Attachment 1 - Alert_one line drawing_ph1_and_2Comb.pdf
PDF 742 KB Posted
- Attached to
- Alert Generator
- Solicitation number
- W50S8F26QA017
- Issued by
-
Department of the Army National Guard
About this file
This document is an electrical one-line diagram and panelboard schedule for an alert crew facilities project at an aircraft shelter. The drawing shows the main electrical distribution system serving three aircraft shelters with detailed circuit configurations and load calculations.
The system comprises two primary panelboards: HP5 (400-amp, 480Y/277 volts, 3-phase, 4-wire) and MPZ5 (208Y/120 volts, 3-phase, 4-wire). HP5 supplies major loads including a 62.5 kVA 400Hz converter serving shelters 1 and 3, bay door motors (two 9-horsepower motors per bay), and shelter lighting circuits with a total connected load of 244.3 kVA and estimated demand load of 199.7 kVA. MPZ5 serves lower-voltage circuits including roof obstruction lights (540 VA), security devices (500 VA), CCTV cameras (500 VA), IDS panel (1,000 VA), and PA system (1,000 VA) with a total connected load of 5.2 kVA at 100 percent demand factor. The electrical distribution system includes transformer T1 (75 kVA, 480V-208Y/120V) supplying the secondary main breaker for HP5, automatic transfer switches for standby generator power, and auxiliary equipment such as fire pump panels and entry control facilities. The panelboard specifications detail circuit breaker ratings, wire gauges, conduit sizes, and phase balancing across all three phases.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANELBOARD NAME: MPZ5 10,000 RMS SYMMETRICAL A.I.C.
PANELBOARD TYPE: MAIN CIRCUIT BREAKER SURFACE MOUNTED, NEMA 3R ENCLOSURE
PANEL LOCATION: EXTERIOR, AIRCRAFT SHELTER 3 208Y/120 VOLTS, 3 PHASE, 4 WIRE
SUPPLIED FROM: HP5 22.5KVA MINI POWER ZONE PANEL WITH 80A SECONDARY MAIN BREAKER
CKT TRIP NO. WIRE / GND. GND. WIRE / NO. TRIP CKT.
NO. AMPS POLES CONDUIT WIRE LOAD SERVED LOAD
VA
Ø LOAD
VA
LOAD SERVED WIRE CONDUIT POLES AMPS NO.
1 20 1 2-#10 , 3/4" #10 RECPT. EXT. 540 A 80 ROOF OBSTRUCTION LIGHTS #12 2-#12 , 3/4" 1 20 2 3 20 1 2-#10 , 3/4" #10 RECPT. EXT. 540 B 500 SECURITY DEVICES #10 2-#10 , 3/4" 1 20 4 5 20 1 2-#12 , 3/4" #12 ALERT CONTROL PANEL 1000 C 500 CCTV CAMERAS #10 2-#10 , 3/4" 1 20 6
7 20 1 2-#12 , 3/4" #12 IDS PANEL 1000 A SPACE 1 8
9 20 1 2-#12 , 3/4" #12 PA SYSTEM 1000 B SPACE 1 10
11 20 1 SPARE C SPACE 1 12
13 20 1 SPARE A
15 20 1 SPARE B TVSS DEVICE 3-#10 , 3/4" 3 20 16
17 1 SPACE C
TOTAL CONNECTED LOAD = 5.2 kVA X 100% DEMAND FACTOR = 5.2 kVA ESTIMATED DEMAND LOAD
PHASE BALANCE (KVA) - A: 1.6 , B: 2 , C: 1.5
P A N E LB O A R D N A M E : H P 5 14 ,000 R M S S Y M M E TR IC A L A . I.C .
P A N E LB O A R D TY P E : M A IN C IR C U IT B R E A K E R S U R F A C E M O U N TE D , N E M A 3R E N C LO S U R E 400 A M P TR IP M A IN B R E A K E R P A N E L LO C A TIO N : E XTE R IO R , A IR C R A F T S H E LTE R 3 480Y /277 V O LTS , 3 P H A S E , 4 W IR E 400 A M P M A IN S
S U P P L IE D F R O M : M D P 1
C K T TR IP N O . W IR E / G N D . G N D . W IR E / N O . TR IP C K T.
N O . A M P S P O LE S C O N D U IT W IR E LO A D S E R V E D LO A D
V A
Ø LO A D
V A
LO A D S E R V E D W IR E C O N D U IT P O LE S A M P S N O .
24167 A 24167 3 110 3 3 -#2 , 1 1 /2 " #6 62 .5K V A 400H Z C O N V TR (N ) 24167 B 24167 62 .5K V A 400H Z C O N V TR (S ) #6 3 -#2 , 1 1 /2 " 3 110 4
1 -#2 N E U TR A L 24167 C 24167 1 -#2 N E U TR A L
7 20 1 2 -#12 , 3 /4 " #12 E XIT, E M E R G . L IG H TIN G B A Y 440 A 6374
9 20 1 2 -#10 , 3 /4 " #10 S H E LTE R L IG H TIN G - E XTE R IO R 2700 B 6374 S O U TH B A Y D O O R #10 3-#8 , 3 /4 " 3 45 10
1720 C 6374 (2 - 9H P M O TO R S - O P TIO N 3 ) 1 -#2 N E U TR A L
13 40 3 3-#8 , 1 " #10 P A N E L M P Z5 (22 .5K V A ) 1720 A 6374
1720 B 6374 S O U TH B A Y D O O R #10 3-#8 , 3 /4 " 3 45 16
443 C 6374 (2 - 9H P M O TO R S - O P TIO N 3 )
19 20 3 3 -#12 , 3 /4 " #12 H TG E XH A U S T P M P (3 /4 H P ) 443 A 6374
443 B 6374 N O R TH B A Y D O O R #10 3-#8 , 3 /4 " 3 45 22
23 20 1 2 -#12 , 3 /4 " #12 L IG H TIN G - N O R TH B A Y 3294 C 6374 (2 - 9H P M O TO R S - O P TIO N 3 )
25 20 1 2 -#12 , 3 /4 " #12 L IG H TIN G - N O R TH B A Y 3294 A 6374
27 20 1 2 -#12 , 3 /4 " #12 L IG H TIN G - S O U TH B A Y 3294 B 6374 N O R TH B A Y D O O R #10 3-#8 , 3 /4 " 3 45 28 29 20 1 2 -#12 , 3 /4 " #12 L IG H TIN G - S O U TH B A Y 3294 C 6374 (2 - 9H P M O TO R S - O P TIO N 3 ) 31 1 S P A C E A S P A R E 1 20 32 33 1 S P A C E B S P A R E 1 20 34 35 1 S P A C E C S P A R E 1 20 36 37 1 S P A C E A
39 1 S P A C E B TV S S D E V IC E 3-#10 , 3 /4 " 3 20 40
41 1 S P A C E C
TO TA L C O N N E C TE D LO A D = 244 .3 k V A X 82% D E M A N D F A C TO R = 199 .7 k V A E S TIM A TE D D E M A N D LO A D
P H A S E B A LA N C E (K V A ) - A : 79 .7 , B : 82 , C : 82 .6