TELECOMM ADDENDUM 001.pdf

PDF 212 KB Posted

Attached to
Construct Security Forces & Communications Training Facility Federal contract opportunity
Solicitation number
W50S8E23B0002
Issued by
Department of the Army New York Army National Guard

About this file

This document includes construction drawings and specifications for a federal construction contract opportunity. The opportunity is to construct a Security Forces and Communications Training Facility at the 106th Rescue Wing in Westhampton Beach, New York for $10-25 million. The solicitation number is W50S8E23B0002. This is a 100% small business set-aside issued by the Department of the Army New York Army National Guard. Drawings are available through DoD SAFE and requests should be sent to the specified email address. The North American Industry Classification code is 236220 and the size standard is $45 million average annual revenue for the past three years. A pre-bid site visit is scheduled and amendments will be posted to SAM.gov. Bids are due by the response date and awards will be made to the responsible bidder whose bid is most advantageous to the government considering only price and price-related factors. Funds have not been appropriated yet and no award will be made until funding is available, though the project has been identified on the National Guard's priority list.

View the file

Other files for this federal contract opportunity

Other files attached to Construct Security Forces & Communications Training Facility, newest first.
File Type Posted
Abstract OF1419 Signed.pdf PDF
Bid Opening Attendance Sheet.pdf PDF
Questions and Answers 8 June 23.pdf PDF
09 67 23.13 Standard Resinous Flooring.pdf PDF
Questions and Answers 5 June 23.pdf PDF
W50S8E23B00020004.pdf PDF
ELEC ADDENDUM 001.pdf PDF
26 12 19 33 71 02 33 82 00 specifications.pdf PDF
Geotechnical Report.pdf PDF
W50S8E23B00020003.pdf PDF
W50S8E23B00020002.pdf PDF
PREBID Conference Slides.pptx PPTX presentation
Site Visit Attendee List W50S8E23B0002.jpg JPG image
W50S8E23B00020001.pdf PDF
W50S8E23B0002 Solicitation.pdf PDF
1170188_Security Forces and Communications Training Facility Specifications VOL1.pdf PDF
1170188_Security Forces and Communications Training Facility Specifications VOL2.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMUNICATIONS COMBINATION VOICE/DATA OUTLET

(TWO VOICE & TWO DATA JACKS) MOUNT 18" AFF, UIO

SUBSCRIPT: S=SIPR

COMMUNICATIONS VOICE OUTLET MOUNT 60" AFF, UIO

FLOOR BOX OR FIRE RATED POKE THROUGH, TWO

QUADRUPLEX RECEPTACLES & TWO QUADRUPLEX

DATA OUTLETS, UIO. (X) DENOTES NUMBER OF

VOICE/DATA DROPS.

COAXIAL CATV OUTLET WALL MOUNTED 60" AFF, UIO

WALL MOUNTED JUNCTION BOX FOR VOICE/DATA

CONNECTION TO MODULAR WORKSTATION FURNITURE,

UIO. (X) DENOTES NUMBER OF VOICE/DATA DROPS.

TV

COMMUNICATIONS

SYMBOL DESCRIPTION

ACCESS CONTROL JUNCTION BOX

BALANCED MAGNETIC DOOR CONTACT

ELECTRIC STRIKE

SEISMIC VIBRATION SENSOR

CARD READER

ELECTRIC LOCKSET

ELECTRIC HINGE

MOTION DETECTION SENSOR

SECURITY PANEL

KEY PAD

MAGLOCK

DC

ES

S

CR

EL

EH

M

SP

KP

ML

AC

SECURITY

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR

ABOVE FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW

GRADE OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

WIRING

J

AUDIO VISUAL FLOOR BOX OR FIRE RATED POKE

THROUGH, AUDIO VISIUAL PORTS & TWO QUADRUPLEX

RECEPTACLES & TWO QUADRUPLEX DATA OUTLETS, UIO

LADDER CABLE TRAY (SIZE AS INDICATED ON PLAN)

WELDED WIRE STYLE CABLE TRAY

(BELOW RAISED FLOOR) (SIZE AS INDICATED ON PLAN)

WELDED WIRE STYLE CABLE TRAY (ABOVE CEILING)

(SIZE AS INDICATED ON PLAN)

COMMUNICATIONS COMBINATION VOICE/DATA OUTLET

(TWO VOICE & TWO DATA JACKS) MOUNT 18" AFF, UIO

S

(2V)

(2D)

(2V) (2D)

GFGI CCTV ROUGH-IN LOCATION. MOUNT AT 10'-0" AFG

ON BUILDING EXTERIOR AND FLUSH WITH CEILING ON

BUILDING INTERIOR. ROUTE 1"C WITH PULLSTRING TO

NEAREST CABLE TRAY. COORDINATE FINAL LOCATION

WITH GOVERNMENT PRIOR TO ROUGH-IN.

ABBREVIATIONS

A OR AMP

AFF

AWG

BLDG

C

CAT

CATV

CFCI

CU

D

DDC

EC

EF

EIA

EMT

EQUIP

ER

ETR

EXIST or EX

FWE

G OR GND

GFGI

GFCI

GRS

H or HT

HVAC

IDF

IDS

IMC

J OR JB

K

KV

KVA

KW

L

LAN

MAX

MDF

MIN

MM

N

NEC

NEMA

NFPA

NIPR

NTS

PDS

PVC

RMC

RPP

RU

SA

SIPR

SM

SPEC

TGB

TIA

TMGB

TP

TR

TYP

UIO

UL

UTP

V

VA

W

WAP

AMPERE(S)

ABOVE FINISHED FLOOR

AMERICAN WIRE GAUGE

BUILDING

CONDUIT

CATEGORY

CABLE TELEVISION

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

COPPER

DEPTH

DIRECT DIGITAL CONTROL FOR HVAC

EMPTY CONDUIT

ENTRANCE FACILITY

ELECTRONICS INDUSTRIAL ALLIANCE

ELECTRICAL METALLIC TUBING

EQUIPMENT

EQUIPMENT ROOM

EXISTING TO REMAIN

EXISTING

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT INSTALLED

GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GALVANIZED RIGID STEEL CONDUIT

HEIGHT

HEATING, VENTILATION & AIR CONDITIONING

INTERMEDIATE DISTRIBUTION FRAME

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

KILO

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

LENGTH

LOCAL AREA NETWORK

MAXIMUM

MAIN DISTRIBUTION FRAME

MINIMUM

MULTIMODE

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NON-SECURE INTERNET PROTOCOL ROUTER

NOT TO SCALE

PROTECTIVE DISTRIBUTION SYSTEM

POLYVINAL CHLORIDE

RIGID METAL CONDUIT

REMOTE POWER PANEL

RACK UNIT

SURGE ARRESTOR

SECURE INTERNET PROTOCAL ROOTER

SINGLE MODE

SPECIFICATIONS

TELECOMMUNICATIONS GROUNDING BUSBAR

TELECOMMUNICATIONS INDUSTRIAL ALLIANCE

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TWISTED PAIR

TELECOMMUNICATIONS ROOM

TYPICAL

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

WATTS or WIRE or WIDTH

WIRELESS ACCESS POINT

GENERAL NOTES:

EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ATC) THAT DOES NOT SERVE

EF,ER OR TR(S) SHALL NOT BE INSTALLED ABOVE OR IN IT SPACES, NOR SHALL

THIS EQUIPMENT PASS THROUGH OR ENTER THE EF, ER OR TR(S).

ANY MOTOR, TRANSFORMER OR OTHER ELECTRICAL DEVICE GREATER THAN

5KVA SHALL HAVE A MINIMUM OF 47" SPACE SEPARATION FROM ANY WALL OF EF,

ER OR TR(S).

CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES

THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR

SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE

FOR RECESSED LIGHTING FIXTURES AND CORRECT ROUGH-IN LOCATIONS OF

ELECTRICAL CONNECTIONS.

VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON

ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST

SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF

OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED,

LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.

REFER TO DETAILS AND RISER DIAGRAMS FOR CABLE AND CONDUIT SIZES NOT

SHOWN ON PLANS.

"PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO

BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH,

INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS

WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS

OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO

FULFILL THE SCOPE OF WORK.

PROVIDE WELDED WIRE TYPE CABLE TRAY IN ALL AREAS EXCEPT TR(S). PROVIDE

LADDER TYPE CABLE TRAY IN TR(S).

FLOOR BOXES AND POKE THRU'S SHALL BE SIZED TO NOT EXCEED

TELECOMMUNICATIONS CABLE MINIMUM BEND RADIUS.

REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF RATED WALLS. FIRESTOP

FIRE RATED BARRIERS IN ACCORDANCE WITH FIRESTOPPING SPECIFICATIONS 07

84 00. SLEEVES AND SLOTS SHALL NOT BE LEFT OPEN AFTER CABLE

INSTALLATION. ALL SLEEVES AND SLOTS SHALL BE FIRESTOPPED IN

ACCORDANCE WITH FIRESTOPPING SPECIFICATION 07 84 00.

EMT: COMPLY WITH ANSI C80.3 AND 797. ALL EMT SHALL BE FACTORY PAINTED.

PROVIDE THE FOLLOWING COLORS FOR EACH SYSTEM:

1. TELECOMMUNICATIONS - ORANGE

2. SECURITY - PURPLE

PROVIDE A MINIMUM OF 12" SEPERATION BETWEEN ALL DATA OUTLETS AND ANY

POWER LOAD GREATER THAN 5KVA.

PROVIDE 3.28’ OF CLEAR, UNOBSTRUCTED SPACE FOR THE INSTALLATION OF ALL

CABLING AND EQUIPMENT MOUNTED ON WALLS, RACKS (FRONT AND REAR),

CABINETS (FRONT AND REAR) AND ENCLOSURES. PROVIDE AT LEAST 6” DEPTH

OFF THE WALL FOR WALL-MOUNTED EQUIPMENT. ALLOCATE SPACE OF 3.28’

WIDE, 3.28’ DEEP AND 7.5’ HIGH FOR EACH EQUIPMENT RACK, CABINET OR

ENCLOSURE. PROVIDE SPACE FOR AN AISLE OF AT LEAST 3.28’ WIDE IN THE

FRONT AND IN THE REAR OF THE SPACE FOR EACH EQUIPMENT RACK, CABINET

OR ENCLOSURE. THIS SPACE SHALL TAKE INTO ACCOUNT THE DEPTH OF RACK-

MOUNTED EQUIPMENT AS WELL AS WALL-MOUNTED EQUIPMENT AND

HARDWARE.

LOCATE LIGHT SWITCHES NEAR THE ENTRANCE(S) TO THE TELECOMMUNICATION

ROOM. DIMMERS AND VACANCY SENSORS ARE NOT PERMITTED TO BE USED

WITHIN THE TELECOMMUNICATION ROOM. PROVIDE A MINIMUM OF 50 FOOT-

CANDLES OF LIGHT AT THE POINT OF CABLE TERMINATION.

MINIMUM SIZE OF TELECOMMUNICATION ROOMS BASED ON THE AREA IT IS

SERVING:

1. 5,000 SQ FT. OR LESS, 10' x 8' MINIMUM.

2. 5,000 SQ FT. TO 8,000 SQ FT., 10' x 9' MINIMUM.

3. 8,000 SQ FT. TO 10,000 SQ FT., 10' x 11' MINIMUM.

DO NOT SERVICE MORE THAN 10,000 SQ FT. FROM ONE TELECOMMUNICATION

ROOM.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

PROVIDE TWO RACK UNITS OF HORIZONTAL CABLE MANAGEMENT FOR EVERY

ONE RACK UNIT PATCH PANEL.

PROVICE AT LEAST TWO WALLS IN EACH TELECOMMUNICATION ROOM WITH AC

GRADE OR BETTER, FIRE-RESISTANT VOID FREE PLYWOOD PAINTED LIGHT GRAY

IN COLOR. THE PLYWOOD SHOULD BE 8 FT. HIGH WITH A MINIMUM THICKNESS OF

¾”. PLYWOOD SHOULD BE KILN-DRIED TO MAXIMUM MOISTURE CONTENT OF

15%. MOUNT PLYWOOD AT 8” AFF MINIMUM.

COORDINATE CABLE TRAY, LIGHT FIXTURE AND MECHANICAL UNIT INSTALLATION

WITHIN A TELECOMMUNICATION ROOM WITH ALL TRADES PRIOR TO

INSTALLATION.

SLEEVES OR CONDUITS ENTERING INTO THE TELECOMMUNICATION ROOM SHALL

EXTEND INTO THE SPACE A MINIMUM OF 3” FROM THE FLOOR, WALL OR CEILING.

PROVIDE A MINIMUM OF (2) 3” CONDUITS BETWEEN ALL TELECOMMUNICATION

ROOMS LOCATED ON THE SAME FLOOR. PROVIDE (3) 1-1/4” INNERDUCT IN ONE OF

THE CONDUITS. PROVIDE PULLSTRING IN ALL EMPTY CONDUIT AND INNERDUCT.

BOND ALL TMGBs AND TGBs TO STRUCTURAL STEEL, ALL DATA RACKS, CABINETS

OR ENCLOSURES, CABLE TRAY AND THE ELECTRICAL PANEL GROUND BUS

WITHIN THE TELECOMMUNICATION ROOMS AS APPLICABLE. ALL BONDING

CONDUCTORS WITHIN A TELECOMMUNICATION ROOM SHALL BE #4 AWG CU,

UIO. ALL BONDS TO THE TMGB OR TGB SHALL BE BY IRREVERSIBLE

COMPRESSION-TYPE CONNECTIONS.

15.

16.

17.

18.

19.

20.

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

A P

P R

O V

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:5

:0

A

M B

IM

/1

N Y

A N

G G a b re s k i B

/1

N

Y A

N G

G a b re s k i_

B

M

E P v

.r v t

T-001

ISSUED FOR CONSTRUCTION

T E

L E

C O

M M

U N

IC

A

T

IO

N S

G E

N E

R A

L N

O T

E S

A N

D A

B B

R E

V

IA

T

IO

N S

R E

P L A

C E

S E

C U

R

IT

Y F

O R

C E

S A

N D

C O

M M

U N

IC

A

T

IO

N T

R A

IN

IN

G F

A C

IL

IT

Y W

E S

T H

A M

P T

O N

B E

A C

H

N E

W Y

O R

K

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

F R

A N

C E

S S

G

A B

R E

S K

I A

IR

P

O R

T

N E

W Y

O R

K

J O

B N

O

G L K

K B

G

T C

G

J M

S

M A

R C

H

S O

L -X

X -X

-X X

X X

W L -1

-D

-0 -D

X X

-X -X

X X

X

A M

E N

D M

E N

T

/0

/2

A

M E

N D

M E

N T

/0

/2

FINISHED CEILING

FINISHED FLOOR

TO NEXT

DOOR

SECURED

ACCESS DOOR

SECURED

ACCESS DOOR

J TO NEXT

DOOR

7 8

FINISHED CEILING

FINISHED FLOOR

SECURED

ACCESS DOOR

TO NEXT

DOOR

J TO NEXT

DOOR

7 8

KEY NOTES:

1 1 1/4" CONDUIT FOR GFGI ACS CABLING,

SEE T-101 & T102.

GFGI BALANCED MAGNETIC SWITCH.

MOUNT ON SECURE SIDE OF DOOR.

4"X4" JUNCTION BOX. MOUNT ABOVE

SUSPENDED CEILING, OR AT 9'-0" AFF

WHERE ROOM DOES NOT HAVE A

SUSPENDED CEILING.

3/4" CONDUIT FOR GFGI ACS CABLING.

CONCEALED ELECTRIC POWER

TRANSFER DEVICE.

GFGI CARD READER. MOUNT ON NON-

SECURE SIDE OF DOOR.

POWER SUPPLY J-BOX.

2#10 & 1#10G - 3/4"C (120 VAC) SEE

E-605, E-606, E-607 &E-608 PANEL

SCHEDULES FOR DOOR CONTROL

CIRCUIT

CEILING

FLOOR

PROJECTOR

TV

AV

OUTLET

1 1/2" CONDUIT WITH

PULLSTRING FROM

PROJECTOR/TV TO AV OUTLET

ON WALL OR TO TABLE.

36"DIA. ACCESS OPENING

4"DIA. TERM-A-DUCT

(116 TOTAL, 32 EACH

END & 26 EACH SIDE)

BONDING RIBBON

(TYPICAL OF 8)

INSERT FOR RACKING

(TYPICAL)

SUMP WITH COVER

(TYPICAL OF 2)

PULLING IRON

(TYPICAL OF 4)

4'-3"

12'-0" 3'-9"

12'-10"

6'-10"

6'-0"

8'-0"

7'-0"

COMMUNICATIONS

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

A P

P R

O V

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:5

:0

A

M B

IM

/1

N Y

A N

G G a b re s k i B

/1

N

Y A

N G

G a b re s k i_

B

M

E P v

.r v t

T-502

ISSUED FOR CONSTRUCTION

T E

L E

C O

M M

U N

IC

A

T

IO

N S

D E

T A

IL

S

R E

P L A

C E

S E

C U

R

IT

Y F

O R

C E

S A

N D

C O

M M

U N

IC

A

T

IO

N T

R A

IN

IN

G F

A C

IL

IT

Y W

E S

T H

A M

P T

O N

B E

A C

H

N E

W Y

O R

K

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

F R

A N

C E

S S

G

A B

R E

S K

I A

IR

P

O R

T

N E

W Y

O R

K

J O

B N

O

G L K

K B

G

T C

G

J M

S

M A

R C

H

S O

L -X

X -X

-X X

X X

W L -1

-D

-0 -D

X X

-X -X

X X

X

SCALE: N.T.S.C1

DETAIL - DOUBLE DOOR

SCALE: N.T.S.C3

DETAIL - SINGLE DOOR

GENERAL NOTES

SEE T-001 FOR GENERAL NOTES, ABBREVIATIONS

AND SYMBOLS.

1.

SCALE: N.T.S.A1

PROJECTOR CONNECTION

A

M E

N D

M E

N T

/0

/2

A

M E

N D

M E

N T

/0

/2

SCALE: N.T.S.A3

TELECOMMUNICATION MANHOLE

RG-11

120VAC

+20dB

+30dB

RG-11

TR-114

TR -216

8-PORT

RG-11 - 1 1/2"C

TV

5 (TYP.)

8 (TYP.)

4(TYP.)

(TYP.)

TV

ROOF

WEATHER HEAD

203 204

RG-11

8-PORT

TV

TV

TV107

TV

TV

TV

KEY NOTES:

1 CATV SERVICE PROVIDER HEADEND.

CATV AMPLIFIER.

3-WAY SPLITTER

5-1000 MHZ TAP, NUMERAL INDICATED

TAP dB.

75 OHM TERMINATOR.

TYPE F COAXIAL TV OUTLET.

CONTRACTOR SHALL MEASURE dB

LEVEL AT EACH OUTLET AND PROVIDE

ATTENUATORS AT TAP PORTS AS

NEEDED TO PROVIDE dB LEVEL BETWEEN +5 AND +15dB AT EACH

OUTLET.

2"C WITH PULLSTRING TO ROOF FOR

CATV SERVICE PROVIDER ENTRANCE

CABLE.

ATTENUATOR

2 STRAND SINGLE MODE FIBER OPTIC

CABLE.

COAX-TO-FIBER OPTIC MEDIA

CONVERTER AND POWER SUPPLY.

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

A P

P R

O V

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

/2

/2

:5

:0

A

M B

IM

/1

N Y

A N

G G a b re s k i B

/1

N

Y A

N G

G a b re s k i_

B

M

E P v

.r v t

T-604

ISSUED FOR CONSTRUCTION

C A

T V

R

IS

E R

D

IA

G R

A M

R E

P L A

C E

S E

C U

R

IT

Y F

O R

C E

S A

N D

C O

M M

U N

IC

A

T

IO

N T

R A

IN

IN

G F

A C

IL

IT

Y W

E S

T H

A M

P T

O N

B E

A C

H

N E

W Y

O R

K

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

F R

A N

C E

S S

G

A B

R E

S K

I A

IR

P

O R

T

N E

W Y

O R

K

J O

B N

O

G L K

K B

G

T C

G

J M

S

M A

R C

H

S O

L -X

X -X

-X X

X X

W L -1

-D

-0 -D

X X

-X -X

X X

X

SCALE: N.T.S.A1

CATV RISER DIAGRAM

A

M E

N D

M E

N T

/0

/2

A

M E

N D

M E

N T

/0

/2

Sheets
T-001 - TELECOMMUNICATIONS GENERAL NOTES AND ABBREVIATIONS
T-502 - TELECOMMUNICATIONS DETAILS
T-604 - CATV RISER DIAGRAM

File details come from the government source that posted it. Updated .