This document contains a Material Approval Submittal form (AF IMT 3000) and four completed Liebert DS Warranty Inspection Check Sheets related to CRAC (Computer Room Air Conditioning) units repairs for the Air National Guard.

The Material Approval Submittal is a federal government form used by contractors to submit Shop Drawings, Equipment Data, Manufacturer's Literature, Certificates, and material samples for government approval. Submissions must be prepared in four copies, signed, and numbered consecutively by contract. The form requires clear identification and tabbing of items to be approved, with attachments numbered to correspond with item numbers. Resubmissions must indicate the previous submission number. The form is not valid unless signed by the contracting officer and is required under contract terms for approval as specified.

The four Warranty Inspection Check Sheets document startup procedures and performance verification for Liebert DS air conditioning units installed at Air National Guard facilities. Each sheet captures equipment serial numbers, model numbers, and comprehensive operational testing including voltage verification, fan amperage, reheat and humidifier operation, condensate pump function, refrigerant charge specifications, compressor performance metrics (suction/discharge pressures, superheat, subcooling), and electrical connectivity checks. All four units feature dual ZR125KCETF5265 compressors and various condenser models. Testing was performed by Vertiv technicians in May 2025, with all units showing normal operational parameters and superheats in the 14-16°F range. The sheets include extensive safety warnings regarding arc flash hazards, electrical shock risks, and high-temperature surfaces, with instructions to follow NFPA 70E protocols.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMENTS

(Number to correspond with applicable Item Number on reverse)

INSTRUCTIONS TO CONTRACTORS

1. The term "material" is defined as articles, supplies, raw materials, equipment, parts, components, and end items that are to be incorporated into the work required by the contract.

2. This form is to be used by contractors for submitting Shop Drawings, Equipment Data, Manufacturer's Literature and Certificates and samples of Materials to the Government for approval in accordance with the provisions of this contract. Unless otherwise specified, it is to be prepared in 4 copies, signed, and provided to the contracting officer with appropriate attachments.

3. Item(s) to be approved will be clearly tabbed or identified. Data pertaining to item(s) to be approved will be clearly identified or tabbed, particularly where documents are voluminous, in order to properly evaluate the materials or articles to be incorporated in the work. Each attachment will be numbered to correspond with the item number shown on the face of this form.

4. Requests submitted shall be numbered consecutively, by contract, in the space entitled "Submission No.". This number, in addition to the Contract No., will be used to identify each Material Approval Submittal. Resubmissions will be indicated in the appropriate block and the insertion of previous submission number and data in addition to a new submission number. A single submission should be used for all work of a section of the specifications, but in NO instance should the submission include work for more than one (1) contract. Submittals requiring priority handling will be submitted by separate submittal using the form and so marked across the face of the form.

5. This Material Approval Submittal is not valid unless it is signed by the contracting officer. This approval is required as called for by the contracting officer under the terms of this contract.

AF IMT 3000, 20030901, V1 (REVERSE)

PSWI-8542-405-CO

Rev. 3 1/2017

Liebert DS Warranty Inspection Check Sheet

WARNING

Arc flash and electric shock hazard. Wear personal protective equipment per NFPA 70E before working within the electric control enclosure or any hazardous voltage electric connection enclosure. Use extreme caution when checking the status of live hazardous voltage circuits. Failure to comply can cause serious injury or death.

Check unit electrical phasing with a phase meter. If phasing is incorrect, change wiring at input source to unit. Do not change any unit or component phasing.

Check the compressors for proper rotation by bumping the contactors and watching the gauge pressures. If the pressures are equalized and the compressor sounds noisy, then compressor is running backwards.

3. Check and record control voltage transformers for proper output. (Secondary voltage should not be under 23 VAC or exceed 27 VAC under load, change tap if necessary).

T1__________Volt

4. Record iCOM Software Version: _________________

NOTE: The software version is located in the Network Menu that is located in Service Menus.

NOTE: Check operation of each component by utilizing the Service Menu that is located in the Service Menus on the iCOM Control.

5. Enable Manual Mode.

6. Enable Fans and record Main Fan amperage.

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

7. Enable Reheats and record amperage. Disable Reheats after test.

RHT1 _____/_____ RHT2 _____/_____ RHT3 _____/_____ Fuse _________

Liebert DS Warranty Inspection Check Sheet

NOTE: On units with Infrared humidifiers, fill pan with water before turning on the lamps. Check water level and adjust high limit float for proper operation.

8. Enable Humidifier and record amperage. Check for leaks at all piping connections.

Disable Humidifier after test.

WARNING

Risk of electric shock and contact with extremely hot parts, can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or energized humidifier bulbs.

L1 __________ L2 __________ L3 __________ Fuse __________

9. Check condensate pump for proper operation by filling pump with water. Check for leaks at all piping connections. Record pump amperage. (If Applicable)

WARNING

Risk of electric shock and contact with hot motor surfaces, Can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or the energized condensate pump motor. Do not remove the condensate pump electric connection terminal cover. Use extreme caution and do not spill water on the motor or the electric connection cover.

L1 __________ L2 __________ Fuse __________

Chilled Water/Freecooling Units

Set 3P 1/2 Actuator Open to On. Check for full valve travel. Set 3P 1/2 Actuator Open to Off.

Set 3P 1/2 Actuator Close to On. Check for complete valve closure. Set 3P 1/2 Actuator Close to Off.

Check for leaks at all piping connections.

Liebert DS Warranty Inspection Check Sheet

Water/Glycol System Operation

If the head pressures recorded below equal 105°F condensing temperature, no adjustment of the glycol/water regulating valves or Motorized Ball Valves are required.

If the condensing temperatures are above 110°F, adjust the glycol/water regulating valves/Motorized Ball Valves to lower the head pressure. If the system has balancing valves in it, these valves should be adjusted to the required GPM for this piece of equipment.

After the condensing temperature has been set up properly, the system should be allowed to run for 10 to 15 minutes to obtain stable conditions.

Note: To adjust the head pressure with Motorized Ball Valves, go to the Service Menus and then to the Options Set-up Menu. Adjust parameter S427 (Ball Valve Setpoint Offset). The default setting is +30. The range is +0 to +70. Lowering the setpoint will decrease the head pressure and an increase in the setpoint will increase the head pressure.

Entering condenser water/glycol temperature __________

Leaving condenser water/glycol temperature ___________

11. Record Suction and Discharge Pressures.

Circuit #1

Suction Pressure ____________ Discharge Pressure ____________

Circuit #2

Suction Pressure ____________ Discharge Pressure ____________

12. Check superheat and record. Superheat should be approximately 15°.

Circuit #1

Superheat __________°F

Circuit #2

Superheat __________°F

Liebert DS Warranty Inspection Check Sheet

13. Check subcooling. (Refer to MC Condenser User Manual and Warranty Inspection sheet for subcooling requirement.)

Circuit #1

Subcooling __________°F

Circuit #2

Subcooling __________°F

14. Record Total Charge

Circuit #1 __________ LBS Circuit #2 __________ LBS

15. Record compressor amperage.

Compressor #1

L1 __________ L2 __________ L3 __________ Fuse __________

Compressor #2

L1 __________ L2 __________ L3 __________ Fuse __________

16. Record compressor crankcase heater amperage.

Compressor #1 ______ Compressor #2 ______ Fuse ______

NOTE: Scroll and Digital Scroll Compressor Additional Oil Requirements System charges over 28lbs (12.7kg) may require additional oil charge to be added.

Refer to the CRV User Manual for the amount of oil required for various system charge levels and associated safety alerts. After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system while the system is running. The amount of oil added by field service must be recorded date of oil addition must be included as well.

Liebert DS Warranty Inspection Check Sheet

WARNING

Arc flash and electric shock hazard. Wear personal protective equipment per NFPA 70E before working within the electric control enclosure or any hazardous voltage electric connection enclosure. Use extreme caution when checking the status of live hazardous voltage circuits. Failure to comply can cause serious injury or death.

Check unit electrical phasing with a phase meter. If phasing is incorrect, change wiring at input source to unit. Do not change any unit or component phasing.

Check the compressors for proper rotation by bumping the contactors and watching the gauge pressures. If the pressures are equalized and the compressor sounds noisy, then compressor is running backwards.

3. Check and record control voltage transformers for proper output. (Secondary voltage should not be under 23 VAC or exceed 27 VAC under load, change tap if necessary).

T1__________Volt

4. Record iCOM Software Version: _________________

NOTE: The software version is located in the Network Menu that is located in Service Menus.

NOTE: Check operation of each component by utilizing the Service Menu that is located in the Service Menus on the iCOM Control.

5. Enable Manual Mode.

6. Enable Fans and record Main Fan amperage.

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

Liebert DS Warranty Inspection Check Sheet

NOTE: On units with Infrared humidifiers, fill pan with water before turning on the lamps. Check water level and adjust high limit float for proper operation.

8. Enable Humidifier and record amperage. Check for leaks at all piping connections.

Disable Humidifier after test.

WARNING

Risk of electric shock and contact with extremely hot parts, can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or energized humidifier bulbs.

L1 __________ L2 __________ L3 __________ Fuse __________

9. Check condensate pump for proper operation by filling pump with water. Check for leaks at all piping connections. Record pump amperage. (If Applicable)

WARNING

Risk of electric shock and contact with hot motor surfaces, Can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or the energized condensate pump motor. Do not remove the condensate pump electric connection terminal cover. Use extreme caution and do not spill water on the motor or the electric connection cover.

L1 __________ L2 __________ Fuse __________

Chilled Water/Freecooling Units

Set 3P 1/2 Actuator Open to On. Check for full valve travel. Set 3P 1/2 Actuator Open to Off.

Set 3P 1/2 Actuator Close to On. Check for complete valve closure. Set 3P 1/2

Liebert DS Warranty Inspection Check Sheet

Water/Glycol System Operation

If the head pressures recorded below equal 105°F condensing temperature, no adjustment of the glycol/water regulating valves or Motorized Ball Valves are required.

If the condensing temperatures are above 110°F, adjust the glycol/water regulating valves/Motorized Ball Valves to lower the head pressure. If the system has balancing valves in it, these valves should be adjusted to the required GPM for this piece of equipment.

After the condensing temperature has been set up properly, the system should be allowed to run for 10 to 15 minutes to obtain stable conditions.

Note: To adjust the head pressure with Motorized Ball Valves, go to the Service Menus and then to the Options Set-up Menu. Adjust parameter S427 (Ball Valve Setpoint Offset). The default setting is +30. The range is +0 to +70. Lowering the setpoint will decrease the head pressure and an increase in the setpoint will increase the head pressure.

Entering condenser water/glycol temperature __________

Leaving condenser water/glycol temperature ___________

11. Record Suction and Discharge Pressures.

Circuit #1

Suction Pressure ____________ Discharge Pressure ____________

Circuit #2

Suction Pressure ____________ Discharge Pressure ____________

12. Check superheat and record. Superheat should be approximately 15°.

Circuit #1

Superheat __________°F

Liebert DS Warranty Inspection Check Sheet

13. Check subcooling. (Refer to MC Condenser User Manual and Warranty Inspection sheet for subcooling requirement.)

Circuit #1

Subcooling __________°F

Circuit #2

Subcooling __________°F

14. Record Total Charge

Circuit #1 __________ LBS Circuit #2 __________ LBS

15. Record compressor amperage.

Compressor #1

L1 __________ L2 __________ L3 __________ Fuse __________

Compressor #2

L1 __________ L2 __________ L3 __________ Fuse __________

16. Record compressor crankcase heater amperage.

Compressor #1 ______ Compressor #2 ______ Fuse ______

NOTE: Scroll and Digital Scroll Compressor Additional Oil Requirements System charges over 28lbs (12.7kg) may require additional oil charge to be added.

Refer to the CRV User Manual for the amount of oil required for various system charge levels and associated safety alerts. After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system

Liebert DS Warranty Inspection Check Sheet

WARNING

Arc flash and electric shock hazard. Wear personal protective equipment per NFPA 70E before working within the electric control enclosure or any hazardous voltage electric connection enclosure. Use extreme caution when checking the status of live hazardous voltage circuits. Failure to comply can cause serious injury or death.

Check unit electrical phasing with a phase meter. If phasing is incorrect, change wiring at input source to unit. Do not change any unit or component phasing.

Check the compressors for proper rotation by bumping the contactors and watching the gauge pressures. If the pressures are equalized and the compressor sounds noisy, then compressor is running backwards.

3. Check and record control voltage transformers for proper output. (Secondary voltage should not be under 23 VAC or exceed 27 VAC under load, change tap if necessary).

T1__________Volt

4. Record iCOM Software Version: _________________

NOTE: The software version is located in the Network Menu that is located in Service Menus.

NOTE: Check operation of each component by utilizing the Service Menu that is located in the Service Menus on the iCOM Control.

5. Enable Manual Mode.

6. Enable Fans and record Main Fan amperage.

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

Liebert DS Warranty Inspection Check Sheet

NOTE: On units with Infrared humidifiers, fill pan with water before turning on the lamps. Check water level and adjust high limit float for proper operation.

8. Enable Humidifier and record amperage. Check for leaks at all piping connections.

Disable Humidifier after test.

WARNING

Risk of electric shock and contact with extremely hot parts, can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or energized humidifier bulbs.

L1 __________ L2 __________ L3 __________ Fuse __________

9. Check condensate pump for proper operation by filling pump with water. Check for leaks at all piping connections. Record pump amperage. (If Applicable)

WARNING

Risk of electric shock and contact with hot motor surfaces, Can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or the energized condensate pump motor. Do not remove the condensate pump electric connection terminal cover. Use extreme caution and do not spill water on the motor or the electric connection cover.

L1 __________ L2 __________ Fuse __________

Chilled Water/Freecooling Units

Set 3P 1/2 Actuator Open to On. Check for full valve travel. Set 3P 1/2 Actuator Open to Off.

Set 3P 1/2 Actuator Close to On. Check for complete valve closure. Set 3P 1/2

Liebert DS Warranty Inspection Check Sheet

Water/Glycol System Operation

If the head pressures recorded below equal 105°F condensing temperature, no adjustment of the glycol/water regulating valves or Motorized Ball Valves are required.

If the condensing temperatures are above 110°F, adjust the glycol/water regulating valves/Motorized Ball Valves to lower the head pressure. If the system has balancing valves in it, these valves should be adjusted to the required GPM for this piece of equipment.

After the condensing temperature has been set up properly, the system should be allowed to run for 10 to 15 minutes to obtain stable conditions.

Note: To adjust the head pressure with Motorized Ball Valves, go to the Service Menus and then to the Options Set-up Menu. Adjust parameter S427 (Ball Valve Setpoint Offset). The default setting is +30. The range is +0 to +70. Lowering the setpoint will decrease the head pressure and an increase in the setpoint will increase the head pressure.

Entering condenser water/glycol temperature __________

Leaving condenser water/glycol temperature ___________

11. Record Suction and Discharge Pressures.

Circuit #1

Suction Pressure ____________ Discharge Pressure ____________

Circuit #2

Suction Pressure ____________ Discharge Pressure ____________

12. Check superheat and record. Superheat should be approximately 15°.

Circuit #1

Superheat __________°F

Liebert DS Warranty Inspection Check Sheet

13. Check subcooling. (Refer to MC Condenser User Manual and Warranty Inspection sheet for subcooling requirement.)

Circuit #1

Subcooling __________°F

Circuit #2

Subcooling __________°F

14. Record Total Charge

Circuit #1 __________ LBS Circuit #2 __________ LBS

15. Record compressor amperage.

Compressor #1

L1 __________ L2 __________ L3 __________ Fuse __________

Compressor #2

L1 __________ L2 __________ L3 __________ Fuse __________

16. Record compressor crankcase heater amperage.

Compressor #1 ______ Compressor #2 ______ Fuse ______

NOTE: Scroll and Digital Scroll Compressor Additional Oil Requirements System charges over 28lbs (12.7kg) may require additional oil charge to be added.

Refer to the CRV User Manual for the amount of oil required for various system charge levels and associated safety alerts. After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system

Liebert DS Warranty Inspection Check Sheet

WARNING

Arc flash and electric shock hazard. Wear personal protective equipment per NFPA 70E before working within the electric control enclosure or any hazardous voltage electric connection enclosure. Use extreme caution when checking the status of live hazardous voltage circuits. Failure to comply can cause serious injury or death.

Check unit electrical phasing with a phase meter. If phasing is incorrect, change wiring at input source to unit. Do not change any unit or component phasing.

Check the compressors for proper rotation by bumping the contactors and watching the gauge pressures. If the pressures are equalized and the compressor sounds noisy, then compressor is running backwards.

3. Check and record control voltage transformers for proper output. (Secondary voltage should not be under 23 VAC or exceed 27 VAC under load, change tap if necessary).

T1__________Volt

4. Record iCOM Software Version: _________________

NOTE: The software version is located in the Network Menu that is located in Service Menus.

NOTE: Check operation of each component by utilizing the Service Menu that is located in the Service Menus on the iCOM Control.

5. Enable Manual Mode.

6. Enable Fans and record Main Fan amperage.

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

L1 __________ L2 __________ L3__________ Fuse __________

Liebert DS Warranty Inspection Check Sheet

NOTE: On units with Infrared humidifiers, fill pan with water before turning on the lamps. Check water level and adjust high limit float for proper operation.

8. Enable Humidifier and record amperage. Check for leaks at all piping connections.

Disable Humidifier after test.

WARNING

Risk of electric shock and contact with extremely hot parts, can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or energized humidifier bulbs.

L1 __________ L2 __________ L3 __________ Fuse __________

9. Check condensate pump for proper operation by filling pump with water. Check for leaks at all piping connections. Record pump amperage. (If Applicable)

WARNING

Risk of electric shock and contact with hot motor surfaces, Can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or the energized condensate pump motor. Do not remove the condensate pump electric connection terminal cover. Use extreme caution and do not spill water on the motor or the electric connection cover.

L1 __________ L2 __________ Fuse __________

Chilled Water/Freecooling Units

Set 3P 1/2 Actuator Open to On. Check for full valve travel. Set 3P 1/2 Actuator Open to Off.

Set 3P 1/2 Actuator Close to On. Check for complete valve closure. Set 3P 1/2

Liebert DS Warranty Inspection Check Sheet

Water/Glycol System Operation

If the head pressures recorded below equal 105°F condensing temperature, no adjustment of the glycol/water regulating valves or Motorized Ball Valves are required.

If the condensing temperatures are above 110°F, adjust the glycol/water regulating valves/Motorized Ball Valves to lower the head pressure. If the system has balancing valves in it, these valves should be adjusted to the required GPM for this piece of equipment.

After the condensing temperature has been set up properly, the system should be allowed to run for 10 to 15 minutes to obtain stable conditions.

Note: To adjust the head pressure with Motorized Ball Valves, go to the Service Menus and then to the Options Set-up Menu. Adjust parameter S427 (Ball Valve Setpoint Offset). The default setting is +30. The range is +0 to +70. Lowering the setpoint will decrease the head pressure and an increase in the setpoint will increase the head pressure.

Entering condenser water/glycol temperature __________

Leaving condenser water/glycol temperature ___________

11. Record Suction and Discharge Pressures.

Circuit #1

Suction Pressure ____________ Discharge Pressure ____________

Circuit #2

Suction Pressure ____________ Discharge Pressure ____________

12. Check superheat and record. Superheat should be approximately 15°.

Circuit #1

Superheat __________°F

Liebert DS Warranty Inspection Check Sheet

13. Check subcooling. (Refer to MC Condenser User Manual and Warranty Inspection sheet for subcooling requirement.)

Circuit #1

Subcooling __________°F

Circuit #2

Subcooling __________°F

14. Record Total Charge

Circuit #1 __________ LBS Circuit #2 __________ LBS

15. Record compressor amperage.

Compressor #1

L1 __________ L2 __________ L3 __________ Fuse __________

Compressor #2

L1 __________ L2 __________ L3 __________ Fuse __________

16. Record compressor crankcase heater amperage.

Compressor #1 ______ Compressor #2 ______ Fuse ______

NOTE: Scroll and Digital Scroll Compressor Additional Oil Requirements System charges over 28lbs (12.7kg) may require additional oil charge to be added.

Refer to the CRV User Manual for the amount of oil required for various system charge levels and associated safety alerts. After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system