| FL | 1 | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | AHU Cooler | 90 | Duct Detector-T1 | M1-13 | Simplex | 4098-9756 | pass | | |
| 1 | AHU Cooler | 90 | Duct Detector-T1 | M1-14 | Simplex | 4098-9756 | pass | | |
| 1 | Mezzanine | 90 | Duct Detector-T1 | M1-43 | Simplex | 4098-9756 | pass | | |
| 1 | Mezzanine | 90 | Duct Detector-T1 | M1-44 | Simplex | 4098-9756 | | Fail | Excessively Dirty |
| 1 | Warehouse | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | South Wall Store Area | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | North Wall Store Area | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Lobby Area Barber Shop | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Old Kitchen Area | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Laundry Store | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | SE Storage Area | 90 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Warehouse | 90 | Main Fire Alarm Panel | | Simplex | 4020 | | Fail | Several Troubles, 18 Ah batteries Fail date code, No Communication to Dispatch |
| 1 | Receiving Exit | 90 | Pull Station-T1 | M1-01 | Simplex | 4099-9001 | pass | | |
| 1 | Sales Exit | 90 | Pull Station-T1 | M1-27 | Simplex | 4099-9001 | pass | | |
| 1 | Main Ent. | 90 | Pull Station-T1 | M1-29 | Simplex | 4099-9001 | pass | | |
| 1 | Laundry Exit West | 90 | Pull Station-T1 | M1-32 | Simplex | 4099-9001 | pass | | |
| 1 | Laundry Exit East | 90 | Pull Station-T1 | M1-34 | Simplex | 4099-9001 | pass | | |
| 1 | Mall Exit East | 90 | Pull Station-T1 | M1-38 | Simplex | 4099-9001 | pass | | |
| 1 | Outdoor Living Exit | 90 | Pull Station-T1 | M1-42 | Simplex | 4099-9001 | pass | | |
| 1 | Mezzanine | 90 | Pull Station-T1 | M1-46 | Simplex | 4099-9001 | pass | | |
| 1 | Receiving Area | 90 | Smoke Detector-T1 | M1-02 | Simplex | 4098-9714 | pass | | |
| 1 | Receiving Area | 90 | Smoke Detector-T1 | M1-03 | Simplex | 4098-9714 | pass | | |
| 1 | MP4 | 90 | Smoke Detector-T1 | M1-04 | Simplex | 4098-9714 | pass | | |
| 1 | MP4 | 90 | Smoke Detector-T1 | M1-05 | Simplex | 4098-9714 | pass | | |
| 1 | Cooler | 90 | Smoke Detector-T1 | M1-06 | Simplex | 4098-9714 | pass | | |
| 1 | Break Room | 90 | Smoke Detector-T1 | M1-07 | Simplex | 4098-9714 | pass | | |
| 1 | Janitor Closet | 90 | Smoke Detector-T1 | M1-08 | Simplex | 4098-9714 | | Fail | Excessively Dirty |
| 1 | Employee Restroom | 90 | Smoke Detector-T1 | M1-09 | Simplex | 4098-9714 | pass | | |
| 1 | Staff Office | 90 | Smoke Detector-T1 | M1-10 | Simplex | 4098-9714 | pass | | |
| 1 | Breakroom Hall | 90 | Smoke Detector-T1 | M1-11 | Simplex | 4098-9714 | | Fail | Excessively Dirty |
| 1 | Manager's Office | 90 | Smoke Detector-T1 | M1-12 | Simplex | 4098-9714 | pass | | |
| 1 | Sales West | 90 | Smoke Detector-T1 | M1-15 | Simplex | 4098-9714 | pass | | |
| 1 | Sales Center | 90 | Smoke Detector-T1 | M1-16 | Simplex | 4098-9714 | pass | | |
| 1 | Sales East | 90 | Smoke Detector-T1 | M1-17 | Simplex | 4098-9714 | pass | | |
| 1 | Sales East | 90 | Smoke Detector-T1 | M1-18 | Simplex | 4098-9714 | pass | | |
| 1 | Sales Center | 90 | Smoke Detector-T1 | M1-19 | Simplex | 4098-9714 | pass | | |
| 1 | Sales West | 90 | Smoke Detector-T1 | M1-20 | Simplex | 4098-9714 | pass | | |
| 1 | Sales West | 90 | Smoke Detector-T1 | M1-21 | Simplex | 4098-9714 | pass | | |
| 1 | Sales Center | 90 | Smoke Detector-T1 | M1-22 | Simplex | 4098-9714 | pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Sales East | 90 | Smoke Detector-T1 | M1-23 | Simplex | 4098-9714 | pass | | |
| 1 | Checkout East | 90 | Smoke Detector-T1 | M1-24 | Simplex | 4098-9714 | pass | | |
| 1 | Checkout West | 90 | Smoke Detector-T1 | M1-25 | Simplex | 4098-9714 | pass | | |
| 1 | Sales West | 90 | Smoke Detector-T1 | M1-26 | Simplex | 4098-9714 | pass | | |
| 1 | Vestibule | 90 | Smoke Detector-T1 | M1-28 | Simplex | 4098-9714 | pass | | |
| 1 | Barber Shop | 90 | Smoke Detector-T1 | M1-30 | Simplex | 4098-9714 | pass | | |
| 1 | Laundry | 90 | Smoke Detector-T1 | M1-31 | Simplex | 4098-9714 | pass | | |
| 1 | Barber Storage | 90 | Smoke Detector-T1 | M1-33 | Simplex | 4098-9714 | pass | | |
| 1 | Mall Area | 90 | Smoke Detector-T1 | M1-35 | Simplex | 4098-9714 | pass | | |
| 1 | Women's Restroom | 90 | Smoke Detector-T1 | M1-36 | Simplex | 4098-9714 | pass | | |
| 1 | Men's Restroom | 90 | Smoke Detector-T1 | M1-37 | Simplex | 4098-9714 | pass | | |
| 1 | Old Restaraunt Area | 90 | Smoke Detector-T1 | M1-39 | Simplex | 4098-9714 | pass | | |
| 1 | Food Support | 90 | Smoke Detector-T1 | M1-40 | Simplex | 4098-9714 | pass | | |
| 1 | Outdoor Living | 90 | Smoke Detector-T1 | M1-41 | Simplex | 4098-9714 | pass | | |
| 1 | Mezzanine | 90 | Smoke Detector-T1 | M1-45 | Simplex | 4098-9714 | pass | | |
| 1 | Break Room | 90 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Men's Restroom | 90 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Women's Restroom | 90 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | In BOSS System | 100 | Duct Detector-T1 | ZN4 | Simplex | 4098-9756 | pass | | |
| 1 | In BOSS System | 100 | Duct Detector-T1 | ZN4 | Simplex | 4098-9756 | pass | | |
| 1 | In 105 | 100 | Duct Detector-T1 | M1-39 | Simplex | 4098-9756 | pass | | |
| 1 | In 106 | 100 | Heat Detector-T1 | M1-31 | Simplex | 4098-9733 | pass | | |
| 1 | In 104 | 100 | Heat Detector-T1 | M1-30 | Simplex | 4098-9733 | pass | | |
| 1 | Women's Restroom Closet | 100 | Heat Detector-T1 | M1-13 | Simplex | 4098-9733 | pass | | |
| 1 | Men's Restroom Closet | 100 | Heat Detector-T1 | M1-06 | Simplex | 4098-9733 | pass | | |
| 1 | Men's Restroom | 100 | Heat Detector-T1 | M1-05 | Simplex | 4098-9733 | pass | | |
| 1 | Women's Restroom | 100 | Heat Detector-T1 | M1-12 | Simplex | 4098-9733 | pass | | |
| 1 | Janitor Closet | 100 | Heat Detector-T1 | M1-10 | Simplex | 4098-9733 | pass | | |
| 1 | Admin. Office Area | 100 | Heat Detector-T1 | M1-08 | Simplex | 4098-9733 | pass | | |
| 1 | Admin. Office Area | 100 | Heat Detector-T1 | M1-09 | Simplex | 4098-9733 | pass | | |
| 1 | Admin. Office Conf. Room | 100 | Heat Detector-T1 | M1-07 | Simplex | 4098-9733 | pass | | |
| 1 | Conf. Room Restroom | 100 | Heat Detector-T1 | M1-04 | Simplex | 4098-9733 | pass | | |
| 1 | Front Entrance | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Rear Exit | 100 | Horn Strobe-T1 | | Simplex | | | Fail | No Strobe |
| 1 | In 103 | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | In 104 | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | In 105 | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | In 105 Rear | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Women's Restroom | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Hall By Restrooms | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Hall By Restrooms | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Office Area | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Office Area | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Office Area Conf. Room | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Conference Room | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Men's Restroom | 100 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | In BOSS System | 100 | Horn-T1 | | Simplex | 4901-9822 | pass | | |
| 1 | Mech. Room | 100 | Main Fire Alarm Panel | | Simplex | 4100 | | Fail | Trouble on Panel, 18 Ah batteries Fail date code, No communication to Dispatch |
| 1 | Rear Exit | 100 | Pull Station-T1 | M1-17 | Simplex | 4099-9001 | Pass | | |
| 1 | Front Entrance | 100 | Pull Station-T1 | M1-14 | Simplex | 4099-9001 | pass | | |
| 1 | By FACP | 100 | Pull Station-T1 | M1-27 | Simplex | 4099-9001 | pass | | |
| 1 | In 103 | 100 | Pull Station-T1 | M1-29 | Simplex | 4099-9001 | pass | | |
| 1 | In 105 | 100 | Pull Station-T1 | M1-37 | Simplex | 4099-9001 | pass | | |
| 1 | Conf. Room Exit | 100 | Pull Station-T1 | M1-02 | Simplex | 4099-9001 | pass | | |
| 1 | Rear Exit | 100 | Smoke Detector-T1 | M1-18 | Simplex | 4098-9714 | pass | | |
| 1 | Front Entrance | 100 | Smoke Detector-T1 | M1-17 | Simplex | 4098-9714 | pass | | |
| 1 | Above FACP | 100 | Smoke Detector-T1 | M1-25 | Simplex | 4098-9714 | pass | | |
| 1 | In 103 | 100 | Smoke Detector-T1 | M1-32 | Simplex | 4098-9714 | pass | | |
| 1 | VESDA | 100 | Smoke Detector-T1 | M1-45 | Simplex | 4098-9714 | pass | | |
| 1 | Conference Room | 100 | Smoke Detector-T1 | M1-40 | Simplex | 4098-9714 | pass | | |
| 1 | Conference Room | 100 | Smoke Detector-T1 | M1-01 | Simplex | 4098-9714 | pass | | |
| 1 | Conference Room | 100 | Smoke Detector-T1 | M1-03 | Simplex | 4098-9714 | pass | | |
| 1 | BOSS System (In) | 100 | Smoke Detector-T1 | ZN3 | Simplex | 4098-9714 | pass | | |
| 1 | BOSS System (Under) | 100 | Smoke Detector-T1 | ZN2 | Simplex | 4098-9714 | pass | | |
| 1 | Smoke | 100 | Smoke Detector-T1 | M1-11 | Simplex | 4098-9714 | pass | | |
| 1 | In 102 | 100 | Smoke Detector-T1 | M1-28 | Simplex | 4098-9714 | pass | | |
| 1 | BOSS VESDA Power Supply | 100 | SPPS | | Simplex | VESDA | pass | | |
| 1 | Mech. Room | 101 | Heat Detector-T1 | M1-06 | Simplex | 4098-9733 | pass | | |
| 1 | Main Ent. | 101 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | East At Rear Exit | 101 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Men's Restroom | 101 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Women's Restroom | 101 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | West At Rear Exit | 101 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | By FACP | 101 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Mech. Room | 101 | Main Fire Alarm Panel | | Simplex | 4009 | | Fail | 18 Ah batteries faile date code, battery trouble on panel |
| 1 | Mech. Room | 101 | Pull Station-T1 | M1-01 | Simplex | 4099-9001 | pass | | |
| 1 | N. Ent. | 101 | Pull Station-T1 | M1-07 | Simplex | 4099-9001 | pass | | |
| 1 | East Hall | 101 | Pull Station-T1 | M1-13 | Simplex | 4099-9001 | pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | West Hall | 101 | Pull Station-T1 | M1-15 | Simplex | 4099-9001 | pass | | |
| 1 | N. Ent. | 101 | Smoke Detector-T1 | M1-08 | Simplex | 4098-9714 | pass | | |
| 1 | Janitor Closet | 101 | Smoke Detector-T1 | M1-09 | Simplex | 4098-9714 | pass | | |
| 1 | Main Hall | 101 | Smoke Detector-T1 | M1-10 | Simplex | 4098-9714 | pass | | |
| 1 | Main Hall | 101 | Smoke Detector-T1 | M1-11 | Simplex | 4098-9714 | pass | | |
| 1 | East Hall | 101 | Smoke Detector-T1 | M1-12 | Simplex | 4098-9714 | pass | | |
| 1 | West Hall | 101 | Smoke Detector-T1 | M1-14 | Simplex | 4098-9714 | pass | | |
| 1 | Room 182 | 102 | Duct Detector-T1 | M1-51 | Simplex | 4098-9756 | pass | | |
| 1 | Room 182 | 102 | Duct Detector-T1 | M1-52 | Simplex | 4098-9756 | pass | | |
| 1 | Room 120 | 102 | Duct Detector-T1 | M1-55 | Simplex | 4098-9756 | Pass | | |
| 1 | Room 120 | 102 | Duct Detector-T1 | M1-53 | Simplex | 4098-9756 | pass | | |
| 1 | Room 120 | 102 | Duct Detector-T1 | M1-47 | Simplex | 4098-9756 | pass | | |
| 1 | Room 184 | 102 | Duct Detector-T1 | M1-76 | Simplex | 4098-9756 | pass | | |
| 1 | Room 184 | 102 | Duct Detector-T1 | M1-77 | Simplex | 4098-9756 | pass | | |
| 1 | Room 137 | 102 | Heat Detector-T1 | M1-31 | Simplex | 4098-9733 | pass | | |
| 1 | Room 107 | 102 | Heat Detector-T1 | M1-79 | Simplex | 4098-9733 | pass | | |
| 1 | Room 107 | 102 | Heat Detector-T1 | M1-80 | Simplex | 4098-9733 | pass | | |
| 1 | Room 108 | 102 | Heat Detector-T1 | M1-69 | Simplex | 4098-9733 | pass | | |
| 1 | Room 108 | 102 | Heat Detector-T1 | M1-70 | Simplex | 4098-9733 | Pass | | |
| 1 | Room 109 | 102 | Heat Detector-T1 | M1-71 | Simplex | 4098-9733 | Pass | | |
| 1 | Room 110 | 102 | Heat Detector-T1 | M1-65 | Simplex | 4098-9733 | pass | | |
| 1 | Room 110 | 102 | Heat Detector-T1 | M1-66 | Simplex | 4098-9733 | pass | | |
| 1 | Room 110 | 102 | Heat Detector-T1 | M1-72 | Simplex | 4098-9733 | pass | | |
| 1 | Room 110 | 102 | Heat Detector-T1 | M1-73 | Simplex | 4098-9733 | pass | | |
| 1 | Room 182 | 102 | Heat Detector-T1 | M1-49 | Simplex | 4098-9733 | pass | | |
| 1 | Room 120 | 102 | Heat Detector-T1 | M1-46 | Simplex | 4098-9733 | pass | | |
| 1 | Room 117 | 102 | Heat Detector-T1 | M1-61 | Simplex | 4098-9733 | pass | | |
| 1 | Room 117 | 102 | Heat Detector-T1 | M1-62 | Simplex | 4098-9733 | pass | | |
| 1 | Room 184 | 102 | Heat Detector-T1 | M1-82 | Simplex | 4098-9733 | pass | | |
| 1 | Room 181 | 102 | Heat Detector-T1 | M1-07 | Simplex | 4098-9733 | pass | | |
| 1 | Room 181 | 102 | Heat Detector-T1 | M1-10 | Simplex | 4098-9733 | pass | | |
| 1 | By 142 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Server Room in 140 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 140 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 138 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Customer Service Area | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Mail Room Entrance | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 137 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | By Room 133 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Room 135 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 135 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 134 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 136 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Hall By 102 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 129 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 129 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 131 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 129 Control Room | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 131 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Room 102 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 102 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 103 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 107 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 107 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Hall at 125 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Men's Restroom | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Men's Restroom | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Women's Restroom | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Women's Restroom | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Room 108 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 108 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 109 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Hall By 120 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Hall By 119 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 110 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 110 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 110 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 110 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Room 110 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Room 112 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 116 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 182 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 120 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 119 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 119 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 116 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 117 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Room 184 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Room 181 | 102 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Elec. Room | 102 | Main Fire Alarm Panel | | Simplex | 4100 | | Fail | Positive and Negative Earth grounds, Several troubles for other buildings, 33 Ah batteries Fail date code |
| 1 | By 142 | 102 | Pull Station-T1 | M1-17 | Simplex | 4099-9001 | pass | | |
| 1 | Mail Room Entrance | 102 | Pull Station-T1 | M1-23 | Simplex | 4099-9001 | pass | | |
| 1 | By 132 | 102 | Pull Station-T1 | M1-37 | Simplex | 4099-9001 | pass | | |
| 1 | Room 107 | 102 | Pull Station-T1 | M1-86 | Simplex | 4099-9001 | pass | | |
| 1 | Room 108 | 102 | Pull Station-T1 | M1-63 | Simplex | 4099-9001 | pass | | |
| 1 | Room 108 | 102 | Pull Station-T1 | M1-74 | Simplex | 4099-9001 | pass | | |
| 1 | Room 110 | 102 | Pull Station-T1 | M1-68 | Simplex | 4099-9001 | pass | | |
| 1 | Room 110 | 102 | Pull Station-T1 | M1-67 | Simplex | 4099-9001 | Pass | | |
| 1 | By 116 | 102 | Pull Station-T1 | M1-58 | Simplex | 4099-9001 | pass | | |
| 1 | By Annunciator | 102 | Pull Station-T1 | M1-60 | Simplex | 4099-9001 | pass | | |
| 1 | Room 182 | 102 | Pull Station-T1 | M1-50 | Simplex | 4099-9001 | pass | | |
| 1 | Room 184 | 102 | Pull Station-T1 | M1-75 | Simplex | 4099-9001 | pass | | |
| 1 | Room 181 | 102 | Pull Station-T1 | M1-01 | Simplex | 4099-9001 | pass | | |
| 1 | By FACP | 102 | Pull Station-T1 | M1-11 | Simplex | 4099-9001 | pass | | |
| 1 | Entrance | 102 | Remote Annunciators-T1 | | Simplex | 4603-9101 | pass | | |
| 1 | Room 138 | 102 | Smoke Detector-T1 | M1-18 | Simplex | 4098-9714 | pass | | |
| 1 | Room 138 | 102 | Smoke Detector-T1 | M1-20 | Simplex | 4098-9714 | pass | | |
| 1 | Hall To 138 | 102 | Smoke Detector-T1 | M1-22 | Simplex | 4098-9714 | Pass | | |
| 1 | Hall By 133 | 102 | Smoke Detector-T1 | M1-30 | Simplex | 4098-9714 | pass | | |
| 1 | Room 136 | 102 | Smoke Detector-T1 | M1-26 | Simplex | 4098-9714 | pass | | |
| 1 | Entrance To 132 | 102 | Smoke Detector-T1 | M1-36 | Simplex | 4098-9714 | pass | | |
| 1 | By 102 | 102 | Smoke Detector-T1 | M1-39 | Simplex | 4098-9714 | pass | | |
| 1 | Men's Restroom | 102 | Smoke Detector-T1 | M1-43 | Simplex | 4098-9714 | pass | | |
| 1 | Women's Restroom | 102 | Smoke Detector-T1 | M1-45 | Simplex | 4098-9714 | pass | | |
| 1 | Hall By Restrooms | 102 | Smoke Detector-T1 | M1-41 | Simplex | 4098-9714 | pass | | |
| 1 | Room 178 | 102 | Smoke Detector-T1 | M1-48 | Simplex | 4098-9714 | pass | | |
| 1 | By 108 | 102 | Smoke Detector-T1 | M1-64 | Simplex | 4098-9714 | pass | | |
| 1 | By 120 | 102 | Smoke Detector-T1 | M1-56 | Simplex | 4098-9714 | Pass | | |
| 1 | By 116 | 102 | Smoke Detector-T1 | M1-57 | Simplex | 4098-9714 | pass | | |
| 1 | Vestibule By Annunciator | 102 | Smoke Detector-T1 | M1-59 | Simplex | 4098-9714 | pass | | |
| 1 | Above FACP | 102 | Smoke Detector-T1 | M1-12 | Simplex | 4098-9714 | pass | | |
| 1 | VESDA Power Supply | 102 | SPPS | | Simplex | Power Supply | pass | | |
| 1 | Room 105 | 102 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Room 106 | 102 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Room 113 | 102 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Storage | 110 | Heat Detector-T1 | M1-18 | Simplex | 4098-9733 | | | Not Tested soon to be demolished |
| 1 | Main Hall | 110 | Horn Strobe-T1 | | Simplex | 4903-9425 | | | Not Tested soon to be demolished |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Room 5 | 110 | Horn Strobe-T1 | | Simplex | 4903-9425 | | | Not Tested soon to be demolished |
| 1 | Restroom | 110 | Horn Strobe-T1 | | Simplex | 4903-9425 | | | Not Tested soon to be demolished |
| 1 | Men's Restroom | 110 | Main Fire Alarm Panel | | Simplex | 4009 | | | Not Tested soon to be demolished |
| 1 | Instrument | 110 | Pull Station-T1 | M1-07 | Simplex | 4099-9001 | | | Not Tested soon to be demolished |
| 1 | Break Room | 110 | Pull Station-T1 | M1-16 | Simplex | 4099-9001 | | | Not Tested soon to be demolished |
| 1 | Men's Restroom | 110 | Pull Station-T1 | M1-19 | Simplex | 4099-9001 | | | Not Tested soon to be demolished |
| 1 | Office | 110 | Pull Station-T1 | M1-24 | Simplex | 4099-9001 | | | Not Tested soon to be demolished |
| 1 | Communication | 110 | Pull Station-T1 | M1-26 | Simplex | 4099-9001 | | | Not Tested soon to be demolished |
| 1 | Storage Room | 110 | Smoke Detector-T1 | M1-01 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Storage Room | 110 | Smoke Detector-T1 | M1-02 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Doppler Room | 110 | Smoke Detector-T1 | M1-03 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Doppler Room | 110 | Smoke Detector-T1 | M1-04 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Instrument | 110 | Smoke Detector-T1 | M1-05 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Instrument | 110 | Smoke Detector-T1 | M1-06 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Instrument | 110 | Smoke Detector-T1 | M1-07 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Break Room | 110 | Smoke Detector-T1 | M1-17 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Navigation | 110 | Smoke Detector-T1 | M1-20 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Corridor | 110 | Smoke Detector-T1 | M1-21 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Branch Office | 110 | Smoke Detector-T1 | M1-22 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Office | 110 | Smoke Detector-T1 | M1-23 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Communication | 110 | Smoke Detector-T1 | M1-25 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Communication | 110 | Smoke Detector-T1 | M1-27 | Simplex | 4098-9714 | | | Not Tested soon to be demolished |
| 1 | Center Main Exit Bay | 111 | Bell-T1 | | Simplex | Bell | pass | | |
| 1 | Electroenvironmental Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Electroenvironmental Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Elec. Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Elec. Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Accessories Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Neudraulic Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Neudraulic Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | Pass | | |
| 1 | Break Room | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Locker Room | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Tool Room | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Tool Room | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Maintenance Group Kitchen | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Capt. Ferguson Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | CSMGT. Ashley Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Lt. Col. Seluidge Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Col. Lanbust Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Col. Lanbust Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Equip. Maint. Cheif Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Extra Office | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Fuel Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Fuel Shop | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Fuel Shop Locker Room | 111 | Heat Detector-T1 | | Simplex | 4098-9733 | pass | | |
| 1 | Neudraulic Shop | 111 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Restroom West | 111 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Maintenance Group | 111 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Fuel Shop | 111 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Fuel Shop Locker Room | 111 | Horn Strobe-T1 | | Simplex | 4903-9425 | pass | | |
| 1 | Elec. Room | 111 | Main Fire Alarm Panel | | Simplex | 4100 | pass | | 18 Ah Batteries 2020-90% |
| 1 | Center Main Bay Exit | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Right Main Bay Exit | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Right Main Bay Exit Tarmac | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Left Main Bay Exit Tarmac | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Electro Environmental Shop | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Elec. Shop | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Pneudraulic Shop | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Break Room | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Restroom West | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Tool Room | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Maintenance Group | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Extra Office | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Maintenance Group Exit | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Field Shop | 111 | Pull Station-T1 | | Simplex | 4099-9001 | pass | | |
| 1 | Fuel Shop Locker Room | 111 | Smoke Detector-T1 | | Simplex | 4098-9714 | pass | | |
| 1 | Restroom | 111 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Restroom | 111 | Strobe-T1 | | Simplex | 4904-9168 | pass | | |
| 1 | Center Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Center Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Right Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Right Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Right Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Left Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Left Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | Left Main Bay Exit | 111 | UVIR Flame Detector | | Simplex | Flame Det. | pass | | |
| 1 | BLDG 113 MECH/ELECT RM 7:M1-14 | 113 | Combo Detector-T1 | M1-14-1 | Simplex | | | | Building under renovation |
| 1 | Bldg+B320 113 Aircraft Bay 7:M1-25 | 113 | Combo Detector-T1 | M1-25-1 | Simplex | | | | Building under renovation |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-33 | 113 | Combo Detector-T1 | M1-33-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 JANITOR CLOSET 7:M1-34 | 113 | Heat Detector-T1 | M1-34-0 | Simplex | 4098-9733 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT LINE 7:M1-37 | 113 | Combo Detector-T1 | M1-37-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-42 | 113 | Combo Detector-T1 | M1-42-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-49 | 113 | Combo Detector-T1 | M1-49-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 NOSE BAY 7:M1-50 | 113 | Combo Detector-T1 | M1-50-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-52 | 113 | Combo Detector-T1 | M1-52-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-53 | 113 | Combo Detector-T1 | M1-53-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-54 | 113 | Combo Detector-T1 | M1-54-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-55 | 113 | Combo Detector-T1 | M1-55-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-56 | 113 | Combo Detector-T1 | M1-56-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-57 | 113 | Combo Detector-T1 | M1-57-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-61 | 113 | Combo Detector-T1 | M1-61-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 FLIGHT BAY 7:M1-62 | 113 | Heat Detector-T1 | M1-62-0 | Simplex | 4098-9733 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-75 | 113 | Combo Detector-T1 | M1-75-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-85 | 113 | Combo Detector-T1 | M1-85-1 | Simplex | | | | Building under renovation |
| 1 | BLDG 113 MEN'S RESTRM PAU-1 7:M1-31 | 113 | Duct Detector-T1 | M1-31-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 MEN'S RESTRM PAU-1 7:M1-32 | 113 | Duct Detector-T1 | M1-32-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT LINE 7:M1-38 | 113 | Duct Detector-T1 | M1-38-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT LINE 7:M1-39 | 113 | Duct Detector-T1 | M1-39-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-47 | 113 | Duct Detector-T1 | M1-47-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-48 | 113 | Duct Detector-T1 | M1-48-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-69 | 113 | Duct Detector-T1 | M1-69-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-70 | 113 | Duct Detector-T1 | M1-70-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-71 | 113 | Duct Detector-T1 | M1-71-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-72 | 113 | Duct Detector-T1 | M1-72-0 | Simplex | 4098-9756 | | | Building under renovation |
| 1 | BLDG 113 MECH/ELECT RM EXIT 7:M1-11 | 113 | Pull Station-T1 | M1-11-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 MECH/ELECT RM EXIT 7:M1-15 | 113 | Pull Station-T1 | M1-15-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-26 | 113 | Pull Station-T1 | M1-26-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-27 | 113 | Pull Station-T1 | M1-27-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT LINE 7:M1-41 | 113 | Pull Station-T1 | M1-41-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT CHIEF 7:M1-44 | 113 | Pull Station-T1 | M1-44-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 BREAK RM EXIT 7:M1-46 | 113 | Pull Station-T1 | M1-46-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 NOSE BAY EXIT 7:M1-51 | 113 | Pull Station-T1 | M1-51-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 ISO DOCK EXIT 7:M1-58 | 113 | Pull Station-T1 | M1-58-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 CORR EXIT BY SUPPLY RM 7:M1-59 | 113 | Pull Station-T1 | M1-59-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 CORROSION CONTROL EXIT 7:M1-65 | 113 | Pull Station-T1 | M1-65-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 SHEETMETAL SHOP EXIT 7:M1-81 | 113 | Pull Station-T1 | M1-81-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-86 | 113 | Pull Station-T1 | M1-86-0 | Simplex | 4099-9001 | | | Building under renovation |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | BLDG 113 AIRCRAFT BAY 7:M1-87 | 113 | Pull Station-T1 | M1-87-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 MACHNE SHOP EXIT 7:M1-88 | 113 | Pull Station-T1 | M1-88-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 WELDING SHOP EXIT 7:M1-89 | 113 | Pull Station-T1 | M1-89-0 | Simplex | 4099-9001 | | | Building under renovation |
| 1 | BLDG 113 MECH/ELECT RM 7:M1-12 | 113 | Smoke Detector-T1 | M1-12-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT LINE 7:M1-36 | 113 | Smoke Detector-T1 | M1-36-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT LINE 7:M1-40 | 113 | Smoke Detector-T1 | M1-40-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | BLDG 113 CORR BY FLIGHT CHIEF 7:M1-43 | 113 | Smoke Detector-T1 | M1-43-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | BLDG 113 CORR BY SUPPLY RM 7:M1-60 | 113 | Smoke Detector-T1 | M1-60-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | BLDG 113 CORROSION CONTROL 7:M1-67 | 113 | Smoke Detector-T1 | M1-67-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | BLDG 113 SHEETMETAL SHOP 7:M1-73 | 113 | Smoke Detector-T1 | M1-73-0 | Simplex | 4098-9714 | | | Building under renovation |
| 1 | RM 131 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 126 By Exit | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Machine Shop Rear | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 132 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 128 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Front left hanger wall | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside RM 125 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside 110 Storage | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 113 Corridor | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 108 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Mens Locker Rear Exit | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside Rm 102 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 102 Rear | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Left Rear Bay | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 129 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Bay by Rm 115 | 113 | Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 126 Exit to Hanger | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 126 By Exit | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 126 Rear | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 126 by Exit | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 126 By Piess | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside RM 128 Left | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside Rm 128 Right | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Machine Shop By Exit to Hanger | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside RM 132 By Exit | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Weld Shop Rear Exit | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Weld Shop Front | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside RM 122 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 122 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Rm 120 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 118 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 121 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Nose Dock Left | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Nose Dock Right | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside 107 Mens Locker | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 111 Rear | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 111 Front | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 113 Corridor | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Rm 113 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RR by 107 Mens | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Mens RR Rear | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Mens Locker RM Front | 113 | speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Mens RR Rear | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Bay Outside Womens RR | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | By Womens Shower | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Womens RR | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 102 Front | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside RM 130 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Sheet Metal Shop Exit to Hanger | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | RM 129 | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Breakroom By Exit | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside Sprinkler Riser RM | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Sprinkler Riser RM | 113 | Speaker Strobe-T1 | | Simplex | | | | Building under renovation |
| 1 | Front Left Hanger Wall | 113 | Speaker-T1 | | Simplex | | | | Building under renovation |
| 1 | By RM 108 | 113 | Speaker-T1 | | Simplex | | | | Building under renovation |
| 1 | Outside RM 102 | 113 | Speaker-T1 | | Simplex | | | | Building under renovation |
| 1 | Left Rear Bay | 113 | Speaker-T1 | | Simplex | | | | Building under renovation |
| 1 | Bay By RM 115 | 113 | Speaker-T1 | | Simplex | | | | Building under renovation |
| 1 | In Sheet Metal Shop | 113 | Power Supply-T1 | | Simplex | 4009 | | | Building under renovation |
| 1 | By 109 | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Main Entrance | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | By 117 | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | In 124 | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Rear Exit Near 124 | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Exit By 133 | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | In 137 Supply Bay | 120 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Comm Room | 120 | Main Fire Alarm Panel | | Simplex | 4100 | | Fail | 33Ah batteries fail date code, trouble on panel |
| 1 | Main Lobby | 120 | Pull Station-T1 | M1-01 | Simplex | 4099-9001 | Pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Hall At Breakroom | 120 | Pull Station-T1 | M1-02 | Simplex | 4099-9001 | Pass | | |
| 1 | Men's Restroom | 120 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Women's Restroom | 120 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Lobby Restroom | 120 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | BDOC | 120 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Mech. Elec. Room | 123 | Duct Detector-T1 | M1-14 | Simplex | 4098-9756 | Pass | | |
| 1 | Mech. Elec. Room | 123 | Duct Detector-T1 | M1-15 | Simplex | 4098-9756 | Pass | | |
| 1 | Office 111 | 123 | Heat Detector-T1 | M1-01 | Simplex | 4098-9733 | Pass | | |
| 1 | Office 102 | 123 | Heat Detector-T1 | M1-03 | Simplex | 4098-9733 | Pass | | |
| 1 | Conference Room 110 | 123 | Heat Detector-T1 | M1-04 | Simplex | 4098-9733 | Pass | | |
| 1 | Women's Restroom | 123 | Heat Detector-T1 | M1-05 | Simplex | 4098-9733 | Pass | | |
| 1 | Closet 108 | 123 | Heat Detector-T1 | M1-07 | Simplex | 4098-9733 | Pass | | |
| 1 | Men's Restroom | 123 | Heat Detector-T1 | M1-09 | Simplex | 4098-9733 | Pass | | |
| 1 | Office 107 | 123 | Heat Detector-T1 | M1-11 | Simplex | 4098-9733 | Pass | | |
| 1 | Main Lobby | 123 | Horn Strobe-T1 | | Simplex | 4903-9425 | | Fail | No Strobe |
| 1 | Rear Office | 123 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Mech. Room | 123 | Main Fire Alarm Panel | | Simplex | 4100 | | Fail | Troubles on panel, 18 Ah batteries fail date code |
| 1 | Rear Exit | 123 | Pull Station-T1 | M1-08 | Simplex | 4099-9001 | Pass | | |
| 1 | Front Exit | 123 | Pull Station-T1 | M1-12 | Simplex | 4099-9001 | Pass | | |
| 1 | Mech. Elec. Room | 123 | Pull Station-T1 | M1-13 | Simplex | 4099-9001 | Pass | | |
| 1 | Front Corridor | 123 | Smoke Detector-T1 | M1-02 | Simplex | 4098-9714 | Pass | | |
| 1 | Comm. Room | 123 | Smoke Detector-T1 | M1-06 | Simplex | 4098-9714 | Pass | | |
| 1 | Mech. Elec. Room | 123 | Smoke Detector-T1 | M1-10 | Simplex | 4098-9714 | Pass | | |
| 1 | Reatroom | 123 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Reatroom | 123 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Alarm Room | 124 | CO Detector-T1 | 1:M1-81 | Simplex | CO | Pass | | |
| 2 | Hallway | 124 | CO Detector-T1 | 1:M1-44 | Simplex | CO | Pass | | |
| 2 | Hallway | 124 | CO Detector-T1 | 1:M1-45 | Simplex | CO | Pass | | |
| 2 | Hallway | 124 | CO Detector-T1 | 1:M1-50 | Simplex | CO | | Fail | Open Circuit |
| 2 | Kitchen | 124 | CO Detector-T1 | 1:M1-60 | Simplex | CO | Pass | | |
| 2 | Bunk Room 1 | 124 | CO Detector-T1 | 1:M1-26 | Simplex | CO | | Fail | Disabled upon arrival |
| 2 | Bunk Room 2 | 124 | CO Detector-T1 | 1:M1-27 | Simplex | CO | Pass | | |
| 2 | Bunk Room 3 | 124 | CO Detector-T1 | 1:M1-32 | Simplex | CO | Pass | | |
| 2 | Bunk Room 4 | 124 | CO Detector-T1 | 1:M1-33 | Simplex | CO | Pass | | |
| 2 | Bunk Room 5 | 124 | CO Detector-T1 | 1:M1-38 | Simplex | CO | Pass | | |
| 2 | Bunk Room 6 | 124 | CO Detector-T1 | 1:M1-39 | Simplex | CO | Pass | | |
| 1 | Mech Room | 124 | Duct Detector-T1 | 1:M1-10 | Simplex | 4098-9756 | Pass | | |
| 1 | Mech Room | 124 | Duct Detector-T1 | 1:M1-11 | Simplex | 4098-9756 | Pass | | |
| 2 | Mech Room | 124 | Duct Detector-T1 | 1:M1-52 | Simplex | 4098-9756 | Pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 2 | Mech Room | 124 | Duct Detector-T1 | 1:M1-53 | Simplex | 4098-9756 | Pass | | |
| 2 | Mech Room | 124 | Duct Detector-T1 | 1:M1-54 | Simplex | 4098-9756 | Pass | | |
| 2 | Mech Room | 124 | Duct Detector-T1 | 1:M1-55 | Simplex | 4098-9756 | Pass | | |
| 1 | Hallway | 124 | Heat Detector-T1 | 1:M1-71 | Simplex | 4098-9733 | Pass | | |
| 1 | Hallway | 124 | Heat Detector-T1 | 1:M1-73 | Simplex | 4098-9733 | Pass | | |
| 1 | Hallway | 124 | Heat Detector-T1 | 1:M1-75 | Simplex | 4098-9733 | Pass | | |
| 1 | Hallway | 124 | Heat Detector-T1 | 1:M1-77 | Simplex | 4098-9733 | Pass | | |
| 1 | Hallway (Combo) | 124 | Heat Detector-T1 | 1:M1-67 | Simplex | 4098-9733 | Pass | | |
| 1 | Hallway (Combo) | 124 | Heat Detector-T1 | 1:M1-69 | Simplex | 4098-9733 | Pass | | |
| 1 | Comm Room | 124 | Heat Detector-T1 | 1:M1-63 | Simplex | 4098-9733 | Pass | | |
| 1 | Deputy Chief Office | 124 | Heat Detector-T1 | 1:M1-65 | Simplex | 4098-9733 | Pass | | |
| 2 | Hallway | 124 | Heat Detector-T1 | 1:M1-47 | Simplex | 4098-9733 | Pass | | |
| 2 | Hallway | 124 | Heat Detector-T1 | 1:M1-49 | Simplex | 4098-9733 | Pass | | |
| 2 | Hallway | 124 | Heat Detector-T1 | 1:M1-57 | Simplex | 4098-9733 | Pass | | |
| 2 | Hallway | 124 | Heat Detector-T1 | 1:M1-59 | Simplex | 4098-9733 | Pass | | |
| 2 | Hallway | 124 | Heat Detector-T1 | 1:M1-43 | Simplex | 4098-9733 | Pass | | |
| 1 | Garage Area @ Door 6 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Garage Area @ Door 3 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Garage Area @ Door 1 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Garage Area @ Door 12 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Garage Area @ Door 9 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Garage Area @ Door 7 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Hallway @ Room 108 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Room 107 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Exit @ Room 102 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Hallway @ Room 101 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Hallway @ Room 104 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 206 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Hallway @ Room 207 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Hallway @ Room 205 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 207 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 205 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 204 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 203 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 202 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Room 201 | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Hallway @ Showers | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Men's Showers | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Women's Showers | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 2 | Break Area | 124 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Comm Room | 124 | Main Fire Alarm Panel | | Simplex | 4100 | | Fail | 35 Ah batteries 2021-100%, Transponder 35 Ah batteries fail date code. Several Troubles |
| 1 | Hallway | 124 | Pull Station-T1 | 1:M1-82 | Simplex | 4099-9001 | Pass | | |
| 1 | Main Entrance | 124 | Pull Station-T1 | 1:M1-83 | Simplex | 4099-9001 | Pass | | |
| 1 | Apparatus Bay | 124 | Pull Station-T1 | 1:M1-01 | Simplex | 4099-9001 | Pass | | |
| 1 | Apparatus Bay | 124 | Pull Station-T1 | 1:M1-02 | Simplex | 4099-9001 | Pass | | |
| 1 | Apparatus Bay | 124 | Pull Station-T1 | 1:M1-03 | Simplex | 4099-9001 | Pass | | |
| 1 | Apparatus Bay | 124 | Pull Station-T1 | 1:M1-04 | Simplex | 4099-9001 | Pass | | |
| 1 | Apparatus Bay | 124 | Pull Station-T1 | 1:M1-05 | Simplex | 4099-9001 | Pass | | |
| 1 | Extinguisher Room | 124 | Pull Station-T1 | 1:M1-06 | Simplex | 4099-9001 | Pass | | |
| 1 | Hallway | 124 | Pull Station-T1 | 1:M1-13 | Simplex | 4099-9001 | Pass | | |
| 2 | Hallway | 124 | Pull Station-T1 | 1:M1-51 | Simplex | 4099-9001 | Pass | | |
| 2 | Day Room | 124 | Pull Station-T1 | 1:M1-61 | Simplex | 4099-9001 | Pass | | |
| 1 | Hallway | 124 | Smoke Detector-T1 | 1:M1-70 | Simplex | 4098-9714 | Pass | | |
| 1 | Hallway | 124 | Smoke Detector-T1 | 1:M1-72 | Simplex | 4098-9714 | Pass | | |
| 1 | Hallway | 124 | Smoke Detector-T1 | 1:M1-74 | Simplex | 4098-9714 | Pass | | |
| 1 | Hallway | 124 | Smoke Detector-T1 | 1:M1-76 | Simplex | 4098-9714 | Pass | | |
| 1 | Alarm Room | 124 | Smoke Detector-T1 | 1:M1-78 | Simplex | 4098-9714 | Pass | | |
| 1 | Office 101 | 124 | Smoke Detector-T1 | 1:M1-14 | Simplex | 4098-9714 | Pass | | |
| 1 | Comm Room | 124 | Smoke Detector-T1 | 1:M1-62 | Simplex | 4098-9714 | Pass | | |
| 1 | Deputy Chief Office | 124 | Smoke Detector-T1 | 1:M1-64 | Simplex | 4098-9714 | Pass | | |
| 1 | Hallway (Combo) | 124 | Smoke Detector-T1 | 1:M1-66 | Simplex | 4098-9714 | Pass | | |
| 1 | Hallway (Combo) | 124 | Smoke Detector-T1 | 1:M1-68 | Simplex | 4098-9714 | Pass | | |
| 2 | Hallway | 124 | Smoke Detector-T1 | 1:M1-46 | Simplex | 4098-9714 | Pass | | |
| 2 | Hallway | 124 | Smoke Detector-T1 | 1:M1-48 | Simplex | 4098-9714 | Pass | | |
| 2 | Hallway | 124 | Smoke Detector-T1 | 1:M1-56 | Simplex | 4098-9714 | Pass | | |
| 2 | Hallway | 124 | Smoke Detector-T1 | 1:M1-58 | Simplex | 4098-9714 | Pass | | |
| 2 | Common Living Area | 124 | Smoke Detector-T1 | 1:M1-15 | Simplex | 4098-9714 | Pass | | |
| 2 | Common Living Area | 124 | Smoke Detector-T1 | 1:M1-16 | Simplex | 4098-9714 | Pass | | |
| 2 | Bunk Room 1 | 124 | Smoke Detector-T1 | 1:M1-24 | Simplex | 4098-9714 | Pass | | |
| 2 | Bunk Room 2 | 124 | Smoke Detector-T1 | 1:M1-28 | Simplex | 4098-9714 | Pass | | |
| 2 | Bunk Room 3 | 124 | Smoke Detector-T1 | 1:M1-30 | Simplex | 4098-9714 | Pass | | |
| 2 | Bunk Room 4 | 124 | Smoke Detector-T1 | 1:M1-34 | Simplex | 4098-9714 | Pass | | |
| 2 | Bunk Room 5 | 124 | Smoke Detector-T1 | 1:M1-36 | Simplex | 4098-9714 | Pass | | |
| 2 | Bunk Room 6 | 124 | Smoke Detector-T1 | 1:M1-40 | Simplex | 4098-9714 | Pass | | |
| 2 | Hallway | 124 | Smoke Detector-T1 | 1:M1-42 | Simplex | 4098-9714 | Pass | | |
| 1 | Women's Restroom | 124 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Men's Restroom | 124 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Room 106 | 124 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | DRC Equipment Room | 125 | Heat Detector-T1 | 5:M1-01 | Simplex | 4098-9733 | Pass | | |
| 1 | DRC Equipment Room | 125 | Heat Detector-T1 | 5:M1-02 | Simplex | 4098-9733 | Pass | | |
| 1 | DRC Equipment Room | 125 | Heat Detector-T1 | 5:M1-04 | Simplex | 4098-9733 | Pass | | |
| 1 | Storage Room | 125 | Heat Detector-T1 | 5:M1-08 | Simplex | 4098-9733 | Pass | | |
| 1 | Storage Room | 125 | Heat Detector-T1 | 5:M1-09 | Simplex | 4098-9733 | Pass | | |
| 1 | Break Room | 125 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Work Room | 125 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Vault Room | 125 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Hallway @ Riser Room | 125 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | DRC Equipment Room | 125 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | DRC Equipment Room | 125 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Comm Room | 125 | Main Fire Alarm Panel | | Simplex | 4010 | | Fail | 18 Ah batteries fail date code |
| 1 | DRC Equipment Room | 125 | Pull Station-T1 | 5:M1-05 | Simplex | 4099-9001 | Pass | | |
| 1 | Storage Room | 125 | Pull Station-T1 | 5:M1-06 | Simplex | 4099-9001 | Pass | | |
| 1 | Entrance | 125 | Pull Station-T1 | 5:M1-10 | Simplex | 4099-9001 | Pass | | |
| 1 | DRC Equipment Room | 125 | Smoke Detector-T1 | 5:M1-03 | Simplex | 4098-9714 | Pass | | |
| 1 | Vault Room | 125 | Smoke Detector-T1 | 5:M1-07 | Simplex | 4098-9714 | Pass | | |
| 1 | Entrance | 125 | Smoke Detector-T1 | 5:M1-11 | Simplex | 4098-9714 | Pass | | |
| 1 | Work Room | 125 | Smoke Detector-T1 | 5:M1-12 | Simplex | 4098-9714 | Pass | | |
| 1 | Work Room | 125 | Smoke Detector-T1 | 5:M1-13 | Simplex | 4098-9714 | Pass | | |
| 1 | Break Room | 125 | Smoke Detector-T1 | 5:M1-14 | Simplex | 4098-9714 | Pass | | |
| 1 | Riser Room | 125 | Smoke Detector-T1 | 5:M1-249 | Simplex | 4098-9714 | Pass | | |
| 1 | Manager's Office | 125 | Smoke Detector-T1 | 5:M1-250 | Simplex | 4098-9714 | Pass | | |
| 1 | Restroom | 125 | Strobe-T1 | | Simplex | 4904-9168 | Pass | | |
| 1 | Soldering Shop | 126 | Heat Detector-T1 | 8:M1-07 | Simplex | 4098-9733 | Pass | | |
| 1 | Mech Room | 126 | Heat Detector-T1 | 8:M1-03 | Simplex | 4098-9733 | Pass | | |
| 1 | Bay 1 Paintbooth | 126 | Heat Detector-T1 | 8:M1-60 | Simplex | 4098-9733 | Pass | | |
| 1 | MAG Room | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Mech Room | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 4 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 4 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Hallway @ MAG Room | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | BAy 3 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Main Office Area | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Men's Restroom | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 2 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 1 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 1 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 2 | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 2 | Restroom | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 2 | Classroom | 126 | Horn Strobe-T1 | | Simplex | 4903-9425 | Pass | | |
| 1 | Bay 1 Paintbooth ANSUL | 126 | Kitchen Hood Supervisory | | Simplex | 4090-9001 | Pass | | |
| 1 | Comm Room | 126 | Main Fire Alarm Panel | | Simplex | 4020 | | Fail | 33 Ah batteries fail date code, trouble on panel |
| 1 | Mech Room | 126 | Pull Station-T1 | 8:M1-01 | Simplex | 4099-9001 | Pass | | |
| 1 | AGE Shop Office | 126 | Pull Station-T1 | 8:M1-05 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 1 North Exit | 126 | Pull Station-T1 | 8:M1-06 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 3 South Exit | 126 | Pull Station-T1 | 8:M1-42 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 4 North Exit | 126 | Pull Station-T1 | 8:M1-49 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 2 South Exit | 126 | Pull Station-T1 | 8:M1-25 | Simplex | 4099-9001 | Pass | | |
| 1 | Engine Shop Office West | 126 | Pull Station-T1 | 8:M1-26 | Simplex | 4099-9001 | Pass | | |
| 1 | Engine Shop Office East | 126 | Pull Station-T1 | 8:M1-27 | Simplex | 4099-9001 | Pass | | |
| 1 | North Hallway | 126 | Pull Station-T1 | 8:M1-36 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 3 North Exit | 126 | Pull Station-T1 | 8:M1-37 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 4 South Exit | 126 | Pull Station-T1 | 8:M1-54 | Simplex | 4099-9001 | Pass | | |
| 1 | Bay 1 South Exit | 126 | Pull Station-T1 | 8:M1-59 | Simplex | 4099-9001 | Pass | | |
| 2 | Break Room | 126 | Pull Station-T1 | 8:M1-30 | Simplex | 4099-9001 | Pass | | |
| 2 | Comm Room South | 126 | Pull Station-T1 | 8:M1-31 | Simplex | 4099-9001 | Pass | | |
| 2 | Comm Room North | 126 | Pull Station-T1 | 8:M1-32 | Simplex | 4099-9001 | Pass | | |
| 2 | Class Room | 126 | Pull Station-T1 | 8:M1-34 | Simplex | 4099-9001 | Pass | | |
| 1 | AGE Shop Office | 126 | Smoke Detector-T1 | 8:M1-04 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 2 Ceiling NW | 126 | Smoke Detector-T1 | 8:M1-10 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 2 Ceiling SW | 126 | Smoke Detector-T1 | 8:M1-12 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 2 Ceiling SE | 126 | Smoke Detector-T1 | 8:M1-14 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 1 Ceiling SE | 126 | Smoke Detector-T1 | 8:M1-16 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 1 Ceiling NE | 126 | Smoke Detector-T1 | 8:M1-18 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 1 Ceiling NW | 126 | Smoke Detector-T1 | 8:M1-19 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 1 Ceiling SW | 126 | Smoke Detector-T1 | 8:M1-22 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 3 Ceiling SW | 126 | Smoke Detector-T1 | 8:M1-41 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 3 SEAL Room | 126 | Smoke Detector-T1 | 8:M1-44 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 3 Ceiling NE | 126 | Smoke Detector-T1 | 8:M1-45 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 3 Ceiling SE | 126 | Smoke Detector-T1 | 8:M1-48 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 4 Ceiling NW | 126 | Smoke Detector-T1 | 8:M1-50 | Simplex | 4098-9714 | Pass | | |
| 1 | Engine Shop Office | 126 | Smoke Detector-T1 | 8:M1-28 | Simplex | 4098-9714 | Pass | | |
| 1 | North Hallway | 126 | Smoke Detector-T1 | 8:M1-35 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 3 Ceiling NW | 126 | Smoke Detector-T1 | 8:M1-38 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 4 Ceiling SW | 126 | Smoke Detector-T1 | 8:M1-53 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 4 Ceiling NE | 126 | Smoke Detector-T1 | 8:M1-55 | Simplex | 4098-9714 | Pass | | |
| 1 | Bay 4 Ceiling SE | 126 | Smoke Detector-T1 | 8:M1-58 | Simplex | 4098-9714 | Pass | | |
| FL | Device Location | Bldg. Num. | Device Type | Device Address | MFG. | Model | Pass | Fail | Comments |
| 1 | Bay 2 AGE Supervisor | 126 | Smoke Detector-T1 | 8:M1-61 | Simplex | 4098-9714 | Pass | | |
| 1 | NDI Lab Hallway | 126 | Smoke Detector-T1 | 8:M1-68 | Simplex | 4098-9714 | Pass | | |
| 1 | NDI Lab | 126 | Smoke Detector-T1 | 8:M1-69 | Simplex | 4098-9714 | Pass | | |
| 2 | Break Room | 126 | Smoke Detector-T1 | 8:M1-29 | Simplex | 4098-9714 | Pass | | |
| 2 | Kitchen | 126 | Smoke Detector-T1 | 8:M1-33 | Simplex | 4098-9714 | Pass | | |
| LL | Mech. Room AHU Supply | 132 | Duct Detector-T1 | M1-26 | Simplex | 4098-9756 | Pass | | |
| LL | Mech. Room AHU Return | 132 | Duct Detector-T1 | M1-27 | Simplex | 4098-9756 | Pass | | |
| LL | Mech. Room AHU Supply | 132 | Duct Detector-T1 | M1-31 | Simplex | 4098-9756 | Pass | | |
| LL | Mech. Room AHU Return | 132 | Duct Detector-T1 | M1-32 | Simplex | 4098-9756 | Pass | | |
| UL | Attic Mech. Room Supply | 132 | Duct Detector-T1 | M1-54 | Simplex | 4098-9756 | Pass | | |