W50S9A-25-Q-A013_Specification - UPS AC Units Replacement_Updated.pdf

PDF 175 KB Posted

Attached to
UPS AC Units Replacement
Solicitation number
W50S9A25QA013
Issued by

About this file

This document is a Specifications document for A/C Units at the UPS Building for the 151st Intelligence Support Squadron (ISS) located at the Roland R. Wright Utah Air National Guard Base in Salt Lake City, UT. The specification requires replacing two existing Marvair 5.0 ton A/C units with two new high-efficiency A/C units that are a minimum of 6 tons, capable of operating in temperatures ranging from 120 to 0 degrees Fahrenheit, and equipped with an economizer and interlocked exhaust fan. Additionally, the specification calls for one mounted exhaust fan with a minimum of 1000 CFM, to be mounted on the top Westside of the South wall and controlled by a thermostat with parameters of on at 80 degrees and off at 75 degrees.

The vendor is expected to provide full delivery, removal, disposal, and installation services, including refrigerant recovery, unit removal and disposal, line voltage wiring, low ambient controls, and installation of the exhaust fan. The delivery and installation timeline is anticipated to be no later than 90 days after receipt of award, with the work to be completed during UTANG operating hours of 0600-1630 Monday through Thursday at the address 765 N 220 W, Salt Lake City, UT 84116. If the vendor cannot meet the 90-day timeline, they are required to state their best alternate delivery schedule.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATIONS

A/C Units UPS Building

BACKGROUND: The 151st Intelligence Support Squadron (ISS), located at the Roland R.

Wright Utah Air National Guard Base in Salt Lake City, UT has a need to replace its existing two Marvair 5.0 ton A/C units with two new High Seasonal Energy Efficiency Ration A/C units, and economizer and electric strip heat.

EQUIPMENT: The following specifications delineate the required criteria for each of the needed items. The proposed products shall meet the stated salient characteristics to be considered acceptable.

1) A/C units

QTY: 2

Salient Characteristics-

• Shall be High efficiency model.

• Shall be a minimum of 6 tons model.

• Shall be capable of operating in outside temperatures of 120 degrees Freiheit to 0 degrees Freiheit weather.

• Shall have an economizer and interlocked exhaust fan.

2) Mounted Exhaust Fan

QTY: 1

Salient Characteristics-

• There will be a minimum of 1000 CFM.

• Mounted on the top Westside of South wall

• Interlocked to the economizer’s, controlled by thermostat o Parameters on at 80 degrees and off at 75 degrees

DELIVERY, REMOVAL/DISPOSAL, & INSTALLATION: Shipment and delivery of these items is anticipated to be no later than 90 days after receipt of award. If this delivery timeline cannot be met, the vendor shall state the best alternate delivery timeline they can provide. The vendor shall provide all tools, equipment, and personnel needed for refrigerant recovery and disposal as per federal guidelines, removal and disposal of the units, setting the new units in place, line voltage wiring, low ambient controls, installation and wiring of mounted exhaust fan and a start-up of the new units during UTANG operating hours of 0600-1630 Monday through Thursday. Delivery and installation will take place at: 765 N 220 W Salt Lake City, UT 84116.

**END SPECIFICATIONS**