Attachment 6 - JLSQ192007 Fire Design Drawings.pdf
PDF 2 MB Posted
- Attached to
- Repair Base Fire Alarm System Federal contract opportunity
- Solicitation number
- W50S91-22-B-0001
- Issued by
- Department of the Army National Guard
About this file
This document provides details for a federal construction contract opportunity and related project documents. The 171st Air Refueling Wing intends to issue a solicitation to award a firm fixed-price contract between $1 million and $5 million to provide construction services to repair the basewide fire alarm system at Coraopolis, PA. Services will include installing addressable fire alarm and mass notification systems in identified buildings, replacing all devices and wiring, and installing a basewide central monitoring system communicating via radio frequency to new systems in buildings and receivers at the BDOC and Command Post. A pre-bid conference will be held on June 17th, followed by a site visit, and bids are due by July 6th. The NAICS code is 238990 and small business size standard is $16.5 million average annual revenue. Interested offerors must register in SAM.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract OF1419_Rpr Base Fire Sys.pdf | ||
| W50S91-22-B-0001_Rpr Base Fire Sys_Amendment 3.pdf | ||
| W50S91-22-B-0001_Rpr Base Fire Sys_Amendment 2.pdf | ||
| W50S91-22-B-0001_Rpr Base Fire Sys_Amendment 1.pdf | ||
| Attachment 1_JLSQ162020 Pitt ANG Repair Base FA System Drawings.pdf | ||
| Attachment 2_JLSQ162020 Pitt ANG Repair Base FA System Specifications.pdf | ||
| W50S91-22-B-0001_Rpr Base Fire Sys.pdf | ||
| Attachment 3_Wage Determination.pdf | ||
| Attachment 4_Brand Name Justification_Rpr Base Fire Alarms.pdf | ||
| Attachment 5_Brand Name Justification_Federal Signal Corp.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
u
PASSENGER
TERMINAL
[J§L]
H
CORRIDOR
OQfO l OUTI.l,E AAEAOF
RAISED FLOOR
SRC ©,
ROOM CAT
DK] ROOM
© OUTUNEAREAOF
LJ
WCP
RAJSEO FLOOR
ROOM
[Jfil::]
-- -- r- w - w w ------T" - w w --
I
EXISTING BUILDING
BUILDING 107 FIRE ALARM DEMOLITION PLAN
-1Q SCALE:3f16"•1'--0"
"""'""'""'""""""""""'iiiiiiiiiioiiia'"
B-3 11119/2021 ISSUEOFORBID
ISSUE DESCRIPTION
SCALE: 3116" = 1'-0"
PROJECT MANAGER CQUIROZ
D. PURPURA
J. JAECKEL
O. SPENCER
I.DENHOLM
Z, SACHSENMAIER
PROJECT NUMBER 102392'1
VESTIBULE
ADAL B107 G-ASNT
PITTSBURGH INTERNATIONAL AIRPORT
EXISTING EST-2 FIRE ALARM
CONTROL PANEL TO REMAIN.
CONTRACTOR TO DEMOLISH FIRE Al.ARM
DEVICES LOCATED WITHIN THE WORK AREA.
INCWOING CEILING MOUNTED SMOKE
DETECTORS, UNDERFLOOR SMOKE
DETECTORS, MANUAL PULL STATIONS, AND
NOTIFICATION DEVICES. CONDUIT N-10
CABLES SHALL BE REMOVED FROM THE AREA
AND PULLED BACK TO ADJACENT BUILDll'fG
AREAS AS REQUIRED TO KEEP ALL FIRE
ALARM DEVICES LOCATED OUTSIDE OF THE
WORK AREA IN SERVICE AT All. TIMES.
ALL WORK WITHIN THE SECURE AREA
SHALL BE PREFORMED UNDER THE
SUPERVISION OF AN ESCORT. ALL
WORKERS SHALL BE WITHIN
EYESIGHT Of ESCORT. WHERE MUL TIPl.E WORKERS WORK WITHIN
THE SECURE AREA ANO WORK IN
DIFFERENT AREAS AN ESCORT SHALL
BE PROVIDED FOR EACH WORK PP.EA
WORK LIMITATIONS MAY OCCUR DUE
TO LIMITED ESCORTS.
BUILDING 107
ADAL B107 FOR G-ASNT
FIRE ALARM DEMOLITION PLAN
""""'"""""""",,,,,,;2" FILENAME 1-
SCALE SEE PLANS I"'"" FAD-101
A
1240378686N Text Box This drawing shows the existing conditions of the Command Post. The JLSQ162020 project shall be responsible for demolition and installation of fire alarm panels and devices for the Command Post and B107.
1240378686N Cross-Out
1240378686N Cross-Out
1240378686N Callout Existing FACP shall be demolished.
0@1
CORRIDOR
Dill,D
0@1
ADMIN.
[JR]
ill
·f , COMM
®,.,0 1~~~ 1§, ASD
SRCROOM
LIL]
®,.,o
®ASD-SF
IT/GASNT EQ CLOSET
CLOSET
[JfilJ
-103
OUTLINE AREA OF
RAISED FLOOR
CAT ROOM
0§0
¼"""
WCP
ROOM
OE]
EXISTING BUILDING
BUILDING 107 FIRE ALARM PLAN
@,ill
, FAA
,,--,7 L©c_~_J
MECHANICAL
[JM:J
A~M~ . i c [Jg:]
SCJIU::3116"•1 '--0"
' F
D, PURPURA
J. JAECKEL
D. SPENCER
I.DENHOLM
H
Z, SACHSENMAIER
PROJECT NUMBER 102392'1
[JM:J
ill
EQUIPMENT
STORAGE
Du
,a
EXISTING EST-2 FIRE ALARM CONTROL PANEL
TO REMAIN. NEW OEVICES SHALL MERFACE
WITH EXISTING FACP.
ALL EXISTING FIRE Al.ARM DEVICES LOCATED OUTSIDE OF THE WORK ARE TO REMAIN ti
SERVICE AT ALL TIMES.
CONTRACTOR TO INSTALL NEW FIRE Al.ARM
DEVICES WITHIN THE WORK AREA IN
ACCORONiCE WITH NFPA 72 ANO UFC 3-800-01
AND AS SHOWN. ROUGH-IN FOR ALL
NOTIACATION DEVICES (STROBES ANO HORN
STROBES) SHALL INCLUDE DEEP 41n ~ 41n BACK
BOXES WITH EXTENSION RINGS AS REQUIRED
TO ACCOMMODATE FlJT\JRE INSTAl.l..ATION OF
SPEAKER STROBES. THE INTENT OF THE
DESIGN SHOWN HERE-IN IS TO ACCOMMODATE
A FUTURE FA/MNS UPGRADE WITHOUT NEEDING
ADDITIONAL ROUGl?IN FOR AUDIO AND VISUAL
NOTIFICATION DEVICES. ALL NEW DEVICES
SHALL BE TIED TO THE EXISTING F/ICP ANO/OR
NEW OOTIFICATION APPI.IAl'ICE EXTENDER
POWER SUPPLY.
PROVIDE NEW NOTIFICATION APPl..lPl-lCE
EXTENDER POWER SUPPLY TO POWER AND
SYNCHRONIZE NEW DEVICES WITHIII THE
WORKAREA.
ALL WORK WITHIN THE SECURE~ SHALL BE
PREFORMED UNDER THE SUPERVISION OF .AN
ESCORT. ALL WORKERS SHALL BE WITHIN
EYESIGHT OF ESCORT. WHERE MULTIPLE
WORKERS WORK WITHIN THE SECURE AREA
.AND WORK IN DIFFERENT AREAS AN ESCORT
SHALL BE PROVIDED FOR EACH WORK AREA.
WORK LIMITATIONS MAY OCCUR DUE TO
LIMITED ESCORTS.
ASPIRATING SMOKE DETECTOR AND POWER
SUPPLY. PROVIDE DETECTION TO COVER ROOM
160 ANO 164A. INCLUDING SUB-FLOOR SPACES.
FIRE SPRINKLER ISOLATION VALVE .AND Al.ARM
WATERFLOW FOR ADJACENT ROOMS 18'A AND
,60.
ADAL B107 G-ASNT
PITTSBURGH INTERNATIONAL AIRPORT
m
®,.,o
I,] co co, FT
FIRE ALARM SYMBOLOGY
ASPIRATING SMOKE DETECTOR AND ASSOCIATED
POWER SUPPLY
MANUAL STATION, FIRE Al.ARM
AUTOMATIC FIRE DETECTOR. UNSPECIFIED TYPE
ASPIRATING SMOKE DETECTOR SAMPLE POINT
IN CEILING
ASPIRATING SMOKE DETECTOR SAMPLE POINT
IN SUB-FLOOR
HORN/STROBE COMBO WALL, CLEAR LENS
STROBE ONLY, WALL MOUNT
STROBE ONLY, CEUNG MOUNT
REMOTE Al.ARM IIIDICATING AND TEST SWITCH
ASPIRATING SMOKE DETECTOR
CEILING MOUNT
CARBON MONOXIDE
CAABON DIOXIDE
FIXED TEMPERATURE
RT$ REMOTE TEST STATION
SF SUB-FLOOR
SOV SOLENOID OUTPUT VALVE
TYP TYPICAL
WP WEATHERPROOF
NOT ALL SUBSCRIPTS AND ABBREVIATIONS MAY BE USED.
HALF-TONE DEVICES ARE EXISTING TO REMAIN,
BUILDING 107
ADAL B107 FOR G-ASNT
FIRE ALARM PLAN
2• FILENAMEI-
""'"""-=="""' SCALE SEE PLANS I"'"" FA-101
A
1240378686N Text Box Use this page in combination with JLSQ162020 drawing 107-FA-101. Companion project "JLSQ192007 ADAL B107 for GASNT" will be in construction at the same time as this Fire Alarm project. Coordinate work for Command Post
1240378686N Cross-Out
1240378686N Callout Provide new NAC, but it will be installed in the location shown on JLSQ162020 drawing 107-FA-101.
1240378686N Callout Existing FACP to be demolished
1240378686N Line
1240378686N Line
1240378686N Callout Project JLSQ162020 is the "future" upgrade. Install new devices IAW drawing 107-FA-101.
1240378686N Callout Install new Aspirating Smoke Detectors under JLSQ162020 project.