This document provides details for a federal construction contract opportunity and related project documents. The 171st Air Refueling Wing intends to issue a solicitation to award a firm fixed-price contract between $1 million and $5 million to provide construction services to repair the basewide fire alarm system at Coraopolis, PA. Services will include installing addressable fire alarm and mass notification systems in identified buildings, replacing all devices and wiring, and installing a basewide central monitoring system communicating via radio frequency to new systems in buildings and receivers at the BDOC and Command Post. A pre-bid conference will be held on June 17th, followed by a site visit, and bids are due by July 6th. The NAICS code is 238990 and small business size standard is $16.5 million average annual revenue. Interested offerors must register in SAM.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

u

PASSENGER

TERMINAL

[J§L]

H

CORRIDOR

OQfO l OUTI.l,E AAEAOF

RAISED FLOOR

SRC ©,

ROOM CAT

DK] ROOM

© OUTUNEAREAOF

LJ

WCP

RAJSEO FLOOR

ROOM

[Jfil::]

-- -- r- w - w w ------T" - w w --

I

EXISTING BUILDING

BUILDING 107 FIRE ALARM DEMOLITION PLAN

-1Q SCALE:3f16"•1'--0"

"""'""'""'""""""""""'iiiiiiiiiioiiia'"

B-3 11119/2021 ISSUEOFORBID

ISSUE DESCRIPTION

SCALE: 3116" = 1'-0"

PROJECT MANAGER CQUIROZ

D. PURPURA

J. JAECKEL

O. SPENCER

I.DENHOLM

Z, SACHSENMAIER

PROJECT NUMBER 102392'1

VESTIBULE

ADAL B107 G-ASNT

PITTSBURGH INTERNATIONAL AIRPORT

EXISTING EST-2 FIRE ALARM

CONTROL PANEL TO REMAIN.

CONTRACTOR TO DEMOLISH FIRE Al.ARM

DEVICES LOCATED WITHIN THE WORK AREA.

INCWOING CEILING MOUNTED SMOKE

DETECTORS, UNDERFLOOR SMOKE

DETECTORS, MANUAL PULL STATIONS, AND

NOTIFICATION DEVICES. CONDUIT N-10

CABLES SHALL BE REMOVED FROM THE AREA

AND PULLED BACK TO ADJACENT BUILDll'fG

AREAS AS REQUIRED TO KEEP ALL FIRE

ALARM DEVICES LOCATED OUTSIDE OF THE

WORK AREA IN SERVICE AT All. TIMES.

ALL WORK WITHIN THE SECURE AREA

SHALL BE PREFORMED UNDER THE

SUPERVISION OF AN ESCORT. ALL

WORKERS SHALL BE WITHIN

EYESIGHT Of ESCORT. WHERE MUL TIPl.E WORKERS WORK WITHIN

THE SECURE AREA ANO WORK IN

DIFFERENT AREAS AN ESCORT SHALL

BE PROVIDED FOR EACH WORK PP.EA

WORK LIMITATIONS MAY OCCUR DUE

TO LIMITED ESCORTS.

BUILDING 107

ADAL B107 FOR G-ASNT

FIRE ALARM DEMOLITION PLAN

""""'"""""""",,,,,,;2" FILENAME 1-

SCALE SEE PLANS I"'"" FAD-101

A

1240378686N Text Box This drawing shows the existing conditions of the Command Post. The JLSQ162020 project shall be responsible for demolition and installation of fire alarm panels and devices for the Command Post and B107.

1240378686N Cross-Out

1240378686N Cross-Out

1240378686N Callout Existing FACP shall be demolished.

0@1

CORRIDOR

Dill,D

0@1

ADMIN.

[JR]

ill

·f , COMM

®,.,0 1~~~ 1§, ASD

SRCROOM

LIL]

®,.,o

®ASD-SF

IT/GASNT EQ CLOSET

CLOSET

[JfilJ

-103

OUTLINE AREA OF

RAISED FLOOR

CAT ROOM

0§0

¼"""

WCP

ROOM

OE]

EXISTING BUILDING

BUILDING 107 FIRE ALARM PLAN

@,ill

, FAA

,,--,7 L©c_~_J

MECHANICAL

[JM:J

A~M~ . i c [Jg:]

SCJIU::3116"•1 '--0"

' F

D, PURPURA

J. JAECKEL

D. SPENCER

I.DENHOLM

H

Z, SACHSENMAIER

PROJECT NUMBER 102392'1

[JM:J

ill

EQUIPMENT

STORAGE

Du

,a

EXISTING EST-2 FIRE ALARM CONTROL PANEL

TO REMAIN. NEW OEVICES SHALL MERFACE

WITH EXISTING FACP.

ALL EXISTING FIRE Al.ARM DEVICES LOCATED OUTSIDE OF THE WORK ARE TO REMAIN ti

SERVICE AT ALL TIMES.

CONTRACTOR TO INSTALL NEW FIRE Al.ARM

DEVICES WITHIN THE WORK AREA IN

ACCORONiCE WITH NFPA 72 ANO UFC 3-800-01

AND AS SHOWN. ROUGH-IN FOR ALL

NOTIACATION DEVICES (STROBES ANO HORN

STROBES) SHALL INCLUDE DEEP 41n ~ 41n BACK

BOXES WITH EXTENSION RINGS AS REQUIRED

TO ACCOMMODATE FlJT\JRE INSTAl.l..ATION OF

SPEAKER STROBES. THE INTENT OF THE

DESIGN SHOWN HERE-IN IS TO ACCOMMODATE

A FUTURE FA/MNS UPGRADE WITHOUT NEEDING

ADDITIONAL ROUGl?IN FOR AUDIO AND VISUAL

NOTIFICATION DEVICES. ALL NEW DEVICES

SHALL BE TIED TO THE EXISTING F/ICP ANO/OR

NEW OOTIFICATION APPI.IAl'ICE EXTENDER

POWER SUPPLY.

PROVIDE NEW NOTIFICATION APPl..lPl-lCE

EXTENDER POWER SUPPLY TO POWER AND

SYNCHRONIZE NEW DEVICES WITHIII THE

WORKAREA.

ALL WORK WITHIN THE SECURE~ SHALL BE

PREFORMED UNDER THE SUPERVISION OF .AN

ESCORT. ALL WORKERS SHALL BE WITHIN

EYESIGHT OF ESCORT. WHERE MULTIPLE

WORKERS WORK WITHIN THE SECURE AREA

.AND WORK IN DIFFERENT AREAS AN ESCORT

SHALL BE PROVIDED FOR EACH WORK AREA.

WORK LIMITATIONS MAY OCCUR DUE TO

LIMITED ESCORTS.

ASPIRATING SMOKE DETECTOR AND POWER

SUPPLY. PROVIDE DETECTION TO COVER ROOM

160 ANO 164A. INCLUDING SUB-FLOOR SPACES.

FIRE SPRINKLER ISOLATION VALVE .AND Al.ARM

WATERFLOW FOR ADJACENT ROOMS 18'A AND

,60.

ADAL B107 G-ASNT

PITTSBURGH INTERNATIONAL AIRPORT

m

®,.,o

I,] co co, FT

FIRE ALARM SYMBOLOGY

ASPIRATING SMOKE DETECTOR AND ASSOCIATED

POWER SUPPLY

MANUAL STATION, FIRE Al.ARM

AUTOMATIC FIRE DETECTOR. UNSPECIFIED TYPE

ASPIRATING SMOKE DETECTOR SAMPLE POINT

IN CEILING

ASPIRATING SMOKE DETECTOR SAMPLE POINT

IN SUB-FLOOR

HORN/STROBE COMBO WALL, CLEAR LENS

STROBE ONLY, WALL MOUNT

STROBE ONLY, CEUNG MOUNT

REMOTE Al.ARM IIIDICATING AND TEST SWITCH

ASPIRATING SMOKE DETECTOR

CEILING MOUNT

CARBON MONOXIDE

CAABON DIOXIDE

FIXED TEMPERATURE

RT$ REMOTE TEST STATION

SF SUB-FLOOR

SOV SOLENOID OUTPUT VALVE

TYP TYPICAL

WP WEATHERPROOF

NOT ALL SUBSCRIPTS AND ABBREVIATIONS MAY BE USED.

HALF-TONE DEVICES ARE EXISTING TO REMAIN,

BUILDING 107

ADAL B107 FOR G-ASNT

FIRE ALARM PLAN

2• FILENAMEI-

""'"""-=="""' SCALE SEE PLANS I"'"" FA-101

A

1240378686N Text Box Use this page in combination with JLSQ162020 drawing 107-FA-101. Companion project "JLSQ192007 ADAL B107 for GASNT" will be in construction at the same time as this Fire Alarm project. Coordinate work for Command Post

1240378686N Cross-Out

1240378686N Callout Provide new NAC, but it will be installed in the location shown on JLSQ162020 drawing 107-FA-101.

1240378686N Callout Existing FACP to be demolished

1240378686N Line

1240378686N Line

1240378686N Callout Project JLSQ162020 is the "future" upgrade. Install new devices IAW drawing 107-FA-101.

1240378686N Callout Install new Aspirating Smoke Detectors under JLSQ162020 project.