W50S9A-25-Q-A013_Specification - UPS AC Units Replacement_Updated.pdf

PDF 258 KB Posted

Attached to
UPS AC Units Replacement
Solicitation number
W50S9A25QA013
Issued by

About this file

This document is a Specification for A/C Units for the UPS Building at the Roland R. Wright Utah Air National Guard Base. The 151st Intelligence Support Squadron requires replacing two existing Marvair 5.0 ton A/C units with two new high-efficiency A/C units. Specific requirements include two A/C units that are a minimum of 6 tons, capable of operating between 120 and 0 degrees Fahrenheit, with an economizer and interlocked exhaust fan. Additionally, one mounted exhaust fan is needed with 1000 CFM, 115/208 volts, a 12-inch shutter style mount, and thermostat-controlled parameters.

The vendor must provide complete delivery, removal, disposal, and installation services, with a targeted delivery timeline of 90 days after award. Installation includes refrigerant recovery, unit removal and disposal, new unit placement, electrical wiring, low ambient controls, and exhaust fan installation. The work must be completed during UTANG operating hours (0600-1630, Monday through Thursday) at the address 765 N 220 W, Salt Lake City, UT 84116. If the 90-day delivery timeline cannot be met, the vendor must propose an alternate delivery schedule.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATIONS

A/C Units UPS Building

BACKGROUND: The 151st Intelligence Support Squadron (ISS), located at the Roland R.

Wright Utah Air National Guard Base in Salt Lake City, UT has a need to replace its existing two Marvair 5.0 ton A/C units with two new High Seasonal Energy Efficiency Ration A/C units, and economizer and electric strip heat.

EQUIPMENT: The following specifications delineate the required criteria for each of the needed items. The proposed products shall meet the stated salient characteristics to be considered acceptable.

1) A/C units

QTY: 2

Salient Characteristics-

• Shall be High efficiency model.

• Shall be a minimum of 6 tons model.

• Shall be capable of operating in outside temperatures of 120 degrees Freiheit to 0 degrees Freiheit weather.

• Shall have an economizer and interlocked exhaust fan.

2) Mounted Exhaust Fan

QTY: 1

Salient Characteristics-

• There will be a minimum of 1000 CFM.

• Shall be 115/208 volts.

• Shall be a 12-inch shutter style mount exhaust fan.

• Interlocked to the economizer’s, controlled by thermostat o Parameters on at 80 degrees and off at 75 degrees

• Mounted on the top Westside of South wall

DELIVERY, REMOVAL/DISPOSAL, & INSTALLATION: Shipment and delivery of these items is anticipated to be no later than 90 days after receipt of award. If this delivery timeline cannot be met, the vendor shall state the best alternate delivery timeline they can provide. The vendor shall provide all tools, equipment, and personnel needed for refrigerant recovery and disposal as per federal guidelines, removal and disposal of the units, setting the new units in place, line voltage wiring, low ambient controls, installation and wiring of mounted exhaust fan and a start-up of the new units during UTANG operating hours of 0600-1630 Monday through Thursday. Delivery and installation will take place at: 765 N 220 W Salt Lake City, UT 84116.

**END SPECIFICATIONS**

File details come from the government source that posted it. Updated .