Attachment 2 Vertiv repair recomendations 9.13.24_Redacted.pdf
PDF 45 KB Posted
- Attached to
- CRAC Maintenance Service
- Solicitation number
- W50S8R27Q0001
About this file
This document is a parts list for Computer Room Air Conditioning (CRAC) unit repairs and maintenance, organized by unit designation and repair category.
The document specifies required parts for three CRAC units (CRAC-1A, CRAC-1B, and CRAC-2B) along with recommended repairs for all units. Required parts for CRAC-1A include a compressor, TXV, filter drier, and fuses. CRAC-1B requires a humidifier make-up valve, hose clamps, swivel adapter, hose trap, barbed tee, and hose. CRAC-2B required parts consist of a compressor, TXV, filter drier, slinger ring, fan motor, fan speed control, fuses, and aquastat. The recommended repairs section (excluding quantities already listed above) identifies preventive maintenance and upgrade items across all eight circuits, including six replacement TXVs and filter driers, eight belts, sixteen filters, twenty-four humidifier lamps, three humidifier make-up valves, hose components, four units of Vapure humidifier treatment, and one unit of POE oil. The document notes an estimated refrigerant requirement of 475-500 lbs. of R-407C for full charging of all circuits and mentions consideration of upgrading controls from iCOM with monochrome displays to iCOM2 with 7-inch touch displays.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CRAC-1A
Part number Description Quantity
172145P1S Compressor
180957P2S TXV
180910P1S Filter drier
195938P3 Fuses 3
CRAC-1B
185108P1S Humidifier make-up valve 1
P15-0150S Hose clamp 1
124216P2S Hose clamp 1
P-5400S Swivel adapter 1
149376P1 Hose trap 1
1A16207P1 Barbed tee 1
P15-0170 Hose 2
CRAC-2B
172145P1S Compressor 1
180957P2S TXV 1
180910P1S Filter drier 1
D-1830S Slinger ring 1
KIT-095E Fan motor 1
1C25447P1S Fan speed control 1
E-1230S Fuses 1
E-3080S Aquastat 1
Recommended repairs - all units (quantities exclude those already required above), these are repairs I would make if I were bidding and carrying a one year warranty on the equipment. Recommending replacement of all filter driers and TXVs while the systems are down for leak checks, new filters, belts, humidifier make-up valves, and humidifier lamps, new drain hoses throughout, and addition of Vapure humidifier treatment. I would also consider upgrading controls from iCOM with monochrome displays to iCOM2 with 7" touch displays. Estimated refrigerant required is probably in the ballpark of 475-
500 lbs. R-407C to fully charge all 8 circuits, oil amounts may need to be adjusted once full charge is known.
180957P2S TXV 6
180910P1S Filter drier 6
181030P6S Belts 8
305475P1 Filters 16
H-002AS Lamps 24
185108P1S Humidifier make-up valve 3
P15-0150S Hose clamp 3
124216P2S Hose clamp 3
P-5400S Swivel adapter 3
149376P1 Hose trap 3
1A16207P1 Barbed tee 3
P15-0170 Hose 6
SKHTSTRKIT2M3 Vapure humidifier treatment 4
NC4316-46 POE oil
File details come from the government source that posted it. Updated .