIRCULATION PUMP
CIRCULATION
FLOW RATE
INJECTION FLOW
RATE
BASIS OF DESIGN
NOTESMANUFACTURER MODEL
RM-01 ESMT E101 2466 SQFT 41.3 MBH 6 12 IN 3/4 IN 500 FT 3.4 FT 94 F CP-05 6 GPM 2 GPM UPONOR TRUFLOW SEE MECHANICAL DETAILS FOR TUBE INBED DEPTH. ALL LOOPS
CONNECTED TO A SINGLE MANIFOLD SHALL HAVE LENGTHS WITHIN 10%
OF EACH OTHER FOR BALANCING.
RM-02 FLSC 104B 488 SQFT 3.3 MBH 2 12 IN 3/4 IN 500 FT 3.4 FT 91 F CP-06 2 GPM 1 GPM UPONOR TRUFLOW SEE MECHANICAL DETAILS FOR TUBE INBED DEPTH. ALL LOOPS
CONNECTED TO A SINGLE MANIFOLD SHALL HAVE LENGTHS WITHIN 10%
OF EACH OTHER FOR BALANCING.
RM-03 ENGINE TRAINING/MAINTENANCE 110 3674 SQFT 63.4 MBH 8 12 IN 3/4 IN 500 FT 3.4 FT 92 F CP-07 8 GPM 2 GPM UPONOR TRUFLOW SEE MECHANICAL DETAILS FOR TUBE INBED DEPTH. ALL LOOPS
CONNECTED TO A SINGLE MANIFOLD SHALL HAVE LENGTHS WITHIN 10%
OF EACH OTHER FOR BALANCING.
RM-04 AGE 112 947 SQFT 24 MBH 4 12 IN 3/4 IN 500 FT 3.4 FT 93 F CP-08 4 GPM 1 GPM UPONOR TRUFLOW SEE MECHANICAL DETAILS FOR TUBE INBED DEPTH. ALL LOOPS
CONNECTED TO A SINGLE MANIFOLD SHALL HAVE LENGTHS WITHIN 10%
OF EACH OTHER FOR BALANCING.
UNIT HEATER AND CABINET UNIT HEATER SCHEDULE
UNIT TAG AREA SERVED DESCRIPTION CAPACITY FLUID TYPE
ENTERING FLUID
TEMP
LEAVING FLUID
TEMP FLUID FLOW RATE FLUID PRESSURE DROP AIR FLOW POWER VOLTS PHASE MANUFACTURER MODEL NOTES
CUH-01 101 VESTIBULE RECESSED, WALL MOUNTED, INVERTED
FLOW
6.6 MBH 60% EG 180 °F 150 °F 1 GPM 2.3 FT 197 CFM 0.03 HP 115 1 TRANE FFNB0201
CUH-02 102C VESTIBULE RECESSED, WALL MOUNTED, INVERTED
FLOW
9.0 MBH 60% EG 180 °F 150 °F 1 GPM 2.3 FT 197 CFM 0.03 HP 115 1 TRANE FFNB0201
CUH-03 104A VESTIBULE RECESSED, WALL MOUNTED, INVERTED
FLOW
1.7 MBH 60% EG 180 °F 150 °F 1 GPM 2.3 FT 197 CFM 0.03 HP 115 1 TRANE FFNB0201
CUH-04 ST2 STAIR 2 WALL MOUNTED, INVERTED FLOW,
DUCTED INLET/OUTLET
6.5 MBH 60% EG 180 °F 150 °F 1 GPM 2.3 FT 197 CFM 0.03 HP 115 1 TRANE FFMB0201
CUH-05 ST3 STAIR 3 WALL MOUNTED, INVERTED FLOW,
DUCTED INLET/OUTLET
6.5 MBH 60% EG 180 °F 150 °F 1 GPM 2.3 FT 197 CFM 0.03 HP 115 1 TRANE FFMB0201
CUH-06 ST4 STAIR 4 FLOOR MOUNTED, DUCTED INLET/OUTLET 2.1 MBH 60% EG 180 °F 150 °F 1 GPM 2.3 FT 197 CFM 0.03 HP 115 1 TRANE FFCB0201
CUH-07 110 ENGINE
TRAINING/MAINTENANCE
WALL MOUNTED, INVERTED FLOW 18.7 MBH 60% EG 180 °F 150 °F 2 GPM 6.8 FT 210 CFM 0.13 HP 115 1 TRANE FFMB0201
UH-01 E101 ESMT CEILING SUSPENDED, HORIZONTAL BLOW 28.5 MBH 60% EG 180 °F 150 °F 4 GPM 0.29 FT 1100 CFM 1/20 HP 115 1 TRANE 72-S UH-02 112 AGE CEILING SUSPENDED, HORIZONTAL BLOW 28.5 MBH 60% EG 180 °F 150 °F 4 GPM 0.29 FT 1100 CFM 1/20 HP 115 1 TRANE 72-S UH-03 E103 MECHANICAL CEILING SUSPENDED, HORIZONTAL BLOW 20.0 MBH 60% EG 180 °F 150 °F 3 GPM 0.18 FT 900 CFM 1/20 HP 115 1 TRANE 60-S UH-04 115 ELECTRICAL CEILING SUSPENDED, HORIZONTAL BLOW 1.0 MBH 60% EG 180 °F 150 °F 1 GPM 0.02 FT 550 CFM 25 W 115 1 TRANE 36-S UH-05 116 MECHANICAL CEILING SUSPENDED, HORIZONTAL BLOW 11.6 MBH - - - - - 400 CFM 1/125 HP 230 1 TRANE UHEC-05 ELECTRIC HEATING ELEMENT UH-06 213 FAN CEILING SUSPENDED, HORIZONTAL BLOW 4.3 MBH 60% EG 180 °F 150 °F 1 GPM 0.02 FT 550 CFM 25 W 115 1 TRANE 36-S
S ym
A c tio n
D e sc rip tio n
D
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-006
VEN
TILATIO
N
EQ
U
IPM
EN
T SC
H
ED
U
L ES
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -006
C D
F
FAN SCHEDULE
MARK SERVICE
AIRFLOW
(CFM) ESP (IN. WC) TSP (IN. WC) TYPE DRIVE RPM
ELECTRICAL BASIS OF DESIGN
NOTESHP V HZ PH VFD MANUFACTURER MODEL
EF-01 AGE VEHICLE EXHAUST 1200 1.5 1.5 UTILITY BELT 1725 1 460 60 3 YES GREENHECK USF-312-10-BI-15 UL-705 LISTED, PROVIDE WITH FULLY WELDED HOUSING, AIRSTREAM TEMPERATURE = 400F
HRV-01 BUILDING OUTSIDE AIR VENTILATION 9650 1.21 SUPPLY
0.25 EXHAUST
4.02 SUPPLY
1.72 EXHAUST
FAN ARRAY DIRECT 1750 (2) 5 SUPPLY
(2) 3 EXHAUST
460 60 3 YES INNOVENT ERU-OU-PO-PL-9600-HW-HW-CW-HM-460 PROVIDE SEALED CABINET CAPABLE OF FULL WASHDOWN WITH DRAIN PANS AND LIGHTS IN
EACH SECTION
VF-01 MECHANICAL ROOM VENTILATION 4400 0 0.78 FC BELT 1031 2 460 60 3 YES GREENHECK LFC-65-FC-20 PROVIDE WITH MIXING BOX AND MERV 7 FILTERS VF-02 EXISTING MECHANICAL ROOM 1900 0 0.78 FC BELT 1031 1-1/2 460 60 3 YES GREENHECK LFC-45-FC-15 PROVIDE WITH MIXING BOX AND MERV 7 FILTERS
NOTE:
ALL SCHEDULED ITEMS REFLECT BASIS OF DESIGN MANUFACTURER AND MODEL ONLY.
CONTRACTOR TO SUBMIT BASIS OF DESIGN PRODUCT OR EQUAL, UNLESS OTHERWISE
NOTED ON DRAWINGS OR IN SPECIFICATIIONS.
AIR CURTAIN SCHEDULE
MARK TYPE CAPACITY CFM
ELECTRICAL BASIS OF DESIGN
NOTESA V PH MANUFACTURER MODEL
ACT-01 UNHEATED, INSECT CONTROL AIR CURTAIN 4800 FPM 14400 11.4 460 3 MARS AIR EP2 144-3 PROVIDE WITH DOOR LIMIT SWITCHES FOR AUTOMATIC OPERATION
DUCT CONSTRUCTION & TESTING SCHEDULE KEY
UNIT TAG
SUPPLY DUCT RETURN DUCT EXHAUST DUCT OUTSIDE AIR DUCT
TEST PRESSURE NOTESPRESSURE CLASS SEAL CLASS LEAK CLASS
PRESSURE
CLASS SEAL CLASS LEAK CLASS
PRESSURE
CLASS SEAL CLASS LEAK CLASS PRESSURE CLASS SEAL CLASS LEAK CLASS
EF-01 N/A N/A N/A N/A N/A N/A -2" A N/A N/A N/A -3"
HRV-01 2" A N/A N/A N/A -2" A 2" A 4"
VF-01 1" B 1" B 1" B B 2"
VF-02 B 1" B 1" B B 2"
FILTER SCHEDULE
UNIT TAG ASSOCIATED UNIT FILTER TYPE FRAME SIZE EFFICIENCY
AIRFLOW
(CFM)
PRESSURE DROP
(IN WC)
FACE VELOCITY
(FPM)
FACE AREA
(FT2) BASIS OF DESIGN NOTES
FINAL FILTER HRV-01 PLEATED 12" MERV 13 9650 0.55 405 23.9 CAMFIL FARR CAMSORB
PRE-FILTER VF-01 PLEATED 2" MERV 7 4400 0.30 310 14.4 CAMFIL FARR 30/30
PRE-FILTER VF-02 PLEATED 2" MERV 7 1900 0.30 310 6.1 CAMFIL FARR 30/30
SUMMER FILTER /
WINTER FILTER
HRV-01 PLEATED 2" MERV 7 9650 0.30 485 26.7 CAMFIL FARR 30/30
HEAT RECOVERY SCHEDULE
ASSOCIATED UNIT
OUTSIDE AIR FLOW
(CFM)
BYPASS
(CFM)
WINTER CONDITIONS SUMMER CONDITIONS MINIMUM
EFFECTIVENESS MANUFACTURER MODEL NOTESENTERING OAT (°F) ENTERING EAT (°F) ENTERING OAT (°F) ENTERING EAT (°F)
HRV-01 9650 9650 10 70 78 78 50% INNOVENT CUSTOM PROVIDED WITH HRV BY MANUFACTURER
HUMIDIFIER GRID SCHEDULE
UNIT TAG ASSOCIATED UNIT TYPE
AIR SIDE STEAM SIDE BASIS OF DESIGN
NOTESFLOW RATE ENTERING CONDITION LEAVING CONDITION
PRESSURE
DROP FLOW RATE MANUFACTURER MODEL
H-01 HRV-01 DISPERSION 9650 CFM 65 °F-DB, 0% RH 68 °F-DB, 40% RH 0.1 IN WC 253 LB/HR DRISTEEM ULTRASORB LV
COIL SCHEDULE
UNIT TAG DESCRIPTION
CAPACITY
ROWS
AIR SIDE WATER SIDE
NOTES
SENSIBLE
(MBH)
TOTAL
(MBH)
ENTERING TEMP
(°F)
LEAVING TEMP
(°F)
FLOW RATE
(CFM)
PRESSURE DROP
(IN WC)
ENTRING TEMP
(°F)
LEAVING TEMP
(°F)
FLOW RATE
(GPM)
PRESSU8RE DROP
(FT H2O) FLUID
CC-01 HRV-01 COOLING COIL 358 358 8 78 53 9650 0.61 45 55 67 8.90 60% EG COIL PROVIDED WITH HRV BY MANUFACTURER HC-01 HRV-01 HEATING COIL 528 528 2 33 68 9650 0.11 180 150 27 1.30 60% EG COIL PROVIDED WITH HRV BY MANUFACTURER
PHC-01 HRV-01 PRE-HEAT COIL 1032 1032 2 -40 33 9650 0.24 180 150 48 3.50 60% EG COIL PROVIDED WITH HRV BY MANUFACTURER
S ym
A c tio n
D e sc rip tio n
D
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-007
VEN
TILATIO
N
TE R
M
IN
AL U
N
IT SC
H
ED
U
LES
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -007
C D
F
VEHICLE EXHAUST SCHEDULE
UNIT TAG DESCRIPTION
HOSE PERFORMANCE
CONTROLS
BASIS OF DESIGN
NOTESSTYLE FLOW RATE PRESSURE DROP LENGTH DIAMETER
SERVICE
TEMPERATURE
MOUNTING
HEIGHT MANUFACTURER MODEL
VEH-01 VEHICLE EXHAUST
HOSE
OVERHEAD HOSE DROP
W/ WINCH
600 CFM 0.70 IN WC 15 FT 6 IN 850 F 15 FT MICROSWITCH ON/OFF VENTAIRE EXH PROVIDE WITH BLAST GATE AND DIESEL STACK ADAPTER
VEH-02 VEHICLE EXHAUST
HOSE
OVERHEAD HOSE DROP
W/ WINCH
600 CFM 0.70 IN WC 15 FT 6 IN 850 F 15 FT MICROSWITCH ON/OFF VENTAIRE EXH PROVIDE WITH BLAST GATE AND DIESEL STACK ADAPTER
1. PERFORMANCE INDICATED IS TYPICAL OF ALL DIFFUSERS FOR A GIVEN STYLE AND MODEL. SEE FLOOR PLANS FOR ACTUAL VOLUMES AND NECK SIZES
2. CONTRACTOR TO PROVIDE BORDER AND FRAME FOR EACH DIFFUSER TO ACCOMODATE MOUNTING LOCATIONS AND ARCHITECTURAL FINISHES.
3. COORDINATE INSTALLATION OF ALL CEILING MOUNTED DIFFUSERS WITH OTHER TRADES INCLUDING LIGHT FIXTURES, SPRINKLER HEADS, OCCUPANCY SENSORS, SPEAKERS, AND SECURITY DEVICES.
4. INSTALL DIFFUSERS SUCH THAT THE 100 FPM THROW LENGTH DOES NOT CONFLICT WITH AN OBSTRUCTION OR ANOTHER DIFFUSER THROW PATTERN.
5. PROVIDE OPPOSED BLADE VOLUME DAMPERS FOR ALL DIFFUSERS.
NOTES:
DIFFUSER, REGISTERS, & GRILLES SCHEDULE
MARK TYPE DESCRIPTION
SYSTEM
CLASSIFICATION NECK SIZE STATIC PRESSURE
DESIGN
AIRFLOW
THROW
(100 FPM) COLOR
BASIS OF DESIGN
COMMENTSMANUFACTURER MODEL
EG-01 RECTANGULAR, PERFORATED FACE DIFFUSER WITH SQUARE NECK,
24"x24" FACE FOR LAY-IN CEILINGS EXHAUST 12" x 12" -0.05 IN WC 575 CFM -- WHITE TITUS PAR
EG-02 RECTANGULAR, LOUVERED DIFFUSER WITH ROUND NECK, 24"x24"
FACE FOR LAY-IN CEILINGS, FOUR-WAY BLOW PATTERN
EXHAUST 12" ø -0.05 IN WC 390 CFM -- WHITE TITUS TDC-A4
EG-03 RECTANGULAR, LOUVERED WALL GRILLE, SINGLE DEFLECTION WITH
BLADES PARALLEL TO LONG DIMENSION
EXHAUST 12" x 12" -0.05 IN WC 440 CFM -- WHITE TITUS 355RL
SG-01 24X48 LOW-VELOCITY, TWO-WAY, RECTANGULAR SUPPLY DIFFUSER SUPPLY 12" ø 0.10 IN WC 575 CFM 3 FT WHITE TITUS TRITEC
SG-02 RECTANGULAR, LOUVERED WALL GRILLE, DOUBLE DEFLECTION,
WITH FRONT BLADE PARALLEL TO SHORT DIMENSION
SUPPLY 12" x 12" 0.10 IN WC 600 CFM 25 FT WHITE TITUS 301FL
SG-03 RECTANGULAR, LOUVERED DIFFUSER WITH ROUND NECK, 24"x24"
FACE FOR LAY-IN CEILINGS, TWO-WAY BLOW PATTERN
SUPPLY 12" ø 0.10 IN WC 400 CFM 12 FT WHITE TITUS TDC-S2
SG-04 RECTANGULAR, LOUVERED DIFFUSER WITH ROUND NECK, ONE-WAY
BLOW PATTERN
SUPPLY 12" ø 0.10 IN WC 400 CFM 25 FT WHITE TITUS TDC-S1
TG-01 RECTANGULAR, LOUVERED WALL GRILLE, SINGLE DEFLECTION WITH
BLADES PARALLEL TO LONG DIMENSION
TRANSFER 12" x 12" 0.05 IN WC 440 CFM -- WHITE TITUS 355RL
EXHAUST SNORKEL SCHEDULE
MARK DESCRIPTION
SNORKEL
CONTROLS
BASIS OF DESIGN
COMMENTSDESIGN FLOW PRESSURE DROP
HOSE
DIAMETER HOSE LENGTH MOUNTING STYLE MANUFACTURER MODEL
ES-01 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-02 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-03 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-04 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-05 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-06 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-07 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-08 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS ES-09 OML WORKSTATION FUME EXHAUST SNORKEL 450 CFM 0.33 IN WC 8 IN 15 FT CEILING MICROSWITCH ON/OFF NEDERMAN FX EXTRACTOR ARM PROVIDE HARD PIPE SNORKEL WITH ROTATABLE COUPLINGS
LOUVER SCHEDULE
UNIT TAG TYPE DESCRIPTION
AIR PROPERTIES PHYSICAL PROPERTIES BASIS OF DESIGN
NOTESAIR FLOW FACE VELOCITY
PRESSURE
DROP HEIGHT WIDTH MANUFACTURER MODEL
EL-01 HRV EXHAUST 9650 CFM 900 FPM 0.10 IN WC 66 IN 42 IN RUSKIN ELF6375DX PROVIDE WITH 1 INCH BY 1 INCH BIRDSCREEN EL-02 VF-01 EXHAUST 4400 CFM 900 FPM 0.10 IN WC 30 IN 48 IN RUSKIN ELF6375DX PROVIDE WITH 1 INCH BY 1 INCH BIRDSCREEN EL-03 AGE VEHICLE EXHAUST 2000 CFM 900 FPM 0.10 IN WC 30 IN 24 IN RUSKIN ELF6375DX PROVIDE WITH 1 INCH BY 1 INCH BIRDSCREEN EL-04 VF-02 EXHAUST 1900 CFM 900 FPM 0.10 IN WC 30 IN 24 IN RUSKIN ELF6375DX PROVIDE WITH 1 INCH BY 1 INCH BIRDSCREEN
VAV SCHEDULE
UNIT TAG MAX CFM MIN CFM RUNOUT STATIC
CONNECTION
SIZE
REHEAT COIL BASIS OF DESIGN
COMMENTSEAT D.B. LAT D.B. FLUID EWT (°F) FLOW (GPM)
CAPACITY
(MBH) FLUID PRESSURE DROP
MANUFACTUR
ER MODEL
VAV-01 4050 1215 0.25 IN WC INLET: 24" x 16"
OUTLET: 38" x 18"
55 °F 65 °F 60% EG 180 °F 3 45 1.5 TITUS DESV-40
VAV-02 4050 -- 0.25 IN WC INLET: 24" x 16" OUTLET: 38" x 18"
-- -- -- -- -- -- -- TITUS DESV-40
VAV-03 4000 -- 0.25 IN WC INLET: 24" x 16" OUTLET: 38" x 18"
-- -- -- -- -- -- -- TITUS DESV-40
VAV-04 2000 600 0.25 IN WC 14" 55 °F 65 °F 60% EG 180 °F 2.5 21.6 1.5 TITUS DESV-14
ACTIVE CHILLED BEAM SCHEDULE
UNIT TAG LOCATION QUANTITY
UNIT TYPE AIR PERFORMANCE COIL PERFORMANCE BASIS OF DESIGN
NOTESSTYLE WIDTH LENGTH
TOTAL
CAPACITY
PRIMARY AIR
FLOW
PRIMARY AIR
TEMPERATURE
PRIMARY AIR
PRESSURE
DROP
THROW (100
FPM)
COIL
CAPACITY FLUID TYPE
FLUID FLOW
RATE
ENTERING FLUID
TEMPERATURE
FLUID
PRESSURE
DROP MANUFACTURER MODEL
CB-01 107 OFFICE 1 CEILING 24 IN 8 FT 5537 BTU/HR 30 CFM 55 F 0.25 IN WC 4 FT 4790 BTU/HR 60% EG 2.1 GPM 57 F 3.9 FT TITUS CBAL TWO-WAY BLOW CB-02 106 MANAGER 1 CEILING 24 IN 4 FT 2219 BTU/HR 30 CFM 55 F 0.07 IN WC 4 FT 1472 BTU/HR 60% EG 0.5 GPM 57 F 1.2 FT TITUS CBAL TWO-WAY BLOW CB-03 104 OPEN OFFICE 4 CEILING 24 IN 8 FT 3657 BTU/HR 40 CFM 55 F 0.15 IN WC 4 FT 2661 BTU/HR 60% EG 0.5 GPM 57 F 0.3 FT TITUS CBAL TWO-WAY BLOW CB-04 104 OPEN OFFICE 8 CEILING 24 IN 8 FT 5831 BTU/HR 60 CFM 55 F 0.34 IN WC 6 FT 4336 BTU/HR 60% EG 0.7 GPM 57 F 0.5 FT TITUS CBAL TWO-WAY BLOW CB-05 105 CONFERENCE 2 CEILING 24 IN 8 FT 4039 BTU/HR 65 CFM 55 F 0.06 IN WC 4 FT 2420 BTU/HR 60% EG 0.6 GPM 57 F 0.4 FT TITUS CBAL TWO-WAY BLOW CB-06 E101 ESMT 9 SUSPENDED 24 IN 8 FT 2569 BTU/HR 27 CFM 55 F 0.09 IN WC 3 FT 1905 BTU/HR 60% EG 0.4 GPM 57 F 0.2 FT TITUS CBLE TWO-WAY BLOW CB-07 104B FLSC 3 CEILING 24 IN 5 FT 923 BTU/HR 35 CFM 55 F 0.02 IN WC 2 FT 300 BTU/HR 60% EG 0.3 GPM 57 F 0.1 FT TITUS CBAL TWO-WAY BLOW CB-08 102 COMMONS 6 CEILING 24 IN 7 FT 4967 BTU/HR 27 CFM 55 F 0.20 IN WC 4 FT 4303 BTU/HR 60% EG 0.6 GPM 57 F 0.3 FT TITUS CBAL ONE-WAY BLOW CB-09 102A LINK 2 CEILING 24 IN 8 FT 6309 BTU/HR 60 CFM 55 F 0.34 IN WC 6 FT 4814 BTU/HR 60% EG 1.0 GPM 57 F 1.2 FT TITUS CBAL TWO-WAY BLOW CB-10 110 ENGINE TRAINING 12 SUSPENDED 24 IN 5 FT 3808 BTU/HR 44 CFM 55 F 0.10 IN WC 4 FT 2718 BTU/HR 60% EG 1.7 GPM 57 F 2.2 FT TITUS CBLE TWO-WAY BLOW CB-11 203 EML CLASSROOM 4 CEILING 24 IN 4 FT 2018 BTU/HR 30 CFM 55 F 0.03 IN WC 2 FT 1271 BTU/HR 60% EG 0.7 GPM 57 F 2.3 FT TITUS CBAL TWO-WAY BLOW CB-12 204 EML CLASSROOM 4 CEILING 24 IN 4 FT 2031 BTU/HR 30 CFM 55 F 0.03 IN WC 2 FT 1284 BTU/HR 60% EG 0.7 GPM 57 F 2.5 FT TITUS CBAL TWO-WAY BLOW CB-13 205 EML CLASSROOM 4 CEILING 24 IN 4 FT 2429 BTU/HR 30 CFM 55 F 0.07 IN WC 4 FT 1682 BTU/HR 60% EG 0.7 GPM 57 F 2.7 FT TITUS CBAL TWO-WAY BLOW CB-14 206 EML CLASSROOM 4 CEILING 24 IN 4 FT 2429 BTU/HR 30 CFM 55 F 0.07 IN WC 4 FT 1682 BTU/HR 60% EG 0.7 GPM 57 F 2.7 FT TITUS CBAL TWO-WAY BLOW CB-15 207 EML CLASSROOM 4 CEILING 24 IN 4 FT 244 BTU/HR 30 CFM 55 F 0.07 IN WC 4 FT 1695 BTU/HR 60% EG 0.7 GPM 57 F 2.9 FT TITUS CBAL TWO-WAY BLOW CB-16 208 EML CLASSROOM 4 CEILING 24 IN 4 FT 1612 BTU/HR 30 CFM 55 F 0.03 IN WC 2 FT 865 BTU/HR 60% EG 0.3 GPM 57 F 0.4 FT TITUS CBAL TWO-WAY BLOW CB-17 102B HALLWAY 2 CEILING 24 IN 5 FT 1502 BTU/HR 27 CFM 55 F 0.03 IN WC 2 FT 827 BTU/HR 60% EG 0.3 GPM 57 F 0.6 FT TITUS CBAL TWO-WAY BLOW CB-18 201 BALCONY 2 CEILING 24 IN 2 FT 124 BTU/HR 25 CFM 55 F 0.14 IN WC 2 FT 937 BTU/HR 60% EG 0.4 GPM 57 F 0.9 FT TITUS CBAL TWO-WAY BLOW CB-19 202 HALLWAY 2 CEILING 24 IN 5 FT 1735 BTU/HR 34 CFM 55 F 0.11 IN WC 3 FT 1312 BTU/HR 60% EG 0.4 GPM 57 F 1.0 FT TITUS CBAL TWO-WAY BLOW
S ym
A c tio n
D e sc rip tio n
D a te
NOTE:
ALL SCHEDULED ITEMS REFLECT BASIS OF DESIGN MANUFACTURER AND MODEL ONLY.
CONTRACTOR TO SUBMIT BASIS OF DESIGN PRODUCT OR EQUAL, UNLESS OTHERWISE
NOTED ON DRAWINGS OR IN SPECIFICATIIONS.
ALASKA DISTRICT
Reference number:
HGFEDCBA
W 911K
B -17-R
-0002
A ppvd
Designed:
Drawn:
Reviewed:
Chief, Subm itted:
Chief, Date:
Dwg Scale:
Plot Scale:
File:
Drawing #:
CON TRACT NO.
CON TRACTOR
STATE
Rec om m ended:
Approved:
Date:
RESIDENT E NG
INEER
ALASKA
A S
S H
O W
N 1:1
A F-171-618-01
E
IE
377-
D
ESIG
N C
O M
PLETE
ISSU
ED
FO
R C
O N
STR
U
C
TIO
N
M
EC
H
AN
IC
A L
M-008
SPAC
E D
ESIG
N
SC
H
ED
U
LE
EIE377 F -35A AD
AL FIELD
TR
AIN
IN
G
D
ETAC
H M
EN
T
EIELS O
N
AFB, AL ASKA
DESIGN COMPLETE
2-22-2017
JC
JC
2-22-2017
M -008
C D
F
NOTE:
ALL SCHEDULED ITEMS REFLECT BASIS OF DESIGN MANUFACTURER AND MODEL ONLY.
CONTRACTOR TO SUBMIT BASIS OF DESIGN PRODUCT OR EQUAL, UNLESS OTHERWISE
NOTED ON DRAWINGS OR IN SPECIFICATIIONS.
SPACE DESIGN CONDITION SCHEDULE
SPACE NAME
SPA…