Site Visit QandA.pdf

PDF 88 KB Posted

Attached to
Construct Transformer Pad Federal contract opportunity
Solicitation number
W50S8J-23-Q-0008
Issued by
Department of the Army New York Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to Construct Transformer Pad, newest first.
File Type Posted
Attachment 1 - SOW_ dated 30May23.pdf PDF
Site Visit Minutes_25May23.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
A00002 Amendment to Update SOW and Extend RFQ due date.pdf PDF
W50S8J23Q0008P00001 Amend Eval Criteria_ NAICS_ Site Visit Info.pdf PDF
Attachment 1 - SOW_ dated 24 Apr 23.pdf PDF
W50S8J23Q0008 Construct Transformer Pad.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Construct Transformer Pad at Stratton ANGB, Scotia, NY

Sol #: W50S8J-23-Q-0008 Project #: VBDZ232104

Questions and Answers – Site Visit held 25 May 2023/10:00 AM EST

1. Q: Do we need to have an electrician involved in this project or will a site contractor be sufficient?

A: Having an electrician is not mandated. However, since this is a transformer pad, we highly encourage electricians monitor the work to avoid obvious errors from electricians standpoint (i.e. sharp edges and corner, wrong conduit size or location.)

2. Q: Do we need to have a special escort to work site since it is on the Range Rd / runway access Rd ?

A: All personnel must be background checked and receive awareness training for working in this section of the base. Base may also provide an escort for that area in addition to background check/badging.

3. Q: Will the base facilities personnel mark out the actual desired location of the new transformer pad and location where the conduits for future building feed are to be terminated?

A: Base will mark the pad location and the direction of the conduits.

4. Q: the SOW is unclear about how many secondary conduits are to be stubbed out and buried 10 ft. away I’m assuming its (1) 4 inch conduit please clarify.

A: The SOW has been updated to reflect conduit requirement