Attach5_Vol_5_Specifications.pdf
PDF 2 MB Posted
- Attached to
- REPLACE FIRE STATION Federal contract opportunity
- Solicitation number
- W50S8R-20-B-0001
About this file
This is a solicitation notice for project number PBXP929798 to replace an existing fire station at Mansfield Air National Guard Base in Mansfield, Ohio. The project includes constructing a new aircraft rescue firefighting facility and emergency management training space. The construction duration is estimated at 660 calendar days from notice to proceed. Optional items to be included are concrete paving and four-fold apparatus doors. Bids will be evaluated without discussions and awarded in accordance with FAR 14.101(e). The project is set aside for small businesses with a NAICS code of 236220 and size standard of $39.5 million average annual revenue. The magnitude is estimated between $10-20 million. The pre-bid conference is scheduled for November 5, 2019 and bids are due November 26, 2019. Interested contractors must register in SAM and check the FedBizOpps website for solicitation documents and any amendments. The facility is located at the 179th Airlift Wing in Mansfield, Ohio.
Volume 5 - Specifications
View the file
Other files for this federal contract opportunity
Show all 50
REPLACE FIRE STATION has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T Y P E B ‐ 3 F I N A L
Replace Fire Station Project Number PBXP929798
Volume 5 – Specifications (4 of 4)
Prepared for
179th Civil Engineering Squadron Ohio Air National Guard
Mansfield LAHM ANG Base
August 2019
CH2M HILL – HDR JV
241 Taylor Street, Suite 100
Dayton, Ohio 45402
REPLACE FIRE STATION – MANSFIELD LAHM ANG BASE 684448
PROJECT PHASE
PW\DEN001\684448 SEALS PAGE
AUGUST 2019 00 01 07 - 1
SECTION 00 01 07
SEALS PAGE
SPECIFICATIONS
DIVISION 01 – GENERAL REQUIREMENTS
Dennis Pearson, P.E.
AUGUST 2019 00 01 07 - 2
DIVISION 03 – CONCRETE
DIVISION 04 – MASONRY
DIVISION 05 – METALS
DIVISION 41 – MATERIAL PROCESSING AND HANDLING EQUIPMENT
Katrina Pearson, P.E.
AUGUST 2019 00 01 07 - 3
DIVISION 02 – EXISTING CONDITIONS
DIVISION 31 – EARTHWORK
DIVISION 32 – EXTERIOR IMPROVEMENTS
DIVISION 33 – UTILITIES
33 11 00, Water Utility Distribution Piping 33 30 00, Sanitary Sewerage 33 40 00, Storm Drainage Utilities
DIVISION 46 – WATER AND WASTEWATER EQUIPMENT
Amanda Thompson, P.E.
AUGUST 2019 00 01 07 - 4
DIVISION 06 – WOOD, PLASTICS, AND COMPOSITES
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
DIVISION 08 – OPENINGS
DIVISION 09 – FINISHES
DIVISION 10 – SPECIALTIES
DIVISION 14 – CONVEYING EQUIPMENT
John Patrick Reseigh, P.E.
AUGUST 2019 00 01 07 - 5
DIVISION 21 – FIRE SUPPRESSION
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
William A. Clay, P.E.
AUGUST 2019 00 01 07 - 6
DIVISION 22 – PLUMBING
DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
Jamin Henry McMurren, P.E.
AUGUST 2019 00 01 07 - 7
DIVISION 26 – ELECTRICAL
DIVISION 33 – UTILITIES
33 71 01.00 40, Overhead Transmission and Distribution 33 71 02, Underground Electrical Distribution
Jennifer Lisa Leschper, P.E.
AUGUST 2019 00 01 07 - 8
DIVISION 27 – COMMUNICATIONS
DIVISION 33 – UTILITIES
33 82 00, Telecommunications Outside Plant (OSP)
Marc Adkison, RCDD
END OF SECTION
REPLACE FI RE STATI ON - MANSFI ELD LAHM ANG BASE 684448
PROJECT TABLE OF CONTENTS
VOLUME 2
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRI CTI ONS
01 22 00. 00 10 PRI CE AND PAYMENT PROCEDURES
01 30 00 ADMI NI STRATI VE REQUI REMENTS
01 32 01. 00 10 PROJECT SCHEDULE
01 33 00 SUBMI TTAL PROCEDURES
SUPPLEMENT:
SUBMI TTAL REGI STER
01 33 29 SUSTAI NABI LI TY REPORTI NG
01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS
01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS
01 45 00. 00 10 QUALI TY CONTROL
01 45 35 SPECI AL I NSPECTI ONS
01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS
01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS
01 58 00 PROJECT I DENTI FI CATI ON
01 74 19 CONSTRUCTI ON WASTE MANAGEMENT AND DI SPOSAL
01 78 00 CLOSEOUT SUBMI TTALS
01 78 23 OPERATI ON AND MAI NTENANCE DATA
01 91 00. 15 TOTAL BUI LDI NG COMMI SSI ONI NG
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION
DI VI SI ON 03 - CONCRETE
03 30 00 CAST- I N- PLACE CONCRETE
03 30 53 MI SCELLANEOUS CAST- I N- PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 UNI T MASONRY
DI VI SI ON 05 - METALS
05 05 23. 13 10 ULTRASONI C I NSPECTI ON OF WELDMENTS
05 05 23. 16 STRUCTURAL WELDI NG
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOI ST FRAMI NG
05 30 00 STEEL DECKS
05 40 00 COLD- FORMED METAL FRAMI NG
05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS
05 51 00 METAL STAI RS
05 51 33 METAL LADDERS
05 52 00 METAL RAI LI NGS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 ROUGH CARPENTRY
06 41 16. 00 10 PLASTI C- LAMI NATE- CLAD ARCHI TECTURAL CABI NETS
06 61 16 SOLI D SURFACI NG FABRI CATI ONS
PROJECT TABLE OF CONTENTS Page 1 August 07, 2019
VOLUME 3
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 PRESSURE TESTI NG AN AI R BARRI ER SYSTEM FOR AI R TI GHTNESS
07 21 13 BOARD AND BLOCK I NSULATI ON
07 22 00 ROOF AND DECK I NSULATI ON
07 27 10. 00 10 BUI LDI NG AI R BARRI ER SYSTEM
07 27 19. 01 SELF- ADHERI NG AI R BARRI ERS
07 53 23 ETHYLENE- PROPYLENE- DI ENE- MONOMER ROOFI NG
07 60 00 FLASHI NG AND SHEET METAL
07 61 14. 00 20 STEEL STANDI NG SEAM ROOFI NG
07 84 00 FIRESTOPPING
07 92 00 JOI NT SEALANTS
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 33 23 OVERHEAD COI LI NG DOORS
08 34 01 FORCED ENTRY RESI STANT COMPONENTS
08 37 13 FOUR- FOLD DOOR SYSTEMS
08 39 54 BLAST RESI STANT DOORS
08 51 23 STEEL WI NDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 87 23. 13 SAFETY FI LMS
08 91 00 METAL WALL LOUVERS
DI VI SI ON 09 - FI NI SHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMI C, QUARRY, AND GLASS TI LI NG
09 51 00 ACOUSTI CAL CEI LI NGS
09 65 00 RESI LI ENT FLOORI NG
09 65 66 RESI LI ENT ATHLETI C FLOORI NG
09 67 23. 15 FUEL RESI STI VE RESI NOUS FLOORI NG, 3- COAT SYSTEM
09 68 00 CARPETING
09 69 13 RI GI D GRI D ACCESS FLOORI NG
09 90 00 PAI NTS AND COATI NGS
DI VI SI ON 10 - SPECI ALTI ES
10 11 00 VI SUAL DI SPLAY UNI TS
10 14 00. 20 I NTERI OR SI GNAGE
10 21 13 TOI LET COMPARTMENTS
10 26 00 WALL AND DOOR PROTECTI ON
10 28 13 TOI LET ACCESSORI ES
DI VI SI ON 14 - CONVEYI NG EQUI PMENT
14 24 23 HYDRAULI C PASSENGER ELEVATORS
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 13 13. 00 20 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON
21 23 00. 00 20 WET CHEMI CAL FI RE EXTI NGUI SHI NG FOR KI TCHEN HOOD
21 30 00 FI RE PUMPS
PROJECT TABLE OF CONTENTS Page 2
VOLUME 4
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBI NG, GENERAL PURPOSE
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS
23 05 48. 00 40 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC PI PI NG AND
EQUIPMENT
23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC
23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS
23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC
23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC
23 09 23. 02 BACNET DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER BUI LDI NG
CONTROL SYSTEMS
23 11 25 FACI LI TY GAS PI PI NG
23 21 23 HYDRONI C PUMPS
23 23 00 REFRI GERANT PI PI NG
23 25 00 CHEMI CAL TREATMENT OF WATER FOR MECHANI CAL SYSTEMS
23 52 43. 00 20 LOW PRESSURE WATER HEATI NG BOI LERS ( UNDER 800, 000 BTU/ HR
OUTPUT)
23 54 16. 00 10 HEATI NG SYSTEM; GAS- FI RED HEATERS
23 64 26 CHI LLED, CHI LLED- HOT, AND CONDENSER WATER PI PI NG SYSTEMS
23 81 00 DECENTRALI ZED UNI TARY HVAC EQUI PMENT
23 81 47 WATER- LOOP HEAT PUMP SYSTEMS
23 82 00. 00 20 TERMI NAL HEATI NG UNI TS
DI VI SI ON 26 - ELECTRI CAL
26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS
26 05 13. 00 40 MEDI UM- VOLTAGE CABLES
26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
26 12 19. 10 THREE- PHASE PAD- MOUNTED TRANSFORMERS
26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM
26 24 13 SWITCHBOARDS
26 24 16. 00 40 PANELBOARDS
26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON
26 28 21. 00 40 AUTOMATI C TRANSFER SWI TCHES
26 32 13. 00 20 SI NGLE OPERATI ON GENERATOR SETS
26 33 53. 00 20 UNI NTERRUPTI BLE POWER SUPPLY ( UPS)
26 41 00 LI GHTNI NG PROTECTI ON SYSTEM
26 51 00 I NTERI OR LI GHTI NG
26 56 00 EXTERI OR LI GHTI NG
VOLUME 5
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
27 51 16 RADI O AND PUBLI C ADDRESS SYSTEMS
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 08 10 ELECTRONI C SECURI TY SYSTEM ACCEPTANCE TESTI NG
28 10 05 ELECTRONI C SECURI TY SYSTEMS ( ESS)
28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM
PROJECT TABLE OF CONTENTS Page 3
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 11 00 CLEARI NG AND GRUBBI NG
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 05 33 LANDSCAPE ESTABLI SHMENT
32 11 23 AGGREGATE BASE COURSES
32 12 13 BI TUMI NOUS TACK AND PRI ME COATS
32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS
32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE
FACILITIES
32 13 73 COMPRESSI ON JOI NT SEALS FOR CONCRETE PAVEMENTS
32 15 00 AGGREGATE SURFACI NG
32 16 19 CONCRETE CURBS, GUTTERS AND SI DEWALKS
32 17 23 PAVEMENT MARKI NGS
32 31 13 CHAI N LI NK FENCES AND GATES
32 92 23 SODDING
DI VI SI ON 33 - UTI LI TI ES
33 11 00 WATER UTI LI TY DI STRI BUTI ON PI PI NG
33 30 00 SANI TARY SEWERAGE
33 40 00 STORM DRAI NAGE UTI LI TI ES
33 71 01. 00 40 OVERHEAD TRANSMI SSI ON AND DI STRI BUTI ON
33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON
33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)
DI VI SI ON 41 - MATERI AL PROCESSI NG AND HANDLI NG EQUI PMENT
41 22 13. 15 BRI DGE CRANES, OVERHEAD ELECTRI C, UNDER RUNNI NG BI D
OPTI ON #4
DI VI SI ON 46 - WATER AND WASTEWATER EQUI PMENT
46 25 14 COALESCI NG OI L- WATER SEPARATORS
- - End of Pr oj ect Tabl e of Cont ent s - -
PROJECT TABLE OF CONTENTS Page 4
SECTI ON 27 10 00
BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
08/11
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ASTM I NTERNATI ONAL ( ASTM)
ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
ELECTRONI C COMPONENTS I NDUSTRY ASSOCI ATI ON ( ECI A)
ECI A EI A/ ECA 310- E ( 2005) Cabi net s, Racks, Panel s, and Associ at ed Equi pment
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I NSULATED CABLE ENGI NEERS ASSOCI ATI ON ( I CEA)
I CEA S- 83- 596 ( 2016) I ndoor Opt i cal Fi ber Cabl es
I CEA S- 90- 661 ( 2012) Cat egor y 3, 5, & 5e I ndi v i dual l y Unshi el ded Twi st ed Pai r I ndoor Cabl es f or Use i n Gener al Pur pose and LAN Communi cat i ons Wi r i ng Syst ems Techni cal Requirements
NATI ONAL ELECTRI CAL CONTRACTORS ASSOCI ATI ON ( NECA)
NECA/ BI CSI 568 ( 2006) St andar d f or I nst al l i ng Bui l di ng Tel ecommuni cat i ons Cabl i ng
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
ANSI / NEMA WC 66 ( 2013) Per f or mance St andar d f or Cat egor y 6 and Cat egor y 7 100 Ohm Shi el ded and Unshi el ded Twi st ed Pai r s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14; TI A 17- 15; TI A 17- 16; TI A 17- 17 )
Nat i onal El ect r i cal Code
SECTI ON 27 10 00 Page 1 PW\DEN001\684448 Jul y 26, 2019
TELECOMMUNI CATI ONS I NDUSTRY ASSOCI ATI ON ( TI A)
TIA-1152 ( 2009) Requi r ement s f or Fi el d Test I nst r ument s and Measur ement s f or Bal anced Twi st ed- Pai r Cabl i ng
TIA-455-21 ( 1988a; R 2012) FOTP- 21 - Mat i ng Dur abi l i t y of Fi ber Opt i c I nt er connect i ng Devices
TIA-526-14 ( 2015c) OFSTP- 14A Opt i cal Power Loss Measur ement s of I nst al l ed Mul t i mode Fi ber Cabl e Pl ant
TIA-526-7 ( 2015a) OFSTP- 7 Measur ement of Opt i cal Power Loss of I nst al l ed Si ngl e- Mode Fi ber Cabl e Pl ant
TIA-568-C.0 ( 2009; Add 1 2010; Add 2 2012) Gener i c Tel ecommuni cat i ons Cabl i ng f or Cust omer Premises
TIA-568-C.1 ( 2009; Add 2 2011; Add 1 2012) Commer ci al Bui l di ng Tel ecommuni cat i ons Cabl i ng Standard
TIA-568-C.2 ( 2009; Er r at a 2010; Add 2 2014; Add 1 2016) Bal anced Twi st ed- Pai r Tel ecommuni cat i ons Cabl i ng and Component s Standards
TIA-568-C.3 ( 2008; Add 1 2011) Opt i cal Fi ber Cabl i ng Component s St andar d
TIA-569 ( 2015d) Commer ci al Bui l di ng St andar d f or Tel ecommuni cat i ons Pat hways and Spaces
TIA-606 ( 2017c) Admi ni st r at i on St andar d f or t he Tel ecommuni cat i ons I nf r ast r uct ur e
TIA-607 ( 2011b) Gener i c Tel ecommuni cat i ons Bondi ng and Gr oundi ng ( Ear t hi ng) f or Cust omer Premises
TIA/EIA-598 ( 2014D; Add 2 2018) Opt i cal Fi ber Cabl e Col or Codi ng
TIA/EIA-604-10 ( 2002a) FOCI S 10 Fi ber Opt i c Connect or I nt er mat eabi l i t y St andar d - Type LC
UNDERWRI TERS LABORATORI ES ( UL)
UL 1286 ( 2008; Repr i nt Jan 2018) UL St andar d f or Saf et y Of f i ce Fur ni shi ngs
UL 1666 ( 2007; Repr i nt Jun 2012) Test f or Fl ame Pr opagat i on Hei ght of El ect r i cal and Opt i cal - Fi ber Cabl es I nst al l ed Ver t i cal l y i n Shaf t s
SECTI ON 27 10 00 Page 2 PW\DEN001\684448
UL 1863 ( 2004; Repr i nt Sep 2016) UL St andar d f or Saf et y Communi cat i on Ci r cui t Accessor i es
UL 444 ( 2008; Repr i nt Apr 2015) Communi cat i ons Cables
UL 467 ( 2013; Repr i nt Jun 2017) UL St andar d f or Saf et y Gr oundi ng and Bondi ng Equi pment
UL 50 ( 2015) UL St andar d f or Saf et y Encl osur es f or El ect r i cal Equi pment , Non- Envi r onment al Consi der at i ons
UL 723 ( 2018) UL St andar d f or Saf et y Test f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Mat er i al s
UL 969 ( 2017; Repr i nt Mar 2018) UL St andar d f or Saf et y Mar ki ng and Label i ng Syst ems
1. 2 RELATED REQUI REMENTS
Section 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM and Sect i on 33 82 00 TELECOMMUNI CATI ONS, OUTSI DE PLANT ( OSP) , appl y t o t hi s sect i on wi t h addi t i ons and modi f i cat i ons speci f i ed her ei n.
1. 3 DEFINITIONS
Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hi s speci f i cat i on shal l be as def i ned i n TIA-568-C.1 , TIA-568-C.2 , TIA-568-C.3 , TIA-569 , TIA-606 and I EEE 100 and her ei n.
1. 3. 1 Campus Di st r i but or ( CD)
A di st r i but or f r om whi ch t he campus backbone cabl i ng emanat es.
( I nt er nat i onal expr essi on f or mai n cr oss- connect ( MC) . )
1. 3. 2 Bui l di ng Di st r i but or ( BD)
A di st r i but or i n whi ch t he bui l di ng backbone cabl es t er mi nat e and at whi ch connect i ons t o t he campus backbone cabl es may be made. ( I nt er nat i onal expr essi on f or i nt er medi at e cr oss- connect ( I C) . )
1. 3. 3 Fl oor Di st r i but or ( FD)
A di st r i but or used t o connect hor i zont al cabl e and cabl i ng subsyst ems or equi pment . ( I nt er nat i onal expr essi on f or hor i zont al cr oss- connect ( HC) . )
1. 3. 4 Tel ecommuni cat i ons Room ( TR)
An encl osed space f or housi ng t el ecommuni cat i ons equi pment , cabl e, t er mi nat i ons, and cr oss- connect s. The r oom i s t he r ecogni zed cr oss- connect bet ween t he backbone cabl e and t he hor i zont al cabl i ng.
1. 3. 5 Ent r ance Faci l i t y ( EF) ( Tel ecommuni cat i ons)
An ent r ance t o t he bui l di ng f or bot h pr i vat e and publ i c net wor k ser vi ce cabl es ( i ncl udi ng wi r el ess) i ncl udi ng t he ent r ance poi nt at t he bui l di ng
SECTI ON 27 10 00 Page 3 PW\DEN001\684448 wal l and cont i nui ng t o t he equi pment r oom.
1. 3. 6 Equi pment Room ( ER) ( Tel ecommuni cat i ons)
An envi r onment al l y cont r ol l ed cent r al i zed space f or t el ecommuni cat i ons equi pment t hat ser ves t he occupant s of a bui l di ng. Equi pment housed t her ei n i s consi der ed di st i nct f r om a t el ecommuni cat i ons r oom because of t he nat ur e of i t s compl exi t y.
1. 3. 7 Open Cabl e
Cabl i ng t hat i s not r un i n a r aceway as def i ned by NFPA 70. Thi s r ef er s t o cabl i ng t hat i s " open" t o t he space i n whi ch t he cabl e has been i nst al l ed and i s t her ef or e exposed t o t he envi r onment al condi t i ons associ at ed wi t h t hat space.
1. 3. 8 Open Of f i ce
A f l oor space di v i s i on pr ovi ded by f ur ni t ur e, moveabl e par t i t i ons, or ot her means i nst ead of by bui l di ng wal l s.
1. 3. 9 Pathway
A physi cal i nf r ast r uct ur e ut i l i zed f or t he pl acement and r out i ng of t el ecommuni cat i ons cabl e.
1. 4 SYSTEM DESCRI PTI ON
The bui l di ng t el ecommuni cat i ons cabl i ng and pat hway syst em shal l i ncl ude per manent l y i nst al l ed backbone and hor i zont al cabl i ng, hor i zont al and backbone pat hways, ser vi ce ent r ance f aci l i t i es, wor k ar ea pat hways, t el ecommuni cat i ons out l et assembl i es, condui t , r aceway, and har dwar e f or spl i c i ng, t er mi nat i ng, and i nt er connect i ng cabl i ng necessar y t o t r anspor t t el ephone and dat a ( i ncl udi ng LAN) bet ween equi pment i t ems i n a bui l di ng.
The hor i zont al syst em shal l be wi r ed i n a st ar t opol ogy f r om t he t el ecommuni cat i ons wor k ar ea t o t he f l oor di st r i but or or campus di st r i but or at t he cent er or hub of t he st ar . The backbone cabl i ng and pat hway syst em i ncl udes i nt r abui l di ng and i nt er bui l di ng i nt er connect i ng cabl i ng, pat hway, and t er mi nal har dwar e. The i nt r abui l di ng backbone pr ovi des connect i v i t y f r om t he f l oor di st r i but or s t o t he bui l di ng di st r i but or s or t o t he campus di st r i but or and f r om t he bui l di ng di st r i but or s t o t he campus di st r i but or as r equi r ed. The backbone syst em shal l be wi r ed i n a st ar t opol ogy wi t h t he campus di st r i but or at t he cent er or hub of t he st ar . The i nt er bui l di ng backbone syst em pr ovi des connect i v i t y bet ween t he campus di st r i but or s and i s speci f i ed i n Sect i on 33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP) .
Pr ovi de t el ecommuni cat i ons pat hway syst ems r ef er enced her ei n as speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM. The t el ecommuni cat i ons cont r act or must coor di nat e wi t h t he NMCI / COSC/ NGEN cont r act or concer ni ng access t o and conf i gur at i on of t el ecommuni cat i ons spaces. The t el ecommuni cat i ons cont r act or may be r equi r ed t o coor di nat e wor k ef f or t wi t hi n t he t el ecommuni cat i ons spaces wi t h t he NMCI / COSC/ NGEN cont r act or .
1. 5 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment .
Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, SECTI ON 27 10 00 Page 4 PW\DEN001\684448 i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Tel ecommuni cat i ons dr awi ngs; G
Tel ecommuni cat i ons Space Dr awi ngs; G
I n addi t i on t o Sect i on 01 33 00 SUBMI TTAL PROCEDURES, pr ovi de shop dr awi ngs i n accor dance wi t h par agr aph SHOP DRAWI NGS.
SD- 03 Pr oduct Dat a
Tel ecommuni cat i ons cabl i ng ( backbone and hor i zont al ) ; G
Pat ch panel s; G
Tel ecommuni cat i ons out l et / connect or assembl i es; G
Equi pment suppor t f r ame; G
Connect or bl ocks; G
Submi t t al s shal l i ncl ude t he manuf act ur er ' s name, t r ade name, pl ace of manuf act ur e, and cat al og model or number . Submi t t al s shal l al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on r ef er ences. Shoul d manuf act ur er ' s dat a r equi r e suppl ement al i nf or mat i on f or c l ar i f i cat i on, t he suppl ement al i nf or mat i on shal l be submi t t ed as speci f i ed i n par agr aph REGULATORY REQUI REMENTS and as r equi r ed f or cer t i f i cat es i n Sect i on 01 33 00 SUBMI TTAL PROCEDURES.
SD- 06 Test Repor t s
Tel ecommuni cat i ons cabl i ng t est i ng; G
SD- 07 Cer t i f i cat es
Tel ecommuni cat i ons Cont r act or Qual i f i cat i ons; G
Key Per sonnel Qual i f i cat i ons; G
Manuf act ur er Qual i f i cat i ons; G
Test pl an; G
SD- 09 Manuf act ur er ' s Fi el d Repor t s
Fact or y r eel t est s; G
SD- 10 Oper at i on and Mai nt enance Dat a
Tel ecommuni cat i ons cabl i ng and pat hway syst em Dat a Package 5; G
SD- 11 Cl oseout Submi t t al s
Recor d Document at i on; G
SECTI ON 27 10 00 Page 5 PW\DEN001\684448
1. 6 QUALI TY ASSURANCE
1. 6. 1 Shop Dr awi ngs
I n except i on t o Sect i on 01 33 00 SUBMI TTAL PROCEDURES, submi t t ed pl an dr awi ngs shal l be a mi ni mum of 11 by 17 i nches i n s i ze usi ng a mi ni mum scal e of 1/ 8 i nch per f oot . I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. Wi r i ng di agr ams shal l i dent i f y c i r cui t t er mi nal s and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . Dr awi ngs shal l i ndi cat e adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces. Submi t t al s shal l i ncl ude t he namepl at e dat a, s i ze, and capaci t y. Submi t t al s shal l al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on references.
1. 6. 1. 1 Tel ecommuni cat i ons Dr awi ngs
Pr ovi de r egi st er ed communi cat i ons di st r i but i on desi gner ( RCDD) appr oved, dr awi ngs i n accor dance wi t h TIA-606 . The i dent i f i er f or each t er mi nat i on and cabl e shal l appear on t he dr awi ngs. Dr awi ngs shal l depi ct f i nal t el ecommuni cat i ons i nst al l ed wi r i ng syst em i nf r ast r uct ur e i n accor dance with TIA-606 . The dr awi ngs shoul d pr ovi de det ai l s r equi r ed t o pr ove t hat t he di st r i but i on syst em shal l pr oper l y suppor t connect i v i t y f r om t he EF t el ecommuni cat i ons and ER t el ecommuni cat i ons, CDs, BDs, and FDs t o t he t el ecommuni cat i ons wor k ar ea out l et s. Pr ovi de a pl ast i c l ami nat ed schemat i c of t he as- i nst al l ed t el ecommuni cat i ons cabl e syst em showi ng cabl i ng, CDs, BDs, FDs, and t he EF and ER f or t el ecommuni cat i ons keyed t o f l oor pl ans by r oom number . Mount t he l ami nat ed schemat i c i n t he EF t el ecommuni cat i ons space as di r ect ed by t he Cont r act i ng Of f i cer . The f ol l owi ng dr awi ngs shal l be pr ovi ded as a mi ni mum:
a. T1 - Layout of compl et e bui l di ng per f l oor - Bui l di ng Ar ea/ Ser vi ng Zone Boundar i es, Backbone Syst ems, and Hor i zont al Pat hways. Layout of compl et e bui l di ng per f l oor . The dr awi ng i ndi cat es l ocat i on of bui l di ng ar eas, ser vi ng zones, ver t i cal backbone di agr ams, t el ecommuni cat i ons r ooms, access poi nt s, pat hways, gr oundi ng syst em, and ot her syst ems t hat need t o be v i ewed f r om t he compl et e bui l di ng per spect i ve.
b. T2 - Ser vi ng Zones/ Bui l di ng Ar ea Dr awi ngs - Dr op Locat i ons and Cabl e I dent i f i cat i on ( I DS) . Shows a bui l di ng ar ea or ser vi ng zone. These dr awi ngs show dr op l ocat i ons, t el ecommuni cat i ons r ooms, access poi nt s and det ai l cal l out s f or common equi pment r ooms and ot her congest ed areas.
c. T4 - Typi cal Det ai l Dr awi ngs - Facepl at e Label i ng, Fi r est oppi ng, Amer i cans wi t h Di sabi l i t i es Act ( ADA) , Saf et y, Depar t ment of Tr anspor t at i on ( DOT) . Det ai l ed dr awi ngs of symbol s and t ypi cal s such as f acepl at e l abel i ng, f acepl at e t ypes, f acepl at e popul at i on i nst al l at i on pr ocedur es, det ai l r acki ng, and r aceways.
1. 6. 1. 2 Tel ecommuni cat i ons Space Dr awi ngs
Pr ovi de T3 dr awi ngs i n accor dance wi t h TIA-606 t hat i ncl ude t el ecommuni cat i ons r ooms pl an v i ews, pat hway l ayout ( cabl e t r ay, r acks, l adder - r acks, et c. ) , mechani cal / el ect r i cal l ayout , and cabi net , r ack, backboar d and wal l el evat i ons. Dr awi ngs shal l show l ayout of appl i cabl e
SECTI ON 27 10 00 Page 6 PW\DEN001\684448 equi pment i ncl udi ng i ncomi ng cabl e st ub or connect or bl ocks, bui l di ng pr ot ect or assembl y, out goi ng cabl e connect or bl ocks, pat ch panel s and equi pment spaces and cabi net / r acks. Dr awi ngs shal l i ncl ude a compl et e l i s t of equi pment and mat er i al , equi pment r ack det ai l s , pr oposed l ayout and anchor age of equi pment and appur t enances, and equi pment r el at i onshi p t o ot her par t s of t he wor k i ncl udi ng c l ear ance f or mai nt enance and oper at i on.
Dr awi ngs may al so be an enl ar gement of a congest ed ar ea of T1 or T2 drawings.
1. 6. 2 Tel ecommuni cat i ons Qual i f i cat i ons
Wor k under t hi s sect i on shal l be per f or med by and t he equi pment shal l be pr ovi ded by t he appr oved t el ecommuni cat i ons cont r act or and key per sonnel .
Qual i f i cat i ons shal l be pr ovi ded f or : t he t el ecommuni cat i ons syst em cont r act or , t he t el ecommuni cat i ons syst em i nst al l er , and t he super v i sor ( i f di f f er ent f r om t he i nst al l er ) . A mi ni mum of 30 days pr i or t o i nst al l at i on, submi t document at i on of t he exper i ence of t he t el ecommuni cat i ons cont r act or and of t he key per sonnel .
1. 6. 2. 1 Tel ecommuni cat i ons Cont r act or
The t el ecommuni cat i ons cont r act or shal l be a f i r m whi ch i s r egul ar l y and pr of essi onal l y engaged i n t he busi ness of t he appl i cat i ons, i nst al l at i on, and t est i ng of t he speci f i ed t el ecommuni cat i ons syst ems and equi pment . The t el ecommuni cat i ons cont r act or shal l demonst r at e exper i ence i n pr ovi di ng successf ul t el ecommuni cat i ons syst ems wi t hi n t he past 3 year s of s i mi l ar scope and si ze. Submi t document at i on f or a mi ni mum of t hr ee and a maxi mum of f i ve successf ul t el ecommuni cat i on syst em i nst al l at i ons f or t he t el ecommuni cat i ons cont r act or .
1. 6. 2. 2 Key Per sonnel
Pr ovi de key per sonnel who ar e r egul ar l y and pr of essi onal l y engaged i n t he busi ness of t he appl i cat i on, i nst al l at i on and t est i ng of t he speci f i ed t el ecommuni cat i ons syst ems and equi pment . Ther e may be one key per son or mor e key per sons pr oposed f or t hi s sol i c i t at i on dependi ng upon how many of t he key r ol es each has successf ul l y pr ovi ded. Each of t he key per sonnel shal l demonst r at e exper i ence i n pr ovi di ng successf ul t el ecommuni cat i ons syst ems wi t hi n t he past 3 year s.
Super vi sor s and i nst al l er s assi gned t o t he i nst al l at i on of t hi s syst em or any of i t s component s shal l be Bui l di ng I ndust r y Consul t i ng Ser vi ces I nt er nat i onal ( BI CSI ) Regi st er ed Cabl i ng I nst al l er s, Techni c i an Level .
Submi t document at i on of cur r ent BI CSI cer t i f i cat i on f or each of t he key personnel.
I n l i eu of BI CSI cer t i f i cat i on, super vi sor s and i nst al l er s assi gned t o t he i nst al l at i on of t hi s syst em or any of i t s component s shal l have a mi ni mum of 3 year s exper i ence i n t he i nst al l at i on of t he speci f i ed copper and f i ber opt i c cabl e and component s. They shal l have f act or y or f act or y appr oved cer t i f i cat i on f r om each equi pment manuf act ur er i ndi cat i ng t hat t hey ar e qual i f i ed t o i nst al l and t est t he pr ovi ded pr oduct s. Submi t document at i on f or a mi ni mum of t hr ee and a maxi mum of f i ve successf ul t el ecommuni cat i on syst em i nst al l at i ons f or each of t he key per sonnel . Document at i on f or each key per son shal l i ncl ude at l east t wo successf ul syst em i nst al l at i ons pr ovi ded t hat ar e equi val ent i n syst em si ze and i n const r uct i on compl exi t y t o t he t el ecommuni cat i ons syst em pr oposed f or t hi s sol i c i t at i on. I ncl ude speci f i c exper i ence i n i nst al l i ng and t est i ng t el ecommuni cat i ons syst ems and pr ovi de t he names and l ocat i ons of at l east t wo pr oj ect i nst al l at i ons
SECTI ON 27 10 00 Page 7 PW\DEN001\684448 successf ul l y compl et ed usi ng opt i cal f i ber and copper t el ecommuni cat i ons cabl i ng syst ems. Al l of t he exi st i ng t el ecommuni cat i ons syst em i nst al l at i ons of f er ed by t he key per sons as successf ul exper i ence shal l have been i n successf ul f ul l - t i me ser vi ce f or at l east 18 mont hs pr i or t o t he i ssuance dat e f or t hi s sol i c i t at i on. Pr ovi de t he name and r ol e of t he key per son, t he t i t l e, l ocat i on, and compl et ed i nst al l at i on dat e of t he r ef er enced pr oj ect , t he r ef er enced pr oj ect owner poi nt of cont act i nf or mat i on i ncl udi ng name, or gani zat i on, t i t l e, and t el ephone number , and gener al l y, t he r ef er enced pr oj ect descr i pt i on i ncl udi ng syst em si ze and const r uct i on compl exi t y.
I ndi cat e t hat al l key per sons ar e cur r ent l y empl oyed by t he t el ecommuni cat i ons cont r act or , or have a commi t ment t o t he t el ecommuni cat i ons cont r act or t o wor k on t hi s pr oj ect . Al l key per sons shal l be empl oyed by t he t el ecommuni cat i ons cont r act or at t he dat e of i ssuance of t hi s sol i c i t at i on, or i f not , have a commi t ment t o t he t el ecommuni cat i ons cont r act or t o wor k on t hi s pr oj ect by t he dat e t hat t he bi d was due t o t he Cont r act i ng Of f i cer .
Not e t hat onl y t he key per sonnel appr oved by t he Cont r act i ng Of f i cer i n t he successf ul pr oposal shal l do wor k on t hi s sol i c i t at i on' s t el ecommuni cat i ons syst em. Key per sonnel shal l f unct i on i n t he same r ol es i n t hi s cont r act , as t hey f unct i oned i n t he of f er ed successf ul exper i ence. Any subst i t ut i ons f or t he t el ecommuni cat i ons cont r act or ' s key per sonnel r equi r es appr oval f r om The Cont r act i ng Of f i cer .
1. 6. 2. 3 Minimum Manuf act ur er Qual i f i cat i ons
Cabl i ng, equi pment and har dwar e manuf act ur er s shal l have a mi ni mum of 3 year s exper i ence i n t he manuf act ur i ng, assembl y, and f act or y t est i ng of component s whi ch compl y wi t h TIA-568-C.1 , TIA-568-C.2 and TIA-568-C.3 .
1. 6. 3 Test Pl an
Pr ovi de a compl et e and det ai l ed t est pl an f or t he t el ecommuni cat i ons cabl i ng syst em i ncl udi ng a compl et e l i s t of t est equi pment f or t he component s and accessor i es f or each cabl e t ype speci f i ed, 60 days pr i or t o t he pr oposed t est dat e. I ncl ude pr ocedur es f or cer t i f i cat i on, val i dat i on, and t est i ng.
1. 6. 4 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 6. 5 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i nc l ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on
SECTI ON 27 10 00 Page 8 PW\DEN001\684448 t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.
1. 6. 5. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 6. 5. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 1 year pr i or t o dat e of del i ver y t o s i t e shal l not be used, unl ess speci f i ed ot her wi se.
1. 7 DELI VERY AND STORAGE
Pr ovi de pr ot ect i on f r om weat her , moi st ur e, ext r eme heat and col d, di r t , dust , and ot her cont ami nant s f or t el ecommuni cat i ons cabl i ng and equi pment pl aced i n st or age.
1. 8 ENVI RONMENTAL REQUI REMENTS
Connect i ng har dwar e shal l be r at ed f or oper at i on under ambi ent condi t i ons of 32 t o 140 degr ees F and i n t he r ange of 0 t o 95 per cent r el at i ve humi di t y, noncondensing.
1. 9 WARRANTY
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 10 MAINTENANCE
1. 10. 1 Oper at i on and Mai nt enance Manual s
Commer ci al of f t he shel f manual s shal l be f ur ni shed f or oper at i on, i nst al l at i on, conf i gur at i on, and mai nt enance of pr oduct s pr ovi ded as a par t of t he t el ecommuni cat i ons cabl i ng and pat hway syst em, Dat a Package 5.
Submi t oper at i ons and mai nt enance dat a i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA and as speci f i ed her ei n not l at er t han 2 mont hs pr i or t o t he dat e of benef i c i al occupancy. I n addi t i on t o r equi r ement s of Dat a Package 5, i ncl ude t he r equi r ement s of par agr aphs TELECOMMUNI CATI ONS DRAWI NGS, TELECOMMUNI CATI ONS SPACE DRAWI NGS, and RECORD DOCUMENTATI ON. Ensur e t hat t hese dr awi ngs and document s depi ct t he as- bui l t conf i gur at i on.
1. 10. 2 Recor d Document at i on
Pr ovi de T5 dr awi ngs i ncl udi ng document at i on on cabl es and t er mi nat i on har dwar e i n accor dance wi t h TIA-606 . T5 dr awi ngs shal l i ncl ude schedul es t o show i nf or mat i on f or cut - over s and cabl e pl ant management , pat ch panel l ayout s and cover pl at e assi gnment s, cr oss- connect i nf or mat i on and connect i ng t er mi nal l ayout as a mi ni mum. T5 dr awi ngs shal l be pr ovi ded on
SECTI ON 27 10 00 Page 9 PW\DEN001\684448 el ect r oni c medi a usi ng Wi ndows based comput er cabl e management sof t war e. A l i censed copy of t he cabl e management sof t war e i nc l udi ng document at i on, shal l be pr ovi ded. Pr ovi de t he f ol l owi ng T5 dr awi ng document at i on as a minimum:
a. Cabl es - A r ecor d of i nst al l ed cabl e shal l be pr ovi ded i n accor dance with TIA-606 . The cabl e r ecor ds shal l i ncl ude onl y t he r equi r ed dat a f i el ds i n accor dance wi t h TIA-606 . I ncl ude manuf act ur e dat e of cabl e wi t h submi t t al .
b. Ter mi nat i on Har dwar e - A r ecor d of i nst al l ed pat ch panel s, cr oss- connect poi nt s, di st r i but i on f r ames, t er mi nat i ng bl ock ar r angement s and t ype, and out l et s shal l be pr ovi ded i n accor dance wi t h TIA-606 . Document at i on shal l i ncl ude t he r equi r ed dat a f i el ds as a mi ni mum i n accor dance wi t h TIA-606 .
PART 2 PRODUCTS
2. 1 COMPONENTS
Component s shal l be UL or t hi r d par t y cer t i f i ed. Wher e equi pment or mat er i al s ar e speci f i ed t o conf or m t o i ndust r y and t echni cal soci et y r ef er ence st andar ds of t he or gani zat i ons, submi t pr oof of such compl i ance.
The l abel or l i s t i ng by t he speci f i ed or gani zat i on wi l l be accept abl e evi dence of compl i ance. I n l i eu of t he l abel or l i s t i ng, submi t a cer t i f i cat e f r om an i ndependent t est i ng or gani zat i on, compet ent t o per f or m t est i ng, and appr oved by t he Cont r act i ng Of f i cer . The cer t i f i cat e shal l s t at e t hat t he i t em has been t est ed i n accor dance wi t h t he speci f i ed or gani zat i on' s t est met hods and t hat t he i t em compl i es wi t h t he speci f i ed or gani zat i on' s r ef er ence st andar d. Pr ovi de a compl et e syst em of t el ecommuni cat i ons cabl i ng and pat hway component s usi ng st ar t opol ogy.
Pr ovi de suppor t st r uct ur es and pat hways, compl et e wi t h out l et s, cabl es, connect i ng har dwar e and t el ecommuni cat i ons cabi net s/ r acks. Cabl i ng and i nt er connect i ng har dwar e and component s f or t el ecommuni cat i ons syst ems shal l be UL l i s t ed or t hi r d par t y i ndependent t est i ng l abor at or y cer t i f i ed, and shal l compl y wi t h NFPA 70 and conf or m t o t he r equi r ement s speci f i ed herein.
2. 2 TELECOMMUNI CATI ONS PATHWAY
Pr ovi de t el ecommuni cat i ons pat hways i n accor dance wi t h TIA-569 and as speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM. Pr ovi de syst em f ur ni t ur e pat hways i n accor dance wi t h UL 1286.
2. 3 TELECOMMUNI CATI ONS CABLI NG
Cabl i ng shal l be UL l i s t ed f or t he appl i cat i on and shal l compl y wi t h TIA-568-C.0 , TIA-568-C.1 , TIA-568-C.2 , TIA-568-C.3 and NFPA 70. Pr ovi de a l abel i ng syst em f or cabl i ng as r equi r ed by TIA-606 and UL 969. Shi p cabl e on r eel s or i n boxes bear i ng manuf act ur e dat e f or f or unshi el ded t wi st ed pai r ( UTP) i n accor dance wi t h I CEA S- 90- 661 and opt i cal f i ber cabl es i n accor dance wi t h I CEA S- 83- 596 f or al l cabl e used on t hi s pr oj ect . Cabl i ng manuf act ur ed mor e t han 12 mont hs pr i or t o dat e of i nst al l at i on shal l not be used.
SECTI ON 27 10 00 Page 10 PW\DEN001\684448
2. 3. 1 Backbone Cabl i ng
2. 3. 1. 1 Backbone Copper
Copper backbone cabl e shal l be sol i d conduct or , 24 AWG, 100 ohm, 25-100
- pai r , Cat egor y 3, UTP, i n accor dance wi t h I CEA S- 90- 661, TIA-568-C.1 , TIA-568-C.2 and UL 444, f or med i nt o 25 pai r bi nder gr oups cover ed wi t h a gr ay t her mopl ast i c j acket and over al l met al l i c shi el d. Cabl e shal l be i mpr i nt ed wi t h manuf act ur er s name or i dent i f i er , f l ammabi l i t y r at i ng, gauge of conduct or , t r ansmi ssi on per f or mance r at i ng ( cat egor y desi gnat i on) at r egul ar l engt h mar ki ng i nt er val s i n accor dance wi t h I CEA S- 90- 661. Pr ovi de pl enum ( CMP) , r i ser ( CMR) , or gener al pur pose ( CM or CMG) communications r at ed cabl i ng i n accor dance wi t h NFPA 70. Subst i t ut i on of a hi gher r at ed cabl e shal l be per mi t t ed i n accor dance wi t h NFPA 70.
2. 3. 1. 2 Backbone Opt i cal Fi ber
Pr ovi de i n accor dance wi t h I CEA S- 83- 596, TIA-568-C.3 , UL 1666 and NFPA 70.
Cabl e shal l be i mpr i nt ed wi t h f i ber count , f i ber t ype and aggr egat e l engt h at r egul ar i nt er val s not t o exceed 40 i nches.
Pr ovi de t he number of st r ands i ndi cat ed, ( but not l ess t han 12 st r ands bet ween t he mai n t el ecommuni cat i on r oom and each of t he ot her t el ecommuni cat i on r ooms) , of s i ngl e- mode( OS1) , t i ght buf f er ed f i ber opt i c cable.
Pr ovi de t i ght buf f er ed f i ber opt i c mul t i mode, 62. 5/ 125- um di amet er (OM1) cabl e as i ndi cat ed.
Pr ovi de pl enum ( OFNP) , r i ser ( OFNR) , or gener al pur pose ( OFN or OFNG) r at ed non- conduct i ve, f i ber opt i c cabl e i n accor dance wi t h NFPA 70. Subst i t ut i on of a hi gher r at ed cabl e shal l be per mi t t ed i n accor dance wi t h NFPA 70. The cabl e cor dage j acket , f i ber , uni t , and gr oup col or shal l be i n accor dance with TIA/EIA-598 .
Pr ovi de pl enum ( OFNP) r i ser ( OFNR) , or gener al pur pose ( OFN or OFNG) r at ed non- conduct i ve, f i ber opt i c cabl e i n accor dance wi t h NFPA 70. Subst i t ut i on of a hi gher r at ed cabl e shal l be per mi t t ed i n accor dance wi t h NFPA 70. The cabl e cor dage j acket , f i ber , uni t , and gr oup col or shal l be i n accor dance with TIA/EIA-598 .
2. 3. 2 Hor i zont al Cabl i ng
Pr ovi de hor i zont al cabl e i n compl i ance wi t h NFPA 70 and per f or mance char act er i st i cs i n accor dance wi t h TIA-568-C.1 .
2. 3. 2. 1 Hor i zont al Copper
Pr ovi de hor i zont al copper cabl e, UTP, 100 ohm i n accor dance wi t h TIA-568-C.2 , UL 444, ANSI / NEMA WC 66, I CEA S- 90- 661. Pr ovi de f our each i ndi v i dual l y t wi st ed pai r , mi ni mum si ze 24 AWG conduct or s, Cat egor y 6, wi t h a gr een t her mopl ast i c j acket . Cabl e shal l be i mpr i nt ed wi t h manuf act ur er s name or i dent i f i er , f l ammabi l i t y r at i ng, gauge of conduct or , t r ansmi ssi on per f or mance r at i ng ( cat egor y desi gnat i on) and l engt h mar ki ng at r egul ar i nt er val s i n accor dance wi t h I CEA S- 90- 661. Pr ovi de pl enum ( CMP) , r i ser ( CMR) , or gener al pur pose ( CM or CMG) communi cat i ons r at ed cabl i ng i n accor dance wi t h NFPA 70. Subst i t ut i on of a hi gher r at ed cabl e shal l be per mi t t ed i n accor dance wi t h NFPA 70. Cabl es i nst al l ed i n condui t wi t hi n and under s l abs shal l be UL l i s t ed and l abel ed f or wet l ocat i ons i n
SECTI ON 27 10 00 Page 11 PW\DEN001\684448 accor dance wi t h NFPA 70.
2. 3. 3 Wor k Ar ea Cabl i ng
2. 3. 3. 1 Wor k Ar ea Copper
Pr ovi de wor k ar ea copper cabl e i n accor dance wi t h TIA-568-C.2 , wi t h a gr een t her mopl ast i c j acket .
2. 3. 3. 2 Wor k Ar ea Opt i cal Fi ber
Pr ovi de opt i cal wor k ar ea cabl e i n accor dance wi t h TIA-568-C.3 .
2. 4 TELECOMMUNI CATI ONS SPACES
Pr ovi de connect i ng har dwar e and t er mi nat i on equi pment i n t he t el ecommuni cat i ons ent r ance f aci l i t y and t el ecommuni cat i on equi pment r oom t o f aci l i t at e i nst al l at i on as shown on desi gn dr awi ngs f or t er mi nat i ng and cr oss- connect i ng per manent cabl i ng. Pr ovi de t el ecommuni cat i ons i nt er connect i ng har dwar e col or codi ng i n accor dance wi t h TIA-606 .
2. 4. 1 Backboards
Pr ovi de voi d- f r ee, i nt er i or gr ade A- C pl ywood 3/ 4 i nch t hi ck 4 by 8 f eet .
Backboar ds shal l be f i r e r at ed by manuf act ur i ng pr ocess. Fi r e st amp shal l be c l ear l y v i s i bl e. Pai nt appl i ed over f i r e r et ar dant backboar d shal l be UL 723 f i r e r et ar dant pai nt . Pr ovi de l abel i ncl udi ng pai nt manuf act ur er , dat e pai nt ed, UL l i s t i ng and name of I nst al l er . When pai nt ed, pai nt l abel and f i r e st amp shal l be c l ear l y v i s i bl e. Backboar ds shal l be pr ovi ded on a mi ni mum of t wo adj acent wal l s i n t he t el ecommuni cat i on spaces.
2. 4. 2 Equi pment Suppor t Fr ame
Pr ovi de i n accor dance wi t h ECI A EI A/ ECA 310- E and UL 50.
a. Racks, f l oor mount ed modul ar t ype, 16 gauge st eel const r uct i on, mi ni mum, t r eat ed t o r esi st cor r osi on. Pr ovi de r ack wi t h ver t i cal and hor i zont al cabl e management channel s, t op and bot t om cabl e t r oughs, gr oundi ng l ug and a sur ge pr ot ect ed power st r i p wi t h 6 dupl ex 20 amp r ecept acl es. Rack shal l be compat i bl e wi t h 19 i nches panel mount i ng.
2. 4. 3 Connect or Bl ocks
Pr ovi de i nsul at i on di spl acement connect or ( I DC) Type 110 f or Cat egor y 6 syst ems. Pr ovi de bl ocks f or t he number of hor i zont al and backbone cabl es t er mi nat ed on t he bl ock pl us 25 per cent spar e.
2. 4. 4 Cabl e Gui des
Pr ovi de cabl e gui des speci f i cal l y manuf act ur ed f or t he pur pose of r out i ng cabl es, wi r es and pat ch cor ds hor i zont al l y and ver t i cal l y on 19 i nches equi pment cabi net s and t el ecommuni cat i ons backboar ds. Cabl e gui des of r i ng or br acket t ype devi ces mount ed on r ack or backboar d f or hor i zont al cabl e management and i ndi v i dual l y mount ed f or ver t i cal cabl e management . Mount cabl e gui des wi t h scr ews, and nut s and l ockwasher s.
2. 4. 5 Pat ch Panel s
Pr ovi de por t s f or t he number of hor i zont al and backbone cabl es t er mi nat ed
SECTI ON 27 10 00 Page 12 PW\DEN001\684448 on t he panel pl us 25 per cent spar e. Pr ovi de pr e- connect or i zed opt i cal f i ber and copper pat ch cor ds f or pat ch panel s. Pr ovi de pat ch cor ds, as compl et e assembl i es, wi t h mat chi ng connect or s as speci f i ed. Pr ovi de f i ber opt i c pat ch cabl es wi t h cr ossover or i ent at i on i n accor dance wi t h TIA-568-C.3 .
Pat ch cor ds shal l meet mi ni mum per f or mance r equi r ement s speci f i ed i n TIA-568-C.1 , TIA-568-C.2 , and TIA-568-C.3 f or cabl es, cabl e l engt h and har dwar e speci f i ed.
2. 4. 5. 1 Modul ar t o 110 Bl ock Pat ch Panel
Pr ovi de i n accor dance wi t h TIA-568-C.1 and TIA-568-C.2 . Panel s shal l be t hi r d par t y ver i f i ed and shal l compl y wi t h EI A/ TI A Cat egor y 6 r equi r ement s. Panel shal l be const r uct ed of 0. 09 i nches mi ni mum al umi num and shal l be cabi net mount ed and compat i bl e wi t h an ECI A EI A/ ECA 310- E 19 i nch equi pment cabi net . Panel shal l pr ovi de 48 non- keyed, 8- pi n modul ar por t s, wi r ed t o T568A. Pat ch panel s shal l t er mi nat e t he bui l di ng cabl i ng on Type 110 I DCs and shal l ut i l i ze a pr i nt ed c i r cui t boar d i nt er f ace. The r ear of each panel shal l have i ncomi ng cabl e st r ai n- r el i ef and r out i ng gui des. Panel s shal l have each por t f act or y number ed and be equi pped wi t h l ami nat ed pl ast i c namepl at es above each por t .
2. 4. 5. 2 Fi ber Opt i c Pat ch Panel
Pr ovi de panel f or mai nt enance and cr oss- connect i ng of opt i cal f i ber cabl es. Panel shal l be const r uct ed of 16 gauge st eel or 11 gauge al umi num mi ni mum and shal l be r ack mount ed and compat i bl e wi t h a ECI A EI A/ ECA 310- E 19 i nches equi pment r ack. Each panel shal l pr ovi de 12 s i ngl e- mode adapt er s as dupl ex LC i n accor dance wi t h TIA/EIA-604-10 wi t h z i r coni a cer ami c al i gnment s l eeves. Pr ovi de dust cover f or unused adapt er s. The r ear of each panel shal l have a cabl e management t r ay a mi ni mum of 8 i nches deep wi t h r emovabl e cover , i ncomi ng cabl e st r ai n- r el i ef and r out i ng gui des.
Panel s shal l have each adapt er f act or y number ed and be equi pped wi t h l ami nat ed pl ast i c namepl at es above each adapt er .
2. 4. 6 Opt i cal Fi ber Di st r i but i on Panel
Rack mount ed opt i cal f i ber di st r i but i on panel ( OFDP) shal l be const r uct ed i n accor dance wi t h ECI A EI A/ ECA 310- E ut i l i z i ng 16 gauge st eel or 11 gauge al umi num mi ni mum. Panel shal l be di v i ded i nt o t wo sect i ons, di st r i but i on and user . Di st r i but i on sect i on shal l have st r ai n r el i ef , r out i ng gui des, spl i ce t r ay and shal l be l ockabl e, user sect i on shal l have a cover f or pat ch cor d pr ot ect i on. Each panel shal l pr ovi de 12 s i ngl e- mode pi gt ai l s and adapt er s. Pr ovi de adapt er s as dupl ex LC wi t h z i r coni a cer ami c al i gnment s l eeves. Pr ovi de dust cover s f or adapt er s. Pr ovi de pat ch cor ds as speci f i ed i n t he par agr aph PATCH PANELS.
2. 5 TELECOMMUNI CATI ONS OUTLET/ CONNECTOR ASSEMBLI ES
2. 5. 1 Out l et / Connect or Copper
Out l et / connect or s shal l compl y wi t h FCC Par t 68, TIA-568-C.1 , and TIA-568-C.2 . UTP out l et / connect or s shal l be UL 1863 l i s t ed, non- keyed, 8- pi n modul ar , const r uct ed of hi gh i mpact r at ed t her mopl ast i c housi ng and shal l be t hi r d par t y ver i f i ed and shal l compl y wi t h TIA-568-C.2 Cat egor y 6 r equi r ement s. Out l et / connect or s pr ovi ded f or UTP cabl i ng shal l meet or exceed t he r equi r ement s f or t he cabl e pr ovi ded. Out l et / connect or s shal l be t er mi nat ed usi ng a Type 110 I DC PC boar d connect or , col or - coded f or bot h T568A and T568B wi r i ng. Each out l et / connect or shal l be wi r ed T568A. UTP out l et / connect or s shal l compl y wi t h TIA-568-C.2 f or 200 mat i ng cycl es. UTP
SECTI ON 27 10 00 Page 13 PW\DEN001\684448 out l et / connect or s i nst al l ed i n out door or mar i ne envi r onment s shal l be j el l - f i l l ed t ype cont ai ni ng an ant i - cor r osi ve, memor y r et ai ni ng compound.
2. 5. 2 Opt i cal Fi ber Adapt er s (Couplers)
Pr ovi de opt i cal f i ber adapt er s sui t abl e f or dupl ex LC i n accor dance wi t h TIA/EIA-604-10 wi t h z i r coni a cer ami c al i gnment s l eeves. Pr ovi de dust cover f or adapt er s. Opt i cal f i ber adapt er s shal l compl y wi t h TIA-455-21 f or 500 mat i ng cycl es.
2. 5. 3 Opt i cal Fi ber Connect or s
Pr ovi de i n accor dance wi t h TIA-455-21 . Opt i cal f i ber connect or s shal l be dupl ex LC i n accor dance wi t h TIA/EIA-604-10 wi t h z i r coni a cer ami c al i gnment s l eeves, compat i bl e wi t h 8/ 125 si ngl e- mode f i ber . The connect or s shal l pr ovi de a maxi mum at t enuat i on of 0. 3 dB at 1310 and 1550 nm wi t h l ess t han a 0. 2 dB change af t er 500 mat i ng cycl es.
2. 5. 4 Cover Pl at es
Pr ovi de i n accor dance wi t h TIA-455-21 . Opt i cal f i ber connect or s shal l be dupl ex LC i n accor dance wi t h TIA/EIA-604-10 wi t h z i r coni a cer ami c al i gnment s l eeves, compat i bl e wi t h 8/ 125 si ngl e- mode f i ber . The connect or s shal l pr ovi de a maxi mum at t enuat i on of 0. 3 dB at 1310 and 1550 nm wi t h l ess t han a 0. 2 dB change af t er 500 mat i ng cycl es.
2. 6 GROUNDI NG AND BONDI NG PRODUCTS
Pr ovi de i n accor dance wi t h UL 467, TIA-607 , and NFPA 70. Component s shal l be i dent i f i ed as r equi r ed by TIA-606 . Pr ovi de gr ound r ods, bondi ng conduct or s, and gr oundi ng busbar s as speci f i ed i n Sect i on 26 20 00 I NTERI OR
DI STRI BUTI ON SYSTEM.
2. 7 FI RESTOPPI NG MATERI AL
Pr ovi de as speci f i ed i n Sect i on 07 84 00 FI RESTOPPI NG.
2. 8 MANUFACTURER' S NAMEPLATE
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number ,…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .