Questions and Answers.docx
DOCX document 13 KB Posted
- Solicitation number
- W90VN624R0002
About this file
This document contains a solicitation for elevator maintenance services on Osan Air Base in South Korea. The contractor will provide preventative maintenance and repair for elevators, auto doors, escalators, conveyor belts, and carousels located across the base. Services include monthly inspections, testing, preventative maintenance, and repairs performed according to standards from the American Society of Mechanical Engineers and original equipment manufacturers. The contractor must also conduct annual safety inspections on all vertical transportation equipment. The solicitation was issued by the Department of the Army Materiel Command Army Contracting Command for the objective of maintaining this equipment and ensuring operational safety. The estimated workload and locations of the equipment are included in an attached technical exhibit.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W90VN6-24-R-0002 P00002 Amended SOL 2.pdf | ||
| W90VN6-24-R-0002 Amended SOL.pdf | ||
| W90VN6-24-R-0002.pdf | ||
| TECHNICAL EXHIBIT 4.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Q1. Shall the offeror propose KRW "0" for CLIN 0002AA and 0002AB Housing Tower (211, 1014, 1015) for base year and then input prices from the 1st Option Year?
A1. CLIN 0002AA is an unpriced CLIN, please propose KRW “0” in the Housing Tower. CLIN 0002AB should be priced.
Q1.1. Shall the offeror propose price of 7 elevators installed at B499 and 1465 for CLIN 0003, and then propose price of 13 elevators from 1st Option Year?
A1.1. CLIN 0003 should be priced for 7 elevators. All following option years will be priced for 13 elevators.
Q2. We think that the standard of monthly PM is not clear (many and/or, and/or).
And we cannot understand the PWS paragraph “ASME and manufacturer’s specifications are mandatory while commercial practice of the ROK Government authorities and prevailing industry standards/regulations shall be coordinated with the COR”.
A2. Elevators undergo monthly PM and annual inspection as per ASME A17.1-2007 standards and manufacturer’s specifications. However, the COR may request compliance with the commercial practices of ROK Government authorities and prevailing industry standards/regulations depending on the circumstances.
Q3. We think that the standards of yearly inspection are not clear (many and/or, and/or).
And we cannot understand the PWS paragraph "ASME, AFI 91-230, Air force Consolidated Occupational Safety Instruction and manufacturer’s specifications are mandatory while commercial practice of the ROK Government authorities and prevailing industry standards/regulations shall be coordinated with the COR.".
A3. The standards for inspection require compliance with ASME and manufacturer’s specifications. Since this is an Air Force base, work must adhere to Air Force standards, including the Air Force Consolidated Occupational Safety Instruction (AFMAN) and AFI 91-230. Compliance with commercial practices of ROK Government authorities and prevailing industry standards/regulations may be requested by the COR if necessary.