Government Answers to Industry Questions UPS.pdf
PDF 169 KB Posted
- Solicitation number
- W91151-24-Q-0030
About this file
This document contains the Government's answers to industry questions regarding a Solicitation for Uninterrupted Power Supply (UPS) Maintenance Support Services (Solicitation #W91151-24-Q-0030) issued by the Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood.
The key details are:
- The solicitation requires the contractor to provide initial preventative maintenance (PM), essential services, semi-annual service, and annual PM for UPS units in 4 buildings. This includes guaranteed 4-hour on-site emergency response 24/7, corrective labor and travel coverage, battery recycling, and reporting.
- The government provided details on the specific UPS models, number of batteries, and battery cabinet information for each building.
- The government clarified that this is a new requirement, not an incumbent contract.
- The government deleted provisions related to single jar battery replacement and full battery string replacement from the Statement of Work.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Government Answers to Industry Questions 04 September 2024
Question 1: Can your customer clarify number of strings, battery models and number of batteries for each UPS unit?
Answer 1:
BLDG# Number of Strings Battery Model Number of Batteries for Each UPS
13 _______1 string____ POWERWARE 9315-160 Model#130_ ___40___
422 _______1 string____ VERTIV LIEBERT 51X150BCAUHAS34 ___36___
36016 _______1 string____ EATON 9390-80 Model# 50___ __144_ _
2207 _______1 string___ EATON 9390-80 Model# 50___ _ 80____
Question 2: Can you provide the OEM and kVA rating for each UPS unit?
Answer 2:
BLDG# OEM kVA
13 _POWERWARE__________ _________130kVA_______
422 _VERTIV LIEBERT ________ _________150kVA_______
36016 _EATON________________ _________50kVA________
2207 _EATON________________ ________50kVA_________
Question 3: Please provide the accurate Make, Model Name, Model # and KVA size of all four (4) UPS systems. The information provided are not accurate model numbers, for example the Vertiv model number lists as a Power Distribution Unit (PDU) and not a UPS.
Answer 3:
BLDG# Make Model Name Model# KVA Size
13 _POWERWARE__ __9315-160__ _____130____ ___130kVA_
422 VERTIV LIEBERT _____EXM_____ 51X150BCAUHAS34 __150kVA_
36016 _ EATON ________ _____ 9390-80 ___ _______50____ __50kVA___
2207 _ EATON ________ _____ 9390-80 ___ _______50____ __50kVA___
Question 4: Would you be able to provide any pictures of the actual name plates for each UPS system, which would help decipher these units?
Answer 4: Yes, pictures attached.
Question 5: Please provide the quantity of battery cabinets, per UPS system and the quantity of batteries per cabinet per UPS
Answer 5:
BLDG# QTY of Battery Cabinets QTY of Batteries per cabinet
13 __________40_____________ _______1__________
422 _________36________ __ ____1_________
36016 _________144_______ ______1__________
2207 __________80_____________ _________1___________
Queston 6: Please confirm if there are any External Maintenance Bypass systems, per USP
Answer 6:
BLDG# External Maintenance Bypass If yes, Identify Yes or No
13 __________No_____________ ________________________
422 __________No_____________ ________________________
36016 __________No_____________ ________________________
2207 __________No_____________ ________________________
Queston 7: Please confirm if any of these UPS’s run in parallel
Answer 7: No, they run in series.
BLDG# Run in Parallel Yes or No
13 ___No, in series ________
422 ___No, in series ________
36016 ___No, in series ________
2207 ___No, in series ________
Question 8: For single jar battery replacement, is the cost of the battery billable to the government?
Answer 8: SOW has been updated. Paragraphs c and f deleted from SOW.
Question 9: For full battery string replacement, is this to be quoted separately on a time and material basis and invoiced separately (freight, labor, disposal, and battery cost), upon approval?
Answer 9: SOW has been updated. Paragraphs c and f deleted from SOW.
Question 10: Can you clarify number of strings for each UPS?
Answer 10: 1 string each battery.
BLDG# Number of Strings For each UPS
13 _______1 string_________
422 _______1 string_________
36016 _______1 string_________
2207 _______1 string_________
Question 11: Is there a manufacture and serial number for each unit?
Answer 11:
BLDG# Manufacturer Number Serial Number For Each UPS For Each UPS
13 ____9315 - 160_________ __EW293ZBA05_________
422 __51X150BCAUHAS34__ __M19D640020_________
36016 __TB0511A01120010___ ___EH362CBC05________
2207 __TB0511A01130010__ ___EJ033CBC01________
Question 12: Will the government please clarify if there is an incumbent providing service on this contract or is this level of effort a new need?
If there is an incumbent, can the government please provide the most recent contract award number & contract value?
Answer 12: This is a new requirement. Please complete the solicitation with the information that is provided in the SOW. If you have specific questions regarding the SOW, please submit them by the due date for questions provided in the updated solicitation.
File details come from the government source that posted it. Updated .