Questions and Answers.pdf

PDF 85 KB Posted

Attached to
CRAC Maintenance Service
Solicitation number
W50S8R27Q0001
Issued by

About this file

This is a Questions and Answers document for a federal service contract requiring maintenance and emergency repair services for four Liebert DS Series data center cooling units (CRAC units) located in Building B409 at 1947 Harrington Memorial Rd, Mansfield, Ohio 44903. The four units are identical models (DS070ASC0EI99B) with 70 kW/~20 tons cooling capacity each, approximately 11–12 years old, with serial numbers C15E8E0070, C15E8E007Z, C15E8E0071, and C15E8E0069, located in Rooms 116 and 110. This is a new requirement with no current incumbent contractor.

The contract involves preventive maintenance (PM) under CLIN 0001 with a contractor-developed PM Plan subject to Contracting Officer Representative (COR) approval, grounded in manufacturer guidance and referenced standards. Emergency response services are available 24/7 with a four-hour on-site response standard under CLIN 0002. Emergency repairs will be priced separately upon COR authorization using OEM parts and are not included in the fixed monthly CLIN 0001 price. Additional CLINs (1001, 2001, 3001, and 4001) are specified on the SAM.gov posting. Pricing submissions should reflect costs aligned with these CLINs; no specific pricing template is required, and contractor quotes are acceptable. Site visit attendance, scheduled for October 14, 2026 at 10:00 AM EDT, is not mandatory for proposal submission. Photos and a second site visit were not provided. Past performance evaluation is based solely on the prime contractor's performance; subcontractor performance cannot be included in the evaluation per solicitation W50S8R27Q0001.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

Q1. Is there a current incumbent performing this service? May we have the contract number or the total contract award amount?

A1. No. New requirement.

Q2. The PWS did not list the equipment (including the manufacturer) that requires servicing. Can a list be provided?

A2. Room 116 Server on Left (w/ Error Codes): SN#:C15E8E0070/Make: Liebert DS/Model#:DS070ASC0EI99B

Room 116 Server on Right: Serial Number#:C15E8E007Z/ Make: Liebert DS/Model#:DS070ASC0EI99B

Room 110 Server on Left: Serial Number#:C15E8E0071/ Make: Liebert DS/Model#:DS070ASC0EI99B

Room 110 Server on Right: Serial Number#:C15E8E0069 /Make: Liebert DS/Model#:DS070ASC0EI99B

Q3. Is there a required service frequency identified for this requirement?

A3. The PWS does not prescribe a rigid calendar frequency for the overall service; it requires the contractor to develop and obtain COR approval for a PM Plan that does so, grounded in manufacturer guidance and the standards referenced. Emergency response remains continuous (24/7) with the stated 4-hour on-site standard.

Q4. Is there a specific pricing sheet or formatting template that must be completed and submitted?

A4. No. Only thing we require is cost to be reflected in accordance with CLIN 0001, 0002, 1001, 2001, 3001, and 4001 on SAM.gov posting. Contractor quote can also be provided.

Q5. Would it be possible to accommodate our technicians for a second optional site visit this Friday, October 16?

A5. Not at this time.

Q6. If a second site visit is definitely not feasible, we would greatly appreciate it if you could provide sufficient on-site photos of the CRAC units, associated equipment, and surrounding work areas so we can accurately understand the existing conditions and prepare our technical approach and pricing.

A6. Photos cannot be provided.

Q7. The notice says a site visit is scheduled for 14 October 2026 at 10:00 AM EDT and that "all offerors SHALL register to attend this conference and site visit." Is attending the site visit a condition of submitting a quote, or is it optional?

A7. Site visit attendance is not required to submit a proposal.

Q8. we would appreciate if you could you confirm the service address for us.

A8. 1947 Harrington Memorial Rd, Mansfield, Ohio 44903

Q9. Equipment inventory: PWS 5.1 and 5.2.1 do not identify the equipment to be maintained. Please provide the manufacturer, model, capacity and quantity of the CRAC/CRAH units in B409, including the unit with serial number C15E8E0070 (PWS 5.2.2.6, CLIN 0002), and confirm whether the fluid coolers, pumps, expansion tank, water tower and chillers referenced in PWS 5.2.1.6 through 5.2.1.14 are within scope.

A9. Room 116 Server on Left (w/ Error Codes): SN#:C15E8E0070/Make: Liebert DS/Model#:DS070ASC0EI99B

Room 116 Server on Right: Serial Number#:C15E8E007Z/ Make: Liebert DS/Model#:DS070ASC0EI99B

Room 110 Server on Left: Serial Number#:C15E8E0071/ Make: Liebert

Room 110 Server on Right: Serial Number#:C15E8E0069 /Make: Liebert

Q10. Emergency repairs under CLIN 0001: PWS 5.2.2.5 and 5.2.2.11 call for repairs upon COR authorization using contractor-furnished OEM parts. Should parts and labor for future emergency repairs be included in the fixed monthly CLIN 0001 price, or will each authorized repair be priced separately, and if included, what has been the historical number of emergency calls per year?

A10. No. these will be evaluated during each emergency requirement.

Q11. Past performance: UA LLC would hold the contract, and a local HVAC contractor would perform the maintenance and repairs. May our past performance volume include contracts performed by that subcontractor?

A11. "Per the evaluation criteria outlined in solicitation W50S8R27Q0001, under Volume II, Past Performance, the Government will not consider the past performance of any subcontractors. The evaluation will be based solely on the past performance of the prime contractor (the "quoter"). Therefore, the past performance of your proposed HVAC subcontractor may not be included."

Q12. The complete equipment list/schedule for Building B409, specifying manufacturer, model number, age, and cooling capacity for each unit.

A12.

Room Position Serial Number

Make Model Cooling Capacity

Estimated Age

Notes

Room

Left C15E8E0070 Liebert

DS

DS070ASC0EI99B

70 kW / ~20 Tons

Approx.

11–12 years old

Currently has Error Codes

Room Position Serial Number

Make Model Cooling Capacity

Estimated Age

Notes

Room

Right C15E8E007Z Liebert

DS

DS070ASC0EI99B

70 kW / ~20 Tons

Approx.

11–12 years old

Room

Left C15E8E0071 Liebert

DS

DS070ASC0EI99B

70 kW / ~20 Tons

Approx.

11–12 years old

Room

Right C15E8E0069 Liebert

DS

DS070ASC0EI99B

70 kW / ~20 Tons

Approx.

11–12 years old

Q13. Any additional technical specifications or historical maintenance context available for unit S/N C15E8E0070.

A13. Historical maintenance documentation for the past 4 years is reflected in Attachment 1 CRAC Start Up Docs – Redacted 2025 and Attachment 2 Vertiv Repair Recommendations 9 – 13 – 2024 Redacted.