ATCH 7. Question-Answer_Replace AC Systems B501, Maui HI.docx
DOCX document 831 KB Posted
- Attached to
- Replace AC Systems, Bldg 501, Maui, HI Federal contract opportunity
- Solicitation number
- W50SLF25RA007
- Issued by
- Department of the Army National Guard
About this file
This document is a Questions and Answers attachment for Solicitation W50SLF25RA007, relating to replacing AC systems at Building 501 for the Hawaii Air National Guard. The solicitation involves removing an existing 40 Nominal Ton Carrier Air-Cooled Liquid Chiller and replacing it with a new 40 Nominal Ton Air-Cooled Chiller, along with replacing two close-coupled centrifugal chilled water pump systems.
The Q&A specifically addresses contractor concerns about valve conditions, with the government agreeing to add valve replacement to the Statement of Work. The procurement is a 100% small business set-aside under NAICS Code 238220 (Plumbing, Heating, and Air-Conditioning Contractors), with a size standard of $19.0M. The solicitation was amended on 3-Sep-2025, extending the offer due date to 11-Sep-2025 at 3:30 pm HST, and the government intends to award a single Firm Fixed Price (FFP) contract through the Department of the Army National Guard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ATCH 1. Revised SOW_KABD250001 Replace AC Systems B501 v 3.pdf | ||
| Solicitation Amendment W50SLF25RA0070001 SF 30.pdf | ||
| Solicitation Amendment - W50SLF25RA0070001.pdf | ||
| ATCH 1. Revsied SOW_KABD250001 Replace AC Systems B501 v 3.docx | DOCX document | |
| ATCH 2. Chiller Specs.pdf | ||
| ATCH 3. Reference Drawings.pdf | ||
| ATCH 5. Service Contract Act WD # 2015-5739 Rev No. 25.pdf | ||
| Solicitation - W50SLF25RA007.pdf | ||
| ATCH 1. SOW_KABD250001 Replace AC Systems, B501 v 2.docx | DOCX document | |
| ATCH 4. DETAILED PRICE PROPOSAL OFFER SPREADSHEET.docx | DOCX document | |
| ATCH 6. WD HI20250001, Modification No. 10.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KABD250001 Replace AC System B501, Maui HI Solicitation RFP Questions & Answers
Date: 03-Sep-2025
1. A couple of concerns that we had after visiting the site. The valve handles on a lot of the equipment are in really bad shape and there is no way that we will be able to close and reopen the chiller valves. They will need to be replaced. Also, there will be a good amount of insulation that will need to be removed just to get access to the valves and that is not called out in the specification either. Here are a couple of pictures of the valves onsite.
Answer: We will add replacement of these valves to SOW. Additionally we added clarifying verbiage to be sure contractor replaces both water pump and motor assembly.
image1.jpeg image2.jpeg image3.jpeg