The Tang Report 2024.xlsx is a comprehensive fire alarm system inspection document detailing the condition of fire detection and notification devices across multiple buildings. The report reveals significant findings, including a total of 2,725 devices tested, with 2,682 passing and 43 failing inspection. Major deficiencies include batteries failing load tests, date code issues, dirty or non-functional smoke detectors, and communication problems with fire alarm panels.

The report covers numerous buildings (numbered 90-1812) and catalogs various device types such as smoke detectors, horn strobes, pull stations, duct detectors, and heat detectors. Specific issues were noted in buildings like 90, 100, 101, 113, 124, and 246, with problems ranging from batteries needing replacement to smoke heads requiring new components. Many fire alarm panels were flagged for troubles, including failed battery date codes and communication issues with dispatch systems. The inspection used Simplex equipment and systematically evaluated devices across different rooms, mechanical areas, and building sections.

View the file

Other files

Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Totals Sheet

Device TotalsDevice CountPassedFailed
Bell22
Co Detector1111
Combo Detector113113
Duct Detector2222
Door Holder422
Elevator Alt Recall11
Elevator Primary Recall11
Heat212212
Horn Strobe5455441
Horn321
Kitchen Hood Supervisory33
Main Fire Panel411526
Power Supply55
Pull Station338338
Remote Annunciator33
Rotary Beacon22
Smoke Detectors1188117513
Speaker Strobe110110
Speaker1919
SPPS22
Strobe9191
Sub Panel11
UVIR Flame Detector88

Total 2725 2682 43

Deficiencies Deficiencies

Building 90
1) Batteries Failed load test. Replace with 9275 X2
2) M1-8 Excessively Dirty. Replace with 9714 and 9792
Building 100
1) Batteries Failed date code. Replace with 9275 X2
Building 101
1) Batteries dead upon arrival. Replace with 9275 X2
Building 102
1) Earth Ground upon arrival.
Building 110
1) M1-2 No answer upon arrival. Replace with 9714 and 9792
Building 111
1) Batteries Failed Load Test. Replace with 9714 and 9792
Building 113
1) Suppression Monitor trouble upon arrival.
2) 4009 Batteries failed date code. Replace with 9724 X2
3) System Batteries failed date code. Replace with 9726 X2
Building 120
1) System slave trouble upon arrival.
2) Batteries Failed date code. 9276 X2
Building 123
1) Batteries failed load test. Replace with 9275 X2
Page 1 of 5
Deficiencies
Building 124
1) M1-36 Smoke head needs replaced. Replace with 9714
2) M1-37 Smoke head needs replaced. Replace with 9714
3) M1-58 Smoke head needs replaced. Replace with 9714
4) M1-59 Smoke head needs replaced. Replace with 9714
5) M1-26 Needs CO2 cartridge replaced.
Building 125
1) M1-249 failed to test. Replace with 9714
2) M1-11 failed to test replace with 9714
Building 126
1) Batteries failed date code. Replace with 9275 X2
Building 132
1) Batteries failed date code. Replace with 9276 X4
Building 134
1) Batteries tested at 80%
Building 240
1) Batteries failed date code. Replace with 9275 X2
Building 246
1) System needs upgrade bad power supply.
2) Smoke detector trouble upon arrival. Replace with 9714 and 9292
Building 262
1) Batteries failed date code. Replace with 9275 X2
Building 263
1) System needs upgrade bad power supply.
Page 2 of 5
Dificiencies
Building 264
1) Batteries failed date code. Replace with 9274 X2
Building 320
1) Strobe in weld shop failed to test.
Building 323
1) Batteries failed date code. Replace with 9274 X2.
Building 400
1) Bateries failed date code. Replace with 9276 X2
Building 401
1) Batteries failed date code. Replace with 9276 X2
Building 402
1) Needs system upgrade.
Building 404
1) Smoke detector outside room 116 needs new head. Replace with 9601.
2) Speaker above exercise bike failed to test.
Building 410
1) Room B21 failed to test M1-42. Replace with 9714 and 9792
2) M2-69 Hall by room A33 failed to test. Replace with 9714 and 9792
3) M1-37 2nd floor exit failed to test. Replace with 9714 and 9792
Building 412C
1) Batteries failed date code. Replace with 9275 X2
Page 3 of 5
Deficiencies
Building 416
1) Batteries load test 80%.
Building 420
1) M1-60 2nd floor dock mechanical room head missing. Replace with 4098-9756.
2) M1-58 2nd floor dock mechanical room head missing. Replace with 4098-9756.
Building 523
1) Batteries failed date code. Replace with
2) Explosion horn failed to test. Replace with 4901-9802
Building 524
1) Batteries load test @ 80%.
Building 1801
1) Batteries failed date code. Replace with 9276 X2
Building 1812
1) Batteries failed date code. Replace with 9276 X2
Building 90100
1) System needs upgrade not communicating.
2) Batteries failed date code. Replace with 9276 X2
3) Batteries failed date code. Replace with 9274 X2
Building 414
1) M2-185 Needs new CO2 cartridge.
2) Batteries failed date code. Replace with 9276 X2.
3) Batteries failed date code. Replace with 9274 X2.
Page 4 of 5
Deficiencies Totals
1) Smoke Detector 4098-9714 = 12
2) Smoke Base 4098-9792 = 6
3) Smoke Detector 4098-9601 = 1
4) Duct Sensor Housing 4 wire 4098-9756 = 2
5) Explosion Horn 4901-9802 = 1
6) Horn / Strobe 4903-9425 = 1
7) 10AH Battery 2081-9274 = 10
8) 18AH Battery 2081-9275 = 18
9) 33AH Battery 2081-9276 = 22
10) 50AH Battery 2081-9296 = 2
11) CO2 Cartridge
Page 5 of 5

Tang Report

FL1Bldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1AHU Cooler90Duct Detector-T1M1-13Simplex4098-9756pass
1AHU Cooler90Duct Detector-T1M1-14Simplex4098-9756pass
1Mezzanine90Duct Detector-T1M1-43Simplex4098-9756pass
1Mezzanine90Duct Detector-T1M1-44Simplex4098-9756FailExcessively Dirty
1Warehouse90Horn Strobe-T1Simplex4903-9425pass
1South Wall Store Area90Horn Strobe-T1Simplex4903-9425pass
1North Wall Store Area90Horn Strobe-T1Simplex4903-9425pass
1Lobby Area Barber Shop90Horn Strobe-T1Simplex4903-9425pass
1Old Kitchen Area90Horn Strobe-T1Simplex4903-9425pass
1Laundry Store90Horn Strobe-T1Simplex4903-9425pass
1SE Storage Area90Horn Strobe-T1Simplex4903-9425pass
1Warehouse90Main Fire Alarm PanelSimplex4020FailSeveral Troubles, 18 Ah batteries Fail date code, No Communication to Dispatch
1Receiving Exit90Pull Station-T1M1-01Simplex4099-9001pass
1Sales Exit90Pull Station-T1M1-27Simplex4099-9001pass
1Main Ent.90Pull Station-T1M1-29Simplex4099-9001pass
1Laundry Exit West90Pull Station-T1M1-32Simplex4099-9001pass
1Laundry Exit East90Pull Station-T1M1-34Simplex4099-9001pass
1Mall Exit East90Pull Station-T1M1-38Simplex4099-9001pass
1Outdoor Living Exit90Pull Station-T1M1-42Simplex4099-9001pass
1Mezzanine90Pull Station-T1M1-46Simplex4099-9001pass
1Receiving Area90Smoke Detector-T1M1-02Simplex4098-9714pass
1Receiving Area90Smoke Detector-T1M1-03Simplex4098-9714pass
1MP490Smoke Detector-T1M1-04Simplex4098-9714pass
1MP490Smoke Detector-T1M1-05Simplex4098-9714pass
1Cooler90Smoke Detector-T1M1-06Simplex4098-9714pass
1Break Room90Smoke Detector-T1M1-07Simplex4098-9714pass
1Janitor Closet90Smoke Detector-T1M1-08Simplex4098-9714FailExcessively Dirty
1Employee Restroom90Smoke Detector-T1M1-09Simplex4098-9714pass
1Staff Office90Smoke Detector-T1M1-10Simplex4098-9714pass
1Breakroom Hall90Smoke Detector-T1M1-11Simplex4098-9714FailExcessively Dirty
1Manager's Office90Smoke Detector-T1M1-12Simplex4098-9714pass
1Sales West90Smoke Detector-T1M1-15Simplex4098-9714pass
1Sales Center90Smoke Detector-T1M1-16Simplex4098-9714pass
1Sales East90Smoke Detector-T1M1-17Simplex4098-9714pass
1Sales East90Smoke Detector-T1M1-18Simplex4098-9714pass
1Sales Center90Smoke Detector-T1M1-19Simplex4098-9714pass
1Sales West90Smoke Detector-T1M1-20Simplex4098-9714pass
1Sales West90Smoke Detector-T1M1-21Simplex4098-9714pass
1Sales Center90Smoke Detector-T1M1-22Simplex4098-9714pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Sales East90Smoke Detector-T1M1-23Simplex4098-9714pass
1Checkout East90Smoke Detector-T1M1-24Simplex4098-9714pass
1Checkout West90Smoke Detector-T1M1-25Simplex4098-9714pass
1Sales West90Smoke Detector-T1M1-26Simplex4098-9714pass
1Vestibule90Smoke Detector-T1M1-28Simplex4098-9714pass
1Barber Shop90Smoke Detector-T1M1-30Simplex4098-9714pass
1Laundry90Smoke Detector-T1M1-31Simplex4098-9714pass
1Barber Storage90Smoke Detector-T1M1-33Simplex4098-9714pass
1Mall Area90Smoke Detector-T1M1-35Simplex4098-9714pass
1Women's Restroom90Smoke Detector-T1M1-36Simplex4098-9714pass
1Men's Restroom90Smoke Detector-T1M1-37Simplex4098-9714pass
1Old Restaraunt Area90Smoke Detector-T1M1-39Simplex4098-9714pass
1Food Support90Smoke Detector-T1M1-40Simplex4098-9714pass
1Outdoor Living90Smoke Detector-T1M1-41Simplex4098-9714pass
1Mezzanine90Smoke Detector-T1M1-45Simplex4098-9714pass
1Break Room90Strobe-T1Simplex4904-9168pass
1Men's Restroom90Strobe-T1Simplex4904-9168pass
1Women's Restroom90Strobe-T1Simplex4904-9168pass
1In BOSS System100Duct Detector-T1ZN4Simplex4098-9756pass
1In BOSS System100Duct Detector-T1ZN4Simplex4098-9756pass
1In 105100Duct Detector-T1M1-39Simplex4098-9756pass
1In 106100Heat Detector-T1M1-31Simplex4098-9733pass
1In 104100Heat Detector-T1M1-30Simplex4098-9733pass
1Women's Restroom Closet100Heat Detector-T1M1-13Simplex4098-9733pass
1Men's Restroom Closet100Heat Detector-T1M1-06Simplex4098-9733pass
1Men's Restroom100Heat Detector-T1M1-05Simplex4098-9733pass
1Women's Restroom100Heat Detector-T1M1-12Simplex4098-9733pass
1Janitor Closet100Heat Detector-T1M1-10Simplex4098-9733pass
1Admin. Office Area100Heat Detector-T1M1-08Simplex4098-9733pass
1Admin. Office Area100Heat Detector-T1M1-09Simplex4098-9733pass
1Admin. Office Conf. Room100Heat Detector-T1M1-07Simplex4098-9733pass
1Conf. Room Restroom100Heat Detector-T1M1-04Simplex4098-9733pass
1Front Entrance100Horn Strobe-T1Simplex4903-9425pass
1Rear Exit100Horn Strobe-T1SimplexFailNo Strobe
1In 103100Horn Strobe-T1Simplex4903-9425pass
1In 104100Horn Strobe-T1Simplex4903-9425pass
1In 105100Horn Strobe-T1Simplex4903-9425pass
1In 105 Rear100Horn Strobe-T1Simplex4903-9425pass
1Women's Restroom100Horn Strobe-T1Simplex4903-9425pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Hall By Restrooms100Horn Strobe-T1Simplex4903-9425pass
1Hall By Restrooms100Horn Strobe-T1Simplex4903-9425pass
1Office Area100Horn Strobe-T1Simplex4903-9425pass
1Office Area100Horn Strobe-T1Simplex4903-9425pass
1Office Area Conf. Room100Horn Strobe-T1Simplex4903-9425pass
1Conference Room100Horn Strobe-T1Simplex4903-9425pass
1Men's Restroom100Horn Strobe-T1Simplex4903-9425pass
1In BOSS System100Horn-T1Simplex4901-9822pass
1Mech. Room100Main Fire Alarm PanelSimplex4100FailTrouble on Panel, 18 Ah batteries Fail date code, No communication to Dispatch
1Rear Exit100Pull Station-T1M1-17Simplex4099-9001Pass
1Front Entrance100Pull Station-T1M1-14Simplex4099-9001pass
1By FACP100Pull Station-T1M1-27Simplex4099-9001pass
1In 103100Pull Station-T1M1-29Simplex4099-9001pass
1In 105100Pull Station-T1M1-37Simplex4099-9001pass
1Conf. Room Exit100Pull Station-T1M1-02Simplex4099-9001pass
1Rear Exit100Smoke Detector-T1M1-18Simplex4098-9714pass
1Front Entrance100Smoke Detector-T1M1-17Simplex4098-9714pass
1Above FACP100Smoke Detector-T1M1-25Simplex4098-9714pass
1In 103100Smoke Detector-T1M1-32Simplex4098-9714pass
1VESDA100Smoke Detector-T1M1-45Simplex4098-9714pass
1Conference Room100Smoke Detector-T1M1-40Simplex4098-9714pass
1Conference Room100Smoke Detector-T1M1-01Simplex4098-9714pass
1Conference Room100Smoke Detector-T1M1-03Simplex4098-9714pass
1BOSS System (In)100Smoke Detector-T1ZN3Simplex4098-9714pass
1BOSS System (Under)100Smoke Detector-T1ZN2Simplex4098-9714pass
1Smoke100Smoke Detector-T1M1-11Simplex4098-9714pass
1In 102100Smoke Detector-T1M1-28Simplex4098-9714pass
1BOSS VESDA Power Supply100SPPSSimplexVESDApass
1Mech. Room101Heat Detector-T1M1-06Simplex4098-9733pass
1Main Ent.101Horn Strobe-T1Simplex4903-9425pass
1East At Rear Exit101Horn Strobe-T1Simplex4903-9425pass
1Men's Restroom101Horn Strobe-T1Simplex4903-9425pass
1Women's Restroom101Horn Strobe-T1Simplex4903-9425pass
1West At Rear Exit101Horn Strobe-T1Simplex4903-9425pass
1By FACP101Horn Strobe-T1Simplex4903-9425pass
1Mech. Room101Main Fire Alarm PanelSimplex4009Fail18 Ah batteries faile date code, battery trouble on panel
1Mech. Room101Pull Station-T1M1-01Simplex4099-9001pass
1N. Ent.101Pull Station-T1M1-07Simplex4099-9001pass
1East Hall101Pull Station-T1M1-13Simplex4099-9001pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1West Hall101Pull Station-T1M1-15Simplex4099-9001pass
1N. Ent.101Smoke Detector-T1M1-08Simplex4098-9714pass
1Janitor Closet101Smoke Detector-T1M1-09Simplex4098-9714pass
1Main Hall101Smoke Detector-T1M1-10Simplex4098-9714pass
1Main Hall101Smoke Detector-T1M1-11Simplex4098-9714pass
1East Hall101Smoke Detector-T1M1-12Simplex4098-9714pass
1West Hall101Smoke Detector-T1M1-14Simplex4098-9714pass
1Room 182102Duct Detector-T1M1-51Simplex4098-9756pass
1Room 182102Duct Detector-T1M1-52Simplex4098-9756pass
1Room 120102Duct Detector-T1M1-55Simplex4098-9756Pass
1Room 120102Duct Detector-T1M1-53Simplex4098-9756pass
1Room 120102Duct Detector-T1M1-47Simplex4098-9756pass
1Room 184102Duct Detector-T1M1-76Simplex4098-9756pass
1Room 184102Duct Detector-T1M1-77Simplex4098-9756pass
1Room 137102Heat Detector-T1M1-31Simplex4098-9733pass
1Room 107102Heat Detector-T1M1-79Simplex4098-9733pass
1Room 107102Heat Detector-T1M1-80Simplex4098-9733pass
1Room 108102Heat Detector-T1M1-69Simplex4098-9733pass
1Room 108102Heat Detector-T1M1-70Simplex4098-9733Pass
1Room 109102Heat Detector-T1M1-71Simplex4098-9733Pass
1Room 110102Heat Detector-T1M1-65Simplex4098-9733pass
1Room 110102Heat Detector-T1M1-66Simplex4098-9733pass
1Room 110102Heat Detector-T1M1-72Simplex4098-9733pass
1Room 110102Heat Detector-T1M1-73Simplex4098-9733pass
1Room 182102Heat Detector-T1M1-49Simplex4098-9733pass
1Room 120102Heat Detector-T1M1-46Simplex4098-9733pass
1Room 117102Heat Detector-T1M1-61Simplex4098-9733pass
1Room 117102Heat Detector-T1M1-62Simplex4098-9733pass
1Room 184102Heat Detector-T1M1-82Simplex4098-9733pass
1Room 181102Heat Detector-T1M1-07Simplex4098-9733pass
1Room 181102Heat Detector-T1M1-10Simplex4098-9733pass
1By 142102Horn Strobe-T1Simplex4903-9425pass
1Server Room in 140102Horn Strobe-T1Simplex4903-9425pass
1Room 140102Horn Strobe-T1Simplex4903-9425pass
1Room 138102Horn Strobe-T1Simplex4903-9425pass
1Customer Service Area102Horn Strobe-T1Simplex4903-9425pass
1Mail Room Entrance102Horn Strobe-T1Simplex4903-9425pass
1Room 137102Horn Strobe-T1Simplex4903-9425pass
1By Room 133102Horn Strobe-T1Simplex4903-9425pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Room 135102Horn Strobe-T1Simplex4903-9425pass
1Room 135102Horn Strobe-T1Simplex4903-9425pass
1Room 134102Horn Strobe-T1Simplex4903-9425pass
1Room 136102Horn Strobe-T1Simplex4903-9425pass
1Hall By 102102Horn Strobe-T1Simplex4903-9425pass
1Room 129102Horn Strobe-T1Simplex4903-9425pass
1Room 129102Horn Strobe-T1Simplex4903-9425pass
1Room 131102Horn Strobe-T1Simplex4903-9425pass
1Room 129 Control Room102Horn Strobe-T1Simplex4903-9425pass
1Room 131102Horn Strobe-T1Simplex4903-9425Pass
1Room 102102Horn Strobe-T1Simplex4903-9425pass
1Room 102102Horn Strobe-T1Simplex4903-9425pass
1Room 103102Horn Strobe-T1Simplex4903-9425pass
1Room 107102Horn Strobe-T1Simplex4903-9425pass
1Room 107102Horn Strobe-T1Simplex4903-9425pass
1Hall at 125102Horn Strobe-T1Simplex4903-9425pass
1Men's Restroom102Horn Strobe-T1Simplex4903-9425pass
1Men's Restroom102Horn Strobe-T1Simplex4903-9425pass
1Women's Restroom102Horn Strobe-T1Simplex4903-9425pass
1Women's Restroom102Horn Strobe-T1Simplex4903-9425Pass
1Room 108102Horn Strobe-T1Simplex4903-9425pass
1Room 108102Horn Strobe-T1Simplex4903-9425pass
1Room 109102Horn Strobe-T1Simplex4903-9425pass
1Hall By 120102Horn Strobe-T1Simplex4903-9425pass
1Hall By 119102Horn Strobe-T1Simplex4903-9425pass
1Room 110102Horn Strobe-T1Simplex4903-9425pass
1Room 110102Horn Strobe-T1Simplex4903-9425pass
1Room 110102Horn Strobe-T1Simplex4903-9425pass
1Room 110102Horn Strobe-T1Simplex4903-9425Pass
1Room 110102Horn Strobe-T1Simplex4903-9425Pass
1Room 112102Horn Strobe-T1Simplex4903-9425pass
1Room 116102Horn Strobe-T1Simplex4903-9425pass
1Room 182102Horn Strobe-T1Simplex4903-9425pass
1Room 120102Horn Strobe-T1Simplex4903-9425pass
1Room 119102Horn Strobe-T1Simplex4903-9425pass
1Room 119102Horn Strobe-T1Simplex4903-9425pass
1Room 116102Horn Strobe-T1Simplex4903-9425pass
1Room 117102Horn Strobe-T1Simplex4903-9425pass
1Room 184102Horn Strobe-T1Simplex4903-9425pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Room 181102Horn Strobe-T1Simplex4903-9425pass
1Elec. Room102Main Fire Alarm PanelSimplex4100FailPositive and Negative Earth grounds, Several troubles for other buildings, 33 Ah batteries Fail date code
1By 142102Pull Station-T1M1-17Simplex4099-9001pass
1Mail Room Entrance102Pull Station-T1M1-23Simplex4099-9001pass
1By 132102Pull Station-T1M1-37Simplex4099-9001pass
1Room 107102Pull Station-T1M1-86Simplex4099-9001pass
1Room 108102Pull Station-T1M1-63Simplex4099-9001pass
1Room 108102Pull Station-T1M1-74Simplex4099-9001pass
1Room 110102Pull Station-T1M1-68Simplex4099-9001pass
1Room 110102Pull Station-T1M1-67Simplex4099-9001Pass
1By 116102Pull Station-T1M1-58Simplex4099-9001pass
1By Annunciator102Pull Station-T1M1-60Simplex4099-9001pass
1Room 182102Pull Station-T1M1-50Simplex4099-9001pass
1Room 184102Pull Station-T1M1-75Simplex4099-9001pass
1Room 181102Pull Station-T1M1-01Simplex4099-9001pass
1By FACP102Pull Station-T1M1-11Simplex4099-9001pass
1Entrance102Remote Annunciators-T1Simplex4603-9101pass
1Room 138102Smoke Detector-T1M1-18Simplex4098-9714pass
1Room 138102Smoke Detector-T1M1-20Simplex4098-9714pass
1Hall To 138102Smoke Detector-T1M1-22Simplex4098-9714Pass
1Hall By 133102Smoke Detector-T1M1-30Simplex4098-9714pass
1Room 136102Smoke Detector-T1M1-26Simplex4098-9714pass
1Entrance To 132102Smoke Detector-T1M1-36Simplex4098-9714pass
1By 102102Smoke Detector-T1M1-39Simplex4098-9714pass
1Men's Restroom102Smoke Detector-T1M1-43Simplex4098-9714pass
1Women's Restroom102Smoke Detector-T1M1-45Simplex4098-9714pass
1Hall By Restrooms102Smoke Detector-T1M1-41Simplex4098-9714pass
1Room 178102Smoke Detector-T1M1-48Simplex4098-9714pass
1By 108102Smoke Detector-T1M1-64Simplex4098-9714pass
1By 120102Smoke Detector-T1M1-56Simplex4098-9714Pass
1By 116102Smoke Detector-T1M1-57Simplex4098-9714pass
1Vestibule By Annunciator102Smoke Detector-T1M1-59Simplex4098-9714pass
1Above FACP102Smoke Detector-T1M1-12Simplex4098-9714pass
1VESDA Power Supply102SPPSSimplexPower Supplypass
1Room 105102Strobe-T1Simplex4904-9168pass
1Room 106102Strobe-T1Simplex4904-9168pass
1Room 113102Strobe-T1Simplex4904-9168pass
1Storage110Heat Detector-T1M1-18Simplex4098-9733Not Tested soon to be demolished
1Main Hall110Horn Strobe-T1Simplex4903-9425Not Tested soon to be demolished
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Room 5110Horn Strobe-T1Simplex4903-9425Not Tested soon to be demolished
1Restroom110Horn Strobe-T1Simplex4903-9425Not Tested soon to be demolished
1Men's Restroom110Main Fire Alarm PanelSimplex4009Not Tested soon to be demolished
1Instrument110Pull Station-T1M1-07Simplex4099-9001Not Tested soon to be demolished
1Break Room110Pull Station-T1M1-16Simplex4099-9001Not Tested soon to be demolished
1Men's Restroom110Pull Station-T1M1-19Simplex4099-9001Not Tested soon to be demolished
1Office110Pull Station-T1M1-24Simplex4099-9001Not Tested soon to be demolished
1Communication110Pull Station-T1M1-26Simplex4099-9001Not Tested soon to be demolished
1Storage Room110Smoke Detector-T1M1-01Simplex4098-9714Not Tested soon to be demolished
1Storage Room110Smoke Detector-T1M1-02Simplex4098-9714Not Tested soon to be demolished
1Doppler Room110Smoke Detector-T1M1-03Simplex4098-9714Not Tested soon to be demolished
1Doppler Room110Smoke Detector-T1M1-04Simplex4098-9714Not Tested soon to be demolished
1Instrument110Smoke Detector-T1M1-05Simplex4098-9714Not Tested soon to be demolished
1Instrument110Smoke Detector-T1M1-06Simplex4098-9714Not Tested soon to be demolished
1Instrument110Smoke Detector-T1M1-07Simplex4098-9714Not Tested soon to be demolished
1Break Room110Smoke Detector-T1M1-17Simplex4098-9714Not Tested soon to be demolished
1Navigation110Smoke Detector-T1M1-20Simplex4098-9714Not Tested soon to be demolished
1Corridor110Smoke Detector-T1M1-21Simplex4098-9714Not Tested soon to be demolished
1Branch Office110Smoke Detector-T1M1-22Simplex4098-9714Not Tested soon to be demolished
1Office110Smoke Detector-T1M1-23Simplex4098-9714Not Tested soon to be demolished
1Communication110Smoke Detector-T1M1-25Simplex4098-9714Not Tested soon to be demolished
1Communication110Smoke Detector-T1M1-27Simplex4098-9714Not Tested soon to be demolished
1Center Main Exit Bay111Bell-T1SimplexBellpass
1Electroenvironmental Shop111Heat Detector-T1Simplex4098-9733pass
1Electroenvironmental Shop111Heat Detector-T1Simplex4098-9733pass
1Elec. Shop111Heat Detector-T1Simplex4098-9733pass
1Elec. Shop111Heat Detector-T1Simplex4098-9733pass
1Accessories Office111Heat Detector-T1Simplex4098-9733pass
1Neudraulic Shop111Heat Detector-T1Simplex4098-9733pass
1Neudraulic Shop111Heat Detector-T1Simplex4098-9733Pass
1Break Room111Heat Detector-T1Simplex4098-9733pass
1Locker Room111Heat Detector-T1Simplex4098-9733pass
1Tool Room111Heat Detector-T1Simplex4098-9733pass
1Tool Room111Heat Detector-T1Simplex4098-9733pass
1Maintenance Group Kitchen111Heat Detector-T1Simplex4098-9733pass
1Capt. Ferguson Office111Heat Detector-T1Simplex4098-9733pass
1CSMGT. Ashley Office111Heat Detector-T1Simplex4098-9733pass
1Lt. Col. Seluidge Office111Heat Detector-T1Simplex4098-9733pass
1Col. Lanbust Office111Heat Detector-T1Simplex4098-9733pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Col. Lanbust Office111Heat Detector-T1Simplex4098-9733pass
1Equip. Maint. Cheif Office111Heat Detector-T1Simplex4098-9733pass
1Extra Office111Heat Detector-T1Simplex4098-9733pass
1Fuel Shop111Heat Detector-T1Simplex4098-9733pass
1Fuel Shop111Heat Detector-T1Simplex4098-9733pass
1Fuel Shop Locker Room111Heat Detector-T1Simplex4098-9733pass
1Neudraulic Shop111Horn Strobe-T1Simplex4903-9425pass
1Restroom West111Horn Strobe-T1Simplex4903-9425Pass
1Maintenance Group111Horn Strobe-T1Simplex4903-9425Pass
1Fuel Shop111Horn Strobe-T1Simplex4903-9425Pass
1Fuel Shop Locker Room111Horn Strobe-T1Simplex4903-9425pass
1Elec. Room111Main Fire Alarm PanelSimplex4100pass18 Ah Batteries 2020-90%
1Center Main Bay Exit111Pull Station-T1Simplex4099-9001pass
1Right Main Bay Exit111Pull Station-T1Simplex4099-9001pass
1Right Main Bay Exit Tarmac111Pull Station-T1Simplex4099-9001pass
1Left Main Bay Exit Tarmac111Pull Station-T1Simplex4099-9001pass
1Electro Environmental Shop111Pull Station-T1Simplex4099-9001pass
1Elec. Shop111Pull Station-T1Simplex4099-9001pass
1Pneudraulic Shop111Pull Station-T1Simplex4099-9001pass
1Break Room111Pull Station-T1Simplex4099-9001pass
1Restroom West111Pull Station-T1Simplex4099-9001pass
1Tool Room111Pull Station-T1Simplex4099-9001pass
1Maintenance Group111Pull Station-T1Simplex4099-9001pass
1Extra Office111Pull Station-T1Simplex4099-9001pass
1Maintenance Group Exit111Pull Station-T1Simplex4099-9001pass
1Field Shop111Pull Station-T1Simplex4099-9001pass
1Fuel Shop Locker Room111Smoke Detector-T1Simplex4098-9714pass
1Restroom111Strobe-T1Simplex4904-9168pass
1Restroom111Strobe-T1Simplex4904-9168pass
1Center Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Center Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Right Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Right Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Right Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Left Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Left Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1Left Main Bay Exit111UVIR Flame DetectorSimplexFlame Det.pass
1BLDG 113 MECH/ELECT RM 7:M1-14113Combo Detector-T1M1-14-1SimplexBuilding under renovation
1Bldg+B320 113 Aircraft Bay 7:M1-25113Combo Detector-T1M1-25-1SimplexBuilding under renovation
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1BLDG 113 AIRCRAFT BAY 7:M1-33113Combo Detector-T1M1-33-1SimplexBuilding under renovation
1BLDG 113 JANITOR CLOSET 7:M1-34113Heat Detector-T1M1-34-0Simplex4098-9733Building under renovation
1BLDG 113 CORR BY FLIGHT LINE 7:M1-37113Combo Detector-T1M1-37-1SimplexBuilding under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-42113Combo Detector-T1M1-42-1SimplexBuilding under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-49113Combo Detector-T1M1-49-1SimplexBuilding under renovation
1BLDG 113 NOSE BAY 7:M1-50113Combo Detector-T1M1-50-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-52113Combo Detector-T1M1-52-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-53113Combo Detector-T1M1-53-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-54113Combo Detector-T1M1-54-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-55113Combo Detector-T1M1-55-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-56113Combo Detector-T1M1-56-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-57113Combo Detector-T1M1-57-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-61113Combo Detector-T1M1-61-1SimplexBuilding under renovation
1BLDG 113 FLIGHT BAY 7:M1-62113Heat Detector-T1M1-62-0Simplex4098-9733Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-75113Combo Detector-T1M1-75-1SimplexBuilding under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-85113Combo Detector-T1M1-85-1SimplexBuilding under renovation
1BLDG 113 MEN'S RESTRM PAU-1 7:M1-31113Duct Detector-T1M1-31-0Simplex4098-9756Building under renovation
1BLDG 113 MEN'S RESTRM PAU-1 7:M1-32113Duct Detector-T1M1-32-0Simplex4098-9756Building under renovation
1BLDG 113 CORR BY FLIGHT LINE 7:M1-38113Duct Detector-T1M1-38-0Simplex4098-9756Building under renovation
1BLDG 113 CORR BY FLIGHT LINE 7:M1-39113Duct Detector-T1M1-39-0Simplex4098-9756Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-47113Duct Detector-T1M1-47-0Simplex4098-9756Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-48113Duct Detector-T1M1-48-0Simplex4098-9756Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-69113Duct Detector-T1M1-69-0Simplex4098-9756Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-70113Duct Detector-T1M1-70-0Simplex4098-9756Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-71113Duct Detector-T1M1-71-0Simplex4098-9756Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-72113Duct Detector-T1M1-72-0Simplex4098-9756Building under renovation
1BLDG 113 MECH/ELECT RM EXIT 7:M1-11113Pull Station-T1M1-11-0Simplex4099-9001Building under renovation
1BLDG 113 MECH/ELECT RM EXIT 7:M1-15113Pull Station-T1M1-15-0Simplex4099-9001Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-26113Pull Station-T1M1-26-0Simplex4099-9001Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-27113Pull Station-T1M1-27-0Simplex4099-9001Building under renovation
1BLDG 113 CORR BY FLIGHT LINE 7:M1-41113Pull Station-T1M1-41-0Simplex4099-9001Building under renovation
1BLDG 113 CORR BY FLIGHT CHIEF 7:M1-44113Pull Station-T1M1-44-0Simplex4099-9001Building under renovation
1BLDG 113 BREAK RM EXIT 7:M1-46113Pull Station-T1M1-46-0Simplex4099-9001Building under renovation
1BLDG 113 NOSE BAY EXIT 7:M1-51113Pull Station-T1M1-51-0Simplex4099-9001Building under renovation
1BLDG 113 ISO DOCK EXIT 7:M1-58113Pull Station-T1M1-58-0Simplex4099-9001Building under renovation
1BLDG 113 CORR EXIT BY SUPPLY RM 7:M1-59113Pull Station-T1M1-59-0Simplex4099-9001Building under renovation
1BLDG 113 CORROSION CONTROL EXIT 7:M1-65113Pull Station-T1M1-65-0Simplex4099-9001Building under renovation
1BLDG 113 SHEETMETAL SHOP EXIT 7:M1-81113Pull Station-T1M1-81-0Simplex4099-9001Building under renovation
1BLDG 113 AIRCRAFT BAY 7:M1-86113Pull Station-T1M1-86-0Simplex4099-9001Building under renovation
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1BLDG 113 AIRCRAFT BAY 7:M1-87113Pull Station-T1M1-87-0Simplex4099-9001Building under renovation
1BLDG 113 MACHNE SHOP EXIT 7:M1-88113Pull Station-T1M1-88-0Simplex4099-9001Building under renovation
1BLDG 113 WELDING SHOP EXIT 7:M1-89113Pull Station-T1M1-89-0Simplex4099-9001Building under renovation
1BLDG 113 MECH/ELECT RM 7:M1-12113Smoke Detector-T1M1-12-0Simplex4098-9714Building under renovation
1BLDG 113 CORR BY FLIGHT LINE 7:M1-36113Smoke Detector-T1M1-36-0Simplex4098-9714Building under renovation
1BLDG 113 CORR BY FLIGHT LINE 7:M1-40113Smoke Detector-T1M1-40-0Simplex4098-9714Building under renovation
1BLDG 113 CORR BY FLIGHT CHIEF 7:M1-43113Smoke Detector-T1M1-43-0Simplex4098-9714Building under renovation
1BLDG 113 CORR BY SUPPLY RM 7:M1-60113Smoke Detector-T1M1-60-0Simplex4098-9714Building under renovation
1BLDG 113 CORROSION CONTROL 7:M1-67113Smoke Detector-T1M1-67-0Simplex4098-9714Building under renovation
1BLDG 113 SHEETMETAL SHOP 7:M1-73113Smoke Detector-T1M1-73-0Simplex4098-9714Building under renovation
1RM 131113Strobe-T1SimplexBuilding under renovation
1RM 126 By Exit113Strobe-T1SimplexBuilding under renovation
1Machine Shop Rear113Strobe-T1SimplexBuilding under renovation
1RM 132113Strobe-T1SimplexBuilding under renovation
1RM 128113Strobe-T1SimplexBuilding under renovation
1Front left hanger wall113Strobe-T1SimplexBuilding under renovation
1Outside RM 125113Strobe-T1SimplexBuilding under renovation
1Outside 110 Storage113Strobe-T1SimplexBuilding under renovation
1Rm 113 Corridor113Strobe-T1SimplexBuilding under renovation
1RM 108113Strobe-T1SimplexBuilding under renovation
1Mens Locker Rear Exit113Strobe-T1SimplexBuilding under renovation
1Outside Rm 102113Strobe-T1SimplexBuilding under renovation
1RM 102 Rear113Strobe-T1SimplexBuilding under renovation
1Left Rear Bay113Strobe-T1SimplexBuilding under renovation
1Rm 129113Strobe-T1SimplexBuilding under renovation
1Bay by Rm 115113Strobe-T1SimplexBuilding under renovation
1Rm 126 Exit to Hanger113Speaker Strobe-T1SimplexBuilding under renovation
1Rm 126 By Exit113Speaker Strobe-T1SimplexBuilding under renovation
1Rm 126 Rear113Speaker Strobe-T1SimplexBuilding under renovation
1RM 126 by Exit113Speaker Strobe-T1SimplexBuilding under renovation
1Rm 126 By Piess113Speaker Strobe-T1SimplexBuilding under renovation
1Outside RM 128 Left113Speaker Strobe-T1SimplexBuilding under renovation
1Outside Rm 128 Right113Speaker Strobe-T1SimplexBuilding under renovation
1Machine Shop By Exit to Hanger113Speaker Strobe-T1SimplexBuilding under renovation
1Outside RM 132 By Exit113Speaker Strobe-T1SimplexBuilding under renovation
1Weld Shop Rear Exit113Speaker Strobe-T1SimplexBuilding under renovation
1Weld Shop Front113Speaker Strobe-T1SimplexBuilding under renovation
1Outside RM 122113Speaker Strobe-T1SimplexBuilding under renovation
1RM 122113Speaker Strobe-T1SimplexBuilding under renovation
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Rm 120113Speaker Strobe-T1SimplexBuilding under renovation
1RM 118113Speaker Strobe-T1SimplexBuilding under renovation
1RM 121113Speaker Strobe-T1SimplexBuilding under renovation
1Nose Dock Left113Speaker Strobe-T1SimplexBuilding under renovation
1Nose Dock Right113Speaker Strobe-T1SimplexBuilding under renovation
1Outside 107 Mens Locker113Speaker Strobe-T1SimplexBuilding under renovation
1RM 111 Rear113Speaker Strobe-T1SimplexBuilding under renovation
1RM 111 Front113Speaker Strobe-T1SimplexBuilding under renovation
1RM 113 Corridor113Speaker Strobe-T1SimplexBuilding under renovation
1Rm 113113Speaker Strobe-T1SimplexBuilding under renovation
1RR by 107 Mens113Speaker Strobe-T1SimplexBuilding under renovation
1Mens RR Rear113Speaker Strobe-T1SimplexBuilding under renovation
1Mens Locker RM Front113speaker Strobe-T1SimplexBuilding under renovation
1Mens RR Rear113Speaker Strobe-T1SimplexBuilding under renovation
1Bay Outside Womens RR113Speaker Strobe-T1SimplexBuilding under renovation
1By Womens Shower113Speaker Strobe-T1SimplexBuilding under renovation
1Womens RR113Speaker Strobe-T1SimplexBuilding under renovation
1RM 102 Front113Speaker Strobe-T1SimplexBuilding under renovation
1Outside RM 130113Speaker Strobe-T1SimplexBuilding under renovation
1Sheet Metal Shop Exit to Hanger113Speaker Strobe-T1SimplexBuilding under renovation
1RM 129113Speaker Strobe-T1SimplexBuilding under renovation
1Breakroom By Exit113Speaker Strobe-T1SimplexBuilding under renovation
1Outside Sprinkler Riser RM113Speaker Strobe-T1SimplexBuilding under renovation
1Sprinkler Riser RM113Speaker Strobe-T1SimplexBuilding under renovation
1Front Left Hanger Wall113Speaker-T1SimplexBuilding under renovation
1By RM 108113Speaker-T1SimplexBuilding under renovation
1Outside RM 102113Speaker-T1SimplexBuilding under renovation
1Left Rear Bay113Speaker-T1SimplexBuilding under renovation
1Bay By RM 115113Speaker-T1SimplexBuilding under renovation
1In Sheet Metal Shop113Power Supply-T1Simplex4009Building under renovation
1By 109120Horn Strobe-T1Simplex4903-9425Pass
1Main Entrance120Horn Strobe-T1Simplex4903-9425Pass
1By 117120Horn Strobe-T1Simplex4903-9425Pass
1In 124120Horn Strobe-T1Simplex4903-9425Pass
1Rear Exit Near 124120Horn Strobe-T1Simplex4903-9425Pass
1Exit By 133120Horn Strobe-T1Simplex4903-9425Pass
1In 137 Supply Bay120Horn Strobe-T1Simplex4903-9425Pass
1Comm Room120Main Fire Alarm PanelSimplex4100Fail33Ah batteries fail date code, trouble on panel
1Main Lobby120Pull Station-T1M1-01Simplex4099-9001Pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Hall At Breakroom120Pull Station-T1M1-02Simplex4099-9001Pass
1Men's Restroom120Strobe-T1Simplex4904-9168Pass
1Women's Restroom120Strobe-T1Simplex4904-9168Pass
1Lobby Restroom120Strobe-T1Simplex4904-9168Pass
1BDOC120Strobe-T1Simplex4904-9168Pass
1Mech. Elec. Room123Duct Detector-T1M1-14Simplex4098-9756Pass
1Mech. Elec. Room123Duct Detector-T1M1-15Simplex4098-9756Pass
1Office 111123Heat Detector-T1M1-01Simplex4098-9733Pass
1Office 102123Heat Detector-T1M1-03Simplex4098-9733Pass
1Conference Room 110123Heat Detector-T1M1-04Simplex4098-9733Pass
1Women's Restroom123Heat Detector-T1M1-05Simplex4098-9733Pass
1Closet 108123Heat Detector-T1M1-07Simplex4098-9733Pass
1Men's Restroom123Heat Detector-T1M1-09Simplex4098-9733Pass
1Office 107123Heat Detector-T1M1-11Simplex4098-9733Pass
1Main Lobby123Horn Strobe-T1Simplex4903-9425FailNo Strobe
1Rear Office123Horn Strobe-T1Simplex4903-9425Pass
1Mech. Room123Main Fire Alarm PanelSimplex4100FailTroubles on panel, 18 Ah batteries fail date code
1Rear Exit123Pull Station-T1M1-08Simplex4099-9001Pass
1Front Exit123Pull Station-T1M1-12Simplex4099-9001Pass
1Mech. Elec. Room123Pull Station-T1M1-13Simplex4099-9001Pass
1Front Corridor123Smoke Detector-T1M1-02Simplex4098-9714Pass
1Comm. Room123Smoke Detector-T1M1-06Simplex4098-9714Pass
1Mech. Elec. Room123Smoke Detector-T1M1-10Simplex4098-9714Pass
1Reatroom123Strobe-T1Simplex4904-9168Pass
1Reatroom123Strobe-T1Simplex4904-9168Pass
1Alarm Room124CO Detector-T11:M1-81SimplexCOPass
2Hallway124CO Detector-T11:M1-44SimplexCOPass
2Hallway124CO Detector-T11:M1-45SimplexCOPass
2Hallway124CO Detector-T11:M1-50SimplexCOFailOpen Circuit
2Kitchen124CO Detector-T11:M1-60SimplexCOPass
2Bunk Room 1124CO Detector-T11:M1-26SimplexCOFailDisabled upon arrival
2Bunk Room 2124CO Detector-T11:M1-27SimplexCOPass
2Bunk Room 3124CO Detector-T11:M1-32SimplexCOPass
2Bunk Room 4124CO Detector-T11:M1-33SimplexCOPass
2Bunk Room 5124CO Detector-T11:M1-38SimplexCOPass
2Bunk Room 6124CO Detector-T11:M1-39SimplexCOPass
1Mech Room124Duct Detector-T11:M1-10Simplex4098-9756Pass
1Mech Room124Duct Detector-T11:M1-11Simplex4098-9756Pass
2Mech Room124Duct Detector-T11:M1-52Simplex4098-9756Pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
2Mech Room124Duct Detector-T11:M1-53Simplex4098-9756Pass
2Mech Room124Duct Detector-T11:M1-54Simplex4098-9756Pass
2Mech Room124Duct Detector-T11:M1-55Simplex4098-9756Pass
1Hallway124Heat Detector-T11:M1-71Simplex4098-9733Pass
1Hallway124Heat Detector-T11:M1-73Simplex4098-9733Pass
1Hallway124Heat Detector-T11:M1-75Simplex4098-9733Pass
1Hallway124Heat Detector-T11:M1-77Simplex4098-9733Pass
1Hallway (Combo)124Heat Detector-T11:M1-67Simplex4098-9733Pass
1Hallway (Combo)124Heat Detector-T11:M1-69Simplex4098-9733Pass
1Comm Room124Heat Detector-T11:M1-63Simplex4098-9733Pass
1Deputy Chief Office124Heat Detector-T11:M1-65Simplex4098-9733Pass
2Hallway124Heat Detector-T11:M1-47Simplex4098-9733Pass
2Hallway124Heat Detector-T11:M1-49Simplex4098-9733Pass
2Hallway124Heat Detector-T11:M1-57Simplex4098-9733Pass
2Hallway124Heat Detector-T11:M1-59Simplex4098-9733Pass
2Hallway124Heat Detector-T11:M1-43Simplex4098-9733Pass
1Garage Area @ Door 6124Horn Strobe-T1Simplex4903-9425Pass
1Garage Area @ Door 3124Horn Strobe-T1Simplex4903-9425Pass
1Garage Area @ Door 1124Horn Strobe-T1Simplex4903-9425Pass
1Garage Area @ Door 12124Horn Strobe-T1Simplex4903-9425Pass
1Garage Area @ Door 9124Horn Strobe-T1Simplex4903-9425Pass
1Garage Area @ Door 7124Horn Strobe-T1Simplex4903-9425Pass
1Hallway @ Room 108124Horn Strobe-T1Simplex4903-9425Pass
1Room 107124Horn Strobe-T1Simplex4903-9425Pass
1Exit @ Room 102124Horn Strobe-T1Simplex4903-9425Pass
1Hallway @ Room 101124Horn Strobe-T1Simplex4903-9425Pass
1Hallway @ Room 104124Horn Strobe-T1Simplex4903-9425Pass
2Room 206124Horn Strobe-T1Simplex4903-9425Pass
2Hallway @ Room 207124Horn Strobe-T1Simplex4903-9425Pass
2Hallway @ Room 205124Horn Strobe-T1Simplex4903-9425Pass
2Room 207124Horn Strobe-T1Simplex4903-9425Pass
2Room 205124Horn Strobe-T1Simplex4903-9425Pass
2Room 204124Horn Strobe-T1Simplex4903-9425Pass
2Room 203124Horn Strobe-T1Simplex4903-9425Pass
2Room 202124Horn Strobe-T1Simplex4903-9425Pass
2Room 201124Horn Strobe-T1Simplex4903-9425Pass
2Hallway @ Showers124Horn Strobe-T1Simplex4903-9425Pass
2Men's Showers124Horn Strobe-T1Simplex4903-9425Pass
2Women's Showers124Horn Strobe-T1Simplex4903-9425Pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
2Break Area124Horn Strobe-T1Simplex4903-9425Pass
1Comm Room124Main Fire Alarm PanelSimplex4100Fail35 Ah batteries 2021-100%, Transponder 35 Ah batteries fail date code. Several Troubles
1Hallway124Pull Station-T11:M1-82Simplex4099-9001Pass
1Main Entrance124Pull Station-T11:M1-83Simplex4099-9001Pass
1Apparatus Bay124Pull Station-T11:M1-01Simplex4099-9001Pass
1Apparatus Bay124Pull Station-T11:M1-02Simplex4099-9001Pass
1Apparatus Bay124Pull Station-T11:M1-03Simplex4099-9001Pass
1Apparatus Bay124Pull Station-T11:M1-04Simplex4099-9001Pass
1Apparatus Bay124Pull Station-T11:M1-05Simplex4099-9001Pass
1Extinguisher Room124Pull Station-T11:M1-06Simplex4099-9001Pass
1Hallway124Pull Station-T11:M1-13Simplex4099-9001Pass
2Hallway124Pull Station-T11:M1-51Simplex4099-9001Pass
2Day Room124Pull Station-T11:M1-61Simplex4099-9001Pass
1Hallway124Smoke Detector-T11:M1-70Simplex4098-9714Pass
1Hallway124Smoke Detector-T11:M1-72Simplex4098-9714Pass
1Hallway124Smoke Detector-T11:M1-74Simplex4098-9714Pass
1Hallway124Smoke Detector-T11:M1-76Simplex4098-9714Pass
1Alarm Room124Smoke Detector-T11:M1-78Simplex4098-9714Pass
1Office 101124Smoke Detector-T11:M1-14Simplex4098-9714Pass
1Comm Room124Smoke Detector-T11:M1-62Simplex4098-9714Pass
1Deputy Chief Office124Smoke Detector-T11:M1-64Simplex4098-9714Pass
1Hallway (Combo)124Smoke Detector-T11:M1-66Simplex4098-9714Pass
1Hallway (Combo)124Smoke Detector-T11:M1-68Simplex4098-9714Pass
2Hallway124Smoke Detector-T11:M1-46Simplex4098-9714Pass
2Hallway124Smoke Detector-T11:M1-48Simplex4098-9714Pass
2Hallway124Smoke Detector-T11:M1-56Simplex4098-9714Pass
2Hallway124Smoke Detector-T11:M1-58Simplex4098-9714Pass
2Common Living Area124Smoke Detector-T11:M1-15Simplex4098-9714Pass
2Common Living Area124Smoke Detector-T11:M1-16Simplex4098-9714Pass
2Bunk Room 1124Smoke Detector-T11:M1-24Simplex4098-9714Pass
2Bunk Room 2124Smoke Detector-T11:M1-28Simplex4098-9714Pass
2Bunk Room 3124Smoke Detector-T11:M1-30Simplex4098-9714Pass
2Bunk Room 4124Smoke Detector-T11:M1-34Simplex4098-9714Pass
2Bunk Room 5124Smoke Detector-T11:M1-36Simplex4098-9714Pass
2Bunk Room 6124Smoke Detector-T11:M1-40Simplex4098-9714Pass
2Hallway124Smoke Detector-T11:M1-42Simplex4098-9714Pass
1Women's Restroom124Strobe-T1Simplex4904-9168Pass
1Men's Restroom124Strobe-T1Simplex4904-9168Pass
1Room 106124Strobe-T1Simplex4904-9168Pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1DRC Equipment Room125Heat Detector-T15:M1-01Simplex4098-9733Pass
1DRC Equipment Room125Heat Detector-T15:M1-02Simplex4098-9733Pass
1DRC Equipment Room125Heat Detector-T15:M1-04Simplex4098-9733Pass
1Storage Room125Heat Detector-T15:M1-08Simplex4098-9733Pass
1Storage Room125Heat Detector-T15:M1-09Simplex4098-9733Pass
1Break Room125Horn Strobe-T1Simplex4903-9425Pass
1Work Room125Horn Strobe-T1Simplex4903-9425Pass
1Vault Room125Horn Strobe-T1Simplex4903-9425Pass
1Hallway @ Riser Room125Horn Strobe-T1Simplex4903-9425Pass
1DRC Equipment Room125Horn Strobe-T1Simplex4903-9425Pass
1DRC Equipment Room125Horn Strobe-T1Simplex4903-9425Pass
1Comm Room125Main Fire Alarm PanelSimplex4010Fail18 Ah batteries fail date code
1DRC Equipment Room125Pull Station-T15:M1-05Simplex4099-9001Pass
1Storage Room125Pull Station-T15:M1-06Simplex4099-9001Pass
1Entrance125Pull Station-T15:M1-10Simplex4099-9001Pass
1DRC Equipment Room125Smoke Detector-T15:M1-03Simplex4098-9714Pass
1Vault Room125Smoke Detector-T15:M1-07Simplex4098-9714Pass
1Entrance125Smoke Detector-T15:M1-11Simplex4098-9714Pass
1Work Room125Smoke Detector-T15:M1-12Simplex4098-9714Pass
1Work Room125Smoke Detector-T15:M1-13Simplex4098-9714Pass
1Break Room125Smoke Detector-T15:M1-14Simplex4098-9714Pass
1Riser Room125Smoke Detector-T15:M1-249Simplex4098-9714Pass
1Manager's Office125Smoke Detector-T15:M1-250Simplex4098-9714Pass
1Restroom125Strobe-T1Simplex4904-9168Pass
1Soldering Shop126Heat Detector-T18:M1-07Simplex4098-9733Pass
1Mech Room126Heat Detector-T18:M1-03Simplex4098-9733Pass
1Bay 1 Paintbooth126Heat Detector-T18:M1-60Simplex4098-9733Pass
1MAG Room126Horn Strobe-T1Simplex4903-9425Pass
1Mech Room126Horn Strobe-T1Simplex4903-9425Pass
1Bay 4126Horn Strobe-T1Simplex4903-9425Pass
1Bay 4126Horn Strobe-T1Simplex4903-9425Pass
1Hallway @ MAG Room126Horn Strobe-T1Simplex4903-9425Pass
1BAy 3126Horn Strobe-T1Simplex4903-9425Pass
1Main Office Area126Horn Strobe-T1Simplex4903-9425Pass
1Men's Restroom126Horn Strobe-T1Simplex4903-9425Pass
1Bay 2126Horn Strobe-T1Simplex4903-9425Pass
1Bay 1126Horn Strobe-T1Simplex4903-9425Pass
1Bay 1126Horn Strobe-T1Simplex4903-9425Pass
1Bay 2126Horn Strobe-T1Simplex4903-9425Pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
2Restroom126Horn Strobe-T1Simplex4903-9425Pass
2Classroom126Horn Strobe-T1Simplex4903-9425Pass
1Bay 1 Paintbooth ANSUL126Kitchen Hood SupervisorySimplex4090-9001Pass
1Comm Room126Main Fire Alarm PanelSimplex4020Fail33 Ah batteries fail date code, trouble on panel
1Mech Room126Pull Station-T18:M1-01Simplex4099-9001Pass
1AGE Shop Office126Pull Station-T18:M1-05Simplex4099-9001Pass
1Bay 1 North Exit126Pull Station-T18:M1-06Simplex4099-9001Pass
1Bay 3 South Exit126Pull Station-T18:M1-42Simplex4099-9001Pass
1Bay 4 North Exit126Pull Station-T18:M1-49Simplex4099-9001Pass
1Bay 2 South Exit126Pull Station-T18:M1-25Simplex4099-9001Pass
1Engine Shop Office West126Pull Station-T18:M1-26Simplex4099-9001Pass
1Engine Shop Office East126Pull Station-T18:M1-27Simplex4099-9001Pass
1North Hallway126Pull Station-T18:M1-36Simplex4099-9001Pass
1Bay 3 North Exit126Pull Station-T18:M1-37Simplex4099-9001Pass
1Bay 4 South Exit126Pull Station-T18:M1-54Simplex4099-9001Pass
1Bay 1 South Exit126Pull Station-T18:M1-59Simplex4099-9001Pass
2Break Room126Pull Station-T18:M1-30Simplex4099-9001Pass
2Comm Room South126Pull Station-T18:M1-31Simplex4099-9001Pass
2Comm Room North126Pull Station-T18:M1-32Simplex4099-9001Pass
2Class Room126Pull Station-T18:M1-34Simplex4099-9001Pass
1AGE Shop Office126Smoke Detector-T18:M1-04Simplex4098-9714Pass
1Bay 2 Ceiling NW126Smoke Detector-T18:M1-10Simplex4098-9714Pass
1Bay 2 Ceiling SW126Smoke Detector-T18:M1-12Simplex4098-9714Pass
1Bay 2 Ceiling SE126Smoke Detector-T18:M1-14Simplex4098-9714Pass
1Bay 1 Ceiling SE126Smoke Detector-T18:M1-16Simplex4098-9714Pass
1Bay 1 Ceiling NE126Smoke Detector-T18:M1-18Simplex4098-9714Pass
1Bay 1 Ceiling NW126Smoke Detector-T18:M1-19Simplex4098-9714Pass
1Bay 1 Ceiling SW126Smoke Detector-T18:M1-22Simplex4098-9714Pass
1Bay 3 Ceiling SW126Smoke Detector-T18:M1-41Simplex4098-9714Pass
1Bay 3 SEAL Room126Smoke Detector-T18:M1-44Simplex4098-9714Pass
1Bay 3 Ceiling NE126Smoke Detector-T18:M1-45Simplex4098-9714Pass
1Bay 3 Ceiling SE126Smoke Detector-T18:M1-48Simplex4098-9714Pass
1Bay 4 Ceiling NW126Smoke Detector-T18:M1-50Simplex4098-9714Pass
1Engine Shop Office126Smoke Detector-T18:M1-28Simplex4098-9714Pass
1North Hallway126Smoke Detector-T18:M1-35Simplex4098-9714Pass
1Bay 3 Ceiling NW126Smoke Detector-T18:M1-38Simplex4098-9714Pass
1Bay 4 Ceiling SW126Smoke Detector-T18:M1-53Simplex4098-9714Pass
1Bay 4 Ceiling NE126Smoke Detector-T18:M1-55Simplex4098-9714Pass
1Bay 4 Ceiling SE126Smoke Detector-T18:M1-58Simplex4098-9714Pass
FLDevice LocationBldg. Num.Device TypeDevice AddressMFG.ModelPassFailComments
1Bay 2 AGE Supervisor126Smoke Detector-T18:M1-61Simplex4098-9714Pass
1NDI Lab Hallway126Smoke Detector-T18:M1-68Simplex4098-9714Pass
1NDI Lab126Smoke Detector-T18:M1-69Simplex4098-9714Pass
2Break Room126Smoke Detector-T18:M1-29Simplex4098-9714Pass
2Kitchen126Smoke Detector-T18:M1-33Simplex4098-9714Pass
LLMech. Room AHU Supply132Duct Detector-T1M1-26Simplex4098-9756Pass
LLMech. Room AHU Return132Duct Detector-T1M1-27Simplex4098-9756Pass
LLMech. Room AHU Supply132Duct Detector-T1M1-31Simplex4098-9756Pass
LLMech. Room AHU Return132Duct Detector-T1M1-32Simplex4098-9756Pass
ULAttic Mech. Room Supply132Duct Detector-T1M1-54Simplex4098-9756Pass