RFI 1.pdf

PDF 106 KB Posted

Attached to
Construct Stormwater Runoff Diversion Federal contract opportunity
Solicitation number
W50S8D22Q0009
Issued by
Department of the Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to Construct Stormwater Runoff Diversion, newest first.
File Type Posted
Pre-Proposal Conference Minutes.pdf PDF
Statement of Work - Revised 24 June 2022.pdf PDF
Solicitation Amendment W50S8D22Q0009_0001.pdf PDF
Pre-Proposal Conference Attendance Sheet.pdf PDF
Attachment 1.2.pdf PDF
W50S8D22Q0009.pdf PDF
Statement of Work.pdf PDF
Attachment 1.1.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1) Do you have a spec on the sump pump and fastener on the header bracing?

‐ The sump pump shall be a ½ ‐ ¾ HP minimum submersible sump pump (Goulds ST51 or equivalent) capable of pumping a minimum of 15 GPM against approximately 25 feet of total dynamic head.

‐ The bracing for the header pipe shall be fastened to the concrete wall of the drainage trench using minimum 3/8 inch x 4 inch concrete screw anchors. The screw holes shall be pre‐drilled to manufacturer specified diameter and prepared with epoxy (Sika Anchorfix‐1 or equivalent).