This document contains a request for information response and related federal contract opportunity solicitation. The request for information response provides clarification on structural drawings for a project at Building 403, including details on how W14x22 beams will attach to block walls and confirmation that the referenced detail for spacing requirements is incorrect. The related federal contract opportunity solicitation is for project number PBXP 169102 to add and alter the Corrosion Control facility at Mansfield Air National Guard Base. The solicitation requires construction services including interior/exterior demolition, site work, security upgrades, mechanical and electrical systems, and communications infrastructure. The base bid is estimated between $1-5 million and has an anticipated 300-day performance period, and includes four additive bid items. The solicitation is set aside for small businesses and responses are due by December 7, 2020, with a pre-bid conference scheduled for November 5, 2020. The solicitation and amendments will be posted to Beta.SAM and interested parties must register in SAM.gov.
View the file
Other files for this federal contract opportunity
Show all 50
ADD/ALTER B403 CC has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
R E
Q U
E S
T O
R S
E C
T
IO
N
From:
Date:
11/06/2020
To: Contracting Officer
1. Solicitation Number:
W50S8R-21-B-0001
2. Location of Project:
Building 403
3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)
Please see below for a some clarifications needed on structural drawings.
Drawing S-111 (sheet 17 of 77) & S-521 (23 of 77)
#1. Is there a detail available showing the how the W14 x 22 horizontal beams attach to the block wall?
#2. Detail 5 on 531 refers you to plans for spacing requirements but no spacing requirements are noted. Please advise.
Attachments:
Date Response Required:
By:
Title:
Requestor's FAX Number:
Requestor's Telephone Number:
C E
R E
S P
O N
S E
To:
Date:
Response:
#1. W14x22 will bear on the pilaster similar to the detail below. The pilaster will be notched to create the bearing surface for the beam. Provide an embed plate w/ headed anchors as shown.
#2. There’s no reference to the plans for spacing on detail 5/S-531, is the right detail referenced?
This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.
This information is a proposed change to the solicitation/contract. An amendment will be issued.
Contracting Officer: